SECTION 16418 SURGE PROTECTIVE DEVICES PART 1 - GENERAL 1.01 REQUIREMENTS A. 1.02 SCOPE A. 1.03 The general provisions of the Contract, including General and Supplementary Conditions and General Requirements, apply to the work specified in this Section. The work under this Section shall include furnishing and installing Surge Protective Devices (SPDs), formerly TVSS, for the protection of AC electrical circuits as shown on the Drawings and herein specified. QUALITY ASSURANCE A. All equipment, materials, and their installation shall conform to the requirements of the National Electrical Code (NEC), local code requirements, and these Specifications. B. SPD units and all components shall be designed, manufactured and tested in accordance with the most recent editions of ANSI/UL 1449 and UL 1283. C. Equipment shall be constructed in accordance with National Electrical Manufacturer's Association (NEMA) standards (NEMA LS-1). D. Submittals are required in accordance with SECTION 16010 of these Specifications. The submittals shall contain, at a minimum, the following: 1. Provide verification that the SPD complies with the required ANSI/UL rd 1449 3 Edition listing by Underwriters Laboratories (UL) or other Nationally Recognized Testing Laboratory (NRTL) acceptable to Fairfax County Department of Public Works and Environmental Services. Compliance may be in the form of a file number that can be verified on UL’s website or on any other NRTL’s website, as long as the website contains the following information at a minimum: model number, SPD Type, system voltage, phases, modes of protection, Short Circuit Current Rating (SCCR), Voltage Protection Ratings (VPRs) for all modes, Maximum Continuous Operating Voltage rating (MCOV) and Nominal Discharge Current (In). UL data and visual inspection takes precedence over manufacturer’s published documentation. 16418-1 11/13 SURGE PROTECTIVE DEVICES SECTION 16418 2. For SPD external mounting applications include electrical/mechanical drawings showing unit dimensions, weights, installation instruction details, and wiring configuration. 3. Where applicable the following additional information shall be included in the submittals: a. Descriptive bulletins. b. Product sheets. PART 2 - PRODUCTS 2.01 2.02 MANUFACTURERS A. Subject to compliance, the following SPD manufacturers are acceptable: ADVANCED PROTECTION TECHNOLOGIES (APT) as listed herein or TOTAL PROTECTION SOLUTIONS (TPS), or the switchboard manufacturers SPD’s for internal or external mounting in or on switchboards shall also be acceptable. Panelboard manufacturers SPD’s for external mounting only shall also be acceptable. B. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features, and functions. Manufacturers listed above are not relieved from meeting these specifications in their entirety. VOLTAGE SURGE SUPPRESSION – GENERAL A. Electrical Requirements: 1. Refer to Drawings for operating voltages and unit configurations. 2. SPD’s shall be UL labeled with 200kA Short Circuit Current Rating (SCCR). Fuse ratings shall not be considered in lieu of demonstrated withstand testing SPDs. 3. Maximum Continuous Operating Voltage (MCOV): System Voltage 208Y/120 480Y/277 4. Allowable System Voltage Fluctuation (%) 25% 15% MCOV 150V 320V The suppression system shall incorporate thermally protected metaloxide varistors (MOVs) as the core surge suppression component for the service entrance and all other distribution levels. The system shall not utilize silicon avalanche diodes, selenium cells, air gaps, or other 16418-2 11/13 SURGE PROTECTIVE DEVICES SECTION 16418 components that may crowbar the system voltage leading to system upset or create any environmental hazards. 5. The SPD shall provide surge current path for all modes of protection: L-N, L-G, and N-G for Wye systems; L-L, L-G in Delta and impedance grounded Wye systems. 6. All SPD’s applied to the distribution system shall have a 20kA Nominal Discharge Current (In) rating regardless of their SPD Type (includes Types 1 and 2) or operating voltage. SPDs having an In less than 20kA shall not be acceptable. 7. ANSI/UL 1449 Listed Voltage Protection Ratings (VPRs) shall not exceed the following: System Voltage 208Y/120 480Y/277 L-N 800V 1200V L-G 800V 1200V L-L 1200V 2000V N-G 800V 1200V (Numerically lower is allowed/preferred; old-style Suppressed Voltage Ratings (SVRs) shall not be submitted, nor evaluated due to outdated less-strenuous testing). B. SPD Design: 1. SPD shall be UL listed Type 1 or Type 2, intended for use without need for external or supplemental overcurrent controls. Every suppression component of every mode, including N-G, shall be protected by internal overcurrent and thermal over temperature controls. SPD’s relaying upon external or supplementary installed safety disconnects do not meet the intent of this specification. 2. The SPD shall be maintenance free and shall not require any user intervention throughout its life. SPDs containing items such as replaceable modules, replaceable fuses, or replaceable batteries shall not be accepted. SPDs requiring any maintenance of any sort such as periodic tightening of connections shall not be accepted. SPDs requiring user intervention to test the unit via a diagnostic test kit or similar device shall not be accepted. 3. The surge current shall be equally distributed to all MOV components to ensure equal stressing and maximum performance. The surge suppression platform must provide equal impedance paths to each matched MOV. Designs incorporating replaceable SPD modules shall not be accepted. 16418-3 11/13 SURGE PROTECTIVE DEVICES C. 2.03 SECTION 16418 4. SPD shall have UL 1283 EMI/RFI filtering with minimum attenuation of 50dB at 100kHz. 5. SPD shall include visual LED diagnostics including a minimum of one green LED indicator per phase, and one red service LED. SPD shall include an audible alarm with on/off silence function and diagnostic test function. SPDs for branch circuit panels not employing an on/off silence function will be acceptable. 6. The SPD must include Form C dry contacts (one NO and one NC) for remote monitoring of its status. Both the NO and NC contacts shall change state under any fault condition or if power is removed from the SPD. Service entrance locations shall have two sets of NO and NC contacts for building power monitoring. 7. SPDs at service entrance locations shall be provided with a surge event counter with a reset button allowing the surge counter to be zeroed. The surge event count shall have a lithium battery backup or be stored in nonvolatile memory and displayed after power is restored. 8. Internally mounted SPDs in switchboards shall be designed to interface with the electrical assembly via factory installed conductors only and not mounted directly to bus bars. 9. Sidemount SPDs shall be factory sealed in order to prevent access to the inside of the unit. Sidemount SPDs shall have factory installed phase, neutral, ground and remote status contact conductors factory installed and shall have a pigtail of conductors protruding outside of the enclosure for field installation. Top mount SPDs for switchboards where sidemount is not feasible due to space constrictions or space allowed for future expansion. SPDs shall have NEMA 1 general purpose enclosures, unless otherwise noted or required for the environment. SPDs located in kitchens or other areas subject to possible water exposure shall be NEMA 4X. SYSTEM APPLICATION A. The SPD applications covered under this section include switchboard assemblies, motor control centers (if present), distribution and branch circuit panelboards. All SPDs shall be tested and demonstrate suitability for application within ANSI/IEEE C62.41 Category C, B, and A environments. B. The minimum current capability (single pulse rated) per phase shall be: 16418-4 11/13 SURGE PROTECTIVE DEVICES SECTION 16418 Service Entrance or Automatic Transfer Switch: Distribution Panelboards & MCC: Branch Circuit Panelboards: C. 2.04 250kA 150kA 100kA SPDs installed on the load side of the service entrance disconnect shall be Type 1. Other SPD locations beyond the service entrance shall be Type 1 or Type 2. SERVICE ENTRANCE SWITCHBOARD/PANELBOARD LOCATIONS [Engineer to edit. Delete SE Distribution Panels if not using. These are used mostly for ball fields] A. The SPD application covered under this section is for service entrance switchboard(s) and service entrance distribution panelboard(s). Service entrance located SPDs shall be tested and demonstrated suitability for application within ANSI/IEEE C62.41 Category C environments. B. The SPD shall be from the same manufacturer as the switchboard. The SPD shall be internal and panel mounted in the front face of the switchboard at the assembly point by the original equipment manufacturer. Alternatively, the SPD from the same or different manufacturer may be mounted external to the switchboard. C. The SPD for service entrance distribution panelboards shall be mounted external and adjacent to the panelboard. D. Locate the SPD (Type 1) on the load side of the main disconnect device, as close as possible to the phase conductors and the ground neutral bar. E. The SPD shall be connected through a three pole, 60A circuit breaker to serve as the disconnecting means for the SPD. This disconnect shall be located in immediate proximity to the SPD. Connections shall be made via conductors originating in the SPD and shall be kept as short as possible. 1. As an option, internal mounted SPD’s in switchboards may be provided with an integral disconnect switch in lieu of using a 60A circuit breaker to serve as the SPD disconnecting means. Connections shall be made via conductors originating in the SPD and connected to the bus bars with suitably sized tap lugs, factor installed. Conductors shall be kept as short as possible. F. All monitoring and diagnostic features shall be visible from the front of the equipment. G. The service entrance distribution panelboard external SPD shall be ADVANCED PROTECTION TECHNOLOGIES (APT) Model No.: [Engineer to edit] 16418-5 11/13 SURGE PROTECTIVE DEVICES 2.05 SECTION 16418 • TE02XAS25E1X for 120/208V SE distribution panelboards • TE04XAS25E1X for 277/480V SE distribution panelboards POWER DISTRIBUTION AND BRANCH CIRCUIT PANELBOARD LOCATIONS A. The SPD application covered under this section includes distribution and branch circuit panelboards. The SPD units shall be tested and demonstrate suitability for application within ANSI/IEEE C62.41 Category B environments. B. The SPD shall be mounted externally and adjacent to the panelboard. The SPD shall be connected through a three pole, 30A circuit breaker to serve as the disconnecting means for the SPD. Connections shall be made via conductors originating in the SPD and shall be kept as short as possible. C. SPDs shall be flush mounted adjacent flush mounted panelboards and surface mounted adjacent to or attached to surface mounted panelboards. D. The external SPD shall be ADVANCED PROTECTION TECHNOLOGIES (APT) Model No.: [Engineer to edit] E. • TE02XDS154XA for 120/208V distribution panelboards • TE04XDS154XA for 277/480V distribution panelboards • TE02XDS104XA for 120/208V branch circuit panelboards • TE04XDS104XA for 277/480V branch circuit panelboards SPDs for motor control centers (MCC) shall be from the same manufacturer as the MCC. The SPD shall be internal and panel mounted in the front face of the MCC at the assembly point by the original equipment manufacturer. Alternatively, the SPD from the same or different manufacturer may be mounted external to the MCC. All monitoring and diagnostic features shall be visible from the front of the equipment. [Engineer edit out if not using MCCs] PART 3 - EXECUTION 3.01 INSTALLATION A. SPD shall be installed per manufacturer’s installation instructions with lead lengths as short (less than 24”) and straight as possible. Gently twist conductors together. B. This Contractor may reasonably rearrange the circuit breaker locations to ensure the shortest and straightest possible leads for the SPD connections. 16418-6 11/13 SURGE PROTECTIVE DEVICES 3.02 3.03 SECTION 16418 C. Before energizing, this Contractor shall verify service and separately derived system neutral to ground bonding jumpers per the National Electrical Code. D. Repaint marred and scratched surfaces with touch-up paint to match original finish. TRAINING A. This Contractor shall provide four (4) hours of technical service training to the Owner’s technical and maintenance staff. B. The training session shall be conducted by a manufacturer’s qualified representative. The training program shall consist of instruction on operation of the assembly. WARRANTY A. SPDs and supporting components and accessories shall be guaranteed by the manufacturer to be free of defects in material and workmanship for a period of ten (10) years from the date of substantial completion of service and activation of the system to which the suppressor is attached. Additionally, during the applicable warranty period, and SPD which fails due to any electrical anomaly, including lightning, shall be replaced by the manufacturer without charge. Special or optional warranties in excess of the warranty period for purposes of this bid are not acceptable. Standard unit warranties in excess of the warranty period stated herein are acceptable. Refer to SECTION 01740 for the start of the warranty period. B. Since “Acts of Nature” or similar statements typically include the threat of lightning to which the SPDs shall be exposed, any such clause limiting warranty responsibility in the general conditions of this specification shall not apply to this particular section. The warranty must specifically provide for unlimited free replacements of the SPD in the event of failure caused by the effects of lightning and all other electrical anomalies. The warranty shall cover the entire device, not just various components, such as modules only. END OF SECTION 16418-7 11/13