data sheet MCIM-C.qxp

advertisement
Data sheet - 07/016
Single Channel Input Unit MCIM-C
Description
The MCIM-C is a variant of the single Channel output unit MCIM.This device is identified as a
call point module by the COOPER addressable panel.The maximum number of addressable
MCIM-C per loop is 200.
Dimensions
Recommendation
18.5 m m
Only connect cable screen to its adjacent earth terminal.
The end of line resistor must always be fitted, even if the input is unused.
Monitored input can detect open or short circuit faults.
Installation
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram below.
3. Recommended Loop Cable Type: FIRETUF, FP200, MICC
63 mm
No addressing of the interface is required. See control panel operation for details.
35 mm
Notes:
5k6
Connexions
Loop In +
EARTH
Lo
op nI
Loop In Earth
Loop Ou t+
MCIM-C
37.5m m
Earth
INTPUT
IN -
LOOP
22k
IN +
Loop Out
Loop Out-
20 mm
Mounting Details (Drilling positions, template over leaf)
Specifications
Loop Load
Min
Nom
Max
Units
Quiescent Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .310 . . . . . . .µA
Operating Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . .18 . . . . . . . . . . . . . . . . . . .30 . . . . . . . .V DC
Inputs Trigger
Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5,6 . . . . . . . . . . . . . . . . . . kohms
End Of Line Resistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22 . . . . . . . . . . . . . . . . . . . kohms
Short Circuit Fault Threshold Resistance . . . . . . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . . . . . . kohms
Open Circuit Fault Threshold Resistance . . . . . . . . . . . . . . . . . . . . .33 . . . . . . . . . . . . . . . . . . . kohms
Environmental
Operating Temperature . . . . . . . . . . . . . . . . . . . . . . . . . -10 . . . . . . . . . . . . . . . . . . +60
Humidity (Non Condensing)
Standards
EN54 : Pt2 & 4
BS5839 : Pt1 (Installation)
Compatibility
Suitable for use with Cooper Analogue Addressable Fire Systems
Physical
Dimensions 63mm x 35mm x 18.5mm
Weight >0.1kg
Ingress Protection IP40
. . . . . .°C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95 . . . . . . . . . . . . . . . . . . .%RH
Download