Technical Datasheet Lumento X4 Ed.3 EN

advertisement
LUMENTO X4
LED DIMMING
RGB CONTROLLER
ZN1DI-RGBX4
Technical Documentation
4
5
FEATURES





Control of RGBW LED or 4 independent channels.
External power supply required (12 or 24 VDC).
LED test function.
Integrated KNX BCU.
Conformity with the CE directives.
3
7
1
2
1. KNX
connector
2. KNX programming and
internal test LED
4. Test button 5. LED control
terminal block
6. External
power supply
3. KNX programming
button
7. Test and reversed
polarity indicator LED
6
Figure 1. LUMENTO X4
KNX programming button: short button press to set the programming mode. If this button is held while plugging the device to
the KNX bus, it enters into safe mode.
KNX programming and internal test LED: the red LED indicates programming mode. When the device goes into safe mode, it
blinks red every 0.5 seconds. The blinking blue LED indicates internal test.
Test button: it tests the functioning of channels connected to the device. Push and hold for 3 seconds to get in/out of the testing
mode.
Test LED and polarity: tricolored LED that indicates which channel (red=channel 1/R, green=channel 2/G, blue=channel 3/B,
qhite=channel 4/W) is being tested. Orange light indicates reverse polarity in external power supply.
GENERAL SPECIFICATIONS
Type of device
Voltage (typical)
Voltage range
KNX supply
Power consumption
Connection type
External power supply
Power supply cable section
Type of control
Operation temperature
Storage temperature
Operation humidity
Storage humidity
Complementary characteristics
Protection class
Operation type
Device action type
Electrical stress period
Electric operation control device
29VDC
21…31VDC
145mW
Typical bus connector TP1, 0.80mm2 section
12 or 24VDC
1.5 mm² to 2.5 mm²
PWM (150, 300, 488 or 600 Hz)
0ºC to +45ºC
-5ºC to +50ºC
30 to 85% RH (no condensation)
30 to 85% RH (no condensation)
Class B
II
Continuous operation
Type 1
Long
Protection degree
IP20, clean environment
Installation
Response on KNX bus failure
Response on KNX bus restart
PCB CTI index
Housing material
Dimensions
Weight
Operation indication
© Zennio Avance y Tecnología S.L.
Surface mounted independent device
Connect LUMENTO as near as possible to both, the LED to dimmer and the external power supply
Data saving
Data recovery
175V
PC-ABS FR V0 halogen free
Without terminal blocks: 144x44x22mm / With terminal blocks: 157x44x22mm
104g
Programming/internal test LED indicates: programming mode (red lighting), safe mode (red
blinking) and internal test (blue blinking).
Test LED indicates: white, test channel 4 (W); red, test channel 1 (R); green, test channel 2 (G);
blue, test channel 3 (B). Reverse polarity of external power supply is indicated by the test LED with
orange light.
Edition 4
For further information www.zennio.com
Page. 1 of 2
LUMENTO X4
LED DIMMING
RGB CONTROLLER
ZN1DI-RGBX4
Technical Documentation
OUTPUTS SPECIFICATIONS AND CONNECTIONS
Maximum current per channel
Number of channels
Total power connected
Connection type
Cable section
Load type
Shortcut protection
Overheating protection
2.5A @ 25ºC ambient temperature
4
120W (12VDC) or 240W (24VDC)
Pluggable screw terminal block
1.5 to 2.5mm²
Common anode
Yes
Yes
WIRING AND ASSEMBLY DIAGRAMS
External power supply:
+ and - terminals of
external power supply 12
or 24VDC
LED
The LED load is connected to the terminal block, matching the anode or the anode common
terminal of the LED stripes with C (anode). The cathode can be connected to several output
channels if it is necessary more than 2.5A (up to 10A) for the LED strip, as long as the length
and section of the wires used for the connections between the outputs and the strip are
the same.
Correspondence
C: Anode
1: Red
2: Green
3: Blue
Recommended installation:
Assembly:
Screw mounting, 2 holes of
3.5mm diameter. Screws
not included.
4: White
NOT recommended:
Vertical position.
If there is not any
other possibility,
install terminal block
up (see fig.)
SAFETY INSTRUCTIONS





Installation should only be performed by qualified professionals according to the laws and regulations applicable in each
country.
Do not connect the mains voltage nor any other external voltage to any point of the KNX bus; it would represent a risk for the
entire KNX system. The facility must have enough insulation between the mains (or auxiliary) voltage and the KNX bus or the
wires of other accessories, in case of being installed.
Once the device is installed, it must not be accessible from outside.
Keep the device away from water and do not cover it with clothes, paper or any other material while in use.
The WEEE logo means that this device contains electronic parts and it must be properly disposed of by following the
instructions at http://zennio.com/weee-regulation.
© Zennio Avance y Tecnología S.L.
Edition 4
For further information www.zennio.com
Page. 2 of 2