SECTION 07720 - ROOF ACCESSORIES

Naturalite(TM) Skylight Systems
Oldcastle Glass® Engineered Products
750 Airport Road, P.O. Box 629
Terrell, TX 75160
(800) 527-4018
(972) 551-6400
fax: (972) 551-6420
This MANU-SPEC(TM) utilizes the Construction Specifications Institute (CSI)
Manual of Practice, including MasterFormat(c), SectionFormat(c) and
PageFormat(c). A MANU-SPEC is a manufacturer specific proprietary product
specification using the proprietary method of specifying applicable to project
specifications and master guide specifications. Optional text indicated by
brackets []; delete optional text in final copy of specification.
This MANU-SPEC specifies roof accessories; including roof scuttles and smoke
vents (listed and non-listed) and drop out fire domes, as manufactured by
Naturalite(TM) Skylights Systems, Oldcastle Glass® Engineered Products. Revise
MANU-SPEC section number and title below to suit project requirements,
specification practices and section content. Refer to CSI MasterFormat for other
section numbers and titles.
SECTION 07720
ROOF ACCESSORIES
This MANU-SPEC section has been developed in cooperation with ARCOM,
publishers of the MASTERSPEC? Master Specification System, a product of the
American Institute of Architects (AIA).
This section uses text from the
MASTERSPEC? Writer's Manual by permission from ARCOM. Refer to the
equivalent MASTERSPEC? section. ARCOM and the AIA do not endorse specific
manufacturers or products.
PART 1 - GENERAL
1.1 SUMMARY
A.
Section Includes: Roof accessories.
Note: Edit paragraph below for type of roof accessories to suit project requirements.
1. Types: Types of roof accessories include:
a.
b.
a.
b.
Roof scuttles.
Heat and smoke vents, non-listed.
c.
d.
e.
f.
c.
Heat and smoke vents, UL Listed .
d.
FM Approved Drop out fire domes.
e.
Fall protection screen.
f. Burglar bars/security grills.
Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and
titles per CSI MasterFormat and specifier's practice.
B.
Related Sections: Section(s) related to this section include:
1. Built-Up Bituminous Roofing: Division 7 Built-Up Roofing Sections.
2. Modified Bituminous Sheet Roofing: Division 7 Modified Bituminous Roofing
Sections.
3. Single Ply Membrane Roofing: Division 7 Single Ply Roofing Sections.
4. Flashing and Sheet Metal: Division 7 Flashing and Sheet Metal Section.
5. Sheet Metal Roofing: Division 7 Sheet Metal Roof Section.
Specifier Note: Article below may be omitted when specifying manufacturer's proprietary
products and recommended installation. Retain Reference Article when specifying
products and installation by an industry reference standard. If retained, list standard(s)
referenced in this section. Indicate issuing authority name, acronym, standard
designation and title. Establish policy for indicating edition date of standard referenced.
Conditions of the Contract or Division 1 References Section may establish the edition
date of standards. This article does not require compliance with standard, but is merely a
listing of references used. Article below should list only those industry standards
referenced in this section.
Note for REFERENCES Article - IF PERTINENT
Specifier's Note: References are not used in MASTERSPEC . This section is retained
from the MANU-SPEC section of that title.
1.2 REFERENCES
A. General: Standards listed by reference, including revisions by issuing authority,
form a part of this specification section to extent indicated. Standards listed are
identified by issuing authority, authority abbreviation, designation number, title or
other designation established by issuing authority. Standards subsequently
referenced herein are referred to by issuing authority abbreviation and standard
designation.
B.
Aluminum Association (AA):
1. AA Specifications for Aluminum Structures.
C. Underwriters Laboratories UL 793 - Standard for Safety Automatically Operated
Roof Vents for Smoke and Heat.
1. Factory Mutual.
D. National Roofing Contractors Association (NRCA):
1. NRCA Roofing and Waterproofing Manual.
E.
Standard 4430 - Approval Standard for Heat and Smoke Vents.
Specifier Note: Article below should be restricted to statements describing design or
performance requirements and functional (not dimensional) tolerances of a complete
system. Limit descriptions to composite and operational properties to extent necessary
to link multiple components of a system, and to interface with other systems.
1.3 SYSTEM DESCRIPTION
A. Performance Requirements: Provide roof accessories which have been
manufactured, fabricated and installed to withstand loads from [Specify
code/standard reference] and to maintain [Specify performance criteria]
performance criteria stated by manufacturer without defects, damage or failure.
B.
Roof Accessories Performance Requirements:
Specifier Note: Edit Performance Requirements paragraph below for loads to suit project
requirements. Roof accessories are commonly used in low-rise construction where roof
elevations do not exceed 60 feet above grade. Roof accessories should be designed to support
a minimum 20 psf snow load and a negative pressure or uplift of 20 psf. Greater capacities may
be required depending on code requirements or project location. Plastic glazing materials are
not designed to support live loads or concentrated impact type loads. "Risk of fall" label is
applied to each dome to warn of potential danger. (1) Performance Requirements: Referenced
standards establish the level of quality of roof accessories available from quality manufacturers
conforming to industry standards. (2) Condensation: Under certain conditions of high humidity
and/or large inside to outside temperature differentials, condensation may occur on the
aluminum framing and plastic glazing material. Thermally broken frames can be specified to
help control compensation on aluminum framing. Double glazing will usually reduce the
occurrence of condensation on the plastic, but will not totally eliminate it. The condensation that
forms between the double layers of plastic will normally dissipate as the airspace is heated by
the sun. Sealed domes are more resistant to the formation of condensation and will reduce
accumulation of dust and foreign matter. Sealed domes are available for most dome glazed unit
skylights at additional cost.
Specifier Note: Edit paragraph below. Specify values, minimum 20 psf recommended. For
Double Leaf Mechanical Heat and Smoke Vents (Part 2 Products) 30 psf required for listed
units.
1. Design framing and dome infill to support the following load requirements:
a.
b.
a.
b.
[Specify] PSF snow load plus dead load.
[Specify] PSF negative wind or uplift load plus dead load.
2. Labeled smoke vents should conform to the approval guidelines of either UL
or FM.
3. Fabrication and installation of roof accessories shall comply with NRCA
recommendation that the top of curb to finish roofing dimension be a minimum
of 8" (203.2 mm).
Specifier Note: Article below includes submittal of relevant data to be furnished by
Contractor either before, during, or after construction. Coordinate this article with
Architect's and Contractor's duties and responsibilities in Conditions of the Contract and
Division 1 Submittal Procedures Section.
1.4 SUBMITTALS
A. Shop Drawings: Submit shop drawings for approval prior to fabrication. Include
details of framing members, glazing materials where applicable, sealants, fasteners,
anchors and thicknesses and types of formed flashing and closures.
B. Samples: Submit selection and verification samples for finishes, colors and
textures.
1. Glazing Samples: Submit a verification sample of plastic glazing material in
specified color.
C. Quality Assurance Submittals: Submit the following:
1. Test Reports: Certified test reports or labeling agency file numbers indicating
compliance with specified performance characteristics and physical properties.
D. Closeout Submittals: Submit the following:
1. Operation and Maintenance Data: Operation and
installed products in accordance with Division 1
(Maintenance Data and Operation Data) Section.
maintaining installed products, and precautions against
methods detrimental to finishes and performance.
2. Warranty: Warranty documents specified herein.
maintenance data for
Closeout Submittals
Include methods for
cleaning materials and
Specifier Note: Article below should include prerequisites, standards, limitations and
criteria which establish an overall level of quality for products and workmanship for this
section. Coordinate below article with Division 1 Quality Assurance Section.
1.5 QUALITY ASSURANCE
A.
Qualifications:
1. Installer Qualifications: Installer experienced in performing work of this
section who has specialized in installation of work similar to that required for
this project.
a.
Installer: Roof accessories shall be installed by installers with a
minimum of two years experience in installation of similar units.
Specifier Note: Retain paragraph below to suit project requirements; otherwise
delete paragraph below.
b.
Certificate: When requested, submit certificate indicating qualification.
2. Manufacturer Qualifications:
a.
Manufacturer: Roof accessories shall be manufactured by a firm with
a minimum of 10 years experience in the fabrication and installation of roof
accessories.
Specifier Note: Paragraph below should list obligations for compliance with specific code
requirements particular to this section. General statements to comply with a particular code are
typically addressed in Conditions of the Contract and Division 1 Regulatory Requirements
Section. Repetitive statements should be avoided.
B. Regulatory Requirements: [Specify applicable requirements of regulatory
agencies]
Specifier Note: Article below should include special and unique requirements.
Coordinate article below with Division 1 Product Requirements Section.
1.6 DELIVERY, STORAGE & HANDLING
A.
General: Comply with Division 1 Product Requirements Sections.
B. Ordering: Comply with manufacturer's ordering instructions and lead time
requirements to avoid construction delays.
C. Delivery: Deliver materials in manufacturer's original, unopened, undamaged
containers with identification labels intact. Sequence deliveries to avoid delays, but
minimize on site storage.
D. Storage and Protection: Store materials protected from exposure to harmful
weather conditions and at temperature and humidity conditions recommended by
manufacturer.
1. Protect from damage from sunlight, weather, excessive temperatures and
construction operations.
1.7 PROJECT CONDITIONS
A. Field Measurements: Verify actual measurements/openings by field
measurements before fabrication; show recorded measurements on shop drawings.
Coordinate field measurements and fabrication schedule with construction progress
to avoid construction delays.
1. Measurements: Take accurate field measurements before fabrication. Do not
delay job progress; allow for field tolerances if taking field measurements before
fabrication is not possible.
Specifier Note: Coordinate article below with Conditions of the Contract and with
Division 1 Closeout Submittals (Warranty) Section.
1.8 WARRANTY
A. Project Warranty: Refer to Conditions of the Contract for project warranty
provisions.
B. Manufacturer's Warranty: Submit, for Owner's acceptance, manufacturer's
standard warranty document executed by authorized company official.
Specifier Note: Coordinate paragraph below with manufacturer's warranty requirements.
Manufacturer offers the Following: Roof Accessory Warranty: Provide written five-year warranty
signed by manufacturer, agreeing to repair or replace work which exhibits defects in materials or
workmanship and guaranteeing weathertight and leak free performance. "Defects" is defined as
uncontrolled leakage of water and abnormal aging or deterioration.
1. Warranty Period: 5 years commencing on date of invoice.
PART 2 - PRODUCTS
2.
Specifier Note: Retain article below for proprietary method specification. Add product attributes, performance characteristics, material standards,
and descriptions as applicable. Use of such phrases as "or equal" or "or approved equal," or similar phrases may cause ambiguity in
specifications. Such phrases require verification (procedural, legal and regulatory) and assignment of responsibility for determining "or equal"
products.
2.1 ROOF ACCESSORIES
A. Manufacturer:
Products.
Naturalite
Skylight
Systems,Oldcastle
Glass®
Engineered
Specifier Note: Paragraph below is an addition to CSI SectionFormat and a supplement to
MANU-SPEC. Retain or delete paragraph below per project requirements and specifier's
practice.
1. Contact: P.O. Box 629, 750 Airport Road, Terrell, TX 75160; Telephone:
(800) 527-4018, (972) 551-6400; (972) 551-6420; www.naturalite.com.
B. Proprietary Product(s)/System(s): Naturalite Roof Accessories, including roof
scuttles, heat and smoke vents, and drop out fire domes.
1. Materials: For each type of material required for the work of this Section,
provide primary materials which are the products of one manufacturer. Provide
secondary materials which are acceptable to the manufacturers of the primary
materials.
Specifier Note: Edit article below to suit project requirements. If substitutions are
permitted, edit text below. Add text to refer to Division 1 Project Requirements (Product
Substitutions Procedures) Section.
2.2 PRODUCT SUBSTITUTIONS
A.
Substitutions: No substitutions permitted.
2.3 MATERIALS
2.4 MANUFACTURED UNITS
Specifier Note: Edit paragraphs below. Select options applicable for project and delete options
not required. (1) Typical glazing is acrylic and can be provided colorless, or in white, bronze, or
grey colors. Single and double dome units are available. Double domes are recommended for
energy conservation. Acrylic is the most common and economical material. Polycarbonate may
be required for greater impact resistance or to meet some fire code requirements. Refer to the
local building code for acceptable types and possible square foot area restrictions. Do not
specify abrasion resistant acrylic or polycarbonate plastic glazing materials for use in domes in
roof accessories. Sheet materials with abrasion resistant coatings should not be thermoformed
for use in domes. (2) Finishes: Aluminum framing components are normally supplied in a natural
mill finish. For more information and costs regarding architectural finishes, contact your nearest
representative. Galvalume materials do not need painting and should not be painted. (3) Fusible
Link: Select either 165?F, 212?F or 360?F UL listed fusible link for mechanical (automatic) heat
and smoke vents. Coordinate with automatic sprinkler system and/or local Fire Marshal.
A. Roof Scuttles: Factory-assembled units including pintle hinges, compensating
and hold open extension springs, bulb curb gasket, inside latch, and padlock hasp.
Cover shall be equipped with an inside/outside release to permit easy closing.
Provide the following:
1. Roof scuttle with insulated metal lid: Lid shall consist of 0.078" extruded
aluminum frame with a 0.090" aluminum cover, 1" thick polyisocynaurate
insulation, and 0.040" aluminum liner. Curb shall be 0.090" aluminum, [9"
(228.6 mm)] [12" (304.8 mm)] high with integral cap flashing, banded
polyisocyanurate insulation and 3" (76.2 mm) mounting flange.
a.
Type: Model RHL.
b.
Finish: Manufacturer's standard mill finish for aluminum.
c.
Size: [Insert inside curb dimensions if not indicated on
drawings].
2. Roof scuttle with dome: Curb shall be 0.090" aluminum, [9" (228.6 mm)] [12"
(304.8 mm)] high with integral cap flashing, banded polyisocynaurate insulation
and 3" mounting flange.
a.
b.
c.
Type: [Model RHD single dome] [Model RHDD double dome].
Glazing: Acrylic plastic glazing.
Outer [Single] Dome Color: [Colorless] [White No. 2447]
d.
Inner Dome Color: [Colorless] [White No. 2447]
e.
Finish: Manufacturer's standard mill finish for aluminum.
f. Size: [Insert inside curb dimensions if not indicated on drawings].
B. Heat and Smoke Vents, Non-Listed: Automatic heat and smoke relief venting
units, factory-assembled for installation on roof deck. Units shall consist of lid, [9"
(228.6 mm)] [12" (304.8 mm)] high 0.125" aluminum [double walled] curb with
integral cap flashing, banded polyisocynaurate insulation and 3" (76.2 mm) mounting
flange. Lid frame shall be 0.78" extruded aluminum connected directly to curb wall
with heavy pintle type hinges and secured by latch-fusible link assembly. Operating
device shall be [[165 degree F] [212 degree F] [286 degree F] [360 degree F] U.L.
listed fusible link] OR [165 degree F Electro Thermal Link] OR [(165 degree F)
(212 degree F)], [(24 Volt AC/DC) (115 Volt AC/DC) ( 230 Volt AC/DC)] McCabe
resettable link]. Cables shall not be directly attached to lid. Lid shall lock in wide
open position.
1. Fire vent with dome:
a. Type: [Model NFD single dome] [Model NFDD double dome]
b. Glazing: Acrylic plastic glazing.
c. Outer [Single] Dome Color: [Colorless] [White No. 2447]
d. [Inner Dome Color: [Colorless] [White No. 2447].]
e. Release: [Manual inside release] [and/or] [Manual outside release]
[No release].
f. Finish: Manufacturer's standard mill finish for aluminum.
g. Size: [Insert inside curb dimensions if not indicated on drawings].
2. Fire vent with insulated metal lid:
a.
Type: [Model NFV insulated metal lid] [Model NFVDL double leaf].
b.
Release: [Manual inside release] [and/or] [Manual outside
release] [No release].
c.
Finish: Manufacturer's standard mill finish for aluminum.
d.
Size: [Insert inside curb dimensions if not indicated on
drawings].
C. UL Listed Double Leaf Mechanical, Heat and Smoke Vents: Automatically
operated heat and smoke vents shall be self-flashing type, including full 4" mounting
flange. Heat and smoke vent shall be factory assembled for installation on roof deck.
Lids shall be capable of opening against a 10 PSF simulated snow or wind load and
positively lock in the wide open position. Vent lids shall not open when subjected to a
60 PSF up-lift pressure. Curb shall be aluminum complete with integral cap flashing
(Insulated curb,optional)(Double wall insulated curb, optional)(Insulated curb
with wood nailer, optional). Manufacturer's standard mill finish on aluminum. Lids
shall be connected to the curb with pintle hinges. Dampening devices shall be
included to prevent failure of curb and frame due to stress produced by lid opening
forces. Lid latches shall be rotary slam type and allow the lid to be manually opened
from the inside (outside release optional), by a single release without disturbing the
latch-fusible link assembly. Fusible link shall be [165 degree F] [212degree F] [286
degree F] UL Listed. Latch shall automatically lock the lid when manually closed.
Operating and latching mechanisms shall be completely enclosed within the unit and
not exposed to outside weather. Each unit shall have applicable approval labels
attached.
1. Fire vent with dome and double leaf, UL Listed.
a.
Type: [Model (GULD) single dome] [Model (GULDD) double
dome].
b.
Framing: [Standard] [Thermalized for condensation control].
c.
Glazing: Impact modified acrylic outer, acrylic or copolyester inner.
d.
Outer [Single] Dome Color: [Colorless] [White].
e.
Inner Dome Color: [Colorless] [White].
f. Inside Manual Release: Mandatory.
g.
Outside Manual Release: Optional
h.
Finish: Manufacturer's standard mill finish for aluminum.
i. Size: [Insert inside curb dimensions if not indicated on drawings].
2. Fire vent with insulated metal lid and double leaf, UL approved:
a.
Type: Model GULV.
b.
Frame: [Standard] [Thermalized for condensation control].
c.
Inside Manual Release: Mandatory.
d.
Outside Manual Release: Optional.
e.
Finish: Manufacturer's standard mill finish for aluminum.
f. Size: [Insert inside curb dimensions if not indicated on drawings].
D. UL Listed High Load (30) Double Leaf Mechanical, Heat and Smoke Vents:
Automatically operated heat and smoke vents shall be self-flashing type, including full
4" mounting flange. Heat and smoke vent shall be factory assembled for installation
on roof deck. Lids shall be capable of opening against a 30 PSF simulated snow or
wind load and positively lock in the wide open position. Vent lids shall not open when
subjected to a 60 PSF up-lift pressure. Curb shall be 0.125" aluminum complete with
integral cap flashing (Insulated curb,optional)(Double wall insulated curb,
optional)(Insulated curb with wood nailer, optional). Manufacturer's standard mill
finish on aluminum. Lids shall be connected to the curb with pintle hinges.
Dampening devices shall be included to prevent failure of curb and frame due to
stress produced by lid opening forces. Lid latches shall be rotary slam type and allow
the lid to be manually opened from the inside (outside release optional), by a single
release without disturbing the latch-fusible link assembly. Fusible link shall be [165
degree F] [212 degree F] [286 degree F] UL Listed. Latch shall automatically lock
the lid when manually closed. Operating and latching mechanisms shall be
completely enclosed within the unit and not exposed to outside weather. Each unit
shall have applicable approval labels attached.
1. Fire vent with dome and double leaf, UL Listed.
a.
dome].
b.
c.
inner.
d.
Type:[Model GULD-HL single dome] [Model GULDD-HL double
Framing: [Standard] [Thermalized for condensation control].
Glazing: Impact Modified Acrylic outer and acrylic or copolyester
Outer [Single] Dome Color: [Colorless] [White]
e.
Inner Dome Color: [Colorless] [White].
f. Inside Manual Release: Mandatory
g.
Outside Manual Release: Optional
h.
Finish: Manufacturer's standard mill finish for aluminum.
i. Size: [Insert inside curb dimensions if not indicated on drawings].
2. Fire vent with insulated metal lid and double leaf, UL Listed:
a.
Type: Model GULV-HL.
b.
Frame: [Standard] [Thermalized for condensation control].
c.
Inside Manual Release: Mandatory
d.
Outside Manual Release: Optional
e.
Finish: Manufacturer's standard mill finish for aluminum.
f. Size: [Insert inside curb dimensions if not indicated on drawings].
E. Drop Out Fire Domes: Automatic heat and smoke domes shall be factoryassembled for installation on roof deck. Drop out design shall consist of an outer
dome of acrylic plastic and a heat activated inner dome of acrylic plastic. Frame shall
be extruded aluminum with integral condensation gutter. Curb shall be double wall
aluminum construction with 3/4" (19 mm) isoboard" insulation and 3" wide roof flange.
Units shall be designed to drop out in less than five minutes when subjected to
standard FM fire exposure test. Each unit shall have Factory Mutual Approval label
attached.
1. Drop-out fire vent, double dome, FM approved:
a.
b.
c.
d.
e.
f.
a.
Type: Model SL-DO-FM.
b.
Glazing: Acrylic plastic glazing.
c.
Outer Dome Color: Colorless.
d.
Inner Dome Color: [Colorless] [White No. 2447].
e.
Finish: Manufacturer's standard mill finish for aluminum.
f. Size: [Insert inside curb dimensions if not indicated on drawings].
F. Fusible Link Activated Drop Out Fire Domes: Automatic heat and smoke
domes shall be factory-assembled for installation on roof deck. Drop out design shall
consist of an outer dome of acrylic plastic and a heat activated inner dome of acrylic
plastic. Frame shall be extruded aluminum with integral condensation gutter. Unit
shall be equiped with a (360 degree)(500 degree) fusible link activated release cable
system. Curb shall be double wall aluminum construction with 3/4" (19 mm) isoboard"
insulation and 3" wide roof flange. Units shall be FM Approved for use with standard
and ESFR sprinkler systems. Each unit shall have a Factory Mutual Approval label
attached.
1. Fusible Link Activated Drop-out fire vent, double dome, FM approved:
a.
b.
c.
d.
e.
g.
Type: Model ESSL-DO-FM.
h.
Glazing: Acrylic plastic glazing.
i. Outer Dome Color: Colorless.
j. Inner Dome Color: [Colorless] [White No. 2447].
k.
Finish: Manufacturer's standard mill finish for aluminum.
f.
l. Size: [Insert inside curb dimensions if not indicated on drawings].
G. Saf-T-Guard Fall Protection Screen: Fall protection screen shall be of welded
wire construction using 5 gauge galvanized wire with a 4” x 4” grid pattern an is prime
painted. Protective screens shall comply with OSHA General Industry Standards
1910.23(e)(8).
H. Burglar Bars/security grill: Burglar Bars shall be of steel angle 1 ½” x 2” x 1/8”
and 1/2” diameter steel bars at [8” x 8” O.C.] [8” x 12” O.C.] [12” x 12” O.C.] and
are prime painted white.
2.5 RELATED MATERIALS
A. Related Materials: Refer to other sections listed in Related Section paragraph
herein for related materials.
PART 3 - EXECUTION
3.
Specifier Note: Article below is an addition to the CSI SectionFormat and a supplement to MANU-SPEC. Revise article below to suit project
requirements and specifier's practice.
3.1 MANUFACTURER'S INSTRUCTIONS
A. Compliance: Comply with manufacturer's product data, including product
technical bulletins, product catalog installation instructions and product carton
instructions for installation.
3.2 EXAMINATION
A. Site Verification of Conditions: Verify substrate conditions, which have been
previously installed under other sections, are acceptable for product installation in
accordance with manufacturer's instructions.
1. Take field dimensions and examine conditions of substrates, supports, and
other conditions under which work is to be performed and notify Contractor, in
writing, of circumstances detrimental to proper completion of work. Do not
proceed with work until unsatisfactory conditions are corrected.
Specifier Note: Openings over which drop out units are to be installed must be free of
obstructions which could prevent the domes from dropping out.
3.3 PREPARATION
A.
Surface Preparation: [Specify applicable product preparation requirements].
Specifier Note: Coordinate article below with manufacturer's recommended installation
details and requirements. Coordination is recommended between the drawings and the
specifications. The drawings should indicate locations, types and dimensions of the roof
accessory units, and details which include adjacent construction. If more than one type
of glazing is used in the roof accessory systems, drawings should indicate locations and
types.
3.4 INSTALLATION
A.
Roof Accessories Installation:
1. Match profiles, sizes and spacings indicated on approved shop drawings.
2. Coordinate installation with adjacent work such as roofing, sheet metal and
other work to ensure creation of a complete weatherproof assembly. Anchor
work securely to supporting structure, but allow for differential and thermal
movement.
3. Isolate between aluminum and dissimilar metals with a protective coating or
plastic strip to prevent electrolytic corrosion.
B. Related Products Installation: Refer to other sections listed in Related Section
paragraph herein for related products installation.
Specifier Note: Coordinate article below with Division 1 Execution Requirements
(Starting And Adjusting, Cleaning, and Protecting Installed Construction) Section.
3.5 ADJUSTING
A. Adjusting: After installation, remove shipping clips from components. Do not
remove "risk-of-fall" labels from units. Touch-up and repair minor damage to eliminate
all evidence of repair. Remove and replace work which cannot be satisfactorily
repaired.
Specifier Note: Coordinate article below with Division 1 Execution Requirements
(Cleaning) Section.
3.6 CLEANING
A. Cleaning: Remove temporary coverings and protection of adjacent work areas.
Repair or replace damaged installed products. Clean installed products in accordance
with manufacturer's instructions prior to owner's acceptance. Remove construction
debris from project site and legally dispose of debris.
1. Clean all exposed surfaces including metal and glazing using non-abrasive
materials and methods recommended by manufacturer of material or product
being cleaned. Remove and replace work that cannot be successfully cleaned.
2. Reclean as necessary to prevent damage. Protect completed work from
damage and deterioration and inspect immediately before final acceptance of
project.
Specifier Note: Coordinate article below with Division 1 Execution Requirements Section.
3.7 PROTECTION
A. Protection: Protect installed product and finish surfaces from damage during
construction.
END OF SECTION 07720
Conditions of Use: Guide specifications must be modified for use on individual projects.
Naturalite® Skylight Systems, its agents, and employees make no warranties express or
implied by operation of law or otherwise made with respect to the cover sheet or specifications,
including any implied warranties of merchantability or fitness for a particular purpose. © 2006
Naturalite® Skylight Systems. All Rights Reserved. A copyright license to reproduce this
specification is hereby granted to non-manufacturing architects, specification writers, and
designers.