Retro-Cx

advertisement

Retro-Commissioning:

A Tool for Improving

HVAC

Systems and Energy Cost

Reduction

Speaker:

William McGuire, P.E.

AGENDA

Retro-Commissioning of Existing

Buildings

Why Retro-Cx

What is Retro-Cx ?

How do you do it / what to look for

Case Studies

Take-Away

Why Retro-Cx

• Older bldgs. (Pre 1990) on average consume more energy

• Antiquated control systems that don’t work

• Energy saving control strategies missed in design

• Neglected maintenance wasting energy and/or causing

IAQ problems

• System upgrades that miss the mark

• Building usage / floor plans changed

Why Retro-Cx

• Energy cost are only expected to rise

• Economic outlook may prevent new construction

• Employee / Community goodwill – “It’s the right thing to do”

• Owners learn more about their own facilities

• Benefits intended to be long lasting

• Simple payback typically less than two years

Why Retro-Cx

Leased Buildings

• LEED EB / ENERGY STAR buildings may become a differentiator

• High energy costs translate into increased rent cost

Why Retro-Cx

Source: US Government Energy Information Administration

Consumption in Gross Energy by Year Constructed - 2003

Energy intensity

10% less

45% less energy consumed

New buildings 35% to 57% more efficient

Why Retro-Cx

A study by Lawrence Berkeley National Laboratory (LBNL) -

2004

Retro-Cx results

• Whole-building electricity savings range from 5% to 15%

• Gas savings range from 1% to 23%

• Payback ranged from 0.2 to 2.1 years

• The bigger the building typically the better the payback period

• Small buildings have opportunity as well

Source: A RetroCommissioning Guide for Building Owners -

PECI

Why Retro-Cx

Lawrence Berkeley National Laboratory (LBNL) – 2004

Value of Energy Savings

Value of Non Energy Savings

$0.11 - $0.72/ft

$0.10 - $0.45/ft

2

2

Non Energy: Equip Life, thermal comfort, IAQ, productivity, liability, etc.

Why Retro-Cx

1996 PECI/EPA/DOE Study of 60 Commercial

Buildings:

15%

33%

40%

HVAC

Problems

Sensors not operating properly

Missing

Equipment

Why Retro-Cx

Retro-Commissioning X-nth Examples

Energy Savings $/sf

Annual Savings Building Sq.Ft.

Savings $/sf % Energy Savings

Hospital

Healthcare

Hospital

Hospital

Office Bldg

Building

Hospital in Orlando

University Research Bldg

Aquarium

Casino

Hospital in Central Florida

185,000

100,000

190,000

150,000

54,000

$100,000

$135,000

$75,000

$80,000

$38,500

ROI

Annual Savings

$200,000

$114,000

$200,000

$75,000

$200,000

$0.54

$1.35

$0.39

$0.53

$0.71

5 year ROI

2,000 %

2,000 %

350 %

400 %

450 %

18%

30%

13%

18%

40%

Retro-commissioning is “GREENER”

If Retro-commissioning our existing buildings can save just 10% energy consumption

•Reduce oil imports by 50%.

•Almost meets Kyoto Protocol.

Exploit our existing buildings, not the environment !

What is

Retro-

Commissioning?

What is Retro-Cx

RETRO-Commissioning is evaluating and performance testing an Existing building’s HVAC….

DISCOM

Design

Installation

Set-up / TAB

Controls /

Optimization

Operation

Maintenance

What is Retro-Cx

Reveals hidden deficiencies that could have been avoided by commissioning.

Highlights O&M problems that could have been avoided through better training.

Reveals hidden control system problems, lowering energy costs.

What is Retro-Cx

Retro-Cx is NOT an energy study!

• Energy studies leave the Owner with proof of what they already suspect , something is wrong .

• It provides no answers as to what to do or were to start.

• Skip all the paperwork and go find the MONEY

What is Retro-Cx

Retro-Commissioning Defined: It’s a Tune-up, not just an

ECM list

PROCESS: An experienced commissioning team investigates the existing systems operation looking for equipment and systems that are not operating “properly”.

RESULT: The most common HVAC discovery is even though the space temperatures are comfortable, the systems are consuming much more energy than necessary due to overcooling, over-heating, over-ventilating. Reveals hidden problems in DISCO&M.

COST: Retro-commissioning’s cost is a few weeks of time for the commissioning team. The cost savings discovered usually pay back the retro-commissioning cost in months.

Retro-

Commissioning

How do you do it?

Uncovering the waste in

DISCO&M

Show Me the Easy Money

HVAC Energy Cost Can Vary Widely

“ Average” building = 46%

HVAC

Energy Cost vs. HVAC Complexity

$2.00/sf Light Commercial

$3.00

Office/School

$4.00

$5.00

$6.00

Institutional

24/7 Hospital

Laboratory

“Wasteful” building =

2X

HVAC Energy Cost

Variation

$1-2 = Good

$4-6 = Evil

Where is the HVAC Energy

Savings?

HVAC systems have many combinations of gas pedal / brake pedals that could be affected by improper

DISCO&M.

Where to Start?

Although each building and system is unique you can start with the following:

• Interview facility personnel

• Review construction documents

• Review the controls workstation

• Walk the site

Where to Start?

Interview facility personnel

• They are a great resource as to why things are the way they are but not necessarily on how they should be

• Keep them informed on what you find, it may trigger additional thoughts

• If interested, train them on how the systems work

Where to Start?

Review construction documents

• Understand the design and how the systems are supposed to work

– Use the schedules and rules of thumb

– Sum up connected loads (air and water)

– Compare design installation to installed

– Check coil ∆Ts

Where to Start?

Review the Controls workstation and look for:

– Incorrect AHU leaving air temperature set points

– Valve commands at 0% or 100%, or valves fighting

– OA Damper commands

– Controlling sensors like RH and CO2

– Pump / fan status on when command is off (in

HAND?)

– Chilled water ∆T (secondary supply & primary return)

– Chilled water supply temperature / set point

– General space temperatures

– System stability

AHU Controls Interrogation

Retro-Cx Example

Dehumidification

Setpoint

Search for

Improper

Set points

Device Operation

Modes

Input values

OA damper position

Coil LAT

Unit LAT

Setpoint

Most common discovery during Retro-Commissioning –

CONTROLS not Optimized:

GAS PEDAL is floored, but the BRAKES are used to control the speed of the systems.

SA SP

Setpoint

Things to look for

Hidden DISCO&M Problems = High Energy

Costs

VFD

DP

OA

SA

T

T

VAV

RA

“DIS” Problems

Improper programming sequence

Coils piped backwards

OA damper occ. / unocc. set points

VAV damper actuator / calibration

Service access restricted

Space thermostat calibration

Sensors in wrong location

VFD / fan sheave sized for ‘max concurrent’

“CO&M” Problems

Overridden BAS temp space set points

Increased VAV airflow set points

High duct static DP set point

Disabled duct static DP reset logic

Decreased cooling coil setpoint

Preheat and Cooling coil fighting

Disable supply air temp reset logic

Actual OA damper position

Dirty filters

T

Things to look for

Chiller Plants

Add / subtract logic

Incorrect set points (chiller and system)

Chillers / pumps / tower fans in manual

Condenser water control

Controlling sensor calibration

Chiller isolation valves

Use Your Experience

• Does the number of operating chillers / boilers make sense?

– Add/subtract logic

– Sensor calibration

– Decoupler issues

• Does the duct static pressure set point seem right?

– Who’s set point is it?

– Sensor calibration?

• Does the number of pumps operating make sense?

– Do the differential water pressure set points make sense?

– Sensor location / calibration

Where is the HVAC Energy

Savings?

Benchmarks

1 hp motor =

Annual Elec Cost

$500

1 Ton cooling (MA unit)

1,000 CFM OA (8 tons)

1 degree Setpoint on AHU

$750 = DX

$400 = CHW

$10,000 = DX

$5,000 = CHW

7% of cooling capacity

(10,000 cfm = 35 tons)

CEP generation capacity = ‘Load’, Attack the Load first

Retro-Commissioning Exercise

Expose the ‘Evil’ in HVAC Systems

One foot on the gas, one on the brake

T T

VFD

DP

VAV

T

One foot on the gas

T T

VFD

DP

VAV

T

Identical air handling systems keep the space comfortable at 72F.

One uses twice the energy.

HOW? Systems sized for peak loads and operates inbetween .

Retro-Commissioning Exercise

Evil Performance = 2 x Groovy

T

T

VFD

DP

Both set-ups have comfortable 72F space temps !!

VAV

T

System Component

Performance

Cost (6 summer months) =

Fan 7,500 cfm =

OA 2,500 cfm (95F/78F) =

(50F LAT, +OA)

Preheat coil =

Reheat coils 20% =

Chilled water 45F =

(42F)

The

Good!

Performance

$12,000 (62 kW, $.07)

5 kW

0 kW

9.5 kW

47 kW (45F)

33 tons (52 LAT)

The

Bad!

$25,000 (129 kW)

10 kW

45 tons

23 kW

23 kW (50%)

72 kW

Retro-

Commissioning

4 Case Studies

Retro-

Commissioning

DISCO&M Case Study

#1

Building

“CO&M”

HVAC System operators and the

Controls vendor were not familiar with the basis of design.

University Biological Science Bldg: Fan Frame

Problems

Two parallel

AHUs headered together

30,000 CFM variable speed fans

4 Different stories of how the ‘system’ was supposed to operate ??

Fan motor frame that kept breaking requiring rewelding

University Biological Science Bldg: – Fan Operation in Surge

Turbulent

‘surge’ zone of fan curve

60 Hz

Design

Adjusted operating point, 49Hz.

45 Hz

30 Hz

Fan Curve #1: Occupied Conditions

Fan Curve #2: Unoccupied Conditions untrained staff

Savings:

How:

$15,000

Fans allowed to back off from 60Hz to 30Hz at

University Biological Science Building Hidden

Discoveries

Static pressure setpoint set too high at 2.2” , instead of 1.0”.

VFD

Fan always at 60Hz.

DP

OA

SA

T

T Re-heat coil required to heat the overcooled air.

VAV

RA

T

Pre-heat Coil improperly on.

Heating summer air from 84F up to 104F .

Cooling Coil actuator broken. Overcooling the air to 49F instead of 55F.

2-position VAV box closing more than necessary to ‘eat’ excess static pressure.

Water Side

Gas: pre-heat coil

Brakes: cooling coil

Gas: re-heat coil

Air Side

Gas: Supply fan

Brakes: VAV damper

University Biological Science Bldg: Retro-Cx Results

PROBLEM

AHU 1-1 Low Leaving Air Temp – Re-heating by VAV:

AHU 1-1 Low Leaving Air Temp – Over-cooling:

AHU 1-1 Pre-heat Coil Operation – Pre-heating:

AHU 1-1 Pre-heat Coil Operation – Re-cooling:

AHU Excess Fan Speed:

Total:

SAVINGS DISCO&M

$15,000 C,O

$30,000 M

$27,000 M

$25,000 M

$17,000 C,O,M

$114,000 per year.

Baseline Savings:

($0.90 / sf)

$114,000 /yr

Prevention: Training

Legacy

Retro-

Commissioning

DISCO&M Case Study

#2

“DSCO&M”

Corporate Mandate: 10% energy savings.

HVAC operators did not understand where the ‘optimized’ operating points were

.

BAS Interrogation - Observed

Problems

Improper Technician set-up of Drives. Release 60hz ceiling for direct drive fans .

Should be

<100% at part load

1.5” ???

Overflowing = extra pumping

BAS Interrogation - VAV w/ Reheat

Optimization Opportunities from Base Design

Min airflow, max heating, still over-cooling the space?

Room is 2 deg lower than setpoint

.

BAS Interrogation - Cooling Towers

Bad Operating Advice from Technician

Technician said lower CW temp.

When OA is 65ºF WB, you cant get less than

71ºF regardless of tower speed.

(6F approach)

BAS Interrogation - CHW

Installation Defects, Bad Data

How did the CHWS go from 44ºF to

50ºF ?

“Short

Decoupler

Effect”

BAS Interrogation - HW Boilers

Improper Base Sequence of Operations

Design coil delta-T is

40ºF

The boilers are dying from short cycling at

20% loading

.

Retro-Commissioning

Case Study #2: Summary

Primary Items

Cooling Tower Operation – Turn 1 off, and modify software for condenser water reset based upon wet bulb temp. Save $1200 /wk for 20 weeks = $24,000

Hot Water Boiler Sequence – Revise controls to turn off lag boiler properly. Save boiler fuel from eliminating pre- and post-purge heat loss. +/- $20,000

Fix CHW Low Delta-T Problem – save secondary pump energy by pumping less colder water. Save 40kw for ½ year = $80,000

AHU Static Pressure 1.5” Setpoint – Optimize SP’s lower to save fan energy.

Assume 5% savings of 475 bhp fan motors = $50,000

Secondary Items

CHW – Constant speed pumps with variable 2-way valves; design oversight? Can save pump energy by going variable primary (add drives). $20,000

VAV with Reheat – many are reheating. Min cfm setting could be lowered to avoid reheating. And SATR logic can be implemented. Save +/$big

Retro-Commissioning Results

PROBLEM

DISCO&M

Cooling Tower Operation:

O

Hot Water Boiler Sequence:

Chilled Water: Low Delta-T Syndrome

AHU Static Pressure Setpoint Optimization:

S

SAVINGS

$24,000

$20,000 IS

$80,000 D or I

$50,000

Constant pump CHW system with 2-way valves : $20,000

VAV re-heating setpoints:

Baseline Savings:

$200,000 /yr

($0.50 / sf)

$ big

D

Total: $200,000 per year.

Retro-

Commissioning

“O&M”

Looking for HIDDEN CAPACITY resulting from possible improper operation.

Hospital BAS Interrogation - Typical Air Handling

Unit

1. Chilled Water Valve – failed open, making 49.6ºF air. 5.4ºF colder than set point

2. Supply Fan VFD – is at 100%, no spare capacity for filter loading

3. Outdoor air damper – Software Override (SWO), changed from design setpoint

Hospital BAS Interrogation - Chiller Plant

Return Chilled water temperature is too low. The return temperature should be 58F. Too many chilled water coils are over-flowing, and producing low return water temperatures. Another LOW

DELTA-T PROBLEM.

The flow of 1149 gpm and the calculated tons of 359, calculate a flow rate of 3.2 gpm/ton. The secondary CHW is pumping over 50% more chilled water than it should be due to failed open

AHU chilled water valves.

Retro-Commissioning

Case Study #3: Summary Not-for-profit Hospital

6 of 30 Air Handling Units had hidden cooling coil valve problems.

Heating boilers are re-heating the overcooled air.

The spare central plant capacity that was ‘discovered’:

Cooling:

Heating:

142 Tons (new spare capacity)

1.7 million btuh (25% of one big boiler)

Baseline Savings: sf)

$200,000 /yr ($0.90 /

Retro-Cx Investment: 1 day

Value:

($1000/ton)

( Incidental)

Defer new 1000 ton chiller

Retro-

Commissioning

“DISCO&M”

Administration wanted energy savings.

Facilities Staff did not want anyone

(us) to look at their system and find potential problems – it might make them look bad.

Hospital BAS Interrogation - Chiller Plant Logic

Problems

Three 550 ton chillers

ON.

(1650 tons)

Building

Load 1000 tons.

(2 chillers needed)

Improper Chiller OFF Logic – Operating more pumps & towers than necessary

For-Profit Hospital: Improper Constant Volume

Pump Set-up

Circuit Setter – 80%

Closed.

Should have trimmed impeller

For-Profit Hospital: AHU Investigation – Improper

Design

Original Design / Construction

Problems: Low first cost solutions = high long term operating costs

Retro-Commissioning

Case Study #4: Summary For-Profit Hospital

PROBLEM

DISCO&M

SAVINGS

AHU Supply Air Temp Reset Logic

Condenser Water Reset Temp Reset Logic

Chiller ON/OFF Logic

Pump Valve Adjustment

AHU Device Tune-up

DIS

Baseline Savings:

($1.50 / sf)

$10,000

$26,000

$58,000

$385,000 /yr

$72,000

$33,000

D

S

O&M

$186,000

Total: $385,000

Implementation Cost: $150,000

Retro-Cx Investment: 5 month

Prevention:

Design review ,

Performance Testing

Training

D

D

Take-Away

Retro-Commissioning Existing Buildings

WHAT TO LOOK FOR:

“Variable” systems and their set points

Gas/Brake systems – pre/re-heat, humidity, VAV, parallel equip

• Starters in ‘Hand’ mode because a control device isn’t working

• ‘HVAC loads’. CEP’s can only meet loads.

BAS Computer Screens = anything at 100% capacity

DISCO&M

Questions?

Download