Naturalite(TM) Skylight Systems Oldcastle Glass® Engineered Products 750 Airport Road, P.O. Box 629 Terrell, TX 75160 (800) 527-4018 (972) 551-6400 fax: (972) 551-6420 This MANU-SPEC(TM) utilizes the Construction Specifications Institute (CSI) Manual of Practice, including MasterFormat(c), SectionFormat(c) and PageFormat(c). A MANU-SPEC is a manufacturer specific proprietary product specification using the proprietary method of specifying applicable to project specifications and master guide specifications. Optional text indicated by brackets []; delete optional text in final copy of specification. This MANU-SPEC specifies roof accessories; including roof scuttles and smoke vents (listed and non-listed) and drop out fire domes, as manufactured by Naturalite(TM) Skylights Systems, Oldcastle Glass® Engineered Products. Revise MANU-SPEC section number and title below to suit project requirements, specification practices and section content. Refer to CSI MasterFormat for other section numbers and titles. SECTION 07720 ROOF ACCESSORIES This MANU-SPEC section has been developed in cooperation with ARCOM, publishers of the MASTERSPEC? Master Specification System, a product of the American Institute of Architects (AIA). This section uses text from the MASTERSPEC? Writer's Manual by permission from ARCOM. Refer to the equivalent MASTERSPEC? section. ARCOM and the AIA do not endorse specific manufacturers or products. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: Roof accessories. Note: Edit paragraph below for type of roof accessories to suit project requirements. 1. Types: Types of roof accessories include: a. b. a. b. Roof scuttles. Heat and smoke vents, non-listed. c. d. e. f. c. Heat and smoke vents, UL Listed . d. FM Approved Drop out fire domes. e. Fall protection screen. f. Burglar bars/security grills. Specifier Note: Revise paragraph below to suit project requirements. Add section numbers and titles per CSI MasterFormat and specifier's practice. B. Related Sections: Section(s) related to this section include: 1. Built-Up Bituminous Roofing: Division 7 Built-Up Roofing Sections. 2. Modified Bituminous Sheet Roofing: Division 7 Modified Bituminous Roofing Sections. 3. Single Ply Membrane Roofing: Division 7 Single Ply Roofing Sections. 4. Flashing and Sheet Metal: Division 7 Flashing and Sheet Metal Section. 5. Sheet Metal Roofing: Division 7 Sheet Metal Roof Section. Specifier Note: Article below may be omitted when specifying manufacturer's proprietary products and recommended installation. Retain Reference Article when specifying products and installation by an industry reference standard. If retained, list standard(s) referenced in this section. Indicate issuing authority name, acronym, standard designation and title. Establish policy for indicating edition date of standard referenced. Conditions of the Contract or Division 1 References Section may establish the edition date of standards. This article does not require compliance with standard, but is merely a listing of references used. Article below should list only those industry standards referenced in this section. Note for REFERENCES Article - IF PERTINENT Specifier's Note: References are not used in MASTERSPEC . This section is retained from the MANU-SPEC section of that title. 1.2 REFERENCES A. General: Standards listed by reference, including revisions by issuing authority, form a part of this specification section to extent indicated. Standards listed are identified by issuing authority, authority abbreviation, designation number, title or other designation established by issuing authority. Standards subsequently referenced herein are referred to by issuing authority abbreviation and standard designation. B. Aluminum Association (AA): 1. AA Specifications for Aluminum Structures. C. Underwriters Laboratories UL 793 - Standard for Safety Automatically Operated Roof Vents for Smoke and Heat. 1. Factory Mutual. D. National Roofing Contractors Association (NRCA): 1. NRCA Roofing and Waterproofing Manual. E. Standard 4430 - Approval Standard for Heat and Smoke Vents. Specifier Note: Article below should be restricted to statements describing design or performance requirements and functional (not dimensional) tolerances of a complete system. Limit descriptions to composite and operational properties to extent necessary to link multiple components of a system, and to interface with other systems. 1.3 SYSTEM DESCRIPTION A. Performance Requirements: Provide roof accessories which have been manufactured, fabricated and installed to withstand loads from [Specify code/standard reference] and to maintain [Specify performance criteria] performance criteria stated by manufacturer without defects, damage or failure. B. Roof Accessories Performance Requirements: Specifier Note: Edit Performance Requirements paragraph below for loads to suit project requirements. Roof accessories are commonly used in low-rise construction where roof elevations do not exceed 60 feet above grade. Roof accessories should be designed to support a minimum 20 psf snow load and a negative pressure or uplift of 20 psf. Greater capacities may be required depending on code requirements or project location. Plastic glazing materials are not designed to support live loads or concentrated impact type loads. "Risk of fall" label is applied to each dome to warn of potential danger. (1) Performance Requirements: Referenced standards establish the level of quality of roof accessories available from quality manufacturers conforming to industry standards. (2) Condensation: Under certain conditions of high humidity and/or large inside to outside temperature differentials, condensation may occur on the aluminum framing and plastic glazing material. Thermally broken frames can be specified to help control compensation on aluminum framing. Double glazing will usually reduce the occurrence of condensation on the plastic, but will not totally eliminate it. The condensation that forms between the double layers of plastic will normally dissipate as the airspace is heated by the sun. Sealed domes are more resistant to the formation of condensation and will reduce accumulation of dust and foreign matter. Sealed domes are available for most dome glazed unit skylights at additional cost. Specifier Note: Edit paragraph below. Specify values, minimum 20 psf recommended. For Double Leaf Mechanical Heat and Smoke Vents (Part 2 Products) 30 psf required for listed units. 1. Design framing and dome infill to support the following load requirements: a. b. a. b. [Specify] PSF snow load plus dead load. [Specify] PSF negative wind or uplift load plus dead load. 2. Labeled smoke vents should conform to the approval guidelines of either UL or FM. 3. Fabrication and installation of roof accessories shall comply with NRCA recommendation that the top of curb to finish roofing dimension be a minimum of 8" (203.2 mm). Specifier Note: Article below includes submittal of relevant data to be furnished by Contractor either before, during, or after construction. Coordinate this article with Architect's and Contractor's duties and responsibilities in Conditions of the Contract and Division 1 Submittal Procedures Section. 1.4 SUBMITTALS A. Shop Drawings: Submit shop drawings for approval prior to fabrication. Include details of framing members, glazing materials where applicable, sealants, fasteners, anchors and thicknesses and types of formed flashing and closures. B. Samples: Submit selection and verification samples for finishes, colors and textures. 1. Glazing Samples: Submit a verification sample of plastic glazing material in specified color. C. Quality Assurance Submittals: Submit the following: 1. Test Reports: Certified test reports or labeling agency file numbers indicating compliance with specified performance characteristics and physical properties. D. Closeout Submittals: Submit the following: 1. Operation and Maintenance Data: Operation and installed products in accordance with Division 1 (Maintenance Data and Operation Data) Section. maintaining installed products, and precautions against methods detrimental to finishes and performance. 2. Warranty: Warranty documents specified herein. maintenance data for Closeout Submittals Include methods for cleaning materials and Specifier Note: Article below should include prerequisites, standards, limitations and criteria which establish an overall level of quality for products and workmanship for this section. Coordinate below article with Division 1 Quality Assurance Section. 1.5 QUALITY ASSURANCE A. Qualifications: 1. Installer Qualifications: Installer experienced in performing work of this section who has specialized in installation of work similar to that required for this project. a. Installer: Roof accessories shall be installed by installers with a minimum of two years experience in installation of similar units. Specifier Note: Retain paragraph below to suit project requirements; otherwise delete paragraph below. b. Certificate: When requested, submit certificate indicating qualification. 2. Manufacturer Qualifications: a. Manufacturer: Roof accessories shall be manufactured by a firm with a minimum of 10 years experience in the fabrication and installation of roof accessories. Specifier Note: Paragraph below should list obligations for compliance with specific code requirements particular to this section. General statements to comply with a particular code are typically addressed in Conditions of the Contract and Division 1 Regulatory Requirements Section. Repetitive statements should be avoided. B. Regulatory Requirements: [Specify applicable requirements of regulatory agencies] Specifier Note: Article below should include special and unique requirements. Coordinate article below with Division 1 Product Requirements Section. 1.6 DELIVERY, STORAGE & HANDLING A. General: Comply with Division 1 Product Requirements Sections. B. Ordering: Comply with manufacturer's ordering instructions and lead time requirements to avoid construction delays. C. Delivery: Deliver materials in manufacturer's original, unopened, undamaged containers with identification labels intact. Sequence deliveries to avoid delays, but minimize on site storage. D. Storage and Protection: Store materials protected from exposure to harmful weather conditions and at temperature and humidity conditions recommended by manufacturer. 1. Protect from damage from sunlight, weather, excessive temperatures and construction operations. 1.7 PROJECT CONDITIONS A. Field Measurements: Verify actual measurements/openings by field measurements before fabrication; show recorded measurements on shop drawings. Coordinate field measurements and fabrication schedule with construction progress to avoid construction delays. 1. Measurements: Take accurate field measurements before fabrication. Do not delay job progress; allow for field tolerances if taking field measurements before fabrication is not possible. Specifier Note: Coordinate article below with Conditions of the Contract and with Division 1 Closeout Submittals (Warranty) Section. 1.8 WARRANTY A. Project Warranty: Refer to Conditions of the Contract for project warranty provisions. B. Manufacturer's Warranty: Submit, for Owner's acceptance, manufacturer's standard warranty document executed by authorized company official. Specifier Note: Coordinate paragraph below with manufacturer's warranty requirements. Manufacturer offers the Following: Roof Accessory Warranty: Provide written five-year warranty signed by manufacturer, agreeing to repair or replace work which exhibits defects in materials or workmanship and guaranteeing weathertight and leak free performance. "Defects" is defined as uncontrolled leakage of water and abnormal aging or deterioration. 1. Warranty Period: 5 years commencing on date of invoice. PART 2 - PRODUCTS 2. Specifier Note: Retain article below for proprietary method specification. Add product attributes, performance characteristics, material standards, and descriptions as applicable. Use of such phrases as "or equal" or "or approved equal," or similar phrases may cause ambiguity in specifications. Such phrases require verification (procedural, legal and regulatory) and assignment of responsibility for determining "or equal" products. 2.1 ROOF ACCESSORIES A. Manufacturer: Products. Naturalite Skylight Systems,Oldcastle Glass® Engineered Specifier Note: Paragraph below is an addition to CSI SectionFormat and a supplement to MANU-SPEC. Retain or delete paragraph below per project requirements and specifier's practice. 1. Contact: P.O. Box 629, 750 Airport Road, Terrell, TX 75160; Telephone: (800) 527-4018, (972) 551-6400; (972) 551-6420; www.naturalite.com. B. Proprietary Product(s)/System(s): Naturalite Roof Accessories, including roof scuttles, heat and smoke vents, and drop out fire domes. 1. Materials: For each type of material required for the work of this Section, provide primary materials which are the products of one manufacturer. Provide secondary materials which are acceptable to the manufacturers of the primary materials. Specifier Note: Edit article below to suit project requirements. If substitutions are permitted, edit text below. Add text to refer to Division 1 Project Requirements (Product Substitutions Procedures) Section. 2.2 PRODUCT SUBSTITUTIONS A. Substitutions: No substitutions permitted. 2.3 MATERIALS 2.4 MANUFACTURED UNITS Specifier Note: Edit paragraphs below. Select options applicable for project and delete options not required. (1) Typical glazing is acrylic and can be provided colorless, or in white, bronze, or grey colors. Single and double dome units are available. Double domes are recommended for energy conservation. Acrylic is the most common and economical material. Polycarbonate may be required for greater impact resistance or to meet some fire code requirements. Refer to the local building code for acceptable types and possible square foot area restrictions. Do not specify abrasion resistant acrylic or polycarbonate plastic glazing materials for use in domes in roof accessories. Sheet materials with abrasion resistant coatings should not be thermoformed for use in domes. (2) Finishes: Aluminum framing components are normally supplied in a natural mill finish. For more information and costs regarding architectural finishes, contact your nearest representative. Galvalume materials do not need painting and should not be painted. (3) Fusible Link: Select either 165?F, 212?F or 360?F UL listed fusible link for mechanical (automatic) heat and smoke vents. Coordinate with automatic sprinkler system and/or local Fire Marshal. A. Roof Scuttles: Factory-assembled units including pintle hinges, compensating and hold open extension springs, bulb curb gasket, inside latch, and padlock hasp. Cover shall be equipped with an inside/outside release to permit easy closing. Provide the following: 1. Roof scuttle with insulated metal lid: Lid shall consist of 0.078" extruded aluminum frame with a 0.090" aluminum cover, 1" thick polyisocynaurate insulation, and 0.040" aluminum liner. Curb shall be 0.090" aluminum, [9" (228.6 mm)] [12" (304.8 mm)] high with integral cap flashing, banded polyisocyanurate insulation and 3" (76.2 mm) mounting flange. a. Type: Model RHL. b. Finish: Manufacturer's standard mill finish for aluminum. c. Size: [Insert inside curb dimensions if not indicated on drawings]. 2. Roof scuttle with dome: Curb shall be 0.090" aluminum, [9" (228.6 mm)] [12" (304.8 mm)] high with integral cap flashing, banded polyisocynaurate insulation and 3" mounting flange. a. b. c. Type: [Model RHD single dome] [Model RHDD double dome]. Glazing: Acrylic plastic glazing. Outer [Single] Dome Color: [Colorless] [White No. 2447] d. Inner Dome Color: [Colorless] [White No. 2447] e. Finish: Manufacturer's standard mill finish for aluminum. f. Size: [Insert inside curb dimensions if not indicated on drawings]. B. Heat and Smoke Vents, Non-Listed: Automatic heat and smoke relief venting units, factory-assembled for installation on roof deck. Units shall consist of lid, [9" (228.6 mm)] [12" (304.8 mm)] high 0.125" aluminum [double walled] curb with integral cap flashing, banded polyisocynaurate insulation and 3" (76.2 mm) mounting flange. Lid frame shall be 0.78" extruded aluminum connected directly to curb wall with heavy pintle type hinges and secured by latch-fusible link assembly. Operating device shall be [[165 degree F] [212 degree F] [286 degree F] [360 degree F] U.L. listed fusible link] OR [165 degree F Electro Thermal Link] OR [(165 degree F) (212 degree F)], [(24 Volt AC/DC) (115 Volt AC/DC) ( 230 Volt AC/DC)] McCabe resettable link]. Cables shall not be directly attached to lid. Lid shall lock in wide open position. 1. Fire vent with dome: a. Type: [Model NFD single dome] [Model NFDD double dome] b. Glazing: Acrylic plastic glazing. c. Outer [Single] Dome Color: [Colorless] [White No. 2447] d. [Inner Dome Color: [Colorless] [White No. 2447].] e. Release: [Manual inside release] [and/or] [Manual outside release] [No release]. f. Finish: Manufacturer's standard mill finish for aluminum. g. Size: [Insert inside curb dimensions if not indicated on drawings]. 2. Fire vent with insulated metal lid: a. Type: [Model NFV insulated metal lid] [Model NFVDL double leaf]. b. Release: [Manual inside release] [and/or] [Manual outside release] [No release]. c. Finish: Manufacturer's standard mill finish for aluminum. d. Size: [Insert inside curb dimensions if not indicated on drawings]. C. UL Listed Double Leaf Mechanical, Heat and Smoke Vents: Automatically operated heat and smoke vents shall be self-flashing type, including full 4" mounting flange. Heat and smoke vent shall be factory assembled for installation on roof deck. Lids shall be capable of opening against a 10 PSF simulated snow or wind load and positively lock in the wide open position. Vent lids shall not open when subjected to a 60 PSF up-lift pressure. Curb shall be aluminum complete with integral cap flashing (Insulated curb,optional)(Double wall insulated curb, optional)(Insulated curb with wood nailer, optional). Manufacturer's standard mill finish on aluminum. Lids shall be connected to the curb with pintle hinges. Dampening devices shall be included to prevent failure of curb and frame due to stress produced by lid opening forces. Lid latches shall be rotary slam type and allow the lid to be manually opened from the inside (outside release optional), by a single release without disturbing the latch-fusible link assembly. Fusible link shall be [165 degree F] [212degree F] [286 degree F] UL Listed. Latch shall automatically lock the lid when manually closed. Operating and latching mechanisms shall be completely enclosed within the unit and not exposed to outside weather. Each unit shall have applicable approval labels attached. 1. Fire vent with dome and double leaf, UL Listed. a. Type: [Model (GULD) single dome] [Model (GULDD) double dome]. b. Framing: [Standard] [Thermalized for condensation control]. c. Glazing: Impact modified acrylic outer, acrylic or copolyester inner. d. Outer [Single] Dome Color: [Colorless] [White]. e. Inner Dome Color: [Colorless] [White]. f. Inside Manual Release: Mandatory. g. Outside Manual Release: Optional h. Finish: Manufacturer's standard mill finish for aluminum. i. Size: [Insert inside curb dimensions if not indicated on drawings]. 2. Fire vent with insulated metal lid and double leaf, UL approved: a. Type: Model GULV. b. Frame: [Standard] [Thermalized for condensation control]. c. Inside Manual Release: Mandatory. d. Outside Manual Release: Optional. e. Finish: Manufacturer's standard mill finish for aluminum. f. Size: [Insert inside curb dimensions if not indicated on drawings]. D. UL Listed High Load (30) Double Leaf Mechanical, Heat and Smoke Vents: Automatically operated heat and smoke vents shall be self-flashing type, including full 4" mounting flange. Heat and smoke vent shall be factory assembled for installation on roof deck. Lids shall be capable of opening against a 30 PSF simulated snow or wind load and positively lock in the wide open position. Vent lids shall not open when subjected to a 60 PSF up-lift pressure. Curb shall be 0.125" aluminum complete with integral cap flashing (Insulated curb,optional)(Double wall insulated curb, optional)(Insulated curb with wood nailer, optional). Manufacturer's standard mill finish on aluminum. Lids shall be connected to the curb with pintle hinges. Dampening devices shall be included to prevent failure of curb and frame due to stress produced by lid opening forces. Lid latches shall be rotary slam type and allow the lid to be manually opened from the inside (outside release optional), by a single release without disturbing the latch-fusible link assembly. Fusible link shall be [165 degree F] [212 degree F] [286 degree F] UL Listed. Latch shall automatically lock the lid when manually closed. Operating and latching mechanisms shall be completely enclosed within the unit and not exposed to outside weather. Each unit shall have applicable approval labels attached. 1. Fire vent with dome and double leaf, UL Listed. a. dome]. b. c. inner. d. Type:[Model GULD-HL single dome] [Model GULDD-HL double Framing: [Standard] [Thermalized for condensation control]. Glazing: Impact Modified Acrylic outer and acrylic or copolyester Outer [Single] Dome Color: [Colorless] [White] e. Inner Dome Color: [Colorless] [White]. f. Inside Manual Release: Mandatory g. Outside Manual Release: Optional h. Finish: Manufacturer's standard mill finish for aluminum. i. Size: [Insert inside curb dimensions if not indicated on drawings]. 2. Fire vent with insulated metal lid and double leaf, UL Listed: a. Type: Model GULV-HL. b. Frame: [Standard] [Thermalized for condensation control]. c. Inside Manual Release: Mandatory d. Outside Manual Release: Optional e. Finish: Manufacturer's standard mill finish for aluminum. f. Size: [Insert inside curb dimensions if not indicated on drawings]. E. Drop Out Fire Domes: Automatic heat and smoke domes shall be factoryassembled for installation on roof deck. Drop out design shall consist of an outer dome of acrylic plastic and a heat activated inner dome of acrylic plastic. Frame shall be extruded aluminum with integral condensation gutter. Curb shall be double wall aluminum construction with 3/4" (19 mm) isoboard" insulation and 3" wide roof flange. Units shall be designed to drop out in less than five minutes when subjected to standard FM fire exposure test. Each unit shall have Factory Mutual Approval label attached. 1. Drop-out fire vent, double dome, FM approved: a. b. c. d. e. f. a. Type: Model SL-DO-FM. b. Glazing: Acrylic plastic glazing. c. Outer Dome Color: Colorless. d. Inner Dome Color: [Colorless] [White No. 2447]. e. Finish: Manufacturer's standard mill finish for aluminum. f. Size: [Insert inside curb dimensions if not indicated on drawings]. F. Fusible Link Activated Drop Out Fire Domes: Automatic heat and smoke domes shall be factory-assembled for installation on roof deck. Drop out design shall consist of an outer dome of acrylic plastic and a heat activated inner dome of acrylic plastic. Frame shall be extruded aluminum with integral condensation gutter. Unit shall be equiped with a (360 degree)(500 degree) fusible link activated release cable system. Curb shall be double wall aluminum construction with 3/4" (19 mm) isoboard" insulation and 3" wide roof flange. Units shall be FM Approved for use with standard and ESFR sprinkler systems. Each unit shall have a Factory Mutual Approval label attached. 1. Fusible Link Activated Drop-out fire vent, double dome, FM approved: a. b. c. d. e. g. Type: Model ESSL-DO-FM. h. Glazing: Acrylic plastic glazing. i. Outer Dome Color: Colorless. j. Inner Dome Color: [Colorless] [White No. 2447]. k. Finish: Manufacturer's standard mill finish for aluminum. f. l. Size: [Insert inside curb dimensions if not indicated on drawings]. G. Saf-T-Guard Fall Protection Screen: Fall protection screen shall be of welded wire construction using 5 gauge galvanized wire with a 4” x 4” grid pattern an is prime painted. Protective screens shall comply with OSHA General Industry Standards 1910.23(e)(8). H. Burglar Bars/security grill: Burglar Bars shall be of steel angle 1 ½” x 2” x 1/8” and 1/2” diameter steel bars at [8” x 8” O.C.] [8” x 12” O.C.] [12” x 12” O.C.] and are prime painted white. 2.5 RELATED MATERIALS A. Related Materials: Refer to other sections listed in Related Section paragraph herein for related materials. PART 3 - EXECUTION 3. Specifier Note: Article below is an addition to the CSI SectionFormat and a supplement to MANU-SPEC. Revise article below to suit project requirements and specifier's practice. 3.1 MANUFACTURER'S INSTRUCTIONS A. Compliance: Comply with manufacturer's product data, including product technical bulletins, product catalog installation instructions and product carton instructions for installation. 3.2 EXAMINATION A. Site Verification of Conditions: Verify substrate conditions, which have been previously installed under other sections, are acceptable for product installation in accordance with manufacturer's instructions. 1. Take field dimensions and examine conditions of substrates, supports, and other conditions under which work is to be performed and notify Contractor, in writing, of circumstances detrimental to proper completion of work. Do not proceed with work until unsatisfactory conditions are corrected. Specifier Note: Openings over which drop out units are to be installed must be free of obstructions which could prevent the domes from dropping out. 3.3 PREPARATION A. Surface Preparation: [Specify applicable product preparation requirements]. Specifier Note: Coordinate article below with manufacturer's recommended installation details and requirements. Coordination is recommended between the drawings and the specifications. The drawings should indicate locations, types and dimensions of the roof accessory units, and details which include adjacent construction. If more than one type of glazing is used in the roof accessory systems, drawings should indicate locations and types. 3.4 INSTALLATION A. Roof Accessories Installation: 1. Match profiles, sizes and spacings indicated on approved shop drawings. 2. Coordinate installation with adjacent work such as roofing, sheet metal and other work to ensure creation of a complete weatherproof assembly. Anchor work securely to supporting structure, but allow for differential and thermal movement. 3. Isolate between aluminum and dissimilar metals with a protective coating or plastic strip to prevent electrolytic corrosion. B. Related Products Installation: Refer to other sections listed in Related Section paragraph herein for related products installation. Specifier Note: Coordinate article below with Division 1 Execution Requirements (Starting And Adjusting, Cleaning, and Protecting Installed Construction) Section. 3.5 ADJUSTING A. Adjusting: After installation, remove shipping clips from components. Do not remove "risk-of-fall" labels from units. Touch-up and repair minor damage to eliminate all evidence of repair. Remove and replace work which cannot be satisfactorily repaired. Specifier Note: Coordinate article below with Division 1 Execution Requirements (Cleaning) Section. 3.6 CLEANING A. Cleaning: Remove temporary coverings and protection of adjacent work areas. Repair or replace damaged installed products. Clean installed products in accordance with manufacturer's instructions prior to owner's acceptance. Remove construction debris from project site and legally dispose of debris. 1. Clean all exposed surfaces including metal and glazing using non-abrasive materials and methods recommended by manufacturer of material or product being cleaned. Remove and replace work that cannot be successfully cleaned. 2. Reclean as necessary to prevent damage. Protect completed work from damage and deterioration and inspect immediately before final acceptance of project. Specifier Note: Coordinate article below with Division 1 Execution Requirements Section. 3.7 PROTECTION A. Protection: Protect installed product and finish surfaces from damage during construction. END OF SECTION 07720 Conditions of Use: Guide specifications must be modified for use on individual projects. Naturalite® Skylight Systems, its agents, and employees make no warranties express or implied by operation of law or otherwise made with respect to the cover sheet or specifications, including any implied warranties of merchantability or fitness for a particular purpose. © 2006 Naturalite® Skylight Systems. All Rights Reserved. A copyright license to reproduce this specification is hereby granted to non-manufacturing architects, specification writers, and designers.