POWER MONITORING

advertisement
POWER MONITORING
CURRENT SWITCH AND RELAY
RIBX SERIES
DESCRIPTION
The Relay in a Box RIBX Series provides a unique
and cost-effective solution to on/off motor control and
current sensing status indication. Combined in a single, convenient junction box with high and low voltage
separation are a control relay and a current sensing
status switch. A three-position closed/open/auto switch
is available to override the output of the relay. This versatile product allows both control and status sensing of
electrical loads by a BAS, all in a self-contained, easyto-install housing.
RIBX - Ring Remote
Current Sensing
RIBX - Internal
Current Sensing
FEATURES
• Cost-effective current sensing with a control
relay
• Self-contained housing with high and low
voltage isolation
• LED indication of relay and sensor trip
• Optional relay contact override switch
• Plenum rated housing
• UL listed for UL 916 Energy Management
and UL 864 Fire
RIBX - Split Ring
Remote Current
Sensing
APPLICATION
Internal Current Sensing (for single-phase loads)
Models with internal current sensing are great for direct
control and current sensing of exhaust fans, pumps, and
other single phase electrical loads up to 20A. The control
relay contacts of these models wire directly in series with
single-phase motors using the wires that exit the housing
through the 1/2" conduit hub. The current of the load is
sensed within the housing. Low voltage wiring from the controller for the control relay coil and status switch enter the
separate Class 2 wiring compartment in the housing
through star bushings or conduit and are connected to
screw terminals.
Remote Current Sensing (for loads with motor starters)
Models with remote current sensing are great for control
and status sensing of electrical loads that require a motor
starter. The control relay contacts of these models are
wired in series with the motor starter coil using the two
wires that exit the housing through the 1/2'' conduit hub.
Currents up to 150A are sensed externally with a current
sensing ring connected to the two gray wires that also exit
through the 1/2'' conduit hub. Low voltage wiring from the
controller for the control relay coil and status switch enter
the separate Class 2 wiring compartment in the housing
through star bushings or conduit and are connected to
screw terminals.
KELE • www.kele.com
BAS Controller
Status In
Optional Override Switch
Closed/Open/Auto
Class 2
Control Out
Single Phase
Exhaust Fan
On/Off
RIBX
Current Sensor
and Control Relay
with Override Switch
Current is sensed internally.
120-277 VAC
10 or 20A
Internal Current Sensing
BAS Controller
Status In
Current Sensor
and Control Relay
with Override Switch
Optional Override Switch
Closed/Open/Auto
Class 2
Control Out
RIBX
Toroid has no open
circuit voltage to prevent
electrical shock hazard.
Relay Switches Starter
Input Coil
Contactor
3-Phase
Power
Motor
Starter
3-Phase Motor
Remote Current Sensing
USA 901-937-4900 • International 901-382-6084
POWER MONITORING
CURRENT SWITCH AND RELAY
RIBX SERIES
SPECIFICATIONS - GENERAL
Enclosure size
4"W x 4"H x 1.8"D with 1/2" NPT
(10.2 x 10.2 x 4.6 cm)
-30° to 140°F (-34° to 60°C)
5% to 95% noncondensing
10 million cycles min mechanical
Operating temp
Humidity
Life rating (all relays)
Status indication
LED#1 ON
LED#2 ON
LED#3 ON
LED#2 & 3 OFF
Remote sensor inside diameter
Ring
0.75'' (1.9 cm)
Split ring
0.75'' x 0.87'' (1.9 x 2.2 cm)
Relay coil frequency
50/60 Hz
Relay coil pull-in/drop-out
Coil Drive
Relay activated
Current switch closed
Current switch open
No current
Status switch
Status switch
Off-state leakage
On-state voltage drop
10-30 VAC/DC
24 VAC/DC
30 VAC/DC @ 0.4A max
<30 micro-amps @ 30 VAC/DC
<0.3V @ 0.1A
<1.6V @ 0.4A
Wire length
Weight
Approvals
Pull-in
DC AC
10 9
22 18
Drop-out
DC AC
2.8 2.1
3.8 3
16" (40.6 cm)
Approx 1 lb (0.45 kg)
UL listed: UL 916 Energy Management, UL 864 Fire, UL listed Canada
ORDERING INFORMATION
MODEL
RIBXLCA
RIBXLCF
RIBXLCJA
RIBXLCJF
RIBXLCRA
RIBXLCRF
RIBXLSA
RIBXLSF
RIBXLSJA
RIBXLSJF
RIBXLSRA
RIBXLSRF
CURRENT CURRENT SENSING OVER
SENSING RANGE/THRESHOLD SW
Internal
Split Ring
Ring
Internal
Split Ring
Ring
RIBX24BA
3-150A / Fixed, 3A
10A resistive
480 VA Pilot Duty
480 VA Ballast
600W Tungsten
240W Tungsten
1/3 hp for N.O.
1/6 hp for N.C.
1/4 hp for N.O.
1/8 hp for N.C.
120/240/277 VAC - 28 VDC
240/277 VAC
277 VAC
120 VAC N.O
120 VAC N.C.
120/240 VAC
120/240 VAC
277 VAC
277 VAC
0.5-10A / Adjustable
0.5-10A / Fixed, 0.5A
10-150A / Adjustable
10-150A / Fixed, 10A
3-150A / Adjustable
3-150A / Fixed, 3 A
10A resistive
480 VA Pilot Duty
480 VA Ballast
600W Tungsten
240W Tungsten
1/3 hp for N.O.
1/6 hp for N.C.
1/4 hp for N.O.
1/8 hp for N.C.
277 VAC
277 VAC
277 VAC
120 VAC N.O
120 VAC N.C.
120/240 VAC
120/240 VAC
277 VAC
277 VAC
0.5-10A / Adjustable
0.5-10A / Fixed, 0.5A
10-150A / Adjustable
10-150A / Fixed, 10A
3-150A / Adjustable
–
Yes
–
Internal
0.5-20A / Fixed, 0.5A
0.5-20A / Adjustable
RIBX24SBA
Internal
0.5-20A / Fixed, 0.5A
RIBX24SBF
RIBXF
RIBXA
RIBXRF
RIBXRA
RIBXJF
RIBXJA
–
0.5-20A / Adjustable
RIBX24BF
Internal
Internal
Ring
Ring
Split Ring
Split Ring
RELAY CONTACT
RATINGS
Yes
20A resistive
1110 VA Pilot Duty
770 VA Pilot Duty
20A Ballast
10A Ballast
10A Tungsten
240W Tungsten
2 hp
1 hp
277 VAC
277 VAC
120 VAC
277 VAC N.O.
277 VAC N.C.
120 VAC N.O.
120 VAC N.C.
277 VAC
120 VAC
RELAY CONTACT
WIRING
RELAY COIL
& CURRENT SWITCH
Relay
Input Current
1- SPDT
Relay
(blue)
NC
(yellow)
COM
(orange)
NO
1- SPST Relay
(orange)
(orange)
12 mA @ 10 VDC
14 mA @ 12 VDC
16 mA @ 24 VDC
18 mA @ 30 VDC
Relay Coil Wiring
10-30 VAC/DC
Common
}
Current Switch Wiring
Closed
Open
Auto
1
30 mA @ 10 VAC
32 mA @ 12 VAC
42 mA @ 24 VAC
50 mA @ 30 VAC
Current
Sensor Status
}
Ring & Split Ring Models
(grey)
Current (grey)
Sensor
1- SPDT Relay
(blue)
(yellow)
(orange)
NC
COM
NO
1- SPST Relay
(orange)
(orange)
1
Closed
Open
Auto
–
Current Switch only
0.5-30A / Fixed, 0.5A
Current Sensor Wiring
–
Internal Models
Current Switch only
0.5-30A / Adjustable
(purple)
Current
–
Current Switch only
3-150A / Fixed, 3A
(purple)
Sensor
–
Current
Switch
only
3-150A / Adjustable
Ring & Split Ring Models
–
(grey)
Current Switch only
10-150A / Fixed, 10A
–
Current (grey)
Sensor
Current Switch only
10-150A / Adjustable
–
1 Internal Yellow jumper determines if SPST contacts are N.O. or N.C.
Relay
Input Current
75 mA @ 24 VAC
32 mA @ 24 VDC
Relay Coil Wiring
24 VAC/DC
Common
}
Current Switch Output
Current
Sensor Status
}
Current Switch Wiring
Current
Sensor Status
}
Order by Model Number above.
Also available in unenclosed circuit board configurations. Contact Kele for more information.
KELE • www.kele.com
USA 901-937-4900 • International 901-382-6084
Download