General
Specification
3RZHU3DFN
Model #: 033
Description:
The MPP-24 power pack is the foundation for any low voltage lighting control system. The MPP-24 supplies low voltage
power to occupancy sensors and other control devices, switching line voltage in response to signals from control devices.
The MPP-24 power pack is attached to existing junction boxes or mounted into fixture wiring trays. Low voltage wiring
should use at least 22-gauge wire. High voltage connections should use at least 14-gauge. Always check local building
codes. After initial wiring is completed, check wiring diagrams to verify the power pack is wired correctly. Improper wiring
can cause damage to the power pack, lighting system, occupancy sensor and other control devices.
Features:
•
•
•
•
Self-contained power supply relay system
LED indicator of relay operation for easy verification
Convert line voltage to low voltage in various lighting control systems
Able to link up to six sensors at a time
Specifications:
Voltage ................................................................................................................................................... 120/277VA, 50/60Hz
Load Requirements:
Ballast ...................................................................................................................................................... 20A @ 120/277VAC
Incandescent ................................................................................................................................................... 20A @120VAC
Motor ....................................................................................................................................................... 1HP @120/240VAC
Output ..................................................................................................................... 150mA @ 24VDC (with relay connected)
Operating Temperature .................................................................................................................... 32° to 131°F (0°to 55°C)
Low Voltage Input:
Control ON .............................................................................................................................................................. 12-24VDC
Hold ON................................................................................................................................................................... 12-24VDC
Hold OFF ................................................................................................................................................................. 12-24VDC
Manual ON (momentary switch required) ............................................................................................................... 12-24VDC
Relative Humidity ............................................................................................................................ 20-90%, non-condensing
Material ............................................................................................................................................................................. ABS
Warranty ....................................................................................................................................................................... 2 years
Testing and Code Compliance:
•
UL Listed device
Wiring Diagram:
Wire Color Code:
Black ............................................................................................................................................... Line
White .......................................................................................................................................... Neutral
Red ................................................................................................................................................ Load
Blue ............................................................................................................................................ Control
Orange ..................................................................................................................................... Hold ON
Gray .....................................................................................................................................Manual ON
Brown ..................................................................................................................................... Hold OFF
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
360° Dual-Technology PIR/Ultrasonic
Low Voltage Occupancy Sensor
Model #: MDC-50L
Description: The MDC-50L 360° Dual-Technology Occupancy Sensor combines advanced passive infrared (PIR)
and ultrasonic technology into one unit. The combined technologies help to avoid false triggering. Selectable operation
modes allow the sensor to turn back on and hold it on as long as either or both technologies detect occupancy. After no
movement is detected for the selected time delay, the lights switch off.
* The MDC-50L operated on 24V supplied by MMP-24 power pack
Specifications
Voltage.......................................................................................24VDC
Current Consumption...................................................................20mA
Power Supply.......................................................MPP-24 Power Pack
Operating Temperature ......................................32°to 131°F (0°to 55°C)
Adjustment Time Delay.............................................. 5 Sec. to 30 Min.
Test Mode.......delaytime is 5 sec. lasts 30 Min. at each time by setting
PIR Adjustment.........................................50% or 100% (DIP switch 1)
Ultrasonic Adjustment ..................... Minimum to Maximum (trimpot 1)
Light Level Adjustment..............................100 Lux --daylight(trimpot 2)
PIR Coverage..............................................................................1600ft 22
Ultrasonic Coverage....................................................................1000ft
Coverage area
The MDC-50L provides a 360° coverage pattern. The coverage
shown represents walking motion at mounting height of 9 feet. For
building spaces with lower levels of activity or with obstacles and
barriers ,coverage size may decrease.
44 ft
(13.4m)
PIR
Coverage
Figure 1
Ultrasonic
Coverage
30 ft x 30 ft
(9.14m x 9.14m)
Ultrasonic Sensitivity Adjustment Trimpot 1
Adjustable: Minimum to Maximum (clockwise)
Ultrasonic
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
Ambient Light Level Adjustment Trimpot 2
Adjustable: 100Lux to daylight ( clockwise)
Installation & wiring
Light
CAUTION!
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING
POWER PACKS OR SENSORS.
Each MPP-24 power pack can supply power for 6 MDC-50L sensors.
When using more sensors than this, multiple power packs are required.
White
Black
MPP-24
Blue
120VAC
277VAC
Red
Hot
Red Lighting
Load
Black
Neutral
Low Voltage Wires
Blue (control output)
Black (common)
Red (+24VDC input)
Standard Wiring:
RED —+24VDC Input
BLACK — Common
BLUE — Control Output
Figure 2
Using an Octagonal Junction Box
1. Pull the low voltage wires from power pack into the Octagonal
Junction Box through the conduit knockout.
2. Connect the low voltage wires to the appropriate wires on the
sensor.
3. Loosen the appliance mounting screws attached to the Octagonal
Junction Box.
4. Align the sensor in the Octagonal Junction Box so that the mounting
screws on the box match the holes on the sensor's rear housing.
5. Push the sensor up into the Octagonal Junction Box and twist
it so that the mounting screws are seated in the hole slots.
6. Tighten the two screws to secure the sensor to the Octagonal
Junction Box.
7. Snap the front cover onto the sensor
4"Octagonal box 2-1/2"
deep mounting
Drop Ceiling
Screws
Wire
Rear Housing
Figure 3
Front Cover
Sensor Adj ustment
PIR
Ultrasonic
sensitivity trimpot
PIR activity
LED(Red)
DIP Switch
Ultrasonic activity
LED(Green)
Ultrasonic
transducer cones
Light level
trimpot
Figure 4
There is a 40-second warm-up period when power is first applied.
The sensors are factory preset to allow for quick installation in most
applications.To make adjustments, open the Front Cover .Set the
DIP Switch to the desired settings. See"DIP Switch Setting" below.
DIP Switch Setting
The MDC-50L has 8 DIP switches under the cover. They are used to
set PIR sensitivity, time delay, override and tigger mode feature settings.
Initial
Trigger Mode Trigger
Option 1
Both
Maintain
Load Output
Either
Either
Option 3
PIR
Either
Option 4
PIR
Ultrasonic
Ultrasonic
Option 6
Both
Both
PIR Sensitivity 1
50%
100%
Time Delay
5 Sec/Autoset
30 Seconds
5 Minutes
10 Minutes
15 Minutes
20 Minutes
25 Minutes
30 Minutes
8
=ON
4
PIR
Option 5
=OFF
3
Either
Option 2
Override
Disabled
Enabled
2
5
6
7
=Factory Setting
PIR Sensitivity setting: Switch 1
50%, sensor's coverage is smaller, just about half of the widest range.
100%,the maximum range of sensor's PIR coverage is 1600 square feet.
Trigger Mode: Switches 2, 3,4
The sensor has 6 trigger options, set with DIP switches 2 , 3 and 4.
In the trigger mode DIP switch setting table:
Both requires motion detection by the PIR and the Ultrasonic.
Either requires motion detection by only one technology.
PIR requires motion detection by the PIR.
Ultrasonic requires motion detection by the Ultrasonic.
Time Delay: Switches 5, 6, 7
The sensor will hold the lights on as long as occupancy is detected. The
time delay countdown starts when no motion is detected. After no motion
is detected for the length of the time delay, the sensor will turn the lights
off.
Override: Switch 8
To override all sensor functions, set to ON position ( DIP Swicth 8 ).
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
360° Passive Infrared
Low Voltage Occupancy Sensor
Model #: MPC-50L
Description: The MPC-50L 360° passive infrared (PIR) occupancy sensors turn lighting systems
on and off based on occupancy and ambient light level. The light level feature keeps lights from
turning on if ambient light level is sufficient. The sensors can be configured to turn lighting on, and
hold it on as long as the sensor detects occupancy. After no movement is detected for a specified
or auto-set time (5 seconds to 30 minutes) the lights switch off. A "walk-through" mode can turn
lights off after only 3 minutes, if no activity is detected after 30 seconds of an occupancy detection.
* The MPC-50L operated on 24V supplied by MMP-24 power pack
Features






Passive Infrared Technology(PIR)
360 ° field of view, 1200 sq.ft.
Time Delay is adjustable from 5 seconds to 30 minutes
Simple, fast installation
Adjustable sensitivity settings
Light level is adjustable.
Specifications
Voltage ................................................................................................................... 24VDC
Current Consumption ................................................................................................. 9mA
Power Supply................................................................................... MPP-24 Power Packs
Operating Temperature .............................................................32 ° to 131°F (0 ° to 55°C)
Adjustable Light Level....................................................................................10FC-150FC
Adjustable Time Delay............................................................... 5 sec.-30min (DIP switch)
Walk-Through Mode ...................................................3 minutes if no activity after 30 sec.
Test Mode .................................................. 5 sec. upon initial power-up or DIP switch reset
PIR Coverage:
Sensitivity Adjustment ........................................................ Automatic or Low (DIP switch)
Coverage ...................................................................................................... Up to 1200 ft 2
Testing & Code Compliance

UL LISTE D
Installation & wiring
CAUTION!
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING
POWER PACKS OR SENSORS.
+24VDC
Wiring
terminals
Control Out
Common
Control Out
+24VDC
Manual ON
Common
Model#:
Manual ON
Each MPP-24 power pack can supply power for 6 MPC-50L sensors. When using
more sensors than this, multiple power packs are required.
MPC-50L
Passive Infrared Occupancy Sensor
+24VDC Connect to MPP-24 or other
Class 2 Power Packs
For Indoor Use Only
Figure 1
Connect the low voltage:
RED wire (+24VDC) from power pack to the +24V terminal on the sensor.
BLACK wire (Common) from power pack to Common terminal on the sensor.
Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY - Connect:
BLUE wire from power pack to Control Out terminal on sensor.
Wiring multiple SINGLE LIGHTING LOADs CONTROLLED BY OCCUPANCY,
DEPENDENT ON LIGHT LEVEL (AMBIENT LIGHT) - Connect:
BLUE wire from power pack to Control Out terminal on sensors.
To add a MANUAL SWITCH such as the YQDS115M Momentary Toggle Switch,
to the above applications - connect:
1. Wire from one side of switch to Common terminal on sensor.
2. Wire from other side of switch to Man Switch terminal on sensor.
Using an Octagonal J-Box
1. Pull the low voltage wires from the power pack into the J-Box through the conduit knockout.
2. Connect the low voltage wires to the appropriate terminals on the sensor.
3. Loosen the appliance mounting screws attached to the J-Box.
4. Align the sensor in the J-Box so that the mounting screws on the box match the key holes on
the sensor’s rear housing.
5. Push the sensor up into the J-Box and twist it so that the mounting screws are seated in
the keyhole slots.
6. Tighten the two screws to secure the sensor to the J-Box.
7. Snap the front cover onto the sensor.
Octagonal box mounting
Drop Ceiling
Screws
Wire
Rear Housing
Figure 2
Front Cover
J-Box Mount
Coverage area
The MPC-50L provides a 360 °coverage pattern, up to 1200 square feet. The coverage shown
represents walking motion at a mounting height of 8 feet. For building spaces with lower levels
of activity or with obstacles and barriers, coverage size may decrease.
Drawings not to scale.
8 ft
44 ft
13.4m
Typical
desk-top
level
Figure 3
22 ft
13 ft
7 ft 3 ft 0
3 ft 7 ft
13 ft
22 ft
Adj ustment
Keyhole slots(for mounting to
4" octagonal box)
Double gang mudring
mounting holes
PIR lens
PIR Activity LED(Red)
Load LED(Green)
Light level Adjustment
Buzzer
Figure 4
DIP switches
Keyhole slots
(for mounting to 4" octagonal box)
The sensors are factory preset to allow for quick installation in most applications. Verification
of proper wiring or coverage, or customizing the sensor's settings can be done using the
following procedures. To make adjustments, open the Front Cover with a small screwdriver.
There is a 40-second warm-up period when power is first applied.
Before making adjustments, make sure the office furniture is installed, lighting circuits are
turned on, and the HVAC systems are in the overridden/on position. VAV systems should be
set to their highest airflow. Set the DIP switches to the desired settings. See “DIP Switch
Setting”.
DIP Switch Setting
The MPC-50L has 9 DIP switches under the cover. They are used to set sensitivity, time
delay, walk through mode, vacancy mode, audible, visual alarm and Hold ON feature settings.
Sensitivity
50%
100%
1
Walk Through 5
Disabled
Enabled
Vacancy
Disabled
Enabled
6
Time Delay
5 Sec/Autoset
30 Seconds
5 Minutes
10 Minutes
15 Minutes
20 Minutes
25 Minutes
30 Minutes
=OFF
=ON
2
3
4
=Factory Setting
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Audible Alert
Disabled
Enabled
7
Visible Alert
Disabled
Enabled
8
Hold ON
Disabled
Enabled
9
Date: 03/01/2016
General
Specification
360° Passive Infrared
Line Voltage Occupancy Sensor
Model #: MPC-50V
Description: The MPC-50V 360 °passive infrared (PIR) occupancy sensors turn lighting systems
on and off based on occupancy and ambient light levels. The light level feature keeps lights from
turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting on,
and hold it on as long as the sensor detects occupancy. After no movement is detected for a
specified time the lights are switched off.
Features






Passive Infrared Technology(PIR)
360 ° field of view, 1200 sq.ft.
Time Delay is adjustable from 5 seconds to 30 minutes
Simple, fast installation
Adjustable sensitivity settings
Light level is adjustable.
Specifications
Voltage ................................................................................................................... 24VDC
Current Consumption ................................................................................................. 9mA
Power Supply................................................................................... MPP-24 Power Packs
Operating Temperature .............................................................32 ° to 131°F (0 ° to 55°C)
Adjustable Light Level....................................................................................10FC-150FC
Adjustable Time Delay............................................................... 5 sec.-30min (DIP switch)
Walk-Through Mode ...................................................3 minutes if no activity after 30 sec.
Test Mode .................................................. 5 sec. upon initial power-up or DIP switch reset
PIR Coverage:
Sensitivity Adjustment ........................................................ Automatic or Low (DIP switch)
Coverage ...................................................................................................... Up to 1200 ft 2
Testing & Code Compliance

UL LISTE D
Installation & wiring
CAUTION!
TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING
POWER PACKS OR SENSORS.
+24VDC
Wiring
terminals
Control Out
Common
Control Out
+24VDC
Manual ON
Common
Model#:
Manual ON
Each MPP-24 power pack can supply power for 6 MPC-50L sensors. When using
more sensors than this, multiple power packs are required.
MPC-50L
Passive Infrared Occupancy Sensor
+24VDC Connect to MPP-24 or other
Class 2 Power Packs
For Indoor Use Only
Figure 1
Connect the low voltage:
RED wire (+24VDC) from power pack to the +24V terminal on the sensor.
BLACK wire (Common) from power pack to Common terminal on the sensor.
Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY - Connect:
BLUE wire from power pack to Control Out terminal on sensor.
Wiring multiple SINGLE LIGHTING LOADs CONTROLLED BY OCCUPANCY,
DEPENDENT ON LIGHT LEVEL (AMBIENT LIGHT) - Connect:
BLUE wire from power pack to Control Out terminal on sensors.
To add a MANUAL SWITCH such as the YQDS115M Momentary Toggle Switch,
to the above applications - connect:
1. Wire from one side of switch to Common terminal on sensor.
2. Wire from other side of switch to Man Switch terminal on sensor.
Using an Octagonal J-Box
1. Pull the low voltage wires from the power pack into the J-Box through the conduit knockout.
2. Connect the low voltage wires to the appropriate terminals on the sensor.
3. Loosen the appliance mounting screws attached to the J-Box.
4. Align the sensor in the J-Box so that the mounting screws on the box match the key holes on
the sensor’s rear housing.
5. Push the sensor up into the J-Box and twist it so that the mounting screws are seated in
the keyhole slots.
6. Tighten the two screws to secure the sensor to the J-Box.
7. Snap the front cover onto the sensor.
Octagonal box mounting
Drop Ceiling
Screws
Wire
Rear Housing
Figure 2
Front Cover
J-Box Mount
Coverage area
The MPC-50L provides a 360 °coverage pattern, up to 1200 square feet. The coverage shown
represents walking motion at a mounting height of 8 feet. For building spaces with lower levels
of activity or with obstacles and barriers, coverage size may decrease.
Drawings not to scale.
8 ft
44 ft
13.4m
Typical
desk-top
level
Figure 3
22 ft
13 ft
7 ft 3 ft 0
3 ft 7 ft
13 ft
22 ft
Adj ustment
Keyhole slots(for mounting to
4" octagonal box)
Double gang mudring
mounting holes
PIR lens
PIR Activity LED(Red)
Load LED(Green)
Light level Adjustment
Buzzer
Figure 4
DIP switches
Keyhole slots
(for mounting to 4" octagonal box)
The sensors are factory preset to allow for quick installation in most applications. Verification
of proper wiring or coverage, or customizing the sensor's settings can be done using the
following procedures. To make adjustments, open the Front Cover with a small screwdriver.
There is a 40-second warm-up period when power is first applied.
Before making adjustments, make sure the office furniture is installed, lighting circuits are
turned on, and the HVAC systems are in the overridden/on position. VAV systems should be
set to their highest airflow. Set the DIP switches to the desired settings. See “DIP Switch
Setting”.
DIP Switch Setting
The MPC-50L has 9 DIP switches under the cover. They are used to set sensitivity, time
delay, walk through mode, vacancy mode, audible, visual alarm and Hold ON feature settings.
Sensitivity
50%
100%
1
Walk Through 5
Disabled
Enabled
Vacancy
Disabled
Enabled
6
Time Delay
5 Sec/Autoset
30 Seconds
5 Minutes
10 Minutes
15 Minutes
20 Minutes
25 Minutes
30 Minutes
=OFF
=ON
2
3
4
=Factory Setting
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Audible Alert
Disabled
Enabled
7
Visible Alert
Disabled
Enabled
8
Hold ON
Disabled
Enabled
9
Date: 03/01/2016
General
Specification
High Bay 360° Passive Infrared
Line Voltage Occupancy Sensor
Model #: MPC-50H
Description:
The MPC-50H occupancy sensor is designed for automatic lighting control in high bay applications, such as warehouses,
distribution centers, gymnasiums, and areas with direct access to the lighting fixtures, specifically for indoor locations.
This product contains a passive infrared sensor (PIR).
Features:
•
•
•
•
•
•
LED indicator of occupancy detection for easy verification of coverage
Easy front access to time delay, sensitivity range and ambient light level adjustment
Easy mounting using ½” knockout at end of luminaire fixture
Hardware choices for side and back mount
Compatible with all program start ballasts
Zero crossing circuitry reduces stress on relay and extends sensor life
Specifications:
Voltage .................................................................................................................................................... 120/277VA,50/60Hz
Load Requirements:
@ 120VAC .......................................................................................................................................800W ballast or tungsten
@ 277VAC ........................................................................................................................................................ 1200W ballast
@ 120VAC ....................................................................................................................................................................1/4 hp
Adjustable Light Level ...................................................................................................................................... 10FC—150FC
Sensitivity Adjustable ..................................................................................................................... 50% or 100%(DIP switch)
Operating Temperature ..................................................................................................................... 32°to 131°F (0°to 55°C)
Relative Humidity ............................................................................................................................ 20-90%, non-condensing
Controls ............................................................................................................................ Light Level Knob and Dip Switches
Material ............................................................................................................................................................................. ABS
Warranty ....................................................................................................................................................................... 2 years
Testing and Code Compliance:
•
•
UL/CUL Listed device
California Title 24
Dimensions:
Coverage:
Lens Specifications:
MPC-50H-L1:
Mounting height ..................................................................................................................................................................50ft
Field of view ..................................................................................................................................................................... 360°
Coverage .................................................................................................................................................................. 2800 sq.ft
MPC-50H-L2:
Mounting height ....................................................................................................................................................................8ft
Field of view ..................................................................................................................................................................... 360°
Coverage .................................................................................................................................................................. 1200 sq.ft
Dip Switch Setting:
Wiring Diagram:
Components:
The MPC-50H has 4 DIP switches under the cover. They
are used to set sensitivity and time delay feature settings.
First switch: Changes the sensitivity of the sensor,
increasing or decreasing the range and height of
detection.
Second, Third, and Forth: Through a combination of these
switches outlined in the table above, the times at which
the loads will turn off can be changed.
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
360° Passive Infrared
Line Voltage Occupancy Sensor
Model #: MPC-52V
Description: The MPC-52V 360° passive infrared (PIR) occupancy sensors turn lighting systems
on and off based on occupancy and ambient light levels. The light level feature keeps lights from
turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting on,
and hold it on as long as the sensor detects occupancy. After no movement is detected for a
specified time the lights are switched off.
Features:

360 ° field of view, 800 sq.ft.

Passive Infrared Technology(PIR)




Time Delay is adjustable from 15 seconds (test mode) to 30 minutes
Simple, fast installation
Adjustable sensitivity settings
Light level is adjustable.
Specifications
Incandescent....................................................................800W-120VAC, 60HZ
Fluorescent ...................................800VA-120VAC / 1200VA-277VAC, 60HZ
Motor..............................................................................1/4 HP ,120VAC, 60HZ
Operating Temperature ...................................................32°to 131°F (0°to 55°C)
Adjustable Light Level ................................................................10FC—150FC
Adjustable Time Delay ................................................................15 sec.-30min.
Sensitivity Adjustment.........................................50% or 100% (DIP switch 1)
Coverage……….........…..…………...................…………………….Up to 800 ft 2
Lead Power Cable………....………….........................…….…………….....4 feet
Testing and Code Compliance:
•
UL Pending
Installation & wiring
Refer to the wire diagram of the sensor (see figure 1), and connect the wires of
ceiling sensors as followed by using the wire nuts provided.
1.. Connect the Hot wire to the Black wire from the senso
2.. Connect the Load wire to the Red wire from the senso
3.. Connect the Neutral wire to the White wire from the senso
4.. This sensor can install together with a snap switch in series, in this case, conne
the sensor hot (black) wire to the load wire of the snap switch ,it can be a single
pole switch, 3-way switches or 4-way switches.
Neutral
White
Red
Black
Hot
Load
MPC-52V
Figure 1
Coverage area
The MPC-52V provides a 360° coverage pattern, up to 800 square feet.
Figure 2 ).For building spaces with lower levels of activity or with
obstacles and barriers, coverage size may decrease.
8 ft
Typical
desk-top
level
34 ft
10.36 m
17 ft 15 ft 7 ft 5 ft 3 ft
0
3 ft 5 ft 7 ft 15 ft 17 ft
Figure 2
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
4" Square J-Box with Round Ring
Auxiliary Mounting Adapter
4" Square J-Box with Single Gang
Auxiliary Mounting Adapter
4"Octagonal J-Box
4" Square J-Box with Double Gang
for the below junction boxes.
4" Square J-Box with Round Ring
Auxiliary Mounting Adapter
4" Square J-Box with Single Gang
The Auxiliary Mounting Adapter allows you to mount ceiling sensors
Product Description
Model Number :MPC-A
Auxiliary Mounting Adapter for Ceiling sensor
Auxiliary Mounting Adapter
4"Octagonal J-Box
4" Square J-Box with Double Gang
for the below junction boxes.
The Auxiliary Mounting Adapter allows you to mount ceiling sensors
Product Description
Model Number :MPC-A
Auxiliary Mounting Adapter for Ceiling sensor
General
Specification
150° Passive Infrared
Line Voltage Occupancy Sensor
Model #: MPW-V
Description: The MPW-V 150° passive infrared (PIR) occupancy sensors turn lighting systems
on and off based on occupancy and ambient light levels. The light level feature keeps lights from
turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting
on, and hold it on as long as the sensor detects occupancy. After no movement is detected for a
specified time the lights are switched off.
Features
 Passive Infrared Technology(PIR)
 150° field of view, 1000 sq.ft.
 Time Delay is adjustable from 5 seconds to 30 minutes
 Simple, fast installation
 Adjustable sensitivity settings
 Light level is adjustable.
Specifications
Voltage ............................................................................................................120-277VAC, 60Hz
Max load.................................................................................................................................10A
2
PIR Coverage.......................................................................................................…...….1000 ft
Operation Temperature..........................................................................32° to 131°F (0° to 55° C)
Range..................................................................................................................25% to 100%
Adjustable Time Delay.......................................................................................30 sec to 30 min.
Testing & Code Compliance

UL LISTE D
COVERAGE PATTERN
The MPW-V privides an eliptical coverage pattern (see Figure 1). The
coverage shown repersents walking motion at a mounting height of
10 feet. The maximun coverage will be up to 1000 ft 2 with a largest
distance of 15 meters. For building spaces with lower levels of activity
or with obstacles and barriers, coverage size may decrease.
INSTALLATION
1.. Make sure that the power has been turned OFF at the circuit breake
2.. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead
Line(Hot), Red lead to Load wire, White lead to Neutral wire.
Wiring Diagram:
Neutral
White
Hot
Black
Load
Red
Neutral
White
Figure 1
- 01-
ADJUSTMENT
PIR Lens
Mounting Yoke
Figure 2
3. Mount device up to walls or ceiling
4. Gently position wires in wall/octagon bo
a. attach sensor switch to the box, and fix it to the wall/ceiling
with two screws.
or b. attach sensor switch to the mounting yoke with wires
through its certral hole, and fix the yoke to the wall/ceiling.
5. Restore power at circuit breaker or fuse, wa one minute.
6. Remove the small cover plate. (illustrated as Figure 3.
7. Locate the adjustment knob on the control panel to perform te
and adjustment.(illustrated as Figure 3 and 4. )
8. Replace the small cover plate after testing and adjustmen
Control Panel Cover
Detection LEDs
Red=PIR
Figure 3
TIME
RANGE
LIGHT
Figure 4
TIME Adjustment Trimpot
Default position: Time (Test at position 1)
Adjustable: 5 sec. to 30 mins (clockwise)
PIR Adjustment Knob
Default position: Center
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
Ambient Light Level Adjustment Trimpot
Default position: Daylight (100% at position 4)
Adjustable: Clock wise
OPERATION
The Sensor Switch is programmed for Occupancy Mode only.
Automatic Turning On/Off the Load
Once the power is on, the load will be turned On according to the
occupancy settings. The sensor time delay operates as programmed.
When the load turns OFF due to the lack of motion detection, the
load can be turned ON again by occupancy detection or switch
activation.
The Sensor keeps the Load On until no motion is detected plus the
set time delay, load(s) will be turned Off automatically.
TROUBLESHOOTING`
TROUBLESHOOTING
WARNING: Turn off the power at the circuit breaker before
installation. Lights do not turn on with occupancy, and the
following condition exists:
PIR Activity LED does not flash:
NOTE: When power is initially applied to the sensor, there is a warm-up
period of up to 1 minute before the LED is active.
1. Check that the circuit breaker or any wall switch connected to the
sensor has been turned back on.
2. Make sure that the PIR Sensitivity is set for Max.
3. Make sure the wire is connected right.
PIR Activity LED flashes:
1. If the sensor’s Light Level has been turned to minimum (at position
1), the lights connected to the Light Level Output might be held off
because of the level of ambient light in the controlled area. To test
whether the Light Level adjustment is the problem, cover the PIR lens
and PIR Activity LED with your hand to see if the lights turn on. If
the lights turn on, the Light Level setting was keeping the lights off
(see, “Sensor Adjustment” for readjustment).
2. Make sure the wire is connected right.
Lights do not turn off automatically:
1. The sensor may be experiencing activations from outside the
controlled or from some type of interference (see “Unwanted Sensor
Activations” below).
2. Make sure the wire is connected right.
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/02/2016
General
Specification
150° Passive Infrared
Line Voltage Occupancy Sensor
Model #: MPW-J
Description: The MPW-J 150° passive infrared (PIR) occupancy sensors turn lighting systems
on and off based on occupancy and ambient light levels. The light level feature keeps lights
from turning on if the ambient light level is sufficient. The sensors can be configured to turn
lighting on, and hold it on as long as the sensor detects occupancy. After no movement is
detected for a specified time the lights are switched off.
Features
 Passive Infrared Technology(PIR)
 150° field of view, 1000 sq.ft.
 Time Delay is adjustable from 5 seconds to 30 minutes
 Simple, fast installation
 Adjustable sensitivity settings
 Light level is adjustable
 Secured ground wire required
Specifications
Voltage ............................................................................................................120-277VAC, 60Hz
Max load.................................................................................................................................10A
2
PIR Coverage.......................................................................................................…...….1000 ft
Operation Temperature..........................................................................32° to 131°F (0° to 55° C)
Range..................................................................................................................25% to 100%
Adjustable Time Delay.......................................................................................30 sec to 30 min.
Testing & Code Compliance

UL LISTE D
COVERAGE PATTERN
The MPW-J privides an elliptical coverage pattern (see Figure 1). The
coverage shown represents walking motion at a mounting height of 10
feet. The maximum coverage will be up to 1000 ft 2 with a largest
distance of 15 meters. For building spaces with lower levels of activity
or with obstacles and barriers, coverage size may decrease.
INSTALLATION
1.. Make sure that the power has been turned OFF at the circuit breake
2.. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead
Line(Hot), Red lead to Load wire, White lead to Neutral wire.
Wiring Diagram:
Neutral
White
Hot
Black
Load
Red
Neutral
White
Figure 1
- 01-
ADJUSTMENT
PIR Lens
Mounting Yoke
Figure 2
3. Mount device up to walls or ceiling
4. Gently position wires in wall/octagon bo
a. attach sensor switch to the box, and fix it to the wall/ceiling
with two screws.
or b. attach sensor switch to the mounting yoke with wires
through its certral hole, and fix the yoke to the wall/ceiling.
5. Restore power at circuit breaker or fuse, wa one minute.
6. Remove the small cover plate. (illustrated as Figure 3.
7. Locate the adjustment knob on the control panel to perform te
and adjustment.(illustrated as Figure 3 and 4. )
8. Replace the small cover plate after testing and adjustmen
Control Panel Cover
Detection LEDs
Red=PIR
Figure 3
TIME
RANGE
LIGHT
Figure 4
TIME Adjustment Trimpot
Default position: Time (Test at position 1)
Adjustable: 5 sec. to 30 mins (clockwise)
PIR Adjustment Knob
Default position: Center
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
Ambient Light Level Adjustment Trimpot
Default position: Daylight (100% at position 4)
Adjustable: Clock wise
OPERATION
The Sensor Switch is programmed for Occupancy Mode only.
Automatic Turning On/Off the Load
Once the power is on, the load will be turned On according to the
occupancy settings. The sensor time delay operates as programmed.
When the load turns OFF due to the lack of motion detection, the
load can be turned ON again by occupancy detection or switch
activation.
The Sensor keeps the Load On until no motion is detected plus the
set time delay, load(s) will be turned Off automatically.
TROUBLESHOOTING`
TROUBLESHOOTING
WARNING: Turn off the power at the circuit breaker before
installation. Lights do not turn on with occupancy, and the
following condition exists:
PIR Activity LED does not flash:
NOTE: When power is initially applied to the sensor, there is a warm-up
period of up to 1 minute before the LED is active.
1. Check that the circuit breaker or any wall switch connected to the
sensor has been turned back on.
2. Make sure that the PIR Sensitivity is set for Max.
3. Make sure the wire is connected right.
PIR Activity LED flashes:
1. If the sensor’s Light Level has been turned to minimum (at position
1), the lights connected to the Light Level Output might be held off
because of the level of ambient light in the controlled area. To test
whether the Light Level adjustment is the problem, cover the PIR lens
and PIR Activity LED with your hand to see if the lights turn on. If
the lights turn on, the Light Level setting was keeping the lights off
(see, “Sensor Adjustment” for readjustment).
2. Make sure the wire is connected right.
Lights do not turn off automatically:
1. The sensor may be experiencing activations from outside the
controlled or from some type of interference (see “Unwanted Sensor
Activations” below).
2. Make sure the wire is connected right.
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/02/2016
General
Specification
150° Dual-Technology PIR/Ultrasonic
Line Voltage Occupancy Sensor
Model #: MDW-V
Description: This Dual Technology Occupancy Sensor combines advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combined technologies help to avoid false triggering even in difficult applications. The
MDW-L turns lighting on and off based on occupancy and ambient light levels. The sensor offers numerous operating
modes that can be combined to create the ideal custom control. Selectable operating mode allow the sensor to turn a
load on, and hold it on as long as either or both technologies detect occupancy. After no movement is detected for the
selected time delay, the lights switch off. A "walk-through" mode can turn lights off after only 3 minutes, if no activity is
detected after 30 seconds following an occupancy detection. This sensor contains a light level sensor. If adequate
daylight is present, the sensor holds the load OFF until light levels drop, even if the area is occupied. * The MDC-50L
operated on 24V supplied by MMP-24 power pack
Specifications
Voltage...........................................................120/277 VAC @50/60Hz
Maximum load..................................................................................8A
Operating Temperature ......................................32°to 131°F (0°to 55°C)
Adjustment Time Delay.............................................. 5 Sec. to 30 Min.
Test Mode.......delaytime is 5 sec. lasts 30 Min. at each time by setting
PIR Adjustment.........................................50% or 100% (DIP switch 1)
Ultrasonic Adjustment ..................... Minimum to Maximum (trimpot 1)
Light Level Adjustment..............................100 Lux --daylight(trimpot 2)
PIR Coverage..............................................................................1000ft 22
Ultrasonic Coverage......................................................................800ft
Coverage area
The MDW-V provides a 150° coverage pattern. The coverage
shown represents walking motion at mounting height of 10 feet. For
building spaces with lower levels of activity or with obstacles and
barriers ,coverage size may decrease.
PIR coverage 50ft
Ultrasonic coverage 30ft
Figure 1
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to
Line(Hot), Red lead to Load wire, White lead to Neutral wire.
Wiring Diagram:
Neutral
White
Load
Red
Hot
Black
Neutral
White
Figure 2
3. Mount device up to walls or ceilings.
4. Gently position wires in wall/octagon box,
a. attach sensor switch to the box, and fix it to the wall/ceiling .
with two screws.
or b. attach sensor switch to the mounting yoke with wires
through its certral hole, and fix the yoke to the wall/ceiling.
5. Restore power at circuit breaker or fuse, wait one minute.
6. Remove the small cover plate. (illustrated as Figure 3. )
7. Locate the adjustment knob on the control panel to perform test
and adjustment.(illustrated as Figure 3 and 4. )
8. Replace the small cover plate after testing and adjustment.
ADJUSTMENT
Mounting Yoke
PIR Lens
Ultrasonic Cones
Figure 3
Control Panel Cover
Detection LEDs
Red=PIR
Blue=Ultrasonic
Figure 4
Ultrasonic
PIR
Light
Ultrasonic & PIR Sensitivity Adjustment Knob
Default position: Center
Adjustable: 25% (Position 1) to 100% (Position 4)
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
Ambient Light Level Adjustment Trimpot
Default position: Daylight (100% at position 4)
Adjustable: Clock wise
Trigger mode: Switches 1, 2, 3
The sensor has 6 trigger options, set with DIP switches1, 2 and 3.
In the trigger mode DIP switch setting table:
DIP SWITCH SETTING
The MDW-L has 7 DIP switches under the cover. They are used to
set trigger mode, time delay and walk through mode feature settings.
Initial
Maintain Re-trigger
Occupancy Occupancy (seconds
Occupancy Logic
Trigger
1
2
3
duration)
Default
Both
Option 1
Either
Either
Either
Option 2
PIR
Either
Either
Option 3
Both
Both
Both
Option 4
PIR
PIR
PIR
Option 5
Ultra
Ultra
Ultra
Time Delay
5 Sec Test
30 Sec
3 Min
5 Min
10 Min
15 Min
20 Min
30 Min
4
5
Either
6
Either
Walk-Through 7
Disabled
Enabled
=OFF
=ON
=Factory Setting
Both requires motion detection by the PIR and the Ultrasonic.
Either requires motion detection by only one technology.
PIR requires motion detection by the PIR.
Ultra requires motion detection by the Ultrasonic.
Initial Occupancy: The method that activates a change from “Standby”
(area unoccupied and loads are off) to“Occupied” (area occupied and
loads are on).
Maintain Occupancy:The method indicating that the area is still
occupied and the lights should remain on.
Re-trigger: After the time delay elapses and the lights turn off, detection
by the selected technology within the number of seconds indicated turns
the lights back on.
To turn off a technology:
Option 4 turns off the Ultrasonic detection
Option 5 turns off the PIR detection
Time Delay: Switches 4, 5, 6
The sensor will hold the lights on as long as occupancy is detected. The
time delay countdown starts when no motion is detected. After no motion
is detected for the length of the time delay, the sensor will turn the lights
off.
Walk-through mode: Switch 7
Turns the lights off three minutes after the area is initially occupied, if no
motion is detected after the first 30 seconds. If motion continues beyond
the first 30 seconds, the selected time delay applies.
There is a 40-second warm-up period when power is first applied.
The sensors are factory preset to allow for quick installation in most
applications.To make adjustments, open the Front Cover .Set the
DIP Switch to the desired settings. See"DIP Switch Setting" below.
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
150° Dual-Technology PIR/Ultrasonic
Low Voltage Occupancy Sensor
Model #: MDW-L
Description: This Dual Technology Occupancy Sensor combines advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combined technologies help to avoid false triggering even in difficult applications. The
MDW-L turns lighting on and off based on occupancy and ambient light levels. The sensor offers numerous operating
modes that can be combined to create the ideal custom control. Selectable operating mode allow the sensor to turn a
load on, and hold it on as long as either or both technologies detect occupancy. After no movement is detected for the
selected time delay, the lights switch off. A "walk-through" mode can turn lights off after only 3 minutes, if no activity is
detected after 30 seconds following an occupancy detection. This sensor contains a light level sensor. If adequate
daylight is present, the sensor holds the load OFF until light levels drop, even if the area is occupied. * The MDC-50L
operated on 24V supplied by MMP-24 power pack
Specifications
Voltage.........................................................................18-28VDC/VAC
Current Consumption...................................................................40mA
Power Supply.......................................................MPP-24 Power Pack
Operating Temperature ......................................32°to 131°F (0°to 55°C)
Adjustment Time Delay.............................................. 5 Sec. to 30 Min.
Test Mode.......delaytime is 5 sec. lasts 30 Min. at each time by setting
PIR Adjustment.........................................50% or 100% (DIP switch 1)
Ultrasonic Adjustment ..................... Minimum to Maximum (trimpot 1)
Light Level Adjustment..............................100 Lux --daylight(trimpot 2)
PIR Coverage..............................................................................1000ft 22
Ultrasonic Coverage......................................................................800ft
Coverage area
The MDW-L provides a 150° coverage pattern. The coverage
shown represents walking motion at mounting height of 10 feet. For
building spaces with lower levels of activity or with obstacles and
barriers ,coverage size may decrease.
PIR coverage 50ft
Ultrasonic coverage 30ft
Figure 1
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to
Common, Red lead to +24V, Blue lead to Control Out.
Red +24V
Common Black
3. Mount device up to walls or ceilings.
4. Gently position wires in wall/octagon box,
a. attach sensor switch to the box, and fix it to the wall/ceiling .
with two screws.
or b. attach sensor switch to the mounting yoke with wires
through its certral hole, and fix the yoke to the wall/ceiling.
5. Restore power at circuit breaker or fuse, wait one minute.
6. Remove the small cover plate. (illustrated as Figure 3. )
7. Locate the adjustment knob on the control panel to perform test
and adjustment.(illustrated as Figure 3 and 4. )
8. Replace the small cover plate after testing and adjustment.
Figure 2
Blue
Control Out
Standard Wiring:
RED —+24VDC Input
BLACK — Common
BLUE — Control Output
Figure 3
ADJUSTMENT
Mounting Yoke
PIR Lens
Ultrasonic Cones
Control Panel Cover
Detection LEDs
Red=PIR
Blue=Ultrasonic
Figure 4
Ultrasonic
PIR
Light
Ultrasonic & PIR Sensitivity Adjustment Knob
Default position: Center
Adjustable: 25% (Position 1) to 100% (Position 4)
Note: Turn toward right for greater room space.
Turn toward left to avoid false alert in smaller room and near
the door way or heat source.
Ambient Light Level Adjustment Trimpot
Default position: Daylight (100% at position 4)
Adjustable: Clock wise
Trigger mode: Switches 1, 2, 3
The sensor has 6 trigger options, set with DIP switches1, 2 and 3.
In the trigger mode DIP switch setting table:
DIP SWITCH SETTING
The MDW-L has 7 DIP switches under the cover. They are used to
set trigger mode, time delay and walk through mode feature settings.
Initial
Maintain Re-trigger
Occupancy Occupancy (seconds
Occupancy Logic
Trigger
1
2
3
duration)
Default
Both
Option 1
Either
Either
Either
Option 2
PIR
Either
Either
Option 3
Both
Both
Both
Option 4
PIR
PIR
PIR
Option 5
Ultra
Ultra
Ultra
Time Delay
5 Sec Test
30 Sec
3 Min
5 Min
10 Min
15 Min
20 Min
30 Min
4
5
Either
6
Either
Walk-Through 7
Disabled
Enabled
=OFF
=ON
=Factory Setting
Both requires motion detection by the PIR and the Ultrasonic.
Either requires motion detection by only one technology.
PIR requires motion detection by the PIR.
Ultra requires motion detection by the Ultrasonic.
Initial Occupancy: The method that activates a change from “Standby”
(area unoccupied and loads are off) to“Occupied” (area occupied and
loads are on).
Maintain Occupancy:The method indicating that the area is still
occupied and the lights should remain on.
Re-trigger: After the time delay elapses and the lights turn off, detection
by the selected technology within the number of seconds indicated turns
the lights back on.
To turn off a technology:
Option 4 turns off the Ultrasonic detection
Option 5 turns off the PIR detection
Time Delay: Switches 4, 5, 6
The sensor will hold the lights on as long as occupancy is detected. The
time delay countdown starts when no motion is detected. After no motion
is detected for the length of the time delay, the sensor will turn the lights
off.
Walk-through mode: Switch 7
Turns the lights off three minutes after the area is initially occupied, if no
motion is detected after the first 30 seconds. If motion continues beyond
the first 30 seconds, the selected time delay applies.
There is a 40-second warm-up period when power is first applied.
The sensors are factory preset to allow for quick installation in most
applications.To make adjustments, open the Front Cover .Set the
DIP Switch to the desired settings. See"DIP Switch Setting" below.
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
Commercial Grade
In-Wall Occupancy/Vacancy Sensor
Model #: DWOS-J
Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body
in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects
occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one
relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level.
Features:








Turn lights ON/OFF automatically (Occupancy Mode)
Manual ON / automatically OFF (Vacancy Mode)
Time delay is adjustable from 15 seconds (test mode) to 30 minutes
Secured ground wire required
Zero Crossing for long relay life
Adjustable sensitivity settings
Light level is adjustable
Standard decorator wall plate included
Specifications:
Voltage ……………………………………..……………………..…........................120-277 Vac, 60 Hz
Incadescent ………………………………………….……….........................................................800W
Fluorescent …………………………………………..…………120VAC/800VA..........277VAC/1600VA
LED/CFL …………………………………………..…………….………...............................…......150W
Motor …………………………………………………………………….…...............................….1/4 HP
Time delay ………………………………………………….…...............................…15 Sec to 30 Mins
Light level …………………………………………...……...…................................…30 Lux – Datlight
Operation temperating …………………………………..………...............................…..32 F to 131 F
Testing & Code Compliance


UL/CUL Listed device
California Title 24
Installation & wiring:
Install the product as illustrated to the right,
connects wires Green lead to ground, Black
lead to Hot, Red lead to Load, White Lead to
Neutral.
Controls
*Coverage Area
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
Commercial Grade
In-Wall Bi-Level
Occupancy/Vacancy Sensor
Model #: DWOS-JD
Description: Replaces standard switches for control of lighting and/or fans. Contains two relays to
control two independent lighting loads or circuits. The passive infrared sensors work by detecting
the difference between heat emitted from the human body in motion and the background space. The
sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no
motion is detected for the set time delay, the load turned off automatically.
Features:








Turn lights ON/OFF automatically (Occupancy Mode)
Manual ON / automatically OFF (Vacancy Mode)
Time delay is adjustable from 15 seconds (test mode) to 30 minutes
Secured ground wire required
Zero Crossing for long relay life
Adjustable sensitivity settings
Light level is adjustable
Standard decorator wall plate included
Specifications:
Voltage ……………………………………..……………………..…........................120/277Vac, 60 Hz
Incadescent ………………………………………….…………………………...............................800W
Fluorescent …………………………………………...................800VA@120VAC, 1600VA@277VAC
Motor …………………………………………………………………….…...............................….1/4 HP
Time delay ………………………………………………….…...............................…15 Sec to 30 Mins
Light level …………………………………………...……...…................................…30 Lux – Datlight
Operation temperating …………………………………..………...............................…..32 F to 131 F
Testing & Code Compliance


UL/CUL Listed device
California Title 24
Installation & wiring:
1
2
Controls
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
Commercial Grade
In-Wall Occupancy/Vacancy Sensor
Model #: DWOS-1277
Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body
in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects
occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one
relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level.
Features:








Turn lights ON/OFF automatically (Occupancy Mode)
Manual ON / automatically OFF (Vacancy Mode)
Time delay is adjustable from 15 seconds (test mode) to 30 minutes
Neutral wire required
Zero Crossing for long relay life
Adjustable sensitivity settings
Light level is adjustable
Standard decorator wall plate included
Specifications:
Voltage ……………………………………..……………………..…........................120/277Vac, 60 Hz
Incadescent ………………………………………….…………………………...............................800W
Fluorescent …………………………………………...................800VA@120VAC, 1600VA@277VAC
Motor …………………………………………………………………….…...............................….1/4 HP
Time delay ………………………………………………….…...............................…15 Sec to 30 Mins
Light level …………………………………………...……...…................................…30 Lux – Datlight
Operation temperating …………………………………..………...............................…..32 F to 131 F
Testing & Code Compliance


UL/CUL Listed device
California Title 24
Installation & wiring:
Install the product as illustrated to the right,
connects wires Green lead to ground, Black
lead to Hot, Red lead to Load, White Lead to
Neutral.
Controls
*Coverage Area
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
Commercial Grade
In-Wall Occupancy/Vacancy Sensor
Model #: DWOS-1277-NL
Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body
in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects
occupancy. After no motion is detected for the set time delay, the load turned off automatically. Night Light will only be
active when it is set to Vacancy Mode, Night Light stays ON if the load is Off, it turns off if there is an Occupancy and the
light turned on. This product has one relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level.
Features:









Turn lights ON/OFF automatically (Occupancy Mode)
Manual ON / automatically OFF (Vacancy Mode)
Time delay is adjustable from 15 seconds (test mode) to 30 minutes
Neutral wire required
Zero Crossing for long relay life
Adjustable sensitivity settings
Light level is adjustable
Night Light feature to pinpoint the location of the switch in a dark area.
Standard decorator wall plate included
Specifications:
Voltage ……………………………………..……………………..…........................120/277Vac, 60 Hz
Incadescent ………………………………………….…………………………...............................800W
Fluorescent …………………………………………...................800VA@120VAC, 1600VA@277VAC
Motor …………………………………………………………………….…...............................….1/4 HP
Time delay ………………………………………………….…...............................…15 Sec to 30 Mins
Light level …………………………………………...……...…................................…30 Lux – Datlight
Operation temperating …………………………………..………...............................…..32 F to 131 F
Testing & Code Compliance


UL/CUL Listed device
California Title 24
Installation & wiring:
Install the product as illustrated to the right,
connects wires Green lead to ground, Black
lead to Hot, Red lead to Load, White Lead to
Neutral.
Controls
*Coverage Area
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
In-Wall Occupancy/Vacancy Sensor
Model #: DWOS-3R
Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body
in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects
occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product includes
adjustable Ambient Light Level.
Features:









Turn lights ON/OFF automatically (Occupancy Mode)
Manual ON / automatically OFF (Vacancy Mode)
Time delay is adjustable from 15 seconds (test mode) to 30 minutes
Neutral wire required
Single pole or three-way
Zero Crossing for long relay life
Adjustable sensitivity settings
Light level is adjustable
Standard decorator wall plate included
Specifications:
Voltage ……………………………………..……………………..…...............................120 Vac, 60 Hz
Incadescent ………………………………………….…………………………...............................800W
Fluorescent …………………………………………..…………….………...............................…800 VA
Motor …………………………………………………………………….…...............................….1/4 HP
Time delay ………………………………………………….…...............................…15 Sec to 30 Mins
Light level …………………………………………...……...…................................…30 Lux – Datlight
Operation temperating …………………………………..………...............................…..32 F to 131 F
Testing & Code Compliance


UL/CUL Listed device
California Title 24
Installation & wiring:
Install the product as illustrated to the right,
connects wires Green lead to ground, Black
lead to Hot and one terminal of 3-way switch,
Red lead
Re
. to Load, White lead to Neutral, and
3-way Blue lead to another terminal of 3-way
switch. Do not connect Red and White together
Controls
*Coverage Area
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
Commercial Grade
In-Wall Occupancy/Vacancy Sensor
Model #: MWOS
Description: This Multi-Technology Wall Switch Sensor combine advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combined technologies helps eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load on, and hold it on as long as either or both technologies
detect occupancy . After no movement is detected for the selected time delay, the lights switch off.
A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an
occupancy detection.
This sensor also contains a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light
levels drop, even if the area is occupied.
Features:




Integrated PIR and Ultrasonic sensor technology to detect very fine motion and provide accurate motion sensing
Allows to choose triggering when both technologies detect motion or when only PIR detects motion
Less false trigger, fast ON/OFF; commercial grade sensor for closet, garage, hotels, meeting room, work places
Adjustable timeout from 15 seconds to 30 minutes; Walk-Through mode: 3 minutes if no activity after first 30
seconds
Specifications:
Voltage ................................................................ 120/277VAC,50/60Hz
Load Requirments:
Incandescent....................................................800W-120VAC,50/60Hz
Fluorescent.........................800VA-120VAC,1600VA-277VAC,50/60Hz
Resistive...........................................................800W-120VAC,50/60Hz
Motor .............................................................. 1/4HP-120VAC,50/60Hz
Adjustment Time Delay................................................. 5Sec to 30Mins
Walk-Through Mode.......................3 minutes if no activity after 30 sec.
Test Mode ....................... 5 sec. at initial power up or DIP switch reset
PIR Adjustment...............................................High or Low (DIP switch)
Ultrasonic Adjustment ......................... Minimum to Maximum (trimpot)
Light Level Adjustment.................................100 Lux --daylight(trimpot)
Operation Temperature................................................... 32° F--131° F
Testing & Code Compliance

UL LISTE D
Installation & wiring
1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect lead wires as WIRING DIAGRAM (see Figure 1): Black lead to
Line(Hot), Red lead to Load wire, White lead to Neutral wire, Green
lead to Ground.
Wiring Diagram:
Neutral
White
Hot
Black
Load
Red
Ground
Green
Load
Neutral(White)
Figure 1
3. Mount device “TOP”up.
4. Gently position wires in wall box, attach sensor switch to the box.
5. Restore power at circuit breaker or fuse, wait one minute.
6. Remove the small cover plate.
7. Locate the adjustment trimpots on the control panel to perform test
and adjustment.
8. Replace the small cover plate after testing and adjustment.
Coverage area
Top View
20'
10'
10'
PIR Coverage: 1200 ft 2
Ultrasonic Coverage: 400 ft 2
20'
5'
4'
20'
40'
Adj ustment
Mounting Yoke
PIR Lens
Ultrasonic Cones
Control Panel Cover
Detection LEDs
ON
2
3
1 2 3 4 5 6 7
OFF
1
4
ULTRASONIC
3
2
Red=PIR
Blue=Ultrasonic
1 LIGHT 4
OFF OCC VAC
ULTRASONIC
OFF OCC VAC
LIGHT
Band switch prescription.
Mode Position
OFF
OCC
VAC
Description
Left
Circuit is permanently opened.
(switched off)
None
Occupancy Mode:
Automatic On, automatic Off
after set time delay.
Center
Right
React to the push-button
Manually toggles
On / Off the load.
Vacancy Mode: Manual On only,
automatic Off after set time delay.
Manually toggles
On/Off the load.
DIP Switch Setting
The MWOS has 7 DIP switches under the cover. They are used to
set sensitivity, time delay, trigger mode, walk through mode feature
settings.
Initial
Trigger Mode Trigger
Option 1
Both
Option 2
Option 3
Option 4
Sensitivity
50%
100%
Maintain
Load Output Re-trigger
Either
Either
PIR
PIR
PIR
US
US
US
Both
Both
Both
Time Delay
5 Sec/Test
30 Seconds
5 Minutes
10 Minutes
15 Minutes
20 Minutes
25 Minutes
30 Minutes
1
Walk Through 7
Disabled
Enabled
=OFF
=ON
4
=Factory Setting
2
5
3
6
General
Specification
In-Wall Occupancy/Vacancy Sensor
Model #: HWOS
Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body
in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects
occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one
relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level.
Features:








Turn lights ON/OFF automatically (Occupancy Mode)
Manual ON / automatically OFF (Vacancy Mode)
Time delay is adjustable from 15 seconds (test mode) to 30 minutes
Neutral wire required
Zero Crossing for long relay life
Adjustable sensitivity settings
Light level is adjustable
Standard decorator wall plate included
Specifications:
Voltage ……………………………………..……………………..…...............................120 Vac, 60 Hz
Incadescent ………………………………………….…………………………...............................500W
Fluorescent …………………………………………..…………….………...............................…500 VA
Motor …………………………………………………………………….…...............................….1/8 HP
Time delay ………………………………………………….…...............................…15 Sec to 30 Mins
Operation temperating …………………………………..………...............................…..32 F to 131 F
*Coverage Area
15'
7.5'
Best: 180 sq.ft.
Regular: 450 sq.ft.
Maximum: 700 sq.ft.
7.5'
15'
5'
4'
15'
30'
Installation & wiring
1. Connect lead wires as wiring diagram (see Figure 2): Black lead to hot
wire, red lead to load wire, white lead to neutral wire, green lead
to ground wire.
Wiring diagram
Neutral
White
Top
Load
Red
Hot
Black
Figure 2
Ground
Green
Load
Neutral
White
2. Device “TOP” upward.
3. Gently position wires in wall box, attach sensor switch to the box.
4. Restore power at circuit breaker or fuse, wait one minute.
5. Locate the toggle switch on both sides of the top cover to perform
test and adjustment.
Changing the color of your switch
Your switch ships with top cover attached. It is convenient for users to
change the top cover. Please proceed as follows:
2.
N
OPE
CLO
S
E
1.
Figure 3
Push down top cover to release
Line up tabs and push up to attach
Testing & Code Compliance

UL LISTE D
 California Title 24
Adj ustment
Mounting Yoke
Fresnel Lens
TOP
TEST
TEST
15 MIN
VAC
VAC
15 MIN
OCC
30 MIN
OCC
30 MIN
LED Indicator
INDOOR
USE ONLY
Control Top Cover
(ON/OFF Button)
Figure 4
Band switch prescription
Mode Position
Function of ON/OFF button
Description
VAC
Vacancy Mode: Manual On only, Manually push
Upper side Automatic Off after set time delay.
On/Off the load.
OCC
Occupancy Mode:
Lower side Automatic On, Automatic Off
after set time delay.
Manually push
On/Off the load.
Time delay setting
Default position
Adjustable
15 Seconds (Test mode)
15 Seconds
15 Minutes
30 Minutes
Ambient light(Default setting)
Notice: If the ambient light level is too high, more than the default setting
the load may not automatic turned ON. If turning ON is desired,
cover the sensor lens with one hand for 2 seconds, the light is
going to turn ON.
Enerlites Inc.
www.enerlites.com
Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com
Date: 03/01/2016
General
Specification
Residential/Commercial
In-Wall Occupancy/Vacancy Sensor
Model #: HWOS-J
Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body
in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects
occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one
relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level.
Features:








Turn lights ON/OFF automatically (Occupancy Mode)
Manual ON / automatically OFF (Vacancy Mode)
Time delay is adjustable from 15 seconds (test mode) to 30 minutes
Secured ground wire required
Zero Crossing for long relay life
Adjustable sensitivity settings
Light level is adjustable
Standard decorator wall plate included
Specifications:
Voltage ……………………………………..……………………..…...............................120 Vac, 60 Hz
Incadescent ………………………………………….…………………………...............................500W
Fluorescent ………………………………………..................500VA @ 120VAC, 1000VA @ 277VAC
Motor …………………………………………………………………….…...............................….1/8 HP
Time delay ………………………………………………….…...............................…15 Sec to 30 Mins
Operation temperating …………………………………..………...............................…..32 F to 131 F
*Coverage Area
15'
7.5'
Best: 180 sq.ft.
Regular: 450 sq.ft.
Maximum: 700 sq.ft.
7.5'
15'
5'
4'
15'
30'
Installation & wiring
1. Connect lead wires as wiring diagram (see Figure 2): Black lead to hot
wire, red lead to load wire, white lead to neutral wire, green lead
to ground wire.
Wiring diagram
Neutral
White
Top
Load
Red
Hot
Black
Figure 2
Ground
Green
Load
Neutral
White
2. Device “TOP” upward.
3. Gently position wires in wall box, attach sensor switch to the box.
4. Restore power at circuit breaker or fuse, wait one minute.
5. Locate the toggle switch on both sides of the top cover to perform
test and adjustment.
Changing the color of your switch
Your switch ships with top cover attached. It is convenient for users to
change the top cover. Please proceed as follows:
2.
N
OPE
CLO
S
E
1.
Figure 3
Push down top cover to release
Line up tabs and push up to attach
Testing & Code Compliance

UL LISTE D
 California Title 24
Adj ustment
Mounting Yoke
Fresnel Lens
TOP
TEST
TEST
15 MIN
VAC
VAC
15 MIN
OCC
30 MIN
OCC
30 MIN
LED Indicator
INDOOR
USE ONLY
Control Top Cover
(ON/OFF Button)
Figure 4
Band switch prescription
Mode Position
Function of ON/OFF button
Description
VAC
Vacancy Mode: Manual On only, Manually push
Upper side Automatic Off after set time delay.
On/Off the load.
OCC
Occupancy Mode:
Lower side Automatic On, Automatic Off
after set time delay.
Manually push
On/Off the load.
Time delay setting
Default position
Adjustable
15 Seconds (Test mode)
15 Seconds
15 Minutes
30 Minutes
Ambient light(Default setting)
Notice: If the ambient light level is too high, more than the default setting
the load may not automatic turned ON. If turning ON is desired,
cover the sensor lens with one hand for 2 seconds, the light is
going to turn ON.