venting categories

advertisement

Chimney Fundamentals

And Operation

The Art of Venting

Flue Gases

Or

How Not To Kill Your

Client

Presenter: Earl Hicks

Objectives

Review New York WAP policy regarding venting systems

BPI Standards

Review combustion process

Define & understand combustion air

How does a vent system work

Identify venting categories and materials

Using venting rules-of-thumb

Inspection of existing flues

Alternative venting methods

NYS WAP Policy

Ensure safe elimination of flue gases from the building

BPI Standards

Building Performance Institute

Any combustion appliance chimney/vent system that is in use must be visually evaluated for defects

A deteriorated chimney should be repaired or relined and causes corrected before reusing.

Principles Of Combustion

Three essential components for combustion

Fuel

Oxygen

Heat

Fuel – Fossil fuels

Oxygen – Air is 20.9% O

2

Heat – Pilot, spark, or igniter

Combustion Principles

The Chemical Reaction

CH

4

+ 4O

2

+ heat = CO

Complete combustion

2

Natural gas

+ 2H

2

O + heat

1 Cu Ft of CH

4

+ 10 Cu Ft of air for complete combustion

11 Cu Ft of flue gases

Combustion Air

Must supply sufficient air for complete combustion when all appliances are in operation simultaneously.

Must determine whether CAZ is a confined or unconfined space per NFPA.

Tightening a dwelling too much may result in the need to bring in outside air for combustion regardless of NFPA classification.

Must follow established standards for bringing in combustion air.

Confined / Unconfined

Confined Space

Not enough air in the combustion appliance zone to provide for complete combustion when all appliances are operating and the building is set in worst case criteria.

Unconfined Space

Enough air is present to provide for complete combustion when all combustion appliances are operating and the house is set for worst case criteria.

Standard 1/20 Rule

Measure the volume of the CAZ.

Add all input Btu ratings of appliance in the CAZ.

If dryer is in CAZ

Electric – consider input rate of 100,000

Gas – consider input rate of 125,000

Divide this total Btu by 20.

The resulting number is the Cu. Ft. separating confined from unconfined space.

Volume of CAZ below result = confined space

Volume of CAZ above result = unconfined space

Example

CAZ = 10’L X 14’W X 8’H

Appliances

• Gas furnace – 75,000 Btu input

• Hot water heater – 40,000 Btu input

• Gas dryer - 125,000 Btu input

Solution

CAZ = 10’L X 14’W X 8’H

Volume = 1120 Cu’

Total appliance input Btu

240,000 Btu

1/20

240,000 ÷ 20 = 12,000 cu ft.

Actual volume is below 12,000 cu ft

CAZ is a confined space

Results: Additional combustion air must be brought into the CAZ

Other Than Standard:

IMPORTANT! The above standard is based on a known infiltration rate of less than .4 air changes per hour

When the ACH is known

For appliances other than fan-assisted, consult NFPA 54 8.3.2.2(1)

For fan-assisted appliances, consult NFPA

54 8.3.2.2(2)

Table

9.3.2.2(a)

Natural

Draft

Appliances

Table

9.3.2.2(b)

Fan Assisted

Appliances

Methods of Bringing In

Combustion Air

Within the dwelling, from other zones

Ducted in horizontally from OD

Directly from OD above and or below

What is Draft

Negative pressure within a flue that pulls products of combustion out from the dwelling.

Factors That Affect

Draft Pressure

Delta T, Indoors to Outdoors

Height of Vent

Interior Volume

Restrictions

Atmospheric Conditions

Pressure Imbalances in the CAZ

Air Flow

How Does A Venting

System Work?

Combustion Gases

What is Considered

Adequate Draft?

OD temp >80 0 F, >-1 Pa or - .005”WC

OD temp 30 0 – 80 0 F, >-2.5 Pa or -.01”WC

OD temp below 30 0 F, >-5 Pa or -.02”WC

(250 pascal = 1”W.C.)

Most Common Poor Draft

Factors Found in the Field

Return air leaks in the basement

Long horizontal vent connectors

Blocked vents

Deteriorated flue

Bird nests

Outside masonry flues with fan assisted heating appliances

Fireplaces with no outside combustion air and without front enclosures.

Overly tight houses

VENTING CATEGORIES

Venting Categories

NFPA 54 and 58 criteria

Standardized

Category I

• Negative pressure, non-condensing

Category II

• Negative Pressure, condensing

• No longer produced

Category III

• Positive pressure, non-condensing

Category IV

• Positive pressure, condensing

Category I

What we normally think of when we think chimney

Negative pressure sucks products of combustion from the appliance breech and deposits them outdoors

Category II

No longer manufactured

Negative pressure vent with combustion gases at or below the dew point

Heavy gases at the dew point are not buoyant enough to vent with a negative pressure flue

Category III

Direct sidewall vented without additional apparatus.

Positive pressure requires joints in flue material to be sealed

Because these 80% appliance flue gases are close to the dew point, and the vent material is single wall, corrosion resistant materials must be used

Drains are typically incorporated to remove flue condensation before it enters the heat exchanger

Category III

Has been used to solve installation problems where no appropriate flue is available

Positive pressure requires joints in flue material to be sealed

Category IV

Positive pressure condensing appliances, joints must be sealed

90%+ AFUE

Appliances are designed to dispose of flue condensate as well as condensate formed within the secondary heat exchanger

May be able to sidewall vent at reduced distances to openings in the building than NFPA suggests

Sealed combustion

Combustion air intake in same pressure plane

Category I Vent Materials

Found With Older Heating

Appliances

Single wall galvanized pipe, 26 gauge

Only as a connector on 70% AFUE and lower gas appliances and all oil appliances

Connector for oil appliances

Masonry

Vitreous clay liner

Oil appliances

Transite

Rated as single wall

Asbestos

Does not meet any venting requirements

Category I Vent Materials cont.

“B” Vent – double wall

Galvanized steel outside, aluminum inner pipe

Rated only for gas appliances

Used as a vent connector for all 78% and

80% AFUE appliances

May not be run outside of the building

Used as a liner in an existing flue chase

Category I Vent Materials

Flexible liner

cont.

Aluminum – gas appliances

Stainless Steel – gas and oil appliances

Used to retrofit existing flue passages to meet code or a specific application

“L” Vent – double wall

Inner and outer pipes are stainless steel

Oil appliances

All Fuel, double wall insulated

Oil

Solid Fuels

Category III Flue Materials

Aluminum

No longer recommended because of corrosion problems

Stainless Steel

Use type specified by manufacturers to reduce corrosion issues

High temperature plastic

Was the most common material specified by manufacturers

Have been involved in recall

Manufacturer specific installation protocol

• Sealed joints, High temperature sealant

• Hanger spacing

• Pitch back to appliance ¼” per Ft.

Category IV Flue Materials

PVC

Low cost

Sealed joints

Must be provided with adequate hanging support

Pitch – back to appliance ¼” per

Ft.

CPVC

Higher operating temperatures than PVC

Follow manufacturer instructions

Manufacturer specific

Sealed Joints

Water In The Flue

Water is a byproduct of combustion

Key for category I appliances is to maintain water in a gaseous state within the flue so that it exits to the outdoors.

Category IV appliances are engineered to remove liquid water from within the secondary heat exchanger and flue.

• 93# (lbs) ~ 10 gallons

• Million Btu = 100,000 Btu @

10 Hrs run time

• 10 Hr run time for natural gas = 10 gallons of water that must be removed from the flue.

70% AFUE Gas Furnace

Overview

21 Cu Ft flue gases for every 1 Cu Ft of natural gas burned

Draft diverter mixes the extra ~10 Cu Ft of air with the flue gases before entering the flue

Reduced efficiency means more heat going up the chimney, hot flue gases (450 0 – 600 0 F)

Dilution gases reduce the relative humidity and increases the dew point

Draft Hood Appliances

1 Cu Ft CH

4

+ 10 Cu Ft air

+ 10 Cu Ft of dilution air mixed at draft hood

21 Cu Ft of flue gases up chimney under maximized conditions

Draft hood

 aids in minimizing fluctuation of draft

Prevents backdraft from affecting burner

Spill Switch

78% & 80% AFUE Furnace

Venting Overview

Draft induced fan does not force flue gasses into the vent.

A category I flue of adequate design must be used

More heat in the building and less up the chimney yields a colder chimney

Cycle time is longer than older furnaces to adequately warm the flue and keep moisture in a gaseous state.

TO WARM UP A CHIMNEY

 If firing rate = 100,000 Btu/hr and SSE = 75%, then 75,000

Btu/hr go to the distribution system and 25,000 Btu/hr go through the vent.

If the burner on-cycle is 12 minutes (.2 hrs), then during one cycle the vent receives:

.2 hr x 25,000 Btu/hr = 5,000 Btu/cycle

MASONRY CHIMNEY:

A masonry chimney (block or brick + tile liner) requires about

4570 Btu/.ft. to go from 0 o to 120 o . So, on a very cold day, about one foot of chimney will be warmed in one burner cycle:

5,000 Btu/cycle @4,570Btu/ft = 1 ft/cycle

TYPE B-VENT CHIMNEY:

A 6" B-vent chimney requires about 90 Btu/.ft. to go from 0 o to

120 o . So,

5,000 Btu/cycle @ 90Btu/ft = 55 ft/cycle

After Weatherization with a

New Furnace:

 If firing rate = 75,000 Btu/hr and SSE =82%, then 61,500 Btu/hr go to the distribution system and 13,500 Btu/hr go through the vent.

 If the burner on-cycle is 6 minutes (.1hrs), then during one cycle the vent receives:

 .1hr x 13,500 Btu/hr =1,350 Btu/cycle

 EXISTING MASONRY CHIMNEY:

 About four inches of the existing masonry chimney will be warmed during one burner cycle:

 1,350 Btu/cycle @ 4,570Btu/ft = .3 ft/cycle

 TYPE B-VENT CHIMNEY:

 During each burner on cycle, enough heat to warm 15feet of B vent goes into the chimney:

 1,350 Btu/cycle @ 90Btu/ft = 15 ft/cycle

Draft Induced Category I Venting

Guidelines

No exterior masonry chimneys without a properly sized metal liner.

Flex or “B”

No interior masonry chimneys over 2 stories

No transite chimneys

No unlined masonry chimneys

No masonry chimneys unless common vented with a draft hood type appliance without a vent damper

Draft Induced Category I

Venting Guidelines

(cont.)

Must have double wall “B” vent connector

Furnace must be properly sized

Furnace must be set up correctly

Temperature rise

Gas input

Heat anticipator or cycle rate set @ 3 cycles per hour

Vent sizing should be in accordance with tables supplied with the furnace or NFPA

When sidewall venting a power vent kit must be used unless the manufacturer specifies otherwise.

New Category I Venting

Rules-Of-Thumb

Use “B” vent as connector from the appliance to the flue

Reduce heat loss in the connector

Pitch connector down toward appliance ¼” per Ft.

Warm air rises

Maximum horizontal distance

(Table 13.2.2)

1 ½ times the diameter of the connector in feet

4” connector = 6’ maximum horizontal distance

Rule-Of-Thumb Continued

Follow NFPA 54 sizing charts

Never used unlined masonry flue

Don’t use outside masonry flue

Never use Transite

If you take the heating appliance out of the flue and leave the water heater in, you are responsible to ensure the water heater will vent properly

Line the flue

Oil Appliance Venting

NFPA 31 sizing guidelines

Masonry

Type “L”

 stainless steel

All fuel

“L” Vent

What We Should See In The Field

Outside

Masonry

“B” Vent

Barometric damper

(“swinging door”) in an oil-fired warm air furnace vent.

Drill test hole between the breech and the barometric damper

Why The Fuss About Venting

Fan Assisted Gas Appliances?

11 Cu Ft flue gas for every 1 Cu

Ft natural gas (Vs. 21 Cu Ft for

70% AFUE)

Lower flue gas temperatures,

(350 0 F)

No dilution air (no draft hood) so gases are close to the dew point

Water must stay in gaseous state to be removed from the building

KEEP FLUE GAS AS WARM

AS POSSIBLE

Tools & Equipment Used for

Vent Inspection & Sizing

NFPA manual

54, Natural Gas

58, LP Gas

31, Oil

211, Solid Fuels

Tape measure

Flashlight

Mirror

Combustion Analyzer

Pressure Probe

Temperature Probe

Boroscope

Digital Cameral

Safety Inspection of the

Venting System

Inside visual inspection

General Safety Inspection

Vent connections

Internal flue inspection

Outside visual inspection

CAZ Test

1” Clearance?

Fire stop?

Combustible?

Flue Safety

Clearance to combustibles

6” single wall pipe, gas

9” single wall pipe, oil

1” “B” vent, gas

Single wall connectors must not pass through walls.

Spill switches

Flue blockage

Condition of flue materials

Draft under worst case conditions

Corrosion

Vent Connections

Pitch

Inspecting An Existing Application

Remove vent connector

Inspect with mirror & light

Is the vent straight or is there an offset

Is there a liner present

Are tiles cracked allowing flue gas to escape

Blockage

Examine termination from outside

Cap

Condition of flue

An appliance that produces soot is a cause for concern.

Auditor should call for clean and service.

Evidence of backdrafting

Unsafe vent

Check the chimney for accumulated debris.

Oil-fired boiler before cleaning – plugged with soot after several years without service.

Same boiler after cleaning

Transite

Connector

Must be

Supported at Base

Termination

Failure

B-vent exposed to the outdoors & not properly supported

Does not meet code

(13.2.20)

Sizing tables 13.6 through 13.10 are not to be used for “B” vent exposed to the outdoors below the roofline.

Draft assisted furnace, or only water heater left in flue?

Condensation bleed through

Condensation

Damage

CAZ Test

Place building in winter mode

Place all combustion appliances in pilot mode, or turn off

Energize all exhaust fans

Measure pressure difference between CAZ in relation to outdoors

Open and close interior doors until the worst case draft condition is reached

Must have draft to continue

OD temp >80 0 F, >-1 Pa or - .005”WC

OD temp 30 0 – 80 0 F, >-2.5 Pa or -.01”WC

OD temp below 30 0 F, >-5 Pa or -.02”WC

Vent Dampers

Used to reduce off cycle losses

Motorized

End switch safety

Thermal

Spill Switch

Thermal Vent Damper

Bimetal petals warp open when heated

Vent Terminations

Follow manufacturer instructions

Use NFPA guidelines if manufacturer instructions are not available

Category I Chimney termination:

A chimney shall extend at least 3 ft. above the highest point where it passes through a roof of a building and at least

2 ft. higher than any portion of a building within a horizontal distance of 10 ft.

Sealed Combustion

Category IV

Concentric Vent Category IV

Alternative Venting

Look for conditions that may affect health or safety of the occupants, the weatherization crew, and YOU.

Dangerous vent, fire hazards, CO, fuel leaks, etc.

Complete a Health and

Safety Warning form if necessary.

Scary, home-made distribution system

REALLY scary homemade vent connector

Sizing Category I Vents

Use the appropriate NFPA manual

54 for Natural gas

58 for LP for Oil

211 for Solid fuels

Find the appropriate chart

One or more appliances?

“B” Vent or masonry?

“B” Connector or single wall?

Using NFPA Sizing Charts

Height of flue

From top of tallest appliance to the top of the flue termination

Increasing the height increases the draw

Horizontal distance to flue

Used with single appliance application

Increased horizontal run decreases draw

Vertical connector height

From the appliance breech to the point where flue gases combine

Used with multiple appliances

Elbows – Charts are listed with up to (2) 90 0 elbows in the vent

Problem #1

Single draft assisted appliance

50,000 BTU input rate

Total chimney height = 17’

Lateral distance = 3’

“B” vent and connector

Problem #2

2 category I appliances

50,000 BTU fan assisted furnace

• Connector rise = 2’

30,000 BTU water heater

• Connector rise = 3’

“B” vent with “B” connectors

Chimney height = 18’

Flexible Flue Liner

Follow manufacturer sizing tables

Use NFPA sizing tables, but reduce capacity by 20%

The masonry or original flue is used as a chase for the liner

If a liner is installed, the remaining space around the liner can not be used to vent other appliances.

More than one liner may be installed in the masonry chase

Other Liner Materials

“B” vent may be used as a liner

Drop down an inadequate or improperly sized flue

Original flue must be straight.

SS flexible liner

1.

2.

3.

4.

5.

Review

The height of a chimney is identified as:

If the chimney height falls between two columns in the NFPA chart, do you round up or down?

For a single category I appliance installation, if the lateral distance falls between two value on the chart, do you round up or down?

Can you use NFPA charts to size a flexible chimney liner?

What is one advantage of using a flexible liner over “B” vent?

Vent Free Heaters

NYS WAP Policy

Operational Requirements

Oxygen Depletion Sensor

NYS WAP Policy

WAP funds cannot be used to purchase or install any type of unvented or ventless combustion appliance including but not limited to unvented kerosene space heaters, unvented natural gas space heaters, unvented propane space heaters, unvented gas fireplaces, and unvented gas fireplace logs.

IAQ / Health & Safety Tests

Unvented Space Heaters: Educate the client about the potential danger of CO and fire from unvented space heaters. Explain that significant amounts of combustion products including water vapor and CO2 are produced.

Combustion Air

Must supply combustion air while operating

Open window while operating

Tucson instructions require defining the space as confined / unconfined

Products of combustion remain in the conditioned space

Must provide some measure of safety for oxygen depletion

Fresh Air Requirements

Tucson Heater

Oxygen Depletion Sensor

If You Take Away Nothing Else

KEEP THE WATER IN A GASEOUS STATE

WHILE IN THE FLUE

Use “B”vent connectors on any new category I gas appliance installation

Most masonry chimney’s will need a liner

Never leave a water heater in a flue alone without ensuring it will vent

Download