General Specification 3RZHU3DFN Model #: 033 Description: The MPP-24 power pack is the foundation for any low voltage lighting control system. The MPP-24 supplies low voltage power to occupancy sensors and other control devices, switching line voltage in response to signals from control devices. The MPP-24 power pack is attached to existing junction boxes or mounted into fixture wiring trays. Low voltage wiring should use at least 22-gauge wire. High voltage connections should use at least 14-gauge. Always check local building codes. After initial wiring is completed, check wiring diagrams to verify the power pack is wired correctly. Improper wiring can cause damage to the power pack, lighting system, occupancy sensor and other control devices. Features: • • • • Self-contained power supply relay system LED indicator of relay operation for easy verification Convert line voltage to low voltage in various lighting control systems Able to link up to six sensors at a time Specifications: Voltage ................................................................................................................................................... 120/277VA, 50/60Hz Load Requirements: Ballast ...................................................................................................................................................... 20A @ 120/277VAC Incandescent ................................................................................................................................................... 20A @120VAC Motor ....................................................................................................................................................... 1HP @120/240VAC Output ..................................................................................................................... 150mA @ 24VDC (with relay connected) Operating Temperature .................................................................................................................... 32° to 131°F (0°to 55°C) Low Voltage Input: Control ON .............................................................................................................................................................. 12-24VDC Hold ON................................................................................................................................................................... 12-24VDC Hold OFF ................................................................................................................................................................. 12-24VDC Manual ON (momentary switch required) ............................................................................................................... 12-24VDC Relative Humidity ............................................................................................................................ 20-90%, non-condensing Material ............................................................................................................................................................................. ABS Warranty ....................................................................................................................................................................... 2 years Testing and Code Compliance: • UL Listed device Wiring Diagram: Wire Color Code: Black ............................................................................................................................................... Line White .......................................................................................................................................... Neutral Red ................................................................................................................................................ Load Blue ............................................................................................................................................ Control Orange ..................................................................................................................................... Hold ON Gray .....................................................................................................................................Manual ON Brown ..................................................................................................................................... Hold OFF Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification 360° Dual-Technology PIR/Ultrasonic Low Voltage Occupancy Sensor Model #: MDC-50L Description: The MDC-50L 360° Dual-Technology Occupancy Sensor combines advanced passive infrared (PIR) and ultrasonic technology into one unit. The combined technologies help to avoid false triggering. Selectable operation modes allow the sensor to turn back on and hold it on as long as either or both technologies detect occupancy. After no movement is detected for the selected time delay, the lights switch off. * The MDC-50L operated on 24V supplied by MMP-24 power pack Specifications Voltage.......................................................................................24VDC Current Consumption...................................................................20mA Power Supply.......................................................MPP-24 Power Pack Operating Temperature ......................................32°to 131°F (0°to 55°C) Adjustment Time Delay.............................................. 5 Sec. to 30 Min. Test Mode.......delaytime is 5 sec. lasts 30 Min. at each time by setting PIR Adjustment.........................................50% or 100% (DIP switch 1) Ultrasonic Adjustment ..................... Minimum to Maximum (trimpot 1) Light Level Adjustment..............................100 Lux --daylight(trimpot 2) PIR Coverage..............................................................................1600ft 22 Ultrasonic Coverage....................................................................1000ft Coverage area The MDC-50L provides a 360° coverage pattern. The coverage shown represents walking motion at mounting height of 9 feet. For building spaces with lower levels of activity or with obstacles and barriers ,coverage size may decrease. 44 ft (13.4m) PIR Coverage Figure 1 Ultrasonic Coverage 30 ft x 30 ft (9.14m x 9.14m) Ultrasonic Sensitivity Adjustment Trimpot 1 Adjustable: Minimum to Maximum (clockwise) Ultrasonic Note: Turn toward right for greater room space. Turn toward left to avoid false alert in smaller room and near the door way or heat source. Ambient Light Level Adjustment Trimpot 2 Adjustable: 100Lux to daylight ( clockwise) Installation & wiring Light CAUTION! TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS OR SENSORS. Each MPP-24 power pack can supply power for 6 MDC-50L sensors. When using more sensors than this, multiple power packs are required. White Black MPP-24 Blue 120VAC 277VAC Red Hot Red Lighting Load Black Neutral Low Voltage Wires Blue (control output) Black (common) Red (+24VDC input) Standard Wiring: RED —+24VDC Input BLACK — Common BLUE — Control Output Figure 2 Using an Octagonal Junction Box 1. Pull the low voltage wires from power pack into the Octagonal Junction Box through the conduit knockout. 2. Connect the low voltage wires to the appropriate wires on the sensor. 3. Loosen the appliance mounting screws attached to the Octagonal Junction Box. 4. Align the sensor in the Octagonal Junction Box so that the mounting screws on the box match the holes on the sensor's rear housing. 5. Push the sensor up into the Octagonal Junction Box and twist it so that the mounting screws are seated in the hole slots. 6. Tighten the two screws to secure the sensor to the Octagonal Junction Box. 7. Snap the front cover onto the sensor 4"Octagonal box 2-1/2" deep mounting Drop Ceiling Screws Wire Rear Housing Figure 3 Front Cover Sensor Adj ustment PIR Ultrasonic sensitivity trimpot PIR activity LED(Red) DIP Switch Ultrasonic activity LED(Green) Ultrasonic transducer cones Light level trimpot Figure 4 There is a 40-second warm-up period when power is first applied. The sensors are factory preset to allow for quick installation in most applications.To make adjustments, open the Front Cover .Set the DIP Switch to the desired settings. See"DIP Switch Setting" below. DIP Switch Setting The MDC-50L has 8 DIP switches under the cover. They are used to set PIR sensitivity, time delay, override and tigger mode feature settings. Initial Trigger Mode Trigger Option 1 Both Maintain Load Output Either Either Option 3 PIR Either Option 4 PIR Ultrasonic Ultrasonic Option 6 Both Both PIR Sensitivity 1 50% 100% Time Delay 5 Sec/Autoset 30 Seconds 5 Minutes 10 Minutes 15 Minutes 20 Minutes 25 Minutes 30 Minutes 8 =ON 4 PIR Option 5 =OFF 3 Either Option 2 Override Disabled Enabled 2 5 6 7 =Factory Setting PIR Sensitivity setting: Switch 1 50%, sensor's coverage is smaller, just about half of the widest range. 100%,the maximum range of sensor's PIR coverage is 1600 square feet. Trigger Mode: Switches 2, 3,4 The sensor has 6 trigger options, set with DIP switches 2 , 3 and 4. In the trigger mode DIP switch setting table: Both requires motion detection by the PIR and the Ultrasonic. Either requires motion detection by only one technology. PIR requires motion detection by the PIR. Ultrasonic requires motion detection by the Ultrasonic. Time Delay: Switches 5, 6, 7 The sensor will hold the lights on as long as occupancy is detected. The time delay countdown starts when no motion is detected. After no motion is detected for the length of the time delay, the sensor will turn the lights off. Override: Switch 8 To override all sensor functions, set to ON position ( DIP Swicth 8 ). Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification 360° Passive Infrared Low Voltage Occupancy Sensor Model #: MPC-50L Description: The MPC-50L 360° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and ambient light level. The light level feature keeps lights from turning on if ambient light level is sufficient. The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is detected for a specified or auto-set time (5 seconds to 30 minutes) the lights switch off. A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds of an occupancy detection. * The MPC-50L operated on 24V supplied by MMP-24 power pack Features Passive Infrared Technology(PIR) 360 ° field of view, 1200 sq.ft. Time Delay is adjustable from 5 seconds to 30 minutes Simple, fast installation Adjustable sensitivity settings Light level is adjustable. Specifications Voltage ................................................................................................................... 24VDC Current Consumption ................................................................................................. 9mA Power Supply................................................................................... MPP-24 Power Packs Operating Temperature .............................................................32 ° to 131°F (0 ° to 55°C) Adjustable Light Level....................................................................................10FC-150FC Adjustable Time Delay............................................................... 5 sec.-30min (DIP switch) Walk-Through Mode ...................................................3 minutes if no activity after 30 sec. Test Mode .................................................. 5 sec. upon initial power-up or DIP switch reset PIR Coverage: Sensitivity Adjustment ........................................................ Automatic or Low (DIP switch) Coverage ...................................................................................................... Up to 1200 ft 2 Testing & Code Compliance UL LISTE D Installation & wiring CAUTION! TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS OR SENSORS. +24VDC Wiring terminals Control Out Common Control Out +24VDC Manual ON Common Model#: Manual ON Each MPP-24 power pack can supply power for 6 MPC-50L sensors. When using more sensors than this, multiple power packs are required. MPC-50L Passive Infrared Occupancy Sensor +24VDC Connect to MPP-24 or other Class 2 Power Packs For Indoor Use Only Figure 1 Connect the low voltage: RED wire (+24VDC) from power pack to the +24V terminal on the sensor. BLACK wire (Common) from power pack to Common terminal on the sensor. Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY - Connect: BLUE wire from power pack to Control Out terminal on sensor. Wiring multiple SINGLE LIGHTING LOADs CONTROLLED BY OCCUPANCY, DEPENDENT ON LIGHT LEVEL (AMBIENT LIGHT) - Connect: BLUE wire from power pack to Control Out terminal on sensors. To add a MANUAL SWITCH such as the YQDS115M Momentary Toggle Switch, to the above applications - connect: 1. Wire from one side of switch to Common terminal on sensor. 2. Wire from other side of switch to Man Switch terminal on sensor. Using an Octagonal J-Box 1. Pull the low voltage wires from the power pack into the J-Box through the conduit knockout. 2. Connect the low voltage wires to the appropriate terminals on the sensor. 3. Loosen the appliance mounting screws attached to the J-Box. 4. Align the sensor in the J-Box so that the mounting screws on the box match the key holes on the sensor’s rear housing. 5. Push the sensor up into the J-Box and twist it so that the mounting screws are seated in the keyhole slots. 6. Tighten the two screws to secure the sensor to the J-Box. 7. Snap the front cover onto the sensor. Octagonal box mounting Drop Ceiling Screws Wire Rear Housing Figure 2 Front Cover J-Box Mount Coverage area The MPC-50L provides a 360 °coverage pattern, up to 1200 square feet. The coverage shown represents walking motion at a mounting height of 8 feet. For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. Drawings not to scale. 8 ft 44 ft 13.4m Typical desk-top level Figure 3 22 ft 13 ft 7 ft 3 ft 0 3 ft 7 ft 13 ft 22 ft Adj ustment Keyhole slots(for mounting to 4" octagonal box) Double gang mudring mounting holes PIR lens PIR Activity LED(Red) Load LED(Green) Light level Adjustment Buzzer Figure 4 DIP switches Keyhole slots (for mounting to 4" octagonal box) The sensors are factory preset to allow for quick installation in most applications. Verification of proper wiring or coverage, or customizing the sensor's settings can be done using the following procedures. To make adjustments, open the Front Cover with a small screwdriver. There is a 40-second warm-up period when power is first applied. Before making adjustments, make sure the office furniture is installed, lighting circuits are turned on, and the HVAC systems are in the overridden/on position. VAV systems should be set to their highest airflow. Set the DIP switches to the desired settings. See “DIP Switch Setting”. DIP Switch Setting The MPC-50L has 9 DIP switches under the cover. They are used to set sensitivity, time delay, walk through mode, vacancy mode, audible, visual alarm and Hold ON feature settings. Sensitivity 50% 100% 1 Walk Through 5 Disabled Enabled Vacancy Disabled Enabled 6 Time Delay 5 Sec/Autoset 30 Seconds 5 Minutes 10 Minutes 15 Minutes 20 Minutes 25 Minutes 30 Minutes =OFF =ON 2 3 4 =Factory Setting Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Audible Alert Disabled Enabled 7 Visible Alert Disabled Enabled 8 Hold ON Disabled Enabled 9 Date: 03/01/2016 General Specification 360° Passive Infrared Line Voltage Occupancy Sensor Model #: MPC-50V Description: The MPC-50V 360 °passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and ambient light levels. The light level feature keeps lights from turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is detected for a specified time the lights are switched off. Features Passive Infrared Technology(PIR) 360 ° field of view, 1200 sq.ft. Time Delay is adjustable from 5 seconds to 30 minutes Simple, fast installation Adjustable sensitivity settings Light level is adjustable. Specifications Voltage ................................................................................................................... 24VDC Current Consumption ................................................................................................. 9mA Power Supply................................................................................... MPP-24 Power Packs Operating Temperature .............................................................32 ° to 131°F (0 ° to 55°C) Adjustable Light Level....................................................................................10FC-150FC Adjustable Time Delay............................................................... 5 sec.-30min (DIP switch) Walk-Through Mode ...................................................3 minutes if no activity after 30 sec. Test Mode .................................................. 5 sec. upon initial power-up or DIP switch reset PIR Coverage: Sensitivity Adjustment ........................................................ Automatic or Low (DIP switch) Coverage ...................................................................................................... Up to 1200 ft 2 Testing & Code Compliance UL LISTE D Installation & wiring CAUTION! TURN POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS OR SENSORS. +24VDC Wiring terminals Control Out Common Control Out +24VDC Manual ON Common Model#: Manual ON Each MPP-24 power pack can supply power for 6 MPC-50L sensors. When using more sensors than this, multiple power packs are required. MPC-50L Passive Infrared Occupancy Sensor +24VDC Connect to MPP-24 or other Class 2 Power Packs For Indoor Use Only Figure 1 Connect the low voltage: RED wire (+24VDC) from power pack to the +24V terminal on the sensor. BLACK wire (Common) from power pack to Common terminal on the sensor. Wiring a SINGLE LIGHTING LOAD CONTROLLED BY OCCUPANCY - Connect: BLUE wire from power pack to Control Out terminal on sensor. Wiring multiple SINGLE LIGHTING LOADs CONTROLLED BY OCCUPANCY, DEPENDENT ON LIGHT LEVEL (AMBIENT LIGHT) - Connect: BLUE wire from power pack to Control Out terminal on sensors. To add a MANUAL SWITCH such as the YQDS115M Momentary Toggle Switch, to the above applications - connect: 1. Wire from one side of switch to Common terminal on sensor. 2. Wire from other side of switch to Man Switch terminal on sensor. Using an Octagonal J-Box 1. Pull the low voltage wires from the power pack into the J-Box through the conduit knockout. 2. Connect the low voltage wires to the appropriate terminals on the sensor. 3. Loosen the appliance mounting screws attached to the J-Box. 4. Align the sensor in the J-Box so that the mounting screws on the box match the key holes on the sensor’s rear housing. 5. Push the sensor up into the J-Box and twist it so that the mounting screws are seated in the keyhole slots. 6. Tighten the two screws to secure the sensor to the J-Box. 7. Snap the front cover onto the sensor. Octagonal box mounting Drop Ceiling Screws Wire Rear Housing Figure 2 Front Cover J-Box Mount Coverage area The MPC-50L provides a 360 °coverage pattern, up to 1200 square feet. The coverage shown represents walking motion at a mounting height of 8 feet. For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. Drawings not to scale. 8 ft 44 ft 13.4m Typical desk-top level Figure 3 22 ft 13 ft 7 ft 3 ft 0 3 ft 7 ft 13 ft 22 ft Adj ustment Keyhole slots(for mounting to 4" octagonal box) Double gang mudring mounting holes PIR lens PIR Activity LED(Red) Load LED(Green) Light level Adjustment Buzzer Figure 4 DIP switches Keyhole slots (for mounting to 4" octagonal box) The sensors are factory preset to allow for quick installation in most applications. Verification of proper wiring or coverage, or customizing the sensor's settings can be done using the following procedures. To make adjustments, open the Front Cover with a small screwdriver. There is a 40-second warm-up period when power is first applied. Before making adjustments, make sure the office furniture is installed, lighting circuits are turned on, and the HVAC systems are in the overridden/on position. VAV systems should be set to their highest airflow. Set the DIP switches to the desired settings. See “DIP Switch Setting”. DIP Switch Setting The MPC-50L has 9 DIP switches under the cover. They are used to set sensitivity, time delay, walk through mode, vacancy mode, audible, visual alarm and Hold ON feature settings. Sensitivity 50% 100% 1 Walk Through 5 Disabled Enabled Vacancy Disabled Enabled 6 Time Delay 5 Sec/Autoset 30 Seconds 5 Minutes 10 Minutes 15 Minutes 20 Minutes 25 Minutes 30 Minutes =OFF =ON 2 3 4 =Factory Setting Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Audible Alert Disabled Enabled 7 Visible Alert Disabled Enabled 8 Hold ON Disabled Enabled 9 Date: 03/01/2016 General Specification High Bay 360° Passive Infrared Line Voltage Occupancy Sensor Model #: MPC-50H Description: The MPC-50H occupancy sensor is designed for automatic lighting control in high bay applications, such as warehouses, distribution centers, gymnasiums, and areas with direct access to the lighting fixtures, specifically for indoor locations. This product contains a passive infrared sensor (PIR). Features: • • • • • • LED indicator of occupancy detection for easy verification of coverage Easy front access to time delay, sensitivity range and ambient light level adjustment Easy mounting using ½” knockout at end of luminaire fixture Hardware choices for side and back mount Compatible with all program start ballasts Zero crossing circuitry reduces stress on relay and extends sensor life Specifications: Voltage .................................................................................................................................................... 120/277VA,50/60Hz Load Requirements: @ 120VAC .......................................................................................................................................800W ballast or tungsten @ 277VAC ........................................................................................................................................................ 1200W ballast @ 120VAC ....................................................................................................................................................................1/4 hp Adjustable Light Level ...................................................................................................................................... 10FC—150FC Sensitivity Adjustable ..................................................................................................................... 50% or 100%(DIP switch) Operating Temperature ..................................................................................................................... 32°to 131°F (0°to 55°C) Relative Humidity ............................................................................................................................ 20-90%, non-condensing Controls ............................................................................................................................ Light Level Knob and Dip Switches Material ............................................................................................................................................................................. ABS Warranty ....................................................................................................................................................................... 2 years Testing and Code Compliance: • • UL/CUL Listed device California Title 24 Dimensions: Coverage: Lens Specifications: MPC-50H-L1: Mounting height ..................................................................................................................................................................50ft Field of view ..................................................................................................................................................................... 360° Coverage .................................................................................................................................................................. 2800 sq.ft MPC-50H-L2: Mounting height ....................................................................................................................................................................8ft Field of view ..................................................................................................................................................................... 360° Coverage .................................................................................................................................................................. 1200 sq.ft Dip Switch Setting: Wiring Diagram: Components: The MPC-50H has 4 DIP switches under the cover. They are used to set sensitivity and time delay feature settings. First switch: Changes the sensitivity of the sensor, increasing or decreasing the range and height of detection. Second, Third, and Forth: Through a combination of these switches outlined in the table above, the times at which the loads will turn off can be changed. Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification 360° Passive Infrared Line Voltage Occupancy Sensor Model #: MPC-52V Description: The MPC-52V 360° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and ambient light levels. The light level feature keeps lights from turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is detected for a specified time the lights are switched off. Features: 360 ° field of view, 800 sq.ft. Passive Infrared Technology(PIR) Time Delay is adjustable from 15 seconds (test mode) to 30 minutes Simple, fast installation Adjustable sensitivity settings Light level is adjustable. Specifications Incandescent....................................................................800W-120VAC, 60HZ Fluorescent ...................................800VA-120VAC / 1200VA-277VAC, 60HZ Motor..............................................................................1/4 HP ,120VAC, 60HZ Operating Temperature ...................................................32°to 131°F (0°to 55°C) Adjustable Light Level ................................................................10FC—150FC Adjustable Time Delay ................................................................15 sec.-30min. Sensitivity Adjustment.........................................50% or 100% (DIP switch 1) Coverage……….........…..…………...................…………………….Up to 800 ft 2 Lead Power Cable………....………….........................…….…………….....4 feet Testing and Code Compliance: • UL Pending Installation & wiring Refer to the wire diagram of the sensor (see figure 1), and connect the wires of ceiling sensors as followed by using the wire nuts provided. 1.. Connect the Hot wire to the Black wire from the senso 2.. Connect the Load wire to the Red wire from the senso 3.. Connect the Neutral wire to the White wire from the senso 4.. This sensor can install together with a snap switch in series, in this case, conne the sensor hot (black) wire to the load wire of the snap switch ,it can be a single pole switch, 3-way switches or 4-way switches. Neutral White Red Black Hot Load MPC-52V Figure 1 Coverage area The MPC-52V provides a 360° coverage pattern, up to 800 square feet. Figure 2 ).For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. 8 ft Typical desk-top level 34 ft 10.36 m 17 ft 15 ft 7 ft 5 ft 3 ft 0 3 ft 5 ft 7 ft 15 ft 17 ft Figure 2 Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 4" Square J-Box with Round Ring Auxiliary Mounting Adapter 4" Square J-Box with Single Gang Auxiliary Mounting Adapter 4"Octagonal J-Box 4" Square J-Box with Double Gang for the below junction boxes. 4" Square J-Box with Round Ring Auxiliary Mounting Adapter 4" Square J-Box with Single Gang The Auxiliary Mounting Adapter allows you to mount ceiling sensors Product Description Model Number :MPC-A Auxiliary Mounting Adapter for Ceiling sensor Auxiliary Mounting Adapter 4"Octagonal J-Box 4" Square J-Box with Double Gang for the below junction boxes. The Auxiliary Mounting Adapter allows you to mount ceiling sensors Product Description Model Number :MPC-A Auxiliary Mounting Adapter for Ceiling sensor General Specification 150° Passive Infrared Line Voltage Occupancy Sensor Model #: MPW-V Description: The MPW-V 150° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and ambient light levels. The light level feature keeps lights from turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is detected for a specified time the lights are switched off. Features Passive Infrared Technology(PIR) 150° field of view, 1000 sq.ft. Time Delay is adjustable from 5 seconds to 30 minutes Simple, fast installation Adjustable sensitivity settings Light level is adjustable. Specifications Voltage ............................................................................................................120-277VAC, 60Hz Max load.................................................................................................................................10A 2 PIR Coverage.......................................................................................................…...….1000 ft Operation Temperature..........................................................................32° to 131°F (0° to 55° C) Range..................................................................................................................25% to 100% Adjustable Time Delay.......................................................................................30 sec to 30 min. Testing & Code Compliance UL LISTE D COVERAGE PATTERN The MPW-V privides an eliptical coverage pattern (see Figure 1). The coverage shown repersents walking motion at a mounting height of 10 feet. The maximun coverage will be up to 1000 ft 2 with a largest distance of 15 meters. For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. INSTALLATION 1.. Make sure that the power has been turned OFF at the circuit breake 2.. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead Line(Hot), Red lead to Load wire, White lead to Neutral wire. Wiring Diagram: Neutral White Hot Black Load Red Neutral White Figure 1 - 01- ADJUSTMENT PIR Lens Mounting Yoke Figure 2 3. Mount device up to walls or ceiling 4. Gently position wires in wall/octagon bo a. attach sensor switch to the box, and fix it to the wall/ceiling with two screws. or b. attach sensor switch to the mounting yoke with wires through its certral hole, and fix the yoke to the wall/ceiling. 5. Restore power at circuit breaker or fuse, wa one minute. 6. Remove the small cover plate. (illustrated as Figure 3. 7. Locate the adjustment knob on the control panel to perform te and adjustment.(illustrated as Figure 3 and 4. ) 8. Replace the small cover plate after testing and adjustmen Control Panel Cover Detection LEDs Red=PIR Figure 3 TIME RANGE LIGHT Figure 4 TIME Adjustment Trimpot Default position: Time (Test at position 1) Adjustable: 5 sec. to 30 mins (clockwise) PIR Adjustment Knob Default position: Center Note: Turn toward right for greater room space. Turn toward left to avoid false alert in smaller room and near the door way or heat source. Ambient Light Level Adjustment Trimpot Default position: Daylight (100% at position 4) Adjustable: Clock wise OPERATION The Sensor Switch is programmed for Occupancy Mode only. Automatic Turning On/Off the Load Once the power is on, the load will be turned On according to the occupancy settings. The sensor time delay operates as programmed. When the load turns OFF due to the lack of motion detection, the load can be turned ON again by occupancy detection or switch activation. The Sensor keeps the Load On until no motion is detected plus the set time delay, load(s) will be turned Off automatically. TROUBLESHOOTING` TROUBLESHOOTING WARNING: Turn off the power at the circuit breaker before installation. Lights do not turn on with occupancy, and the following condition exists: PIR Activity LED does not flash: NOTE: When power is initially applied to the sensor, there is a warm-up period of up to 1 minute before the LED is active. 1. Check that the circuit breaker or any wall switch connected to the sensor has been turned back on. 2. Make sure that the PIR Sensitivity is set for Max. 3. Make sure the wire is connected right. PIR Activity LED flashes: 1. If the sensor’s Light Level has been turned to minimum (at position 1), the lights connected to the Light Level Output might be held off because of the level of ambient light in the controlled area. To test whether the Light Level adjustment is the problem, cover the PIR lens and PIR Activity LED with your hand to see if the lights turn on. If the lights turn on, the Light Level setting was keeping the lights off (see, “Sensor Adjustment” for readjustment). 2. Make sure the wire is connected right. Lights do not turn off automatically: 1. The sensor may be experiencing activations from outside the controlled or from some type of interference (see “Unwanted Sensor Activations” below). 2. Make sure the wire is connected right. Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/02/2016 General Specification 150° Passive Infrared Line Voltage Occupancy Sensor Model #: MPW-J Description: The MPW-J 150° passive infrared (PIR) occupancy sensors turn lighting systems on and off based on occupancy and ambient light levels. The light level feature keeps lights from turning on if the ambient light level is sufficient. The sensors can be configured to turn lighting on, and hold it on as long as the sensor detects occupancy. After no movement is detected for a specified time the lights are switched off. Features Passive Infrared Technology(PIR) 150° field of view, 1000 sq.ft. Time Delay is adjustable from 5 seconds to 30 minutes Simple, fast installation Adjustable sensitivity settings Light level is adjustable Secured ground wire required Specifications Voltage ............................................................................................................120-277VAC, 60Hz Max load.................................................................................................................................10A 2 PIR Coverage.......................................................................................................…...….1000 ft Operation Temperature..........................................................................32° to 131°F (0° to 55° C) Range..................................................................................................................25% to 100% Adjustable Time Delay.......................................................................................30 sec to 30 min. Testing & Code Compliance UL LISTE D COVERAGE PATTERN The MPW-J privides an elliptical coverage pattern (see Figure 1). The coverage shown represents walking motion at a mounting height of 10 feet. The maximum coverage will be up to 1000 ft 2 with a largest distance of 15 meters. For building spaces with lower levels of activity or with obstacles and barriers, coverage size may decrease. INSTALLATION 1.. Make sure that the power has been turned OFF at the circuit breake 2.. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead Line(Hot), Red lead to Load wire, White lead to Neutral wire. Wiring Diagram: Neutral White Hot Black Load Red Neutral White Figure 1 - 01- ADJUSTMENT PIR Lens Mounting Yoke Figure 2 3. Mount device up to walls or ceiling 4. Gently position wires in wall/octagon bo a. attach sensor switch to the box, and fix it to the wall/ceiling with two screws. or b. attach sensor switch to the mounting yoke with wires through its certral hole, and fix the yoke to the wall/ceiling. 5. Restore power at circuit breaker or fuse, wa one minute. 6. Remove the small cover plate. (illustrated as Figure 3. 7. Locate the adjustment knob on the control panel to perform te and adjustment.(illustrated as Figure 3 and 4. ) 8. Replace the small cover plate after testing and adjustmen Control Panel Cover Detection LEDs Red=PIR Figure 3 TIME RANGE LIGHT Figure 4 TIME Adjustment Trimpot Default position: Time (Test at position 1) Adjustable: 5 sec. to 30 mins (clockwise) PIR Adjustment Knob Default position: Center Note: Turn toward right for greater room space. Turn toward left to avoid false alert in smaller room and near the door way or heat source. Ambient Light Level Adjustment Trimpot Default position: Daylight (100% at position 4) Adjustable: Clock wise OPERATION The Sensor Switch is programmed for Occupancy Mode only. Automatic Turning On/Off the Load Once the power is on, the load will be turned On according to the occupancy settings. The sensor time delay operates as programmed. When the load turns OFF due to the lack of motion detection, the load can be turned ON again by occupancy detection or switch activation. The Sensor keeps the Load On until no motion is detected plus the set time delay, load(s) will be turned Off automatically. TROUBLESHOOTING` TROUBLESHOOTING WARNING: Turn off the power at the circuit breaker before installation. Lights do not turn on with occupancy, and the following condition exists: PIR Activity LED does not flash: NOTE: When power is initially applied to the sensor, there is a warm-up period of up to 1 minute before the LED is active. 1. Check that the circuit breaker or any wall switch connected to the sensor has been turned back on. 2. Make sure that the PIR Sensitivity is set for Max. 3. Make sure the wire is connected right. PIR Activity LED flashes: 1. If the sensor’s Light Level has been turned to minimum (at position 1), the lights connected to the Light Level Output might be held off because of the level of ambient light in the controlled area. To test whether the Light Level adjustment is the problem, cover the PIR lens and PIR Activity LED with your hand to see if the lights turn on. If the lights turn on, the Light Level setting was keeping the lights off (see, “Sensor Adjustment” for readjustment). 2. Make sure the wire is connected right. Lights do not turn off automatically: 1. The sensor may be experiencing activations from outside the controlled or from some type of interference (see “Unwanted Sensor Activations” below). 2. Make sure the wire is connected right. Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/02/2016 General Specification 150° Dual-Technology PIR/Ultrasonic Line Voltage Occupancy Sensor Model #: MDW-V Description: This Dual Technology Occupancy Sensor combines advanced passive infrared (PIR) and ultrasonic technologies into one unit. The combined technologies help to avoid false triggering even in difficult applications. The MDW-L turns lighting on and off based on occupancy and ambient light levels. The sensor offers numerous operating modes that can be combined to create the ideal custom control. Selectable operating mode allow the sensor to turn a load on, and hold it on as long as either or both technologies detect occupancy. After no movement is detected for the selected time delay, the lights switch off. A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an occupancy detection. This sensor contains a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even if the area is occupied. * The MDC-50L operated on 24V supplied by MMP-24 power pack Specifications Voltage...........................................................120/277 VAC @50/60Hz Maximum load..................................................................................8A Operating Temperature ......................................32°to 131°F (0°to 55°C) Adjustment Time Delay.............................................. 5 Sec. to 30 Min. Test Mode.......delaytime is 5 sec. lasts 30 Min. at each time by setting PIR Adjustment.........................................50% or 100% (DIP switch 1) Ultrasonic Adjustment ..................... Minimum to Maximum (trimpot 1) Light Level Adjustment..............................100 Lux --daylight(trimpot 2) PIR Coverage..............................................................................1000ft 22 Ultrasonic Coverage......................................................................800ft Coverage area The MDW-V provides a 150° coverage pattern. The coverage shown represents walking motion at mounting height of 10 feet. For building spaces with lower levels of activity or with obstacles and barriers ,coverage size may decrease. PIR coverage 50ft Ultrasonic coverage 30ft Figure 1 1. Make sure that the power has been turned OFF at the circuit breaker. 2. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to Line(Hot), Red lead to Load wire, White lead to Neutral wire. Wiring Diagram: Neutral White Load Red Hot Black Neutral White Figure 2 3. Mount device up to walls or ceilings. 4. Gently position wires in wall/octagon box, a. attach sensor switch to the box, and fix it to the wall/ceiling . with two screws. or b. attach sensor switch to the mounting yoke with wires through its certral hole, and fix the yoke to the wall/ceiling. 5. Restore power at circuit breaker or fuse, wait one minute. 6. Remove the small cover plate. (illustrated as Figure 3. ) 7. Locate the adjustment knob on the control panel to perform test and adjustment.(illustrated as Figure 3 and 4. ) 8. Replace the small cover plate after testing and adjustment. ADJUSTMENT Mounting Yoke PIR Lens Ultrasonic Cones Figure 3 Control Panel Cover Detection LEDs Red=PIR Blue=Ultrasonic Figure 4 Ultrasonic PIR Light Ultrasonic & PIR Sensitivity Adjustment Knob Default position: Center Adjustable: 25% (Position 1) to 100% (Position 4) Note: Turn toward right for greater room space. Turn toward left to avoid false alert in smaller room and near the door way or heat source. Ambient Light Level Adjustment Trimpot Default position: Daylight (100% at position 4) Adjustable: Clock wise Trigger mode: Switches 1, 2, 3 The sensor has 6 trigger options, set with DIP switches1, 2 and 3. In the trigger mode DIP switch setting table: DIP SWITCH SETTING The MDW-L has 7 DIP switches under the cover. They are used to set trigger mode, time delay and walk through mode feature settings. Initial Maintain Re-trigger Occupancy Occupancy (seconds Occupancy Logic Trigger 1 2 3 duration) Default Both Option 1 Either Either Either Option 2 PIR Either Either Option 3 Both Both Both Option 4 PIR PIR PIR Option 5 Ultra Ultra Ultra Time Delay 5 Sec Test 30 Sec 3 Min 5 Min 10 Min 15 Min 20 Min 30 Min 4 5 Either 6 Either Walk-Through 7 Disabled Enabled =OFF =ON =Factory Setting Both requires motion detection by the PIR and the Ultrasonic. Either requires motion detection by only one technology. PIR requires motion detection by the PIR. Ultra requires motion detection by the Ultrasonic. Initial Occupancy: The method that activates a change from “Standby” (area unoccupied and loads are off) to“Occupied” (area occupied and loads are on). Maintain Occupancy:The method indicating that the area is still occupied and the lights should remain on. Re-trigger: After the time delay elapses and the lights turn off, detection by the selected technology within the number of seconds indicated turns the lights back on. To turn off a technology: Option 4 turns off the Ultrasonic detection Option 5 turns off the PIR detection Time Delay: Switches 4, 5, 6 The sensor will hold the lights on as long as occupancy is detected. The time delay countdown starts when no motion is detected. After no motion is detected for the length of the time delay, the sensor will turn the lights off. Walk-through mode: Switch 7 Turns the lights off three minutes after the area is initially occupied, if no motion is detected after the first 30 seconds. If motion continues beyond the first 30 seconds, the selected time delay applies. There is a 40-second warm-up period when power is first applied. The sensors are factory preset to allow for quick installation in most applications.To make adjustments, open the Front Cover .Set the DIP Switch to the desired settings. See"DIP Switch Setting" below. Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification 150° Dual-Technology PIR/Ultrasonic Low Voltage Occupancy Sensor Model #: MDW-L Description: This Dual Technology Occupancy Sensor combines advanced passive infrared (PIR) and ultrasonic technologies into one unit. The combined technologies help to avoid false triggering even in difficult applications. The MDW-L turns lighting on and off based on occupancy and ambient light levels. The sensor offers numerous operating modes that can be combined to create the ideal custom control. Selectable operating mode allow the sensor to turn a load on, and hold it on as long as either or both technologies detect occupancy. After no movement is detected for the selected time delay, the lights switch off. A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an occupancy detection. This sensor contains a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even if the area is occupied. * The MDC-50L operated on 24V supplied by MMP-24 power pack Specifications Voltage.........................................................................18-28VDC/VAC Current Consumption...................................................................40mA Power Supply.......................................................MPP-24 Power Pack Operating Temperature ......................................32°to 131°F (0°to 55°C) Adjustment Time Delay.............................................. 5 Sec. to 30 Min. Test Mode.......delaytime is 5 sec. lasts 30 Min. at each time by setting PIR Adjustment.........................................50% or 100% (DIP switch 1) Ultrasonic Adjustment ..................... Minimum to Maximum (trimpot 1) Light Level Adjustment..............................100 Lux --daylight(trimpot 2) PIR Coverage..............................................................................1000ft 22 Ultrasonic Coverage......................................................................800ft Coverage area The MDW-L provides a 150° coverage pattern. The coverage shown represents walking motion at mounting height of 10 feet. For building spaces with lower levels of activity or with obstacles and barriers ,coverage size may decrease. PIR coverage 50ft Ultrasonic coverage 30ft Figure 1 1. Make sure that the power has been turned OFF at the circuit breaker. 2. Connect lead wires as WIRING DIAGRAM (see Figure 2): Black lead to Common, Red lead to +24V, Blue lead to Control Out. Red +24V Common Black 3. Mount device up to walls or ceilings. 4. Gently position wires in wall/octagon box, a. attach sensor switch to the box, and fix it to the wall/ceiling . with two screws. or b. attach sensor switch to the mounting yoke with wires through its certral hole, and fix the yoke to the wall/ceiling. 5. Restore power at circuit breaker or fuse, wait one minute. 6. Remove the small cover plate. (illustrated as Figure 3. ) 7. Locate the adjustment knob on the control panel to perform test and adjustment.(illustrated as Figure 3 and 4. ) 8. Replace the small cover plate after testing and adjustment. Figure 2 Blue Control Out Standard Wiring: RED —+24VDC Input BLACK — Common BLUE — Control Output Figure 3 ADJUSTMENT Mounting Yoke PIR Lens Ultrasonic Cones Control Panel Cover Detection LEDs Red=PIR Blue=Ultrasonic Figure 4 Ultrasonic PIR Light Ultrasonic & PIR Sensitivity Adjustment Knob Default position: Center Adjustable: 25% (Position 1) to 100% (Position 4) Note: Turn toward right for greater room space. Turn toward left to avoid false alert in smaller room and near the door way or heat source. Ambient Light Level Adjustment Trimpot Default position: Daylight (100% at position 4) Adjustable: Clock wise Trigger mode: Switches 1, 2, 3 The sensor has 6 trigger options, set with DIP switches1, 2 and 3. In the trigger mode DIP switch setting table: DIP SWITCH SETTING The MDW-L has 7 DIP switches under the cover. They are used to set trigger mode, time delay and walk through mode feature settings. Initial Maintain Re-trigger Occupancy Occupancy (seconds Occupancy Logic Trigger 1 2 3 duration) Default Both Option 1 Either Either Either Option 2 PIR Either Either Option 3 Both Both Both Option 4 PIR PIR PIR Option 5 Ultra Ultra Ultra Time Delay 5 Sec Test 30 Sec 3 Min 5 Min 10 Min 15 Min 20 Min 30 Min 4 5 Either 6 Either Walk-Through 7 Disabled Enabled =OFF =ON =Factory Setting Both requires motion detection by the PIR and the Ultrasonic. Either requires motion detection by only one technology. PIR requires motion detection by the PIR. Ultra requires motion detection by the Ultrasonic. Initial Occupancy: The method that activates a change from “Standby” (area unoccupied and loads are off) to“Occupied” (area occupied and loads are on). Maintain Occupancy:The method indicating that the area is still occupied and the lights should remain on. Re-trigger: After the time delay elapses and the lights turn off, detection by the selected technology within the number of seconds indicated turns the lights back on. To turn off a technology: Option 4 turns off the Ultrasonic detection Option 5 turns off the PIR detection Time Delay: Switches 4, 5, 6 The sensor will hold the lights on as long as occupancy is detected. The time delay countdown starts when no motion is detected. After no motion is detected for the length of the time delay, the sensor will turn the lights off. Walk-through mode: Switch 7 Turns the lights off three minutes after the area is initially occupied, if no motion is detected after the first 30 seconds. If motion continues beyond the first 30 seconds, the selected time delay applies. There is a 40-second warm-up period when power is first applied. The sensors are factory preset to allow for quick installation in most applications.To make adjustments, open the Front Cover .Set the DIP Switch to the desired settings. See"DIP Switch Setting" below. Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification Commercial Grade In-Wall Occupancy/Vacancy Sensor Model #: DWOS-J Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level. Features: Turn lights ON/OFF automatically (Occupancy Mode) Manual ON / automatically OFF (Vacancy Mode) Time delay is adjustable from 15 seconds (test mode) to 30 minutes Secured ground wire required Zero Crossing for long relay life Adjustable sensitivity settings Light level is adjustable Standard decorator wall plate included Specifications: Voltage ……………………………………..……………………..…........................120-277 Vac, 60 Hz Incadescent ………………………………………….……….........................................................800W Fluorescent …………………………………………..…………120VAC/800VA..........277VAC/1600VA LED/CFL …………………………………………..…………….………...............................…......150W Motor …………………………………………………………………….…...............................….1/4 HP Time delay ………………………………………………….…...............................…15 Sec to 30 Mins Light level …………………………………………...……...…................................…30 Lux – Datlight Operation temperating …………………………………..………...............................…..32 F to 131 F Testing & Code Compliance UL/CUL Listed device California Title 24 Installation & wiring: Install the product as illustrated to the right, connects wires Green lead to ground, Black lead to Hot, Red lead to Load, White Lead to Neutral. Controls *Coverage Area Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification Commercial Grade In-Wall Bi-Level Occupancy/Vacancy Sensor Model #: DWOS-JD Description: Replaces standard switches for control of lighting and/or fans. Contains two relays to control two independent lighting loads or circuits. The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turned off automatically. Features: Turn lights ON/OFF automatically (Occupancy Mode) Manual ON / automatically OFF (Vacancy Mode) Time delay is adjustable from 15 seconds (test mode) to 30 minutes Secured ground wire required Zero Crossing for long relay life Adjustable sensitivity settings Light level is adjustable Standard decorator wall plate included Specifications: Voltage ……………………………………..……………………..…........................120/277Vac, 60 Hz Incadescent ………………………………………….…………………………...............................800W Fluorescent …………………………………………...................800VA@120VAC, 1600VA@277VAC Motor …………………………………………………………………….…...............................….1/4 HP Time delay ………………………………………………….…...............................…15 Sec to 30 Mins Light level …………………………………………...……...…................................…30 Lux – Datlight Operation temperating …………………………………..………...............................…..32 F to 131 F Testing & Code Compliance UL/CUL Listed device California Title 24 Installation & wiring: 1 2 Controls Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification Commercial Grade In-Wall Occupancy/Vacancy Sensor Model #: DWOS-1277 Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level. Features: Turn lights ON/OFF automatically (Occupancy Mode) Manual ON / automatically OFF (Vacancy Mode) Time delay is adjustable from 15 seconds (test mode) to 30 minutes Neutral wire required Zero Crossing for long relay life Adjustable sensitivity settings Light level is adjustable Standard decorator wall plate included Specifications: Voltage ……………………………………..……………………..…........................120/277Vac, 60 Hz Incadescent ………………………………………….…………………………...............................800W Fluorescent …………………………………………...................800VA@120VAC, 1600VA@277VAC Motor …………………………………………………………………….…...............................….1/4 HP Time delay ………………………………………………….…...............................…15 Sec to 30 Mins Light level …………………………………………...……...…................................…30 Lux – Datlight Operation temperating …………………………………..………...............................…..32 F to 131 F Testing & Code Compliance UL/CUL Listed device California Title 24 Installation & wiring: Install the product as illustrated to the right, connects wires Green lead to ground, Black lead to Hot, Red lead to Load, White Lead to Neutral. Controls *Coverage Area Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification Commercial Grade In-Wall Occupancy/Vacancy Sensor Model #: DWOS-1277-NL Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turned off automatically. Night Light will only be active when it is set to Vacancy Mode, Night Light stays ON if the load is Off, it turns off if there is an Occupancy and the light turned on. This product has one relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level. Features: Turn lights ON/OFF automatically (Occupancy Mode) Manual ON / automatically OFF (Vacancy Mode) Time delay is adjustable from 15 seconds (test mode) to 30 minutes Neutral wire required Zero Crossing for long relay life Adjustable sensitivity settings Light level is adjustable Night Light feature to pinpoint the location of the switch in a dark area. Standard decorator wall plate included Specifications: Voltage ……………………………………..……………………..…........................120/277Vac, 60 Hz Incadescent ………………………………………….…………………………...............................800W Fluorescent …………………………………………...................800VA@120VAC, 1600VA@277VAC Motor …………………………………………………………………….…...............................….1/4 HP Time delay ………………………………………………….…...............................…15 Sec to 30 Mins Light level …………………………………………...……...…................................…30 Lux – Datlight Operation temperating …………………………………..………...............................…..32 F to 131 F Testing & Code Compliance UL/CUL Listed device California Title 24 Installation & wiring: Install the product as illustrated to the right, connects wires Green lead to ground, Black lead to Hot, Red lead to Load, White Lead to Neutral. Controls *Coverage Area Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification In-Wall Occupancy/Vacancy Sensor Model #: DWOS-3R Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product includes adjustable Ambient Light Level. Features: Turn lights ON/OFF automatically (Occupancy Mode) Manual ON / automatically OFF (Vacancy Mode) Time delay is adjustable from 15 seconds (test mode) to 30 minutes Neutral wire required Single pole or three-way Zero Crossing for long relay life Adjustable sensitivity settings Light level is adjustable Standard decorator wall plate included Specifications: Voltage ……………………………………..……………………..…...............................120 Vac, 60 Hz Incadescent ………………………………………….…………………………...............................800W Fluorescent …………………………………………..…………….………...............................…800 VA Motor …………………………………………………………………….…...............................….1/4 HP Time delay ………………………………………………….…...............................…15 Sec to 30 Mins Light level …………………………………………...……...…................................…30 Lux – Datlight Operation temperating …………………………………..………...............................…..32 F to 131 F Testing & Code Compliance UL/CUL Listed device California Title 24 Installation & wiring: Install the product as illustrated to the right, connects wires Green lead to ground, Black lead to Hot and one terminal of 3-way switch, Red lead Re . to Load, White lead to Neutral, and 3-way Blue lead to another terminal of 3-way switch. Do not connect Red and White together Controls *Coverage Area Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification Commercial Grade In-Wall Occupancy/Vacancy Sensor Model #: MWOS Description: This Multi-Technology Wall Switch Sensor combine advanced passive infrared (PIR) and ultrasonic technologies into one unit. The combined technologies helps eliminate false triggering even in difficult applications. Selectable operating modes allow the sensor to turn a load on, and hold it on as long as either or both technologies detect occupancy . After no movement is detected for the selected time delay, the lights switch off. A "walk-through" mode can turn lights off after only 3 minutes, if no activity is detected after 30 seconds following an occupancy detection. This sensor also contains a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels drop, even if the area is occupied. Features: Integrated PIR and Ultrasonic sensor technology to detect very fine motion and provide accurate motion sensing Allows to choose triggering when both technologies detect motion or when only PIR detects motion Less false trigger, fast ON/OFF; commercial grade sensor for closet, garage, hotels, meeting room, work places Adjustable timeout from 15 seconds to 30 minutes; Walk-Through mode: 3 minutes if no activity after first 30 seconds Specifications: Voltage ................................................................ 120/277VAC,50/60Hz Load Requirments: Incandescent....................................................800W-120VAC,50/60Hz Fluorescent.........................800VA-120VAC,1600VA-277VAC,50/60Hz Resistive...........................................................800W-120VAC,50/60Hz Motor .............................................................. 1/4HP-120VAC,50/60Hz Adjustment Time Delay................................................. 5Sec to 30Mins Walk-Through Mode.......................3 minutes if no activity after 30 sec. Test Mode ....................... 5 sec. at initial power up or DIP switch reset PIR Adjustment...............................................High or Low (DIP switch) Ultrasonic Adjustment ......................... Minimum to Maximum (trimpot) Light Level Adjustment.................................100 Lux --daylight(trimpot) Operation Temperature................................................... 32° F--131° F Testing & Code Compliance UL LISTE D Installation & wiring 1. Make sure that the power has been turned OFF at the circuit breaker. 2. Connect lead wires as WIRING DIAGRAM (see Figure 1): Black lead to Line(Hot), Red lead to Load wire, White lead to Neutral wire, Green lead to Ground. Wiring Diagram: Neutral White Hot Black Load Red Ground Green Load Neutral(White) Figure 1 3. Mount device “TOP”up. 4. Gently position wires in wall box, attach sensor switch to the box. 5. Restore power at circuit breaker or fuse, wait one minute. 6. Remove the small cover plate. 7. Locate the adjustment trimpots on the control panel to perform test and adjustment. 8. Replace the small cover plate after testing and adjustment. Coverage area Top View 20' 10' 10' PIR Coverage: 1200 ft 2 Ultrasonic Coverage: 400 ft 2 20' 5' 4' 20' 40' Adj ustment Mounting Yoke PIR Lens Ultrasonic Cones Control Panel Cover Detection LEDs ON 2 3 1 2 3 4 5 6 7 OFF 1 4 ULTRASONIC 3 2 Red=PIR Blue=Ultrasonic 1 LIGHT 4 OFF OCC VAC ULTRASONIC OFF OCC VAC LIGHT Band switch prescription. Mode Position OFF OCC VAC Description Left Circuit is permanently opened. (switched off) None Occupancy Mode: Automatic On, automatic Off after set time delay. Center Right React to the push-button Manually toggles On / Off the load. Vacancy Mode: Manual On only, automatic Off after set time delay. Manually toggles On/Off the load. DIP Switch Setting The MWOS has 7 DIP switches under the cover. They are used to set sensitivity, time delay, trigger mode, walk through mode feature settings. Initial Trigger Mode Trigger Option 1 Both Option 2 Option 3 Option 4 Sensitivity 50% 100% Maintain Load Output Re-trigger Either Either PIR PIR PIR US US US Both Both Both Time Delay 5 Sec/Test 30 Seconds 5 Minutes 10 Minutes 15 Minutes 20 Minutes 25 Minutes 30 Minutes 1 Walk Through 7 Disabled Enabled =OFF =ON 4 =Factory Setting 2 5 3 6 General Specification In-Wall Occupancy/Vacancy Sensor Model #: HWOS Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level. Features: Turn lights ON/OFF automatically (Occupancy Mode) Manual ON / automatically OFF (Vacancy Mode) Time delay is adjustable from 15 seconds (test mode) to 30 minutes Neutral wire required Zero Crossing for long relay life Adjustable sensitivity settings Light level is adjustable Standard decorator wall plate included Specifications: Voltage ……………………………………..……………………..…...............................120 Vac, 60 Hz Incadescent ………………………………………….…………………………...............................500W Fluorescent …………………………………………..…………….………...............................…500 VA Motor …………………………………………………………………….…...............................….1/8 HP Time delay ………………………………………………….…...............................…15 Sec to 30 Mins Operation temperating …………………………………..………...............................…..32 F to 131 F *Coverage Area 15' 7.5' Best: 180 sq.ft. Regular: 450 sq.ft. Maximum: 700 sq.ft. 7.5' 15' 5' 4' 15' 30' Installation & wiring 1. Connect lead wires as wiring diagram (see Figure 2): Black lead to hot wire, red lead to load wire, white lead to neutral wire, green lead to ground wire. Wiring diagram Neutral White Top Load Red Hot Black Figure 2 Ground Green Load Neutral White 2. Device “TOP” upward. 3. Gently position wires in wall box, attach sensor switch to the box. 4. Restore power at circuit breaker or fuse, wait one minute. 5. Locate the toggle switch on both sides of the top cover to perform test and adjustment. Changing the color of your switch Your switch ships with top cover attached. It is convenient for users to change the top cover. Please proceed as follows: 2. N OPE CLO S E 1. Figure 3 Push down top cover to release Line up tabs and push up to attach Testing & Code Compliance UL LISTE D California Title 24 Adj ustment Mounting Yoke Fresnel Lens TOP TEST TEST 15 MIN VAC VAC 15 MIN OCC 30 MIN OCC 30 MIN LED Indicator INDOOR USE ONLY Control Top Cover (ON/OFF Button) Figure 4 Band switch prescription Mode Position Function of ON/OFF button Description VAC Vacancy Mode: Manual On only, Manually push Upper side Automatic Off after set time delay. On/Off the load. OCC Occupancy Mode: Lower side Automatic On, Automatic Off after set time delay. Manually push On/Off the load. Time delay setting Default position Adjustable 15 Seconds (Test mode) 15 Seconds 15 Minutes 30 Minutes Ambient light(Default setting) Notice: If the ambient light level is too high, more than the default setting the load may not automatic turned ON. If turning ON is desired, cover the sensor lens with one hand for 2 seconds, the light is going to turn ON. Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016 General Specification Residential/Commercial In-Wall Occupancy/Vacancy Sensor Model #: HWOS-J Description: The passive infrared sensors work by detecting the difference between heat emitted from the human body in motion and the background space. The sensor switch can turn a load on and hold it as long as the sensor detects occupancy. After no motion is detected for the set time delay, the load turned off automatically. This product has one relay (equal to Single Pole Switch), also includes adjustable Ambient Light Level. Features: Turn lights ON/OFF automatically (Occupancy Mode) Manual ON / automatically OFF (Vacancy Mode) Time delay is adjustable from 15 seconds (test mode) to 30 minutes Secured ground wire required Zero Crossing for long relay life Adjustable sensitivity settings Light level is adjustable Standard decorator wall plate included Specifications: Voltage ……………………………………..……………………..…...............................120 Vac, 60 Hz Incadescent ………………………………………….…………………………...............................500W Fluorescent ………………………………………..................500VA @ 120VAC, 1000VA @ 277VAC Motor …………………………………………………………………….…...............................….1/8 HP Time delay ………………………………………………….…...............................…15 Sec to 30 Mins Operation temperating …………………………………..………...............................…..32 F to 131 F *Coverage Area 15' 7.5' Best: 180 sq.ft. Regular: 450 sq.ft. Maximum: 700 sq.ft. 7.5' 15' 5' 4' 15' 30' Installation & wiring 1. Connect lead wires as wiring diagram (see Figure 2): Black lead to hot wire, red lead to load wire, white lead to neutral wire, green lead to ground wire. Wiring diagram Neutral White Top Load Red Hot Black Figure 2 Ground Green Load Neutral White 2. Device “TOP” upward. 3. Gently position wires in wall box, attach sensor switch to the box. 4. Restore power at circuit breaker or fuse, wait one minute. 5. Locate the toggle switch on both sides of the top cover to perform test and adjustment. Changing the color of your switch Your switch ships with top cover attached. It is convenient for users to change the top cover. Please proceed as follows: 2. N OPE CLO S E 1. Figure 3 Push down top cover to release Line up tabs and push up to attach Testing & Code Compliance UL LISTE D California Title 24 Adj ustment Mounting Yoke Fresnel Lens TOP TEST TEST 15 MIN VAC VAC 15 MIN OCC 30 MIN OCC 30 MIN LED Indicator INDOOR USE ONLY Control Top Cover (ON/OFF Button) Figure 4 Band switch prescription Mode Position Function of ON/OFF button Description VAC Vacancy Mode: Manual On only, Manually push Upper side Automatic Off after set time delay. On/Off the load. OCC Occupancy Mode: Lower side Automatic On, Automatic Off after set time delay. Manually push On/Off the load. Time delay setting Default position Adjustable 15 Seconds (Test mode) 15 Seconds 15 Minutes 30 Minutes Ambient light(Default setting) Notice: If the ambient light level is too high, more than the default setting the load may not automatic turned ON. If turning ON is desired, cover the sensor lens with one hand for 2 seconds, the light is going to turn ON. Enerlites Inc. www.enerlites.com Phone: 949-756-0536 Fax: 949-756-0528 e-mail: sales@enerlites.com Date: 03/01/2016