INSTALLATION INSTRUCTIONS
FOR LED EMERGENCY LIGHTING FIXTURE
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
IMPORTANT SAFEGUARDS:
IMPORTANT: Let the battery charge up for at least 24 hours. Then normal operation of this unit should
take effect. To check, press the “ TEST “ button. The LED lamps on the unit should turn ON. During
an electrical power failure, the led lamps will automatically come on for a minimum of 90 minutes. In
accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of
30 seconds and annually for 90 minutes. Refer to your local codes for any additional requirements that
may apply.
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT IN
DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE - For your protection, read and
follow these warnings and instructions carefully before installing or maintaining this equipment. These
instructions do not attempt to cover all installation and maintenance situations.
WARNING: RISK OF FIRE - Lamps are hot. Keep combustible material away from hot parts. Observe
lamp manufacture’s warnings, recommendations and restrictions on lamp operation and maintenance.
Make sure lamps are correctly installed.
• A
ll service shall be performed by qualified service personnel. This product must be installed
and maintained in accordance with the applicable installation codes by a person familiar with
the construction operation of the product and the hazards involved.
• This product must be installed in accordance with the applicable installation codes and ordinances.
• Before wiring to power supply, turn off electricity at fuse or circuit breaker.
• Disconnect A.C. power and unplug battery before servicing.
• Consult your local building code for approved wiring and installation.
• May be used outdoors under cover. (0°C-50°C)
• Do not let power supply cord touch hot surfaces.
• Do not mount near gas or electric heater.
• E
quipment should be mounted in Iocations and at heights where it will not readily be subjected
to tampering by unauthorized personnel.
• T
he use of accessory equipment not recommended by the manufacturer may cause
an unsafe condition.
• Do not use this equipment for other than intended use.
• T
he AC voltage rating of this equipment is specified on the product label.
Do not connect equipment to any other voltage.
SAVE THESE INSTRUCTIONS
1300 South Wolf Rd • Des Plaines, IL 60018 • Phone: 847-827-9880 • www.junolightinggroup.com
©2016 Acuity Brands Lighting, Inc.
Printed in China
Rev 2/13
P3508
pg 1 of 4
INSTALLATION INSTRUCTIONS
FOR LED EMERGENCY LIGHTING FIXTURE
IMPORTANT: Let the battery charge
up for at least 24 hours. Then normal
operation of this unit should take
effect. To check, press the “TEST”
button. The LED lamps on the unit
should turn ON. During an electrical
power failure, the led lamps will
automatically come on for a minimum
of 90 minutes. In accordance with
NFPA 101, your emergency lighting
system must be tested monthly
for a minimum of 30 seconds and
annually for 90 minutes. Refer to
your local codes for any additional
requirements that may apply.
USE FLEXIBLE CONDUIT ONLY.
INSTALLATION
CONDUIT
1. Secure back plate to wall surface.
Route wires through hole in
conduit flange and make conduit
connection. For 120V, use black
and white wires and for 277V, use
red and white wires.
J-BOX MOUNTING
1. Feed fixture leads through the
back plate and connect to AC
power supply (Fig A). For 120V
use black and white wires and for
277V, use red and white wires.
2. Attach back plate to J-Box and
secure with screws.
3. Complete the battery connection.
(Fig. B)
4. Align snaps and push housing
directly onto the back plate
(Fig. C). Apply continuous AC
power and press “TEST” button
to check light.
2. Complete the battery connection
(Fig. B).
3. Align snaps and push housing
directly onto the back plate
(Fig. C). Apply continuous AC
power and press “TEST” button
to check light.
WARNING: Unused wires must be
capped using enclosed wire nuts.
BATTERY CONNECTOR
PLUG IN
FIG. A
FIG. B
FIG. C
1300 South Wolf Rd • Des Plaines, IL 60018 • Phone: 847-827-9880 • www.junolightinggroup.com
©2016 Acuity Brands Lighting, Inc.
Printed in China
Rev 2/13
P3508
pg 2 of 4
INSTALLATION INSTRUCTIONS
FOR LED EMERGENCY LIGHTING FIXTURE
OPERATION
1. During an electrical power failure, the LED lamps will automatically come on for a minimum of 90 minutes.
2. To test, depress the “TEST” switch. The emergency LED lamps will illuminate. When the switch is released, the
lamps will go off.
WIRING DIAGRAM
REMOTE CAPABLE
REGULAR
CHARGER
BOARD
CHARGER
BOARD
AC INPUT CONNECTOR
(MOUNTING PLATE)
277V
RED
120V
BLACK
0V
NOTE:
Unused input lead must
be properly insulated
with wire nut or other
approved method
WHITE
AC INPUT CONNECTOR
(MOUNTING PLATE)
277V
RED
120V
BLACK
0V
WHITE
YELLOW(+)
YELLOW(+)
BLUE(-)
BLUE(-)
YELLOW(+)
YELLOW(+)
BLUE(-)
LAMP
BLUE(-)
LAMP
YELLOW(+)
LAMP
BLUE(-)
LAMP
RED
BLACK
RED
BLACK
BATTERY
TO REMOTE
READY
TEST
BATTERY
READY
TEST
NOTE:
Use 18-22 AWG stranded
wire to connect remote
lamp heads.
WARRANTY
Juno Lighting Group provides five year limited warranty on LED components from date of purchase. Juno Lighting Group’s obligation is expressly
limited to repair or replacement, without charge, at Juno Lighting Group’s factory after prior written return authorization has been granted. This
warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s factory. This warranty is in lieu of all other
warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty of merchantability. Also,
there are no warranties which extend beyond the description of the product on the company’s literature setting forth terms of sale.
Product Services Phone (888) 387-2212
1300 South Wolf Rd • Des Plaines, IL 60018 • Phone: 847-827-9880 • www.junolightinggroup.com
©2016 Acuity Brands Lighting, Inc.
Printed in China
Rev 2/13
P3508
pg 3 of 4
INSTALLATION INSTRUCTIONS
For Units Equipped with Self Diagnostics Option
1) Introduction
Once the unit is properly installed according to the Installation instruction sheet and AC power is supplied, the unit will come ON.
The dual-color LED indicator will also come ON, automatically initiating the self-diagnostic test function. The LED indicator points
out the current unit status. A STEADY GREEN on the LED indicator indicates a normal service; BLINKING GREEN indicates that
the unit is in testing mode; GREEN/RED FLASHING indicates that the battery is charging; RED (STEADY and BLINKING) would
indicate a fault or a service alert. Refer to section 3 – Fault Indication for more details. The LED indicator would be OFF when the
unit is in Emergency mode.
2) Self – Diagnostic Service
The self-diagnostic function is factory preset without any field adjustment. The automatic self-diagnostic feature serves the
following tests –
a. On-line real time monitoring of battery and lamps: Identifies battery charging, disconnection and failure along with lamp failure.
b. Self-testing and a 30-second discharge once every 30 days (conforming to NFPA code requirements), after AC power has been
supplied for a minimum of 24 hours.
c. Self-testing and a 30-minute discharge once every 180 days, after AC power has been supplied for a minimum of 24 hours.
d. Self-testing and a 90-minute discharge once every 365 days (conforming to NFPA code requirements), after AC power has been
supplied for a minimum of 24 hours.
3) Fault Indication
Function Unit is in normal mode
Battery Disconnected LED Indication
Battery Recharge
STEADY Green
STEADY Red
Red and Green (flashing alternatively)
Battery Recharge Failure* FLASHING Red
Battery Failure** Red BLINKING ‘2’ times
LAMP Failure Red BLINKING ‘4’ times
Remote LAMP Failure Red BLINKING ‘5’ times
* A battery recharge failure will come up if the battery is NOT able to recharge within the 24hrs charging time
** A battery failure will come up if the battery is NOT able to operate the lamps for the period of a discharge test
4) Manual Testing
This unit also provides for manual testing by pushing the test switch in a specific pattern. The different patterns and the resulting
tests are listed in the table below.
ACTION REACTION AND LED INDICATION
Push test button once (within 2 seconds) 30-second test; FLASHING Green
Push test button ‘2’ times (within 2 seconds) 30-minute test; Green BLINKING ‘2’ times
Push test button ‘3’ times (within 2 seconds) 90-minute test; Green BLINKING ‘3’ times
Push & Hold test button (3-5 seconds) System Interruption
Push & Hold test button (more than 6 seconds) System Reset
5) Operation
During an electrical power failure, the lamps will automatically come ON for a minimum of 90 minutes.
To test this unit, the battery needs to be charged initially for 2 hours before depressing the test switch
(to do manual test). On pressing the test switch, the Lamps will illuminate. The Lamps will turn OFF after
30-sec /30-min /90-min depending on the number of times the switch has been pressed.