BILLS OF QUANTITIES PROJECT NAME : DOEHLER Egypt S.A.E. 5 Engineering Square-Plot#4 of North Expansions 6th October City-Egypt DIVISION - 15 - Mech. Works (Fire Fighting) FIRE FIGHTING SYSTEM Ref. .1 DESCRIPTION DRAWING REF. : 02-01-DD-FF Unit Price Amount L.E L.E Quantity Unit 20 set 0 1 1 set set 0 0 24 24 18 24 36 12 24 6 36 mt mt mt mt mt mt mt mt mt 0 0 0 0 0 0 0 0 0 3 set 0 5 Set 0 0 Sprinkle Head: Supplying, installing, connecting and testing of Quick Response / ESFFR Sprinkler heads type, UL/FM approved as shown on drawings and specifications. . 1-2 Upright sprinklers heads K 8 rating temp 74 C NonStorage 2 Zone Control Station Supplying, installing, connecting and testing of Zone control station (Z) consist of (OS&Y) gate valve and check valve with tamper switch and flow switch both wired to fire alarm, pressure gauge, and 1.5 inch inspector test and drain (assembly with sight glass), Pressure relife valve, complete with all fittings as per FM Stander and as shown on drawings and specifications. 2-1 6 inch Zone control station 2-2 3 inch Zone control station 3 Fire Water Line: 3-1 3-2 3-3 3-4 3-5 3-6 3-7 3-8 3-9 Supply, lift into position, install, test, set to work, and commission Above ground pipes, Seamless black Steel ASTM A 53 Schedule 40 category including, grooved fittings expansion joints, galvanized hangers and supports, and all pipes are painted with two coats of red oxide primer and two coats of fire red Diameter 150 mm (6 Inch) Diameter 150 mm (6 Inch) Underground Diameter 100 mm (4 Inch) Diameter 75 mm (3 Inch) Diameter 65 mm (2 ½ Inch) Diameter 65 mm (2 Inch) Diameter 40 mm (1 ½ Inch) Diameter 25 mm (1 Inch) Diameter 20 mm (3/4 Inch) 4 Automatic Direct Fire Detection And Suppression System: For electric panels Supplying, installing, connecting, testing and commissioning The FM-200 gaseous fireextinguishing agent Automatic Systems, as per "NFPA-2001 Standard on Clean Agent" Fire Extinguishing Systems complete with but not limited to Cylinder Mounting Bracket, Flexible Detector, Actuation and Discharge Tubing, Pressure Switch, Recharge Adapter, FM-200 Cylinder, all necessary accessories and ancillary works required for interlock with (fire detection system) and as shown on details drawing and as specified. 4-1 Extinguisher Charged with 12.0 Lbs. of FM-200 5 5.1 Fire Hose cabinet: Supply, lift into position, install, test, set to work, and commission Fire Hose cabinet with 30 meters length, 40 mm (1.5 Inch) diameter fire hose cabinet assembly complete with bronze adjustable spray nozzle, (multipurpose dry chemical powder fire extinguisher 6-Kg capacity), as per drawings. BILL SUMMARY DOEHLER Egypt S.A.E. FIREFIGHTING INTEGRATED MECHANICAL ENGINEERING OFFICE BILLS OF QUANTITIES PROJECT NAME : DOEHLER Egypt S.A.E. 5 Engineering Square-Plot#4 of North Expansions 6th October City-Egypt DIVISION - 15 - Mech. Works (Fire Fighting) FIRE FIGHTING SYSTEM Notes: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 DOEHLER Egypt S.A.E. DRAWING REF. : 02-01-DD-FF Prices including lifting tools, scissor lift and all equipments needed to complete the work. Material given in the drawing and/or spec's not necessarily repeated in the Bill of Quantities. The Technical Specification forms an partnumber of the Bill Quantities. include dismantlingand The Tenderer is committed to integral check the of ofthe pages ofPrices the Bill of Quantities should any be found missing or duplicated or the figures or writing indistinct, the Tenderer must notify The Tenderer is deemed to have visited the site and fully acquainted himself as to the location of each of the pipesto each of the roads in which the pipes will be installed. Access Access for the plant, equipment and materials. Surface conditions All safety regulations and employer site safety procedures. Installation methods according to site condition Quantities will surveyed according to actual quantities which will be installed, and all material need to complete works according to FMequipments standards should to be included on BOQ prices All materials, components and used are FM approved. All materials used are the best new available, guaranteed and subject to the consultant approval. Execution is subject to approval of project consultant. Materials or products are to be taken as samples of what will be required. Subject to the consultant approval. The unit prices include wall opening and repair any damage may happened during installation. The unit price shall cover all costs, without being limited to, all charges for additional supervision, labor, transportation supply materials all72, temporary worksaccording and all services and the fulfillment of all All installationsand should be of according toand NFPA FM Standard, to site conditions and according to safety consultant approval. safety, food and plant operation requirements should to apply by contractor during installation. Water or/and Electricity required for completion of the work shall be coordinated with the owner as per owner capability, otherwise willrequested provide bybycontractor. Contractor committed by tests project consultant. The tests and measurement required by the consultant obligated to the contractor The contract price includes the submissions of all user manuals, catalogues, software’s and other related and data sheets should to submit to review by consultant for approval before installations Shop drawing, as built drawing should to submit by contractor to review. FIREFIGHTING INTEGRATED MECHANICAL ENGINEERING OFFICE