Evaporative Cooling

advertisement
Energy Efficient Buildings
Evaporative Cooling
Examples of evaporative cooling include:
Boiling water
Evaporation from body
Evaporation from lakes and oceans
Roof ponds
Roof misting
Swimming pools
Cooling towers
The energy transferred during evaporation is so great, that it can effectively cool
buildings using relatively little energy. A typical residential-size evaporative cooler is
shown below. In this unit, a fan pulls outdoor air through the sides of the unit and
forces it into a duct that leads into the conditioned space. Water from the “water tank”
in the bottom of the unit is pumped to the top of the unit and falls through fibrous mats
called “evaporative pads” that line three sides of the unit. As outdoor air is pulled
through the wet “evaporative pads”, it evaporates some of the water and leaves at a
lower temperature and higher humidity. These units are sometimes called “swamp
coolers” and are widely used in hot dry climates, since they cool and humidify air using
very little energy.
1
As air passes through the wet evaporative pads, the air gives up sensible heat to
evaporate the water; hence the temperature of the air decreases. Simultaneously, the
air is gaining latent energy and the humidity of the air increases. The overall process
occurs at constant enthalpy; hence the process is adiabatic. The process is depicted on
the psychrometric chart shown below. First consider outdoor air in hot dry Arizona at T
= 90 F and RH = 25%. As the air passes through the wet “evaporative pads”, evaporative
cooling reduces the temperature at constant enthalpy. The minimum air temperature
occurs when air is 100% saturated. This minimum temperature could be achieved in an
infinitely thick evaporative pad. However, in practice the air leaves the evaporative pad
slightly less than 100% humidity. Thus, in Arizona the air temperature would be
reduced from a hot 90 F to a cool 70 %.
Next consider outdoor air in hot, humid Mississippi T = 90 F and RH = 70%. As the air
passes through the wet “evaporative pads”, evaporative cooling reduces the
temperature at constant enthalpy. The minimum air temperature would occur at about
82 F, and the actual leaving air temperature would be even higher. Thus, the cooling
potential of evaporative coolers is much greater in dry climates.
The performance of evaporative coolers can be modeled using the concept of
effectiveness. We define effectiveness as:
 Tactual T1 - T2,act


Tmax
T1 - Twb,1
2
Most coolers about 80% effective. In Arizona example shown above, the effectiveness
is:

T1 - T2,act
T1 - Twb,1

90  70
 80%
90 - 65
The effectiveness concept shows that that lowest possible temperature of the air exiting
the cooler is entering air wet-bulb temperature. Thus, wet-bulb temperature can be
used to as guide to the effectiveness of evaporative coolers. The chart below shows
95% design wet-bulb temperatures in the U.S. The graph shows that practically the
entire western part of the U.S. has design wet-bulb temperatures less than 70 F. This
suggests that evaporative coolers could regularly cool air to less than 70 F over most of
the western U.S., and do so using much less energy than vapor compression air
conditioners and chillers.
Sizing Stand-Alone Evaporative Coolers
To size stand-alone evaporative coolers it is necessary to determine the temperature,
Tsup, and flow rate, msup, of air supplied to the building. Consider the figure shown
below.
3
The first step is to solve for Tsup at design conditions.

Tdes - Tsup
 Tactual

Tmax
Tdes - Tdes, wb
Tsup  Tdes -  (Tdes - Tdes, wb )
If Tsup < Tset, then evaporative cooler can provide cooling.
The second step is to determine the flow rate of air at design conditions, msup, from an
energy balance on the house. Consider only the sensible heat load since an evaporative
cooler is incapable of removing moisture.
m sup c p Tsup  Q des,sen  m sup c p Tset
m sup 
Q des,sen
c p (Tsen - Tsup )
Indirect Evaporative-Cooling Systems
In most cases, direct evaporative cooling capacity declines when cooling loads increase.
Thus, direct evaporative cooling is often combined with some sort of supplementary
cooling.
An energy-efficient source of supplementary cooling is indirect evaporative cooling.
Indirect evaporative cooling systems use water from a cooling tower to cool air through
4
a heat exchanger. The word “indirect” refers to the fact that the cooling water does not
come into direct contact with the supply air to the building. To understand, indirect
evaporative cooling it is necessary to understand cooling tower performance.
Cooling Tower Performance
The performance of typical cooling tower at a water flow rate of 3 gpm/ton is shown
below. The curves predict the temperature of the cold water leaving the cooling tower
as a function of the water temperature range (Th-Tc) and entering air web bulb
temperature. Temperature range is generally known and can be used as an input value
in these charts.
Source: ASHRAE Handbook, HVAC Systems and Equipment, 2004.
5
Case Study of Building with Indirect/Direct Cooling
The office building described below houses a leading energy efficiency company in
Boulder Colorado. The building uses in indirect/direct cooling system to meet its entire
cooling load.
Example
Design an indirect/ direct evaporative cooling system for a building in Boulder Colorado
to maintain indoor air conditions of T4 = 72 F at RH4 = 60% or less with 100% outside air.
The peak load in the space is 60,000 Btu/hr and the sensible heat fraction is 70%.
Design outside air conditions are T0 = 91 F, Twb0 = 59 F. Find the volume flow rate of
supply air and water consumption of the evaporative cooler.. Assume the cooling tower
water to supply air heat exchanger is sized so that Th-Tc = 10 F.
6
A diagram of an indirect/direct evaporative cooling system is shown below. Indirect
cooling occurs when outside air is sensibly cooled by passing through a water-to-air heat
exchanger; the cool water for the heat exchanger is from a cooling tower. Next the air
temperature is further reduced by direct evaporative cooling.
Th
Cooling
Tower
Qspace = 60,000 Btu/hr, SHF = 70%
Evap
Cooler
0
1
2
3
Conditioned
Space
Tc
4
The temperature of water from the cooling tower, Tc, is a function of Twb and the
temperature range (Th-Tc) = 10 F. At these conditions, Tc = 73 F. With 73 F cooling
water, the air leaving the heat exchanger can be cooled to T2 = 78 F.
The performance of the system is depicted on the psychrometric chart for elevation of
5,000 ft shown below. Outdoor air enters at 0 and is cooled indirectly to 2 by the waterto-air heat exchanger. The air leaves the 80%-effective direct-evaporative cooler at 3’.
The cool air at 3’ is delivered to the conditioned space and leaves at the zone set-point
temperature of 72 F at point 4’. The slope of the line from 3’ to 4’ is determined by the
ratio of sensible to latent heat added in the zone.
7
If the evaporative cooler is 80% effective then:

 Tactual
T -T
 2 3'
Tmax
T2 - T2,wb
T3'  T2 -  (T2 - T2,wb )  78 - 0.8 ( 78 - 54 )  58.8 F
At T3' = 58.8 F, i3' = 24.7 Btu/lba. Point 4’ must lie on line starting at 3’ and with a slope
defined by the zone SHR = 0.70. The enthalpy at 4’ is i4' = 29.6 Btu/lba. An energy
balance on space gives:
ma = Qspace / (i4' - i3') = 60,000 Btu/hr / (29.6 - 24.7) Btu/lba = 12,245 lba/hr
Va = ma v0 = 12,245 lba/hr x 16.8 ft3/lba / 60 min/hr = 3,429 cfm
Mass balance on water through evaporative cooler gives:
mw = ma (w3' - w2) = 12,245 lba/hr (0.0096 - 0.0056) lbw/lba
mw = 49.0 lb/hr = 5.9 gallons/hr
Assuming the total water + sewer charge for water is $5.00 /ccf, the cost of water would
be about:
8
Cw = 5.9 gallons/hr $5.00 /ccf / (7.48 gal/ft3 100 ft3/cf) = $0.039 /hr
For comparison, the cost of electricity for a 0.6 kW/ton chiller if electricity cost $0.10
/kWh would be about:
Ce = 60,000 Btu/hr 0.6 kW/ton / (12,000 Btu/ton-hr) x $0.10 /kWh = $0.300 /hr
In this example, the cost of electrical cooling is about 7 times greater than the cost of
evaporative cooling.