diesel fuel tank

advertisement
DIESEL FUEL TANK
National Fire Protection Association (NFPA)
)
SPP Pumps Limited, 1420 Lakeview, Arlington Business Park, Theale, Reading, Berkshire, RG7 4SA
OPERATION
The diesel fuel tank is to provide a minimum of 8 hours run time on full load for the main diesel
pumpset.
TANK Design
The calculated capacity of the fuel tank is in accordance with NFPA20
The fuel tank is supplied as a loose item (without legs) and should be adequately braced, bracketed
and installed by others in such a manner and location that the feed pipe is elevated above the engine
fuel pump centreline.
Supply and return pipework between the fuel tank and engine is not of our supply
Features
- Fill connection
- Vent connection with flash arrestor
- Drain connection
- Feed (valved with facility for locking in open position) and return connections
- Easily visible fuel level gauge
- Low level switch (at two thirds capacity)
- Inspection / cleaning access hole
- Sludge and sediment trap
Options Available
- Double skin
- Additional low / high level switches
All equipment is CE Marked.
Our policy is one of continuous improvement and we reserve the right to alter the specifications of our offered products at anytime without notice.
Download