ABB - Electrical Power and Controls Inc.

advertisement
Thermal
Overload relays
Thermal overload relays
Type TA
Class 10
Class 20
Description
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2
• CSA File No: LR98336
• Available for starter construction with
A Line contactors and separate panel
mounting
• Trip indication
• Remote trip and reset option available
• Designed for close couple mounting
• Single phase and phase unbalance protection
• Separate base mounting available for all
overload relays
• Isolated alarm circuit (N.O.) contact
• Class 10 adjustable overload relays are
standard with all ABB Line starters
• Ambient compensation:
-25°C to +55°C (-13oF to +131oF)
• Reset can also be adjusted to function as a
stop button
• Manual test
• Manual or automatic reset
• Screwdriver guide holes
• Factory calibrated and tested
• All terminal screws are available from the
front
• Wide adjustment range
• UL File No: E48139
Tripping classes of the thermal overload relays
Standard classes in IEC 947-4-1 are classes: 10 A, 10, 20, 30. The tripping class indicates
according to IEC 947-4-1 the maximum tripping time in seconds under specified conditions of
test at 7.2 times the setting current and specifies tripping and non tripping times for 1.5 and 7.2
times the setting current. Mostly used class is 10 A.
Abstract from IEC 947-4-1
Tripping class
Max. tripping time
at 1.5 x setting current
(warm state)
Tripping time at
7.2 x setting current
(cold state)
At 1.05 x setting current
Low Voltage Products & Systems
Th
Ov erm
e
a
re rloa l
lay d
s
10 A
10
20
30
(s)
120
240
480
720
(s)
2 – 10
4 – 10
6 – 20
9 – 30
no tripping
2.1
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
2
Description
TA thermal overload relays are used with A Line contactors for the protection of
motors having a nominal voltage of up to 600VAC max per UL/CSA (690VAC and
800VDC per IEC).
Product range
• Standard relays:
Types: TA25DU, TA42DU, TA75DU, TA80DU, TA110DU, TA200DU and TA450DU
– TA25 to TA110 and TA200 are directly connected in the motor circuit.
– TA450DU relays are fed through a linear type transformer
• Special construction
Thermal overload relays with different certifications and approvals.
Relays for protection EEx e motors.
Construction and function
• General
Thermal O/L relays and their accessories meet UL, CSA and most other important
international standards (IEC), European standards (EN) and the most important
national standards (DIN-VDE, NFC-UTE, BS, etc.). They meet the certification
and approval directives required throughout the world.
Thermal overload relays are 3 pole. The motor current flows through their bimetals
(1 per phase) which are indirectly heated. Under the effect of the heating, the
bimetals bend, cause the relay to trip and the position of the auxiliary contacts to
change.
The relay setting range is graduated in amps. In compliance with international and
national standards, the setting current is the motor nominal current and not the
tripping current (no tripping at 1.05 x setting current, tripping at 1.2 times setting
current).
The tripping curves (cold or warm starting, 3 phases and 2 phases) are shown on
page 2.14.
The relays are built to be self protecting in the event of an overload until the short
circuit protection device is activated.
Terminals L1, L3, L5
Manual test
Manual or automatic reset
Frame size
TA....DU
Trip indication light
Tripping contact (95, 96)
Amp setting range
Signaling contact, (97, 98)
2.2
1SXU000023C0202
Terminals T1, T2, T3
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Description
2
Application
Technical data
• All the relays have:
–
–
–
–
–
Free tripping: the resetting button, even if held in, does not prevent tripping of the thermal overload relay in the
event of a fault.
Temperature compensation
Phase failure protection according to IEC 947-4-1: Within the limits of the setting range, a reduced tripping time, and
thus improved motor protection, is obrtained in case of a phase failure.
Tripping class: 10A, for TA relays
Test functions and resetting: see table below.
• Auxiliary contacts
The relays have two built in auxiliary contacts: NC marked 95-96; NO marked 97-98. Both contacts are physically separate
and can thus be used for 2 different circuits (control circuit and indication circuit).
Function of TA25DU – TA450DU thermal O/L relays
Resetting
Relay tripped
Effect of blue
TA25DU
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Relay not tripped
Contacts
Manual
Automatic
Resetting
Yes
No
button indexed
95-96
on R
(RESET ONLY)
97-98
Effect of blue
Open
{95-96
97-98 Closed
Resetting
Closed when the
button is pressed
No effect
Closed
{ 95-96
97-98 Open
Both manual and automatic
No
No effect
Open when the
button is pressed
Yes
No
No
button indexed
95-96
on R/O
Closed when the
No effect
button is released
Open when the button is pressed
Closed when the button is released
(RESET/OFF)
97-98
Open when the
button is pressed
No effect
2.3
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
Selection guide
TA25DU – TA80DU
2
Types
TA25DU
TA42DU
TA75DU
TA80DU
Main characteristics
Construction
3 pole with ambient temperature variation compensation.
Protection against single phase operation. Built in auxiliary contacts: 1N.O. + 1N.C.
Resetting
Convertible:
Setting ranges
Number
18
3
from
to
0.1 – 0.16A
24 – 32A
18 – 25A
29 – 42A
Manual to Automatic
6
4
18 – 25A
60 – 80A
29 – 42A
60 – 80A
Mounted with contactors
Mounting kit
No kit is required for mounting thermal O/L relays below contactors
Types of contactors
A/AE/AL9
for combined mounting
A/AE/AL12
A/AE/AL16
A/AE/AL26
A/AE/AL30
A/AE30
A/AE40
A/AE/AL40
A/AE/AF50
A/AE/AF63
A/AE/AF75
Mounted separately (i.e. separate from contactor)
Separate mounting kit
DB25
A/AE/AF95
A/AE/AF110
DB80
Accessories
Tripping coil
DS25-A
Resetting coil
DR25-A
Terminal shroud
Terminals protected against direct contact (without the addition of terminal shrouds)
Function markers
2.4
1SXU000023C0202
BA5-50
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Selection guide
TA110DU – TA450DU
2
Types
TA110DU
TA200DU
TA450DU
Main characteristics
Construction
3 pole with ambient temperature variation compensation.
Protection against single phase operation. Built in auxiliary contacts: 1N.O. + 1N.C.
Resetting
Setting ranges
Number
from
to
1
3
5
2
4
6
R
95
97
96
98
Convertible: manual to automatic
A
A
2
6
3
65 – 90
80 – 110
65 – 90
150 – 200
130 – 185
220 – 310
Mounted with contactors
Mounting kit
No kit is required for mounting thermal O/L relays
See page 2.7.
Types of contactors
for combined mounting
A/AE/AF95
A/AE/AF110
A/AF145
A/AF185
A/AF210 + DT450/A300
A/AF260 + DT450/A300
A/AF300 + DT450/A300
Mounted separately (i.e. separate from contactor)
Separate mounting kit
DB200
No kit required for separate mounting of thermal O/L relays
Accessories
Tripping coil
Resetting coil
Terminal shroud
1
LT200 –
Function markers
LT450 –
BA5-50
1 Terminals protected against direct contact (without the addition of terminal shrouds)
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2.5
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
TA25 - TA450
Class 10
for Contactors A9 – A/AF300
2
For
Contactor
TA25DU
A/AE/AL9 – A/AE/AL40
A/AE30 - A/AE/40
TA42DU
A/AE/AF50 - A/AE/AF75
A/AE/AF95 - A/AE/AF110
TA75DU
A/AF145 - A/AF185
A/AF210 - A/AF300
Setting Range
A
0.1 - 0.16
0.16 - 0.25
0.25 - 0.4
0.4 - 0.63
0.63 - 1.0
1.0 - 1.4
1.3 - 1.8
1.7 - 2.4
2.2 - 3.1
2.8 - 4.0
3.5 - 5.0
4.5 - 6.5
6.0 - 8.5
7.5 - 11
10 - 14
13 - 19
18 - 25
24 - 32
18 - 25
22 - 32
29 - 42
18 - 25
22 - 32
29 - 42
36 - 52
45 - 63
60 - 80
29 -42
36 - 52
45 - 63
60 - 80
65 - 90
80 - 110
65 - 90
80 - 110
100 - 135
110 - 150
130 - 175
150 - 200
130 - 185
165 - 235
220 - 310
AF400 - AF750
Suffix
Code
Catalog
Number
A
TA25DU0.16
B
TA25DU0.25
C
TA25DU0.4
D
TA25DU0.63
E
TA25DU1.0
F
TA25DU1.4
G
TA25DU1.8
H
TA25DU2.4
J
TA25DU3.1
K
TA25DU4.0
L
TA25DU5.0
M
TA25DU6.5
N
TA25DU8.5
P
TA25DU11
Q
TA25DU14
R
TA25DU19
S
TA25DU25
T
TA25DU32
A
TA42DU25
B
TA42DU32
C
TA42DU42
A
TA75DU25
B
TA75DU32
C
TA75DU42
D
TA75DU52
E
TA75DU63
F
TA75DU80
C
TA80DU42
D
TA80DU52
E
TA80DU63
F
TA80DU80
A
TA110DU90
B
TA110DU110
A
TA200DU90
B
TA200DU110
C
TA200DU135
D
TA200DU150
E
TA200DU175
F
TA200DU200
A
TA450DU185 1
B
TA450DU235
C
TA450DU310
See electronic overloads, pages 2.21
List
Price
$ 63
78
102
135
165
165
225
488
1 TA450 overloads require mounting kits for installation.
TA80DU
TA110DU
2.6
1SXU000023C0202
Discount schedule TAA [OW] — TA25
Discount schedule TBA [OX] — TA42, TA75
Discount schedule TCA [OY] — TA80, TA110, TA200, TA450
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
TA25 - TA80
Class 20
for Contactors A9 - A80
2
Setting range
A ... A
TA25DU
TA42DU
TA75DU
Packing
unit piece
Catalog number
List
price
TA25DU1.8-20
TA25DU2.4-20
TA25DU3.1-20
TA25DU4.0-20
TA25DU5.0-20
TA25DU6.5-20
TA25DU8.5-20
TA25DU11-20
TA25DU14-20
TA25DU19-20
TA25DU25-20
TA25DU32-20 (1)
$ 63
TA42DU trip class 20 for contactors A30, A40 and (T) AL30, (T) AL40
18 … 25
AZ
1
1SAZ311401R1001
22 …32
BZ
1
1SAZ311401R1002
29 … 42
CZ
1
1SAZ311401R1003
TA42DU25-20
TA42DU32-20
TA42DU42-20
$ 78
TA75DU trip class 20 for contactors A50 … A75 and AE50 … AE75
18 … 25
AZ
1
1SAZ321401R1001
22 … 32
BZ
1
1SAZ321401R1002
29 … 42
CZ
1
1SAZ321401R1003
36 … 52
DZ
1
1SAZ321401R1004
45 … 63
EZ
1
1SAZ321401R1005
60 … 80
FZ
1
1SAZ321401R1006
TA75DU25-20
TA75DU32-20
TA75DU42-20
TA75DU52-20
TA75DU63-20
TA75DU80-20
$ 102
TA80DU trip class 20 for contactors A95, A110, AE 95 and AE110
29 … 42
AZ
1
1SAZ331401R1003
36 … 52
BZ
1
1SAZ331401R1004
45 … 63
CZ
1
1SAZ331401R1005
60 … 80
DZ
1
1SAZ331401R1006
TA80DU42-20
TA80DU52-20
TA80DU63-20
TA80DU80-20
$ 135
Suffix
Reference code
TA25DU trip class 20 for contactors A9 … A40 and (T) AL9 … (T) AL30
1.3 … 1.8
GZ
1
1SAZ211401R1025
1.7 … 2.4
HZ
1
1SAZ211401R1028
2.2 … 3.1
JZ
1
1SAZ211401R1031
2.8 … 4.0
KZ
1
1SAZ211401R1033
3.5 … 5.0
LZ
1
1SAZ211401R1035
4.5 … 6.5
MZ
1
1SAZ211401R1038
6.0 … 8.5
NZ
1
1SAZ211401R1040
7.5 … 11
PZ
1
1SAZ211401R1043
10 … 14
QZ
1
1SAZ211401R1045
13 … 19
RZ
1
1SAZ211401R1047
18 … 25
SZ
1
1SAZ211401R1051
TZ
1
1SAZ211401R1053
24 … 32 (1)
(1)
with terminal block DX25: 1x16mm2
No Tripping at 1.05 Ie
Tripping at 1.2 Ie within 2 hours
Time
Class 30 9 - 30 sec
Class 20 6 - 20 sec
TA80DU
Class 10 4 - 10 sec
Ie (adjusted current)
1.2 Ie
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
7.2 Ie
Discount schedule TAA [OW] — TA25
Discount schedule TBA [OX] — TA42, TA75
Discount schedule TCA [OY] — TA80, TA110, TA200, TA450
2.7
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
Accessories
2
Separate mounting kits
DB25/25A
For O/L
Amps
relays
TA25DU
TA25DU
TA42DU, TA75DU, TA80DU
TA110DU, TA200DU
0.1 – 25
24 – 32
18 – 80
100 – 200
Catalog
number
DB25/25A
DB25/32A
DB80
DB200
List
price
$ 30
38
45
60
Terminal block — AWG #8 cable
Mounting on:
Catalog
number
TA25DU (25A or less) or DB25/25A
List
price
$ 15
DX25
LC terminal blocks can be used to convert standard connections into Faston connections: 2 x 6.3mm or 4 x 2.8mm per pole.
The connections are protected against accidental contact.
The LC30-T has a terminal block for the 3 power terminals and a second for the 4 auxiliary terminals of a TA25DU thermal
O/L relay.
The LC26-B1 has two identical terminal blocks each for 3 power terminals. This block allows the power terminals to be
mounted with two DB25 kits or a TA25DU thermal O/L relay and DB25 kit assembly.
NOTE: According to DIN 46429 part 1 and NFC 20-120 the max. capacity of a Faston connection is 25 A.
DB80
Mounting kit – for TA450 overload relay
For contactor
Catalog
number
A145 – A185
A210 – A300
DT450/A185
DT450/A300
List
price
$ 225
Terminal shrouds – for contactors and overload relays
DB200
Contactor
Overload
relay
TA25DU
A9 – A16
A26 – A40
Catalog
number
Included
List
price
—
A30 – A40
TA42DU
Included
—
A50 – A75
TA75DU
Included
—
A95 – A110
TA80DU
TA110DU
Included
A145 – A185
TA200DU
LT185-AY
A145 – A185
Load side of TA200DU
LT200A185
—
$ 10
50
Terminal lug kits
2.8
1SXU000023C0202
Wire
range
6 – 250MCM
4 – 400MCM
(2) 4 – 500MCM
For
overloads
TA110DU, TA200DU
TA450DU185
TA450DU310
Discount schedule ABA [OF] — A-contactor accessories
Discount schedule TAA [OW] — TA25
Discount schedule TBA [OX] — TA42, TA75
Discount schedule TCA [OY] — TA80, TA110, TA200, TA450
Catalog
number
List
price
EHTK210
ATK300HK
ATK300/2HK
$ 45
78
120
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Accessories
2
Remote tripping coils
U voltage at 50/60 Hz
DS25A
Catalog
number 1
DS25-A remote tripping coil
24V
48V
110V
220/380V
500V
DS25-A-24
DS25-A-48
DS25-A-110
DS25-A-220/380
DS25-A-500
DS25-A remote resetting coil
24V
48V
110V
220/380V
500V
DR25-A-24
DR25-A-48
DR25-A-110
DR25-A-220/380
DR25-A-500
List
price
$ 60
Application
•The DS25-A coil is used for remote electrical tripping of the TA25 DU thermal O/L relay and is connected to the relay's
normally closed 95-96 auxiliary contact.
•The DR 25-A coil is used for remote electrical resetting of the TA25DU thermal O/L relay which is
adjusted for “Manual resetting;” it is connected to the relay’s normally open 97-98 auxiliary contact.
The coils are not designed for continuous duty. Impulse duration: 0.2 to 0.35 s.
Set the button to “Man” (Manual resetting).
Mounting: clipped on to TA25DU thermal O/L relay.
DR25A
Installation diagrams
For connection of DS25-A to TA25DU relay
L1
L2/N
START
STOP
21
For connection of DR25-A to TA25DU relay
13
22
14
L1
OL
A1
M
A2
95
96
21
13
22
M
13
L2/N
START
STOP
14
OL
M
A1
13
E2
OL
97
98
OL
TRIPPING
COIL
OFF
24
13
14
OL
A1
M
A2
95
96
OVERLOAD
TRIP
L1
E2
OFF
HAND
L2/N
AUTO
23
24
13
14
OL
M
A1
OVERLOAD
RESET
E1
E1
OL
RESETTING
COIL
L2/N
AUTO
23
96
14
OVERLOAD
RESET
E1
HAND
95
M
14
OVERLOAD
TRIP
L1
A2
E2
95
96
OL
97
OL
TRIPPING
COIL
A2
98
E1
E2
OL
RESETTING
COIL
1 Cannot be used with TA42, TA75, or TA200 overload relays.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Discount schedule TAA [OW] — TA25
2.9
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
Technical data
TA25DU – TA450DU
2
Intermittent duty
Switching frequency
For intermittent operations, the diagram opposite specifies relay operating limits.
s
0.5
120
100
ta
=
80
To avoid untimely tripping, TA and T thermal O/L relays have been designed to withstand roughly 15 switching operations
per hour with an approximately equal distribution between working and rest cycles.
In these conditions, the motor starting time must not exceed 1 second and the starting current must be lower than or equal
to 6 times the motor In.
ta =
(ops/h)
140
Switching frequency:
1s
Example: Motor starting time:
1 sec.
Load factor:
40 %
Switching frequency:
60 ops./h according to diagram
ta
40
ta =
20
ta = 3.5
For a higher number of operations and for load variations (e.g. frequent starting and braking), it is advisable to use
CUSTORAPID® protection.
60
=1
.5s
For motors subject to particularly severe operating conditions (e.g. locked rotor) it is advisable to use protection combined
with a thermal O/L relay and the CUSTORAPID® system.
3s
Protection of motors with long starting time
s
See electronic overload relay section, pages 2.21 - 2.32.
0
0
20
40
60
Closing time
80 100(%)
Switching frequency
in relation to load factor.
ta: motor starting time.
Mounting position
On a support at an angle of ± 30° in relation to the vertical plane (standard position).
Other mounting positions possible, except mounting on a horizontal plane (in this case the tripping
mechanism would be located above the bimetals).
Special version for EEx e motors
Consult factory.
[s]
40
Tripping limits at ambient temperatures varying by + 20°C
Ambient temperature compensation
Thermal O/L relays are compensated against ambient temperature
variations by a compensation bimetal which is sensitive to the
ambient temperature.
Tripping time
11
10
Thermal O/L relays are designed to operate between –5 °C and
+40 °C in compliance with standard IEC 947-4-1. For a wider range
of –25° C to +55 °C consult the graph opposite.
6
4
3
2
Example: tripping at – 25 °C. Tripping takes place before 1.5 times
the setting current.
1
Resetting: TA25DU – TA450 DU thermal O/L relays have convertible
manual/automatic resetting.
7 8
7.4
Multiple of the setting current
3
4
5
6
TA thermal O/L relay cold-state
tripping characteristics
2.10
1SXU000023C0202
Delivery: in manual resetting mode.
1.5
Ambient temperature
compensation limits
according to IEC 947-4-1
1.4
Multiple of the setting current
20
1.3
Tripping
1.2
1.1
No tripping
1.0
0.9
-20
-10
0
10
20
30
Ambient temperature
40
50
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Technical data
TA25DU – TA80DU
Types
TA25DU
TA42DU
Standards:
(international, European)
2
TA80DU
IEC 947-4-1, EN 60947-4-1
Rated insulation voltage Ui
according to IEC 947-4-1
Rated impulse withstand voltage Uimp
according to IEC 947-4-1
Permissible ambient temperature
– for storage
– for operation
V
690
kV
6
°C
°C
–40 to +70
–25 to +55 with temperature compensation (maximum values: see page 2.9)
Climatic withstand DIN 50017
Mounting positions
 
Humidity in alternate climate KFW, 30 cycles
On a support at an angle of ±30° in relation to the vertical plane (standard position). Other positions
possible except mounting on a horizontal plane (in this case the tripping mechanism
would be located above the bimetals).
Shock withstand
shock duration ms
at nominal Ie Critical direction
of shocks A1, A2
multiples of g
Resistance to vibrations
(±1 mm, 50 Hz)
Mounting
TA75DU
15
12
multiples of g
8
– on contactor Latching below the contactor, screw fixing on main terminals
– separate with DB - kit Using screws: 2 x M4 or 35 mm EN 50022
Terminals and cross-sectional areas for main conductors (motor side)
• screw terminal
– with cable clamp
– via tunnel connector
– flat type for lug or bar
A2
A1
• conductor cross-sectional area
– rigid solid or rigid stranded
– flexible with cable end
– recommended bars
mm2
mm2
mm
TA25DU setting ranges:
from 0.1-0.16A 24-32 A
to 18-25A
M4
–
–
M5
–
–
2 x 1.5 - 6
2 x 1.5 - 4
–
1 x 10 2 x 0.75- 6 –
M6
–
–
M6
–
M6
–
1 x 2.5 - 35 or 2 x 2.5 x 16
1 x 2.5 - 25 or 2 x 2.5 x 10
–
–
Terminals and cross-sectional area
for auxiliary conductors
• screw terminal (screw size)
– with cable clamp
• conductor cross-sectional area
– rigid solid or rigid stranded
– flexible with cable end
M 3.5
2 x mm2
2 x mm2
Degree of protection
0.75 - 4
0.75 - 2.5
All the terminals are protected against direct contact according to
VDE 0106/Part. 100. (without additional terminal shrouds)
Pole Technical Characteristics
Types
TA25
DU
Number of poles
Resistance per phase in mΩ
and heat dissipation in W
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
TA80
DU
TA10
DU
TA200
DU
TA450
DU
see page 2.6
Tripping class according to IEC 947-4-1, EN 60947-1
Max. switching frequency
without untimely tripping
TA75
DU
direct contact according to
VDE0106/part 100 (with
additional terminal shrouds
for the main terminals
3
Setting ranges
Rated operational frequencies
TA42
DU
All the terminals are
protected against direct
10 A
Hz
0 - 400
50/60
Up to 15 starts/h or 60 starts/h with 40 % on-load factor when neither
the starting current of 6 x In nor the starting time 1 s are exceeded.
see page 2.13
2.11
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
2
Technical data
TA110DU – TA450DU
Types
TA110DU
TA200DU
Standards:
(international, European)
Rated insulation voltage Ui
according to IEC 947-4-1
Rated impulse withstand voltage Uimp
according to IEC 947-4-1
Permissible ambient temperature
– for storage
– for operation
TA450DU
IEC 947-4-1, EN 60947-4-1
V
690
1000
kV
6
8
°C
°C
–40 to +70
–25 to +55 with temperature compensation (maximum values: see page 2.9)
Climatic withstand DIN 50017
Mounting positions
Humidity in alternate climate KFW, 30 cycles
On a support at an angle of ±30° in relation to the vertical plane (standard position). Other positions possible except mounting on a horizontal plane (in this case the tripping mechanism would
   be located above the bimetals).
Shock withstand
shock duration ms
at nominal Ie 15
Critical direction
of shocks A1, A2
multiples of g
12
Resistance to vibrations
(±1 mm, 50 Hz)
multiples of g
8
Mounting
– on contactor
4 x M5 screws
– separate with DB - kit
Terminals and cross-sectional areas for main conductors (motor side)
• screw terminal
A2
– with cable clamp
A1
– via tunnel connector
– flat type for lug or bar
• conductor cross-sectional area
– rigid solid or rigid stranded
– flexible with cable end
– recommended bars
mm2
mm2
mm
–
HC, M8
–
–
–
M10
16 – 35
16 – 35
12 x 3
–
–
M10
25 – 120
25 – 95
20 x 4
2 x 240
2 x 240
20 x 4...5
Terminals and cross-sectional area
for auxiliary conductors
• screw terminal (screw size)
– with cable clamp
• conductor cross-sectional area
– rigid solid or rigid stranded
– flexible with cable end
M 3.5
2 x mm2
2 x mm2
Degree of protection
0.75 - 4
0.75 - 2.5
All the terminals are protected against direct contact according to
VDE 0106/Part. 100. (with additional terminal shrouds)
Technical characteristics of auxiliary contacts for thermal O/L relays: TA25DU to TA450DU
Auxiliary contacts
normally closed N.C.
normally open N.O.
Terminal marking
95-96
97-98
VAC
500
500
Conventional thermal current (in free air) Ith
A
10
6
Rated operational current Ie, AC-15
up to 240 V
up to 440 V
up to 500 V
A
A
A
3.0
1.9
1.0
1.5
0.95
0.75
Rated operational current Ie DC-13
up to 250 V
A
0.12
0.04
Protection against short circuits
gG (gl) fuses (according to IEC 269)
S 271/S 281circuit-breaker
A
A
10
k3
6
k1
VAC
VDC
500
440
500
440
Rated operational voltage Ue
Maximum potential difference between N.C. and N.O. auxiliary contacts
2.12
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Technical data
Motor protection; Choice of protective device
2
Motor Protection — general
It is very important to choose an adequate protective device for the safety of the motor during operation and for its durability.
The efficiency of protection methods varies according to the application. The overview below will help you to choose.
There is no general rule and we are available to advise you for special applications and especially in the case of difficult starting.
Protective devices and efficiency
Protection in relation to current:
Protection in relation to temperature:
Fuses
Protective relay with
phase fault protection
Motor protection
via CUSTORAPID®
thermistor
Motor protection
via SPEM electronic
relay
SPEM
M
3~
M
3~
M
3~
M
3~
Causes of dangerous overloads for the motor windings
1 Overload with current 1.2 times the nominal current
❑
●
●
●
2 S1-S8 nominal duties
according to IEC 34-I
❑
■
●
●
3 Operation with starting,
braking, reversal in operating direction
❑
■
●
●
4 Operation with starting
rate at > 15 cycles/hour
❑
■
●
●
■ for motors with
special rotor
●
●
●
5 Locked rotor
■
●
6 Overloads due to phase failure
❑
●
7 Network undervoltage or overvoltage
❑
●
●
●
8 Fluctuation of network frequency
❑
●
●
❑
9 Ambient temperature too high
❑
●
●
❑
10 Overheating due to external
cause (i.e. overheating of bearings)
❑
❑
●
❑
11 Motor cooling disturbed ❑
❑
●
❑
12
Undercurrent protection
on drop in load
13
Protection of asymmetry:
wrong phase direction
rotation or asymmetrical load
14
Earth fault protection
15
Automatic disconnection for
auxiliary load fault
Protection efficiency:
Note: Fuses
Fuses do not protect motors against overloads. They are only used to protect installations and lines against short circuits.
❑ unsuitable
To ensure efficient protection of a motor against short circuits, it is advisable to use aM type fuses in association with thermal
OLR relays.
■ very average efficiency
For the selection of fuses or circuit-breakers, refer to the indications given in this catalogue concerning contactors on the one
hand and thermal O/L relays on the other.
● perfectly efficient
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
In general, fuse protection for direct-on-line starting must be sized as follows:
– aM fuses: choose the fuse rating immediately above the full load value of the motor current.
– gG (gI) fuses: determine the fuse rating immediately above the motor current value and choose the next highest fuse rating.
2.13
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
2
Technical data
Resistance and Joule losses per phase
Short circuit protection
Resistance and Joule losses per phase, short circuit protection
Setting range
Resistance
current
per phase
from – to
A A
mΩ
TA25DU
0.1– 0.16
0.16– 0.25
0.25– 0.4
Joule losses
per phase at
max. setting
W
85850
85150
13750
2.2
2.2
2.2
0.4– 0.63
0.63– 1.0
1.0– 1.4
5370
2190
1120
2.2
2.2
2.2
1.3– 1.8
1.7– 2.4
2.2– 3.1
670
383
229
2.2
2.2
2.2
2.8– 4.0
3.5– 5.0
4.5– 6.5
137
87.5
61
2.2
2.2
2.2
6.0– 8.5
7.5– 11
10– 14
13– 19
18– 25
24– 32
30.4
18.2
11.2
6.3
4.7
3.2
2.2
2.2
2.2
2.3
2.9
3.3
TA42DU
18– 25
22– 32
29– 42
5.5
2.89
1.84
3.43
2.91
3.24
TA75DU
18– 25
22– 32
29– 42
36– 52
45– 63
60– 80
5.5
2.89
1.84
1.3
0.936
0.615
3.43
2.91
3.24
3.51
3.72
3.94
TA80DU
29– 42
36– 52
45– 63
60– 80
1.84
1.3
0.936
0.615
3.24
3.51
3.72
3.94
2.14
1SXU000023C0202
Setting range
Resistance
current
per phase
from – to
A A
mΩ
Joule losses
per phase at
max. setting
W
TA110DU
80– 110
0.378
3.78
TA200DU
100– 135
110– 150
130– 175
150– 200
0.318
0.255
0.214
0.182
5.79
5.74
6.55
7.28
TA450DU
130– 185
165– 235
220– 310
—
—
—
2.5
2.5
2.5
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Technical data
Tripping curves
2
TA25DU
TA75DU
TA110DU/SU
TA450DU
TA-DU thermal O/L relays are 3-pole with manual or automatic resetting mode selection.
The resetting button can also be used for stopping.
Built-in auxiliary contacts are physically separate and, consequently, can be used in different circuits (control circuit/indication circuit).
Each relay is temperature compensated and ensures phase failure protection.
Protective relays up to size TA75DU are protected against direct contact via the front face. Terminal shrouds are available for TA200DU to TA450DU size relays.
The connecting terminals are delivered in open position with (+,-) pozidriv screws and screwdriver guidance. It is advisable to tighten unused terminal screws.
Thermal O/L relay tripping curves
TA25DU TA42DU, TA75DU and TA80DU 40
40
40
20
20
20
10
8
6
10
8
6
1
2 Phases
2
2 Phases
1
40
3 Phases
20
Seconds
Seconds
2 Phases
3 Phases
4
2
10
8
6
from warm state
4
from warm state
1.5
2
3
4
5
6
7
8 9 10
3 Phases
10
8
6
2 Phases
4
1
0.8
Tripping current
in multiples of the setting current
1 1.2
1.5
2
3
4
5
6
7
8 9 10
Tripping current
in multiples of the setting current
TA200DU 0.8
1 1.2
1.5
2
3
4
5
6
7
8 9 10
Tripping current
in multiples of the setting current
TA450DU
(tripping class 10A)
(tripping class 10A)
120
100
80
60
120
100
80
60
40
40
20
20
10
8
6
10
8
6
2
2 Phases
1
3 Phases
40
Triping time
from cold state
minutes
4
4
Minutes
3 Phases
2
1
1 1.2
2 Phases
1
from warm state
1
0.8
from cold state
2
20
3 Phases
2
4
40
2 Phases
3 Phases
10
8
6
Minutes
4
Tripping time
Tripping time
from cold state
2
10
8
6
from cold state
Seconds
4
Minutes
120
100
80
60
20
Tripping time
(tripping class 10A)
120
100
80
60
40
from cold state
2
2 Phase
1
40
3 Phase
20
seconds
20
Seconds
TA110DU
(tripping class 10A) 120
100
80
60
Minutes
Tripping time
(tripping class 10A) 2 Phases
10
8
6
2
2 Phase
4
3 Phases
4
10
8
6
3 Phase
2
from warm state
from warm state
1
1
0.8
1 1.2 1.5
2
3
4
5
6 7 8 9 10
Tripping current
in multiples of the setting current
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
0.8
1 1.2
1.5
2
3
4
5
6 7 8 9 10
Tripping current
as multiple of setting current
2.15
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
Technical data, Class 20 OLR
Resistance and Joule losses per phase
Short circuit protection
2
UL
UL
Resistance
per phase
Power Loss
per phase
gL/gG
A
600V
CB
A
mOhm
Thermal overload relay TA25DU trip class 20
1.3 … 1.8
10
1.7 … 2.4
16
2.2 … 3.1
16
2.8 … 4.0
20
3.5 … 5.0
25
4.5 … 6.5
25
6.0 … 8.5
32
7.5 … 11
40
10 … 14
50
13 … 19
63
18 … 25
80
24 … 32
100
Fuse/600V
K5
A
at upper
current setting
W
25
25
25
25
25
25
32
40
50
63
80
100
6
10
10
15
20
25
35
45
60
60
70
100
-
670.3
381
235.3
140.7
91.2
54.5
32.1
15.5
12
6.3
4.7
3.2
2.2
2.2
2.3
2.3
2.3
2.3
2.3
1.9
2.4
2.3
3.0
3.3
Thermal overload relay TA42DU trip class 20
18 … 25
100
22 … 32
125
29 … 42
160
160
160
160
80
100
150
80
80
80
5.5
2.89
1.84
3.43
2.91
3.24
Thermal overload relay TA75DU trip class 20
18 …25
100
22 … 32
125
29 …42
160
36 … 52
200
45 … 63
200
60 … 80
250
160
160
160
200
250
250
80
100
150
175
200
250
80
80
80
125
125
125
5.5
2.89
1.84
1.3
0.936
0.615
3.43
2.91
3.24
3.51
3.72
3.94
Thermal overload relay TA80DU trip class 20
29 … 42
160
36 … 52
200
45 … 63
200
60 … 80
250
160
200
250
250
150
175
200
250
80
125
125
150
1.84
1.3
0.936
0.615
3.24
3.51
3.72
3.94
Setting Range
from ... to
A
A
Short-circuit protection (fuses)
Type "2"
co-ordination
Type "1"
co-ordination
gL/gG
A
Type 1 co-ordination according to IEC 60947-4-1: Under short-circuit conditions, the starter shall cause no danger to persons or
installation and may not be suitable for further service without repair and replacement of parts.
Type 2 co-ordination according to IEC 60947-4-1: Under short-circuit conditions, the contactor or starter shall cause no danger
to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment.
Standard technical data, operating data and dimensions see TA...Relay Main Catalog
2.16
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Technical data, Class 20 OLR
Short-circuit ratings
2
Setting Range
Catalog number
A ... A
480V
1.3 … 1.8
1.7 … 2.4
2.2 … 3.1
2.8 … 4.0
3.5 … 5.0
4.5 … 6.5
6.0 … 8.5
7.5 … 11
10 … 14
13 … 19
18 … 25
24 … 32
18 … 25
22 …32
29 … 42
18 … 25
22 … 32
29 … 42
36 … 52
45 … 63
60 … 80
29 … 42
36 … 52
45 … 63
60 … 80
TA25DU-1.8-20
TA25DU-2.4-20
TA25DU-3.1-20
TA25DU-4.0-20
TA25DU-5.0-20
TA25DU-6.5-20
TA25DU-8.5-20
TA25DU-11-20
TA25DU-14-20
TA25DU-19-20
TA25DU-25-20
TA25DU-32-20
TA42DU-25-20
TA42DU-32-20
TA42DU-42-20
TA75DU-25-20
TA75DU-32-20
TA75DU-42-20
TA75DU-52-20
TA75DU-63-20
TA75DU-80-20
TA80DU-42-20
TA80DU-52-20
TA80DU-63-20
TA80DU-80-20
Setting Range
Catalog number
A ... A
1.3 … 1.8
1.7 … 2.4
2.2 … 3.1
2.8 … 4.0
3.5 … 5.0
4.5 … 6.5
6.0 … 8.5
7.5 … 11
10 … 14
13 … 19
18 … 25
24 … 32
18 … 25
22 …32
29 … 42
18 … 25
22 … 32
29 … 42
36 … 52
45 … 63
60 … 80
29 … 42
36 … 52
45 … 63
60 … 80
Voltage
TA25DU
TA42DU
TA75DU
TA80DU
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
TA25DU
TA42DU
TA75DU
TA80DU
10 kA
18 kA
Fuse K5
CB
Fuse K5
CB
Fuse K5
CB
6
10
10
15
20
25
35
45
60
60
70
100
80
100
150
80
100
150
175
200
250
150
175
200
250
80
80
80
80
80
80
125
125
125
80
125
125
150
6
10
10
15
20
25
35
45
60
60
70
100
80
100
150
80
100
150
175
200
250
150
175
200
250
-
6
10
10
15
20
25
35
45
60
60
70
100
150
150
200
150
150
200
250
250
250
150
175
250
250
-
Fuse K5
CB
Fuse K5
CB
Fuse K5
CB
6
10
10
15
20
25
35
45
60
60
70
100
80
100
150
80
100
150
175
200
250
150
175
200
250
80
80
80
80
80
80
125
125
125
80
125
125
150
6
10
10
15
20
25
35
45
60
60
70
100
80
100
150
80
100
150
175
200
250
150
175
200
250
-
6
10
10
15
20
25
35
45
60
60
70
100
150
150
200
150
150
150
175
250
250
150
175
250
250
-
Voltage
600V
TA25DU-1.8-20
TA25DU-2.4-20
TA25DU-3.1-20
TA25DU-4.0-20
TA25DU-5.0-20
TA25DU-6.5-20
TA25DU-8.5-20
TA25DU-11-20
TA25DU-14-20
TA25DU-19-20
TA25DU-25-20
TA25DU-32-20
TA42DU-25-20
TA42DU-32-20
TA42DU-42-20
TA75DU-25-20
TA75DU-32-20
TA75DU-42-20
TA75DU-52-20
TA75DU-63-20
TA75DU-80-20
TA80DU-42-20
TA80DU-52-20
TA80DU-63-20
TA80DU-80-20
5 kA
5 kA
10 kA
18 kA
2.17
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
2
Technical data, Class 20 OLR
Table for tripping time
Tripping times of thermal overload relays as a function of a multiple of the setting current from cold state
(tolerance +/- 20% of the tripping time).
Tripping times of thermal overload relays:
at multiple of setting current
Setting Range
3
4
from ... to
A
A
5
6
7.2
8
Tripping times in seconds
Thermal overload relays TA25DU trip class 20
1.3 … 1.8
1.7 … 2.4
2.2 … 3.1
2.8 … 4.0
3.5 … 5.0
4.5 … 6.5
6.0 … 8.5
7.5 … 11
10 … 14
13 … 19
18 … 25
24 … 32
47.1
43.3
47.5
45.6
47.8
47.4
46.1
42.3
39.4
38.1
44.4
44.4
27
25
28
27
29
28
27
25
25
21
25
27
Thermal overload relays TA42DU, TA75DU, TA80DU trip class 20
18 … 25
51.6
29
22 … 32
67.9
38
29 … 42
58.8
33
36 ... 52
59.9
34
45 ... 63
65.8
34
60 ... 80
71.9
35
2.18
1SXU000023C0202
20.3
18.9
20.8
19.8
21.2
20.3
20
17.8
16.8
13.6
16.1
17.7
15.8
14.4
16
15.3
16
15.5
15
14.1
13
10
11
13
12.7
11.9
13.1
12.5
13.2
12.5
11.7
10.9
9.9
7.4
9
9.8
11.5
10.4
11.8
11
11.8
11
10
10.5
8.5
6.2
8
8.5
20.3
26.9
22.5
22.7
22.4
23.4
15
20
16
16
16
17
11.7
14.8
12.2
12.3
12.4
13.9
10
12.5
10.3
10.5
10.5
12
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Approximate dimensions
T25DU – TA42DU
00.00
Inches
00.00
[Millimeters]
2
TA25DU
0.51
13
3.70
3.15
94
80
TA25DU32
only
0.24
6
3.70
1.73
94
44
TA25DU & DB25
TA25/32A
4.25
108
0.24
1.73
6
44
0.35
6
1.38
35
0.51
13
1.88
3.31
48
84
0.17
4.2
TA25DU & DB25/32
TA25+AB25
1.73
4.25
44
108
0.24
6
0.35
6
1.38
35
0.51
13
1.88
4.41
48
112
0.17
4.2
TA42DU
TA25/32A+AB32
0.51
13
3.54
90
0.24
6
4.35
2.13
110.5
54
TA42
TA42DU / TA75DU & DB80
5.03
127.7
2.36
60
0.24
1.97
6
50
0.51
13
3.86
2.95
98
75
0.17
4.2
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2.19
1SXU000023C0202
TA75+AB80A
al
rm ad
e
Th erlo s
Ov elay
r
2
Approximate dimensions
TA75DU – TA200DU
00.00
Inches
00.00
[Millimeters]
TA75DU
0.51
13
3.99
93
0.24
6
4.35
2.13
110.5
54
TA80DU
2.85
72.3
TA75
TOUCH SAFE COVER
0.47
12.0
3.77
0.47
1.18
12.0
30.0
0.50
12.5
95.7
2 - M4 Mtg. Slots
4.37
2.12
111.0
54.0
TA110DU
TA80 OVERLOAD RELAY
TOUCH SAFE COVER
1.48
37.5
5.44
0.24
6.0
2.52
138.1
64.0
6 - 0.21 HOLES
.61
15.5
3.14
80.0
0.24
6.0
4.73
120.1
0.07
1.7
1.98
50.2
TA200DU
TA110 OVERLOAD RELAY
2.20
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Th
Ov erm
e
a
re rloa l
lay d
s
Approximate dimensions
TA450DU
00.00
Inches
00.00
[Millimeters]
2
TA450DU
0.18
4.5
0.24
2.99
6.0
76.0
0.2 DIA.
5.0 DIA.
6.62
168.0
2.17
0.96
0.82
55.0
24.5
21.0
2
1.11
4
6
28.3
7.60
193.0
2.28
58.0
2.28
58.0
T450DU/SU
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2.21
1SXU000023C0202
al
rm ad
e
Th erlo s
Ov elay
r
Notes
2
2.22
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Electronic overload relays
E16DU – E1250DU
El
e
Ov ctro
e
n
re rloa ic
lay d
s
Electronic
Overload relays
2
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Description
• Available for starter construction with
A Line contactors and separate panel
mounting
• Designed for close couple mounting
• Separate base mounting available for
all overload relays
• E16DU Class 10, 20, & 30, field
selectable
• E200DU – E800DU Class 10, 20 & 30,
field selectable
• Stop button
• Screwdriver guide holes
• All terminal screws are available from the
front
• Single phase and phase unbalance
protection
• Isolated alarm circuit (N.O.) contact
• Ambient compensation:
-25°C to +70°C (-13oF to +158oF)
• Manual test
• Manual or automatic reset
• Factory calibrated and tested
• Wide adjustment range
• UL File No: E48139
• CSA File No: LR98336
Tripping classes of the thermal overload relays
Standard classes in IEC 947-4-1 are classes: 10 A, 10, 20, 30. The
tripping class indicates according to IEC 947-4-1 the maximum tripping
time in seconds under specified conditions of test at 7.2 times the
setting current and specifies tripping and non tripping times for 1.5 and
7.2 times the setting current. Mostly used class is 10 A.
Abstract from IEC 947-4-1
Tripping class
Max. tripping time
at 1.5 x setting current
(warm state)
Tripping time at
7.2 x setting current
(cold state)
At 1.05 x setting current
10 A
10
20
30
(s)
120
240
480
720
(s)
2 – 10
4 – 10
6 – 20
9 – 30
no tripping
2.23
1SXU000023C0202
nic
ro ad
t
ec o
El verl ys
O ela
r
Catalog number explanation
2
Reset, manual or automatic
Nominal current setting
Trip indicator test function
Stop button
Catalog number explanation
E16DU 1.0
Frame size
E16DU
E200DU
E320DU
E500DU
E800DU
2.24
1SXU000023C0202
Amp rating
1.0
200
320
500
800
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
El
e
Ov ctro
e
n
re rloa ic
lay d
s
Selection by motor horsepower
UL/CSA Starters with electronic overload
2
200V
Motor horsepower
3 Phase, 1800 RPM
230V
460V
575V
—
—
—
—
—
—
1/2
3/4
—
1
2
3
5
—
7 1/2
10
—
10
15
20
25
30
—
40
50
60
75
100
125
150
200
250
—
—
—
—
—
1/2
—
3/4
1
1 1/2
2
3
5
7 1/2
10
10
—
15
20
—
30
—
40
50
60
75
100
—
5/6
200
250
300
1/4
1/3
1/2
3/4
—
1 1/2
2
—
3
5
7 1/2
10
15
20
25
—
30
40
50
60
75
—
100
125
150
200
250
300
400
500
600
700
—
1/4,1/3
—
1/2
3/4
1
1 1/2
2
—
3
5
7 1/2
10
15
20
—
25
30
40
50
60
—
75
100
125
150
200
250
350
400
500
600
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Starter components
Open
Complete starter
Catalog number
List Price
11-2B1
Contactor
Catalog number
List Price
A9-30-10-84
11-2C1
A9-30-10-84
Overload relay
Catalog number
List Price
E16DU1.0 (0.3 - 1.0)
$ 78
E16DU2.7 (0.9-2.7)
$ 198
$ 96
11-2D1
A9-30-10-84
E16DU6.3 (2.0-6.3)
11-2E1
21-2E1
31-2E1
204
233
A9-30-10-84
A12-30-10-84
A16-30-10-84
84
102
E16DU18.9 (5.7-18.9)
41-2E1
336
A26-30-10-84
183
E45DU30 (9-30)
51-2E2
414
A30-30-10-84
252
E45DU45 (15-45)
61-2E2
71-2E1
81-2E1
91-2E1
472
544
608
649
A40-30-10-84
A50-30-11-84
A63-30-11-84
A75-30-11-84
297
330
372
413
E45DU45 (15-45)
112
E80DU80 (27-80)
188
861
A110-30-11-84
480
E140DU140 (50-140)
261
E200DU200 (60-200)
325
E320DU320 (100-320)
775
E500DU500 (150-500)
865
E800DU800 (250-800)
950
105
A1-2E1
B1-2E2
C1-2E2
D1-2E3
E1-2E3
F1-2E3
G1-70E5
H1-70E5
T1-70E8
U1-70E8
1,415
1,830
2,422
3,027
3,177
4,125
5,700
8,346
8,646
A145-30-11-84
A185-30-11-84
A210-30-11-84
A260-30-11-84
A300-30-11-84
AF400-30-11-70
AF460-30-11-70
AF580-30-11-70
AF750-30-11-70
Discount schedule TS [OZ]
825
1,290
1,635
1,815
1,875
3,120
4,425
6,900
7,200
2.25
1SXU000023C0202
nic
ro ad
t
ec o
El verl ys
O ela
r
E16DU – E1250DU
for contactors and mini contactors
2
Catalog
number
Setting
range
Trip
class
List
price
Contactor
Suffix
code
0.1-0.32A
0.3-1.0A
0.9-2.7A
2.0-6.3A
5.7-18.9A
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
$ 96
B...6-B...7 / A...9...A...16...
B...6-B...7 / A...9...A...16...
B...6-B...7 / A...9...A...16...
B...6-B...7 / A...9...A...16...
B...6-B...7 / A...9...A...16...
A1
B1
C1
D1
E1
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
10, 20, 30
105
112
188
261
325
775
865
950
2,970
A...26 ... A...40
A...26 ... A...40
A...50 ... A...75
A...95 ... A...110
A...145 ... A...185
A...210 ... A...300
AF...400 ... AF...460
AF...580 ... AF...750
AF...1350 ... AF...1650
E1
E2
E1
E1
E2
E3
E5
E8
E12
Trip Class, Selectable 10, 20, 30
E16DU
E45DU
E16DU0.32
E16DU1.0
E16DU2.7
E16DU6.3
E16DU18.9
Trip Class selectable, 10, 20, 30
E80DU
E140DU
E45DU30
E45DU45
E80DU80
E140DU140
E200DU200
E320DU320
E500DU500
E800DU800
E1250DU1250
9-30A
15-45A
27-80A
50-140A
65-200A
105-320A
170-500A
270-800A
375-1250A
NOTE: Electronic overload relays are not suitable for single-phase and DC motors.
Universal motor controller
E200DU
E320DU
Universal motor controller with thermal overload protection 0.24 - 63 A in a single device type. Bushing-type
transformer, cable cross section 25mm2 (max. diameter including insulation - 11mm). Integrated motor control
functions: Direct starting, reverse starting, star-delta starting, servo-drive functions. Diagnostic functions:
Overload phase failure, trip categories, 5, 10, 20, 30. Integrated storage of parameters and motor data. 6 digital
inputs, 3 relay outputs. Fieldbus-independent interface for connection to FBP fieldbus connectors, interface to
operating panel ACS100-PAN.
Description
E500DU
E800DU
E1250DU
UMC22-FBP.0
Contactor
Setting range
A9 - AF1650
0.63 - 63 A
Trip class
5, 10, 20, 30
Catalog number
1SAJ510000R0600
List price
$ 603
Universal Motor Controller, UMC22-FBP.0
2.26
1SXU000023C0202
Discount schedule TS [OZ]
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
El
e
Ov ctro
e
n
re rloa ic
lay d
s
Accessories
2
Mounting kits
for direct mounting on contactors AF400 – AF750
For
overload relays
On
contactor
Catalog
number
List
price
E500DU
AF400 – AF460
AF400 – AF460 w/reversing kits
DT500/AF460S
DT500/AF460L
$ 395
E800DU
AF580 – AF750
AF580 – AF750 w/reversing kits
DT800/AF750S
DT800/AF750L
415
Separate mounting kits
DB16E
For
overload relays
Catalog
number
List
price
E16DU
DB16E
$ 15
E45DU
DB45E
39
E80DU
DB80E
48
E140DU
DB140E
70
Lug kits
Wire range
6– 250 MCM
4– 400 MCM
(2) 4– 500 MCM
(2) 2/0– 500 MCM
(3) 2/0– 500 MCM
(4) 1/0– 750 MCM
Electronic
overload
Catalog
number
E200DU200
E320DU320
E320DU320
E500DU500
E800DU800
E12150DU1250
ATK185
ATK300
ATK300/2
ATK580/2HK
ATK750/3HK
ATK1350/4
List
price
$ 45
68
110
160
235
235
Terminal shrouds
Operating panel, ACS100-PAN
For
overload relays
Catalog
number
E200DU
E320DU
LT200E
LT320E
E500DU
E800DU
LT500E
LT800-E
List
price
$ 41
52
60
Accessories for universal motor controller UMC22-FBP
Operating, diagnostics and parameter setting panel for Universal Motor Controller UMC22-FBP.
Setting of motor and bus parameters.
Type
Designation
Usage with
Catalog number
ACS100-PAN
Operating panel
UMC22-FBP
1SAJ510001R0002
List price
$ 114
Accessories for operating panel ACS100-PAN
Extension cable 3 m and door mounting set IP65 (front side) for ACS100-PAN operating panel.
Type
Designation
Usage with
Catalog number
ACS100-CAB.300
Extension cable 3m with door
mounting set
List price
ACS100-PAN
1SAJ510002R0001
$ 98
ACS100-CAB.070
Extension cable 3m with front
mounting set
ACS100-PAN
1SAJ510003R0001
67
Current transformers for use with the universal motor controller UMC22-FBP
Secondary-linear transformer, 3-phase with terminal block, intended for conductors Cu 2.5mm2.
Type
Designation
KORC 4L 185 R/4
Current transformer
Current range recommended
60 - 185 A
Catalog number
KORC-4L-185R/4
List price
$ 600
Connection kit for use with the KORC-current transformers
Connection kit for applications with KORC-current transformers with A-series contactors
Type
Designation
Appropriate for contactor type
Catalog number
List price
DT 450 / A185
Connection kit
AF145 - AF185
DT450/A185
$ 225
DT 450 / A300
Connection kit
AF260 - AF300
DT450/A300
225
DT 500 / AF460L
Connection kit 1
AF400 - AF460
DT500/AF460L
395
DT 800 / AF750L
Connection kit 1
AF580 - AF750
DT800/AF750L
415
1 Connection kit for Star-Delta-Starter
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Discount schedule ABA [OF] – All products except DB16E
Discount schedule TS [OZ] – DB16E
2.27
1SXU000023C0202
nic
ro ad
t
ec o
El verl ys
O ela
r
Technical data
E16/E45/E80/E140DU
2
General technical data
E16DU
Type
E45DU30
E45DU45
E80DU80
Standards:
Approvals and certificates
IEC/EN 60 947-4-1 / IEC/EN 60 947-5-1
UL, CSA
V
Rated insulation voltage Ui V
Rated operating voltage Ue kV
Impulse withstand voltage Uimp Permissible ambient temperature
– Storage °C
– Operation
°C
Climatic resistance according to
Mounting position
Resistance to shock
Shock duration ms
multiple of g
Resistance to vibrations to EN 61373
Mounting
– by screws:
600
600
– 25 to + 70
– 25 to + 70
on request
on request (1)
on request
separate mounting with Kit for single set up by screws 4xM5
– onto contactor:
• Connection cross-sections
– single-core or stranded – flexible with wire end ferrule or direct mounting onto contactor - no kit necessary
mm2
mm2
M5/2,3 ... 2,6 Nm
M8/6 ... 6,5 Nm
1 x 2,5 ... 16
2 x 2,5 ... 16
1 x 10 ... 95
2 x 6 ... 35
1 x 2,5 ... 10
2 x 2,5 ... 10
1 x 10 ... 70
2 x 6 ... 35
Connection to aux.-contacts terminals
• Screw terminal
– with self-disengaging clamping piece
• Connection cross-sections
– single-core or stranded mm2
– flexible with wire end ferrule 600
600
6
Connection terminals and attachment type
Main contactors (load side)
• Screw terminal
– with self-disengaging clamping piece
E140DU140
M3,5/0,8 ... 1,0 Nm
1 x 1 ... 4
2 x 1 ... 4
mm2
1 x 0,75 ... 2,5
2 x 0,75 ... 2,5
Protection degree to IEC/EN 60 947-1
IP 20
IP 10
All terminals are safe from finger-touch and safe from touch
by the back of the hand to EN 50274
Technical data of the conducting paths
E16DU
Type
Number of conducting paths
Setting ranges
Tripping classes to IEC/EN 60 947-4-1
Frequency range Switching frequency
without early tripping
A ... A
Hz
0,1 ... 18,9
E45DU30
E45DU45
E80DU80
E140DU140
3
9 … 30
15 ... 45
27 ... 80
10 or selectable 10, 20, 30
50 and 60 (only for a.c. operating 3 phase)
80 ops./h with 40% if the making current does not
exceed 6 x in and starting time does not exceed 1s.
50 ... 140
Load rating of auxiliary contacts
Contact
Rated operating voltage Ue
Rated thermal continuous current
Rated operating current Ie at AC-15 230 V
at AC-15 400 V
at AC-15 500 V
at DC-13 24 V
at DC-13 60 V
at DC-13 110 V
at DC-13 220 V
Short-circuit protection fuse gG
STOTZ safety circuit-breaker: S271, S281
V
A
A
A
A
A
A
A
A
A
NC (95-96)
600
6
3
1,1
0,7
1,5
0,5
0,4
0,2
6
(2)
NO (97-98)
600
6
3
1,1
0,7
1,5
0,5
0,4
0,2
6
(2)
(1) on request
2.28
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
El
e
Ov ctro
e
n
re rloa ic
lay d
s
Technical data
E200/ 320/500/ 800/1250DU
2
General technical data
E200DU
Type
Standards:
Approvals and certificates
Rated insulation voltage Ui
Rated operating voltage Ue
Impulse withstand voltage Uimp
Permissible ambient temperature
– Storage
– Operation
Climatic resistance according to
Mounting position
Resistance to shock
Resistance to vibrations to EN 61373
Mounting
– by screws:
E320DU
V
V
kV
°C
°C
IEC 68-2-1, IEC 68-2-2
IEC 68-2-14, IEC 68-2-30
Shock duration ms
multiple of g
by screws
4 x M5
– onto contactor:
Connection terminals and attachment type
Main contuctors (load side)
• Screw terminals
– with busbar or cable lugs
Connection terminals and attachment type
Auxiliary contacts
• Screw terminal
– with self-disengaging clamping piece
– tigtening torque
• Connection cross-sections
– single-core or stranded – flexible with wire end ferrule M8
Protection degree to IEC/EN 60 947-1
E800DU
E1250DU
– 25 to + 70
– 25 to + 70
IEC 68-2-1, IEC 68-2-2,
IEC 68-2-30
any
30
5
category 1 class B
by screws
by screws
by screws
4 x M5
4 x M5
4 x M6
with DT ...
with DT ...
mounting kit
mounting kit
M10
M10
(rail order
separately)
M12
(rail order
separately)
by screws
4 x M6
with DT ...
mounting kit
M12
M3,5
1,0
Nm
mm2
mm2
E500DU
IEC/EN 60 947-4-1 / IEC/EN 60 947-5-1
UL, CSA
600
600
6
2 x 0,75 ... 4
2 x 0,75 ... 2,5
All terminals are safe from finger-touch and safe from touch
by the back of the hand to EN 50274
IP 00
Technical data of the conducting paths
Type
E200DU
Number of conducting paths
Setting ranges
Tripping classes to IEC/EN 60 947-4-1
Frequency range
Switching frequency
without early tripping
3
60 ... 200
100 ... 320
150 ... 500
250 ... 800
375 ... 1250
10, 20, 30 selectable
50 and 60 (only for a.c.operating 3 phase)
80 ops./h with 40% if the making current does not
exceed 6 x in and starting time does not exceed 1s.
A ... A
Hz
E320DU
E500DU
E800DU
E1250DU
Load rating of auxiliary contacts
E200DU, E320DU, E500DU, E800DU, E1250DU
Type
Contact
Rated operating voltage Ue
Rated thermal continuous current
at AC-15 230 V
Rated operating current Ie
at AC-15 400 V
at AC-15 500 V
at DC-13 24 V
at DC-13 60 V
at DC-13 110 V
at DC-13 220 V
Short-circuit protection fuse
gG
STOTZ safety circuit-breaker: S271, S281
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
V
A
A
A
A
A
A
A
A
A
NC (95-96)
600
6
3
1,1
0,7
1,5
0,5
0,4
0,2
6
(1)
NO (97-98)
600
6
3
1,1
0,7
1,5
0,5
0,4
0,2
6
(1)
2.29
1SXU000023C0202
nic
ro ad
t
ec o
El verl ys
O ela
r
2
Technical data
Universal motor controller
UMC22-FBP
General technical data
Type
UMC22-FBP
Rated operating voltage Ue (three-phase system) V AC/Hz
max. 690/50
Rated operating current range
A
0.24 ... 63
Trip classes
5, 10, 20, 30
Short-circuit-protection
separate fuses on power line side
Supply voltage
V DC
19.2 ... 31.2, including ripple
Supply current
mA
max. 130 (at 18 ... 30 V DC)
Total device power dissipation
W
max. 3.1 (at 24 V DC)
LEDs on front
LED 1, green: device ready for operation
LED 2, yellow: motor current > 33 % of Is
LED 3, red: fault (trip, device fault, etc.)
Mechanical relay contact lifetime 500 000 switching cycles
Electrical lifetime 250 V AC / 0.5 A 100 000 switching cycles
250 V AC / 1.5 A 50 000 switching cycles
mm2 max. 2.5, max. 2 x 1.5
Terminal conductor cross section Current transformer bushing holes Internal clearance and creepage distances
mm Mounting Dimensions (W x H x D)
Net weight 11 mm Ø (25 mm“)
> 5.5 (safety insulation up to 250 V AC)
on DIN rail (EN 50022-35) or wall mounting with 4 screws M4
mm 70 x 105 x 110 (incl. FieldBusPlug and Control Panel)
kg
0.39 (current transf. + control unit)
Degree of protection
Storage temperature range °C
Operating temperature range
°C
IP 20
-25...+70
0...+55
Technical description Order Code 2CDC 135 004 D02xx
FieldBusPlug connection
see FBP catalogue
Digital inputs
Number of digital inputs 6 (DI0 ... DI5)
Power supply for digital inputs
1-Signal (range including ripple)
18 … 30V, 70 mA
+13 V ... +31,2 V
0-Signal (range including ripple) -31,2 V ... +13 V
Input current per channel (24 V DC) typ. 6.0 mA
Input resistor to 0 V 3.9 kOhm
Line length unshielded
Line length shielded 4
1
3
max. 600 m
max. 1000 m
Digital outputs
Number of digital relay outputs
3 (DO0...DO2)
Grouping of contacts mon
3 contacts with 1 com-
2
5
Switching capacity per relay contact
AC15: DC13: 120 V AC,
max. 3 A 240 V AC,
max. 1.5 A
24 V DC, max. 0.1 A
125 V DC, max. 0.22 A
250 V DC, max. 0.11 A
max. load for all contacts
4 A (terminal 5 or 6)
min load for switching signals
12 V, 1 W or 1 VA
PTC Input - direct connection of PTC sensors from the motor
Conductor holes through the current transformers max. 25 mm2
(max. diameter incl. insulation 11 mm)
2.30
1SXU000023C0202
6
Parameter Options:
1 = Control function
2 = check back via aux.-contact
3 = Fault output, e.g. to lamp
4 = PTC Input
5 = digital inputs for control signals
6 = Connections for earth fault monitor
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Technical data
Terms and technical definitions
El
e
Ov ctro
e
n
re rloa ic
lay d
s
2
Altitude
Characterizes the place of use. It is expressed in meters above sea
level.
Circuits
• Auxiliary circuit – all the conductive parts of a contactor designed
to be inserted in a different circuit from the main circuit and the
contactor control circuits.
• Control circuit – all the conductive parts of a contactor (other
than the main circuit and the auxiliary circuit) used to control the
contactor’s closing operation or opening operation or both.
• Main circuit – all the conductive parts of a contactor designed to
be inserted in the circuit that it controls.
Insulation Class according to NFC 20 040 and VDE 0110
Characterizes adaptation of the devices to ambient temperature and
operating conditions. For given clearances and creepage distances,
a device will have different insulating voltages depending on
insulation classes A, B, C & D. Class C corresponds to most industrial
applications. The devices in this catalog belong to Class C.
Coordination of equipment protections during a short circuit
This is the addition upstream of the contactor and thermal overload
relay of a short circuit (SCPD) protection device such as a circuit
breaker, a fuse with a high breaking capacity or other fuses.
IEC publication 947-4-1 defines coordination Types 1 & 2:
• Type 1 – Coordination requires that, in the event of a short circuit,
the contactor or starter does not endanger persons or installations
and will not be able to operate without being repaired or parts being
replaced.
• Type 2 – Coordination requires that, in short circuit conditions, the
contactor or starter does not endanger persons or installations and
will be able to operate afterwards. The risk of contacts being welded
is acceptable. In this case, the manufacturer must stipulate the
measures to be taken with respect to maintenance of the equipment.
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Rated operational current Ie
Current rated by the manufacturer. It is mainly based on the rated
operational voltage Ue, the rated frequency, the utilization category,
the rated duty and the type of protective enclosure, if necessary.
Conventional free air thermal current Ith
Current that the contactor can withstand in free air for a duty time of 8
hours without the temperature rise of its various parts exceeding the
maximum values given by the standard.
Cycle time
Cycle time is the sum of the current flow time and the no-current time
for given cycle.
Electrical durability
Number of on-load operations that the contactor is able to carry out; it
depends on the utilization category.
Mechanical durability
Number of no-current operations that a contactor is able to carry out.
Load factor
Ratio of the on-load operating time to the total cycle time x 100.
Switching frequency
Number of switching cycles per hour.
2.31
1SXU000023C0202
nic
ro ad
t
ec o
El verl ys
O ela
r
E16DU
E16DU + DB16E
69.5
65.2
9.3
64.5
14.8
1.2
2.4
36.3
82.7
4.4
50
E45DU
37.5
53
57
14 14
44.6
5.5
68.5
E2327D
44.4
5.65
41.7
35.7
14
E2326D
10.3
8.2
91.1
9.3
74.6
2
Approximate dimensions
E16DU – E140DU
E80DU
E140DU
2.32
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Approximate dimensions
E200DU – E320DU
El
e
Ov ctro
e
n
re rloa ic
lay d
s
2
E200DU
E320DU
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2.33
1SXU000023C0202
nic
ro ad
t
ec o
El verl ys
O ela
r
2
Approximate dimensions
E500DU – E800DU
E1250DU + AF1350 / AF1650
E500DU
AF1350 / AF1650 + E1250DU
E800DU
Drilling plan
(dimensions in mm)
2.34
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Approximate dimensions
Starter combination with contactor and terminal shroud
El
e
Ov ctro
e
n
re rloa ic
lay d
s
2
AF400 / AF460 + E500DU + DT500 / AF460S + LT500
Drilling plan
AF400 / AF460 + E500DU + DT500 / AF460L
Drilling plan
(dimensions in mm)
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
2.35
1SXU000023C0202
nic
ro ad
t
ec o
El verl ys
O ela
r
2
Approximate dimensions
Starter combination with contactor and terminal shroud
AF580 / AF750 + E800DU + DT800 / AF750S + LT800
Drilling plan
AF580 / AF750 + E800DU + DT800 / AF750L
Drilling plan
(dimensions in mm)
2.36
1SXU000023C0202
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb.us/lowvoltage
Download