2009 versus 2012 IECC Maryland Affordable Housing Coalition June 26th, 2012 2009 versus 2012 IECC • • • • Overview Reading the Code on Your Own Compliance Paths Low-rise Construction (Residential Code) – Envelope, Air-sealing, Mechanical • Mid-rise Construction (Commercial Code) – Envelope, Air-sealing, Mechanical, Electrical, Extras © 2011 Steven Winter Associates, Inc. All rights reserved 2 2009 versus 2012 IECC • Some aspects of 2012 have been relaxed • Opportunities exist to cost-effectively implement aspects of 2012 • The 2012 is ~ 10-15% more efficient than 2009 • The 2012 is ~ 30% more efficient than 2006 © 2011 Steven Winter Associates, Inc. All rights reserved 3 2009 versus 2012 IECC Reading the Code Residential Chapter Commercial Chapter 2009 IECC Chapter 4 Chapter 5 2012 IECC Chapter R4 Chapter C4 • Must read chapter by hierarchy – Understand each section by its context – Like finding the best “grape” of knowledge © 2011 Steven Winter Associates, Inc. All rights reserved 4 2009 versus 2012 IECC Reading the Code Section 401: Intro Section 405 Section 402 Section 404 Section 403 402.1 402.4 402.2 402.3 © 2011 Steven Winter Associates, Inc. All rights reserved 402.4.1 Building Thermal Envelope: Air-sealing 5 2009 versus 2012 IECC • Two Generic Compliance Methods to either code Mandatory Residential Measures OR Prescriptive Pathway © 2011 Steven Winter Associates, Inc. All rights reserved Performance Pathway 6 2009 versus 2012 IECC • Two Generic Compliance Methods to either code Mandatory Residential Measures Prescriptive Pathway Performance Pathway Envelopes Prescriptive By Component Performance By Component UA- Alternative © 2011 Steven Winter Associates, Inc. All rights reserved 7 2009 versus 2012 IECC • Low-Rise, Wood-Framed Construction – Envelopes: Prescriptive by Measure Climate Zone 4, 3 Stories and Under, Wood Frame by Component (Table 402.1.1 - 2009 IECC, Page 27; Table R402.1.1 - 2012 IECC, Page R-29) Window Skylights U-value U-value 2009 IECC 2012 IECC 0.35 0.35 0.60 0.55 © 2011 Steven Winter Associates, Inc. All rights reserved Wood Ceiling Mass Wall Frame Wall R-value R-value R-value 38 13 5/10 49 20 or 13+5 8/13 Floor R-value 19 19 Basement Crawlspace Wall R-value R-value 10/13 10/13 10/13 10/13 8 2009 versus 2012 IECC • Low-Rise, Wood-Framed Construction – Envelopes: Performance by Measure Climate Zone 4, 3 Stories and Under, Wood Frame by Assembly (Table 402.1.3 - 2009 IECC, Page 28; Table R402.1.3 - 2012 IECC, Page R-30) Window Skylights U-value U-value 2009 IECC 2012 IECC 0.35 0.35 0.60 0.55 © 2011 Steven Winter Associates, Inc. All rights reserved Wood Ceiling Mass Wall Frame Wall U-value U-value U-value 0.030 0.026 0.082 0.057 0.141 0.098 Floor U-value 0.047 0.047 Basement Crawlspace Wall U-value U-value 0.059 0.059 0.065 0.065 9 2009 versus 2012 IECC • Low-Rise, Wood-Framed Construction – Envelopes: Performance by Measure Window Skylights U-value U-value 2009 IECC 2012 IECC 0.35 0.35 0.60 0.55 Wood Ceiling Mass Wall Frame Wall U-value U-value U-value 0.030 0.026 0.082 0.057 0.141 0.098 Floor U-value 0.047 0.047 Basement Crawlspace Wall R-value R-value 0.059 0.059 0.065 0.065 If already using blown ceiling insulation and roof/ ceiling trusses are 24” O.C., then the project is nearly meeting this requirement. Only ½” extra needed. © 2011 Steven Winter Associates, Inc. All rights reserved 10 2009 versus 2012 IECC • Low-Rise, Wood-Framed Construction – Envelopes: UA Alternative Compliance – Can exceed insulation on a component to tradeoff for another – Example: 1000 Sqft House, over crawlspace Component Walls Ceiling Floor Windows Proposed R-13 R-60 R-30 U-0.31 2012 IECC Surface Area R-20 1040 R-48 1000 R-19 1000 U-0.35 150 Component Proposed UA Walls 85 Ceiling 17 Floor 35 Windows 47 Total © 2011 Steven Winter Associates, Inc. All rights reserved 183 Code UA 59 26 47 53 185 11 2009 versus 2012 IECC • Two Generic Compliance Methods to either code Mandatory Residential Measures OR Prescriptive Pathway © 2011 Steven Winter Associates, Inc. All rights reserved Performance Pathway 12 2009 versus 2012 IECC • Low-Rise, Wood-Framed Construction – Performance “Whole” building: Includes heating, cooling, and hot water LOADS. – HVAC efficiencies do not improve performance approach results – Variety of available energy models: commercial and public • RESCheck (free) • EnergyGauge • REMRate © 2011 Steven Winter Associates, Inc. All rights reserved 13 2009 versus 2012 IECC • Air-sealing Mandatory Residential Measures Air-sealing Prescriptive Pathway Performance Pathway Envelopes Mandatory Items Testing Prescriptive By Component Performance By Component UA- Alternative © 2011 Steven Winter Associates, Inc. All rights reserved 14 2009 versus 2012 IECC • Locations for Air-Sealing: – Any two separate materials at boundary conditions have gaps that will leak air © 2011 Steven Winter Associates, Inc. All rights reserved 15 2009 versus 2012 IECC • Air-sealing differences Component Air-barrier 2009 IECC Air-permeable Insulation is on inside of air-barrier 2012 IECC Deleted Exterior thermal envelope insulation for framed walls shall Walls N/A be installed in substantial contact with the air-barrier. Walls N/A Knee-walls sealed Windows, Skylights and Doors Does not require Skylights be Air-sealed Does require skylights be air-sealed Common Wall Air barrier is installed in common wall between dwelling Deleted units Fireplaces Air-barriers at fireplaces Air-barriers at fireplaces and gasketed doors Infiltration Requirements Component Verification Target Infiltration Rates 2009 IECC Visual inspection or testing allowed 7 ACH @ 50 Pascal © 2011 Steven Winter Associates, Inc. All rights reserved 2012 IECC Testing required, but code official determines whether a third party will be involved 3 ACH @ 50 Pascal 16 2009 versus 2012 IECC • Air-sealing testing methodology, standard home Negative Pressure © 2011 Steven Winter Associates, Inc. All rights reserved 17 2009 versus 2012 IECC • Air-sealing testing methodology © 2011 Steven Winter Associates, Inc. All rights reserved 18 2009 versus 2012 IECC • Air-sealing testing methodology, multifamily home Negative Pressure © 2011 Steven Winter Associates, Inc. All rights reserved 19 2009 versus 2012 IECC • Air-sealing methods © 2011 Steven Winter Associates, Inc. All rights reserved 20 2009 versus 2012 IECC • Air-sealing methods © 2011 Steven Winter Associates, Inc. All rights reserved 21 2009 versus 2012 IECC • Mechanical Measures Mandatory Residential Measures Air-sealing Prescriptive Pathway Performance Pathway Mechanical Envelopes Mandatory Items Testing Prescriptive By Component Performance By Component UA- Alternative © 2011 Steven Winter Associates, Inc. All rights reserved Piping Duct Leakage Air-Handler Leakage 22 2009 versus 2012 IECC • Mechanical Measures Component HVAC Pipe Insulation Exposed Pipe Insulation Circulating Systems Hot Water Pipe Insulation 2009 IECC R-3 on pipes >105◦ or <55◦ N/A R-2 and accessable on/off switch N/A © 2011 Steven Winter Associates, Inc. All rights reserved 2012 IECC R-3 on pipes >105◦ or <55◦ Protected from sun, wind, rain: no adhesive tape allowed R-3 and accessable on/off switch R-3 23 2009 versus 2012 IECC • Mechanical Measures Duct Leakage Requirements Component Filter Boxes Leakage to the outdoors Total Duct Leakage Exemption to Duct Leakage Sealed Air-handler 2009 IECC Required to be air-sealed 8 CFM/ 100 ft2 at 25 Pa OR Total Duct leakage 6CFM/100 ft2 at 25 Pa (w/ AHU) or 4 CFM50 w/out AHU Not required if all ducts are in thermal envelope N/A © 2011 Steven Winter Associates, Inc. All rights reserved 2012 IECC Required to be air-sealed N/A 4CFM/100 ft2 at 25 Pa (w/ AHU) or 3 CFM50 w/out AHU Not required if all ducts are in thermal envelope Manufacturer designation that air-leakage <2% design flow 24 2009 versus 2012 IECC • Mechanical Measures, Duct Leakage © 2011 Steven Winter Associates, Inc. All rights reserved 25 2009 versus 2012 IECC • Lighting Component Lighting 2009 IECC 50% of the permanently installed fixtures have high efficiency lamps 2012 IECC 75% of the permanently installed fixtures have high efficiency lamps • High Efficiency = CFLs or – 60 lumens per watt for lamps over 40 watts – 50 lumens per watt for lamps btwn 15-40 watts – 40 lumens per watt for lamps btwn <15 watts © 2011 Steven Winter Associates, Inc. All rights reserved 26 2009 versus 2012 IECC Commercial Code (4 Stories and Taller) © 2011 Steven Winter Associates, Inc. All rights reserved 27 2009 versus 2012 IECC • Code Organization Mandatory Commercial Measures Lights OR Air-sealing Prescriptive © 2011 Steven Winter Associates, Inc. All rights reserved Performance Additional Efficiency Mechanical 28 2009 versus 2012 IECC • Envelopes Mandatory Commercial Measures Lights Air-sealing Prescriptive Performance Additional Efficiency Mechanical Envelopes Prescriptive By Component Performance By Component UA- Alternative © 2011 Steven Winter Associates, Inc. All rights reserved 29 2009 versus 2012 IECC • Envelopes © 2011 Steven Winter Associates, Inc. All rights reserved 30 2009 versus 2012 IECC • Air-sealing Mandatory Commercial Measures Lights Air-sealing Prescriptive Performance Additional Efficiency Mechanical Envelopes Prescriptive By Component Performance By Component UA- Alternative © 2011 Steven Winter Associates, Inc. All rights reserved 31 2009 versus 2012 IECC • Air-sealing © 2011 Steven Winter Associates, Inc. All rights reserved 32 2009 versus 2012 IECC • Envelope © 2011 Steven Winter Associates, Inc. All rights reserved 33 2009 versus 2012 IECC • Mechanical Systems Mandatory Commercial Measures Lights Air-sealing Prescriptive Performance Envelopes Prescriptive By Component Additional Efficiency Mechanical Min HVAC Performance Commissioning Performance By Component UA- Alternative © 2011 Steven Winter Associates, Inc. All rights reserved 34 2009 versus 2012 IECC • Mechanical Systems © 2011 Steven Winter Associates, Inc. All rights reserved 35 2009 versus 2012 IECC • Commissioning © 2011 Steven Winter Associates, Inc. All rights reserved 36 2009 versus 2012 IECC • Commissioning © 2011 Steven Winter Associates, Inc. All rights reserved 37 2009 versus 2012 IECC • Commissioning © 2011 Steven Winter Associates, Inc. All rights reserved 38 2009 versus 2012 IECC • Lighting Mandatory Commercial Measures Lights Air-sealing Prescriptive Performance Envelopes Prescriptive By Component Additional Efficiency Mechanical Min HVAC Performance Commissioning Performance By Component UA- Alternative © 2011 Steven Winter Associates, Inc. All rights reserved 39 2009 versus 2012 IECC • Lighting © 2011 Steven Winter Associates, Inc. All rights reserved 40 2009 versus 2012 IECC • Lighting – “Bulbs” not Fixtures – Hole in 2009 allowed exterior lighting to be irrelevant for high-rise buildings © 2011 Steven Winter Associates, Inc. All rights reserved 41 2009 versus 2012 IECC • Lighting Mandatory Commercial Measures Lights Air-sealing Prescriptive Performance Envelopes Prescriptive By Component Additional Efficiency Mechanical Min HVAC Performance Commissioning Performance By Component Performance HVAC UA- Alternative Performance Lighting Renewables © 2011 Steven Winter Associates, Inc. All rights reserved 42 2009 versus 2012 IECC • Additional Efficiency – Performance HVAC OR © 2011 Steven Winter Associates, Inc. All rights reserved 43 2009 versus 2012 IECC • Additional Efficiency – Performance Lighting OR © 2011 Steven Winter Associates, Inc. All rights reserved 44 2009 versus 2012 IECC • Additional Efficiency – Performance Lighting Building Component Renewable Energy Watts Renewable by Percent 2009 IECC N/A N/A 2012 IECC 0.5 Watts/sqft OR 1854 W 3% of MEP loads • 2kW system costs about $11,000 before rebates © 2011 Steven Winter Associates, Inc. All rights reserved 45 2009 versus 2012 IECC Questions? © 2011 Steven Winter Associates, Inc. All rights reserved 46