SYMBOL DESIGNATIONS SYMBOL DESIGNATIONS SYMBOL SCHEDULE NOTES A # B. MOUNTING HEIGHTS INDICATED ARE STANDARD. DIMENSIONAL NUMBERS INDICATED AT DEVICES SHALL OVERRIDE THESE STANDARDS. MOUNTED HEIGHTS ARE TO THE CENTER OF THE DEVICE, UNLESS NOTED OTHERWISE. b D. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION. LIGHT FIXTURE ID - REFER TO LT FIXT SCHEDULE (FIXT SCHEDULE OVERRIDES SYMBOL ABBREVIATION) A - INDICATES LIGHT FIXTURE TYPE # - INDICATES CIRCUIT NUMBER b - INDICATES SWITCHING TROFFER TYPE LIGHT FIXTURE, SIZE AS INDICATED CEILING MOUNT 48" 2 DOUBLE POLE TOGGLE SWITCH 48" 3 THREE WAY TOGGLE SWITCH 48" 4 FOUR WAY TOGGLE SWITCH 48" a TOGGLE SWITCH - "a" INDICATES SWITCHING 48" PILOT LIGHT TOGGLE SWITCH 48" ILLUMINATED TOGGLE - TOGGLE SWITCH 48" K KEYED SWITCH 48" MC MOMENTARY CONTACT TOGGLE SWITCH 48" TS TIMER SWITCH 48" MUTLI SWITCH, MULTI GANG BOX 48" DIMMER SWITCH (# = WATTAGE) 48" DOWNLIGHT CLG FIXT, RECESSED OR SURFACE MOUNT HEAVY DASHED LINE WEIGHT INDICATES EXISTING ITEM TO BE REMOVED. # CEILING WALL WASH FIXT, AIMED AS INDICATED SMALL MOUNT FIXTURE OR SCONCE LIGHT SOLID LINE WEIGHT INDICATES EXISTING ITEM TO REMAIN. HEAVY SOLID LINE WEIGHT INDICATES NEW ITEM OR NEW LOCATION. REMOVE EXISTING ITEM D VERIFY LINEAR RECESSED , LENGTH AS INDICATED VERIFY LINEAR WALL MOUNT FIXT, LENGTH AS INDICATED VERIFY S EXISTING ITEM TO REMAIN NL NEW LOCATION FOR RELOCATED ITEM OCCUPANCY SENSOR WALL SWITCH PHOTO ELECTRIC CELL UNDER CABINET FIXTURE, LENGTH AS INDICATED TC TIME CLOCK 60" TRACK FIXTURE, NUMBER OF HEADS AS INDICATED C CONTACTOR 60" R RELAY EMERGENCY BATTERY LIGHT - WALL CLG MNT VERIFY EXIT LIGHT, FILLED QUADRANT INDICATES FACES WALL/CEILING MOUNT VERIFY KEYNOTE MISCELLANEOUS NOTE # RACEWAYS CONDUIT CONCEALED IN CEILING OR WALLS # CONDUIT EXPOSED ON THE CEILING OR WALLS CONDUIT BURIED UNDERGROUND (# = DEPTH) MMS P J I SMOKE DETECTOR (P=PHOTOELEC, I=IONIZATION) B-T BEAM DET (B-T=TRANSMITTER, B-R=RECEIVER) RS F F RS TRANSFORMER VERIFY RL F F MOTOR OR MOTOR CONNECTION VERIFY F MOTOR CONTROLLER, STARTER OF VFD VERIFY F F VERIFY F VERIFY MANUAL MOTOR STARTER SW W/THERM OVERLOAD 18" QUADPLEX RECEPTACLE - WALL MOUNT 18" CONDUIT WITH BREAK OR CONTINUATION EMERGENCY QUADPLEX RECEPTACLE - WALL MOUNT 18" CIRCUIT HOME RUN - L1 INDICATES PANEL - NUMBER GFI RECEPTACLE, DUPLEX/QUADPLEX - WALL MOUNT 18" SPECIAL PURPOSE RECEPTACLE - WALL/CLG MNT 18" CONDUCTOR COUNT - UNLESS NOTED OTHERWISE / SHORT HASH INDICATES 1#12 LINE / LONG HASH INDICATES 1#12 NEUTRAL / HASH W/DOT INDICATES 1#12 GROUND EMERGENCY SPECIAL PURPOSE RECEPT - WALL/CLG 18" MM CM SD DH VERIFY # S WIREWAY, DUCT BANK, OR FLOOR DUCT AS NOTED MONITOR MODULE CONTROL MODULE FIRE/SMOKE DAMPER CONNECTION DOOR HOLD OR DOOR HOLD CONNECTION VERIFY BELL - WALL/CEILING MOUNT 82" F F BELL/STROBE - WALL/CLG MOUNT (# = CANDELA) 82" F F CHIME - WALL/CEILING MOUNT 82" F CHIME/STROBE - WALL/CLG MOUNT (# = CANDELA) 82" F HORN - WALL/CEILING MOUNT 82" F HORN/STROBE - WALL/CLG MOUNT (# = CANDELA) 82" # # F GROUND REFERENCE BUS - AS NOTED - WALL/CLG MNT TAMPER SWITCH F # F # S FLOW SWITCH 82" F S 72" STROBE - WALL/CLG MNT (# = CANDELA) F POWER POLE - DEVICES AS INDICATED REMOTE INDICATOR LAMP - WALL/CLG MOUNT F # FLOOR BOX - DEVICES AS INDICATED 72" 48" # F # REMOTE STATION - WALL/CLG MOUNT FIREMAN'S STATION - WALL MOUNT FS # # JUNCTION BOX - WALL/CEILING MOUNT RL TS F VERIFY COMBINATION SMOKE DETECTOR AND ALARM FS F VERIFY CONDUIT WITH BUSHED END SA F VERIFY 18" G F DUCT MOUNTED PHOTOELECTRIC DETECTOR F EMERGENCY DUPLEX RECEPT - WALL/CLG MNT G P HEAT DETECTOR (#=FIXED TEMP, R=RATE OF RISE) F CONDUIT WITH BEND UP PULL BOX, SIZE AS NOTED B 48" 48" F VERIFY DUPLEX RECEPTACLE - WALL/CEILING MOUNT P F MANUAL PULL STATION EQUIPMENT CABINET MOTOR RATED TOGGLE CONDUIT WITH BEND DOWN L1 1.3 VERIFY R VERIFY DISCONNECT SWITCH MR F # BRANCH CIRCUIT PANEL COMBINATION STARTER & DISCONNECT SWITCH CONDUIT CONCEALED IN THE FLOOR OR BELOW UG F POWER ELEC EQUIP CONNECTION TAG - SEE EQUIP SCHEDULE # VERIFY PUSH BUTTON STATION - BUTTONS AS INDICATED SITE LIGHTING POLE TOP FIXT, ROUND/ RECT HEAD FEEDER SIZE TAG - SEE POWER RISER SCHEDULE #/A 48" PC SITE LIGHTING POLE FIXT, ROUND/RECTANGLE HEAD - NUMBER OF HEADS INDICATED EQUIPMENT IDENTIFICATION TAG - SEE EQUIP SCHEDULES # Sheet Number Sheet Name E000 ELECTRICAL TITLE SHEET ED001 ELECTRICAL SITE PLAN - DEMOLITION E001 ELECTRICAL SITE PLAN - NEW ED100 LOWER LEVEL DEMOLITION PLAN ED101 FIRST LEVEL DEMOLITION PLAN ED102 SECOND LEVEL DEMOLITION PLAN ED103 THIRD LEVEL DEMOLITION PLAN E100 LOWER LEVEL LIGHTING PLAN E101 FIRST LEVEL LIGHTING PLAN E102 SECOND LEVEL LIGHTING PLAN E103 THIRD LEVEL LIGHTING PLAN E200 LOWER LEVEL POWER PLAN E201 FIRST LEVEL POWER PLAN E202 SECOND LEVEL POWER PLAN E203 THIRD LEVEL POWER PLAN E204 ROOF POWER PLAN E300 LOWER LEVEL SYSTEMS PLAN E301 FIRST LEVEL SYSTEMS PLAN E302 SECOND LEVEL SYSTEMS PLAN E303 THIRD LEVEL SYSTEMS PLAN E404 LIGHTNING PROTECTION PLAN E405 LIGHTNING PROTECTION DETAILS E500 ELECTRICAL RISER DIAGRAM E600 ELECTRICAL SCHEDULES E601 ELECTRICAL SCHEDULES E602 PANEL SCHEDULES E603 PANEL SCHEDULES E604 PANEL SCHEDULES E605 PANEL SCHEDULES E606 PANEL SCHEDULES E607 PANEL SCHEDULES E608 PANEL SCHEDULES E609 PANEL SCHEDULES E700 LIGHTING DETAILS E701 ELECTRICAL DETAILS E702 ELECTRICAL DETAILS E703 FIRE ALARM DETAILS M901 PLUMBING ELECTRICAL SCHEDULES M902 MECHANICAL ELECTRICAL SCHEDULES M903 MECHANICAL ELECTRICAL SCHEDULES M904 MECHANICAL ELECTRICAL SCHEDULES Grand total: 41 FIRE ALARM NOTES & TAGS xx ## Sheet List OCCUPANCY SENSOR - CLG MOUNT OS REMOVE EXISTING ITEM AND RELOCATE AS INDICATED X J SINGLE POLE TOGGLE SWITCH 4 CHANNEL OR INDUSTRIAL, LENGTH AS INDICATED GENERAL MTG HT DESIGNATIONS SWITCHES AND CONTROLS LIGHT FIXTURE CIRCUIT TYPE - NO HATCH INDICATES NORMAL CIRCUIT - ANGLED HATCH INDICATES CRITICAL CIRCUIT - SOLID HATCH INDICATES LIFE SAFETY CIRCUIT C. MOUNTING HEIGHTS INDICATED ARE FOR STUD WALL CONSTRUCTION. WHEN BLOCK OR BRICK CONSTRUCTION IS USED, ADJUST MOUNTING HEIGHTS TO ALIGN DEVICE PLATES WITH RUNNING JOINT. RL SYMBOL LIGHTING A. THESE SYMBOLS COMPRISE A STANDARD LIST, NOT ALL SYMBOLS MAY APPEAR ON THESE DRAWINGS. R MTG HT F S F SPEAKER - WALL/CEILING MOUNT 82" F # S F SPEAKER/STROBE - WALL/CLG MOUNT(# = CANDELA) 82" # S AF COMBINATION FIRE ALARM/MASS NOTIFICATION: SPEAKER/STROBE - WALL/CLG MOUNT(# = CANDELA) 82" AF FACP CABLE TRAY, TYPE/SIZE AS INDICATED FIRE ALARM CONTROL PANEL - WALL MOUNT RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number 50358 Date 07/24/15 Project For STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 VERIFY ELECTRICAL ABBREVIATIONS A, AMP AMPERES C CONDUIT EWC ELECTRIC WATER COOLER MC MOMENTARY CONTACT PE PNEUMATIC ELECTRIC TSTAT THERMOSTAT AA AUDIBLE ALARM CAB CABINET F FUSE OR FUSED MCB MAIN CIRCUIT BREAKER PF POWER FACTOR TYP TYPICAL AC ABOVE COUNTER CB CIRCUIT BREAKER FA FIRE ALARM MLO MAIN LUG ONLY PH PHASE UC UNDER COUNTER Drawn By ADD ADDENDUM CCTV CLOSED CIRCUIT TV FACP FIRE ALARM CONTROL PANEL MRS MOTOR RATED SWITCH PNL PANEL UG UNDERGROUND Checked By AFC AVAILABLE FAULT CURRENT CKT CIRCUIT FSD FIRE-SMOKE DAMPER MSB MAIN SWITCHBOARD PRI PRIMARY UH UNIT HEATER AFCI ARC FAULT CIRCUIT INTERRUPTER CU COPPER FV FILM VIEWER MT EMPTY RECEPT RECEPTACLE UNO UNLESS NOTED OTHERWISE AFF ABOVE FINISHED FLOOR DN DOWN G, GND GROUND NC NORMALLY CLOSED REFG REFRIGERATOR V VOLT AHU AIR HANDLING UNIT EC ELECTRICAL CONTRACTOR GFI GROUND FAULT INTERRUPTER NEC NATIONAL ELECTRICAL CODE RTU ROOF TOP UNIT VA VOLT-AMP AL ALUMINUM ELEC ELECTRIC OR ELECTRICAL IG ISOLATED GROUND NIC NOT IN CONTRACT SEC SECONDARY VAC VOLTS ALTERNATING CURRENT ANT ANTENNA EM EMERGENCY JBOX JUNCTION BOX NO NORMALLY OPEN SPKR SPEAKER VDC VOLTS DIRECT CURRENT ATS AUTOMATIC TRANSFER SWITCH EMT ELECTRICAL METALLIC TUBING KV KILOVOLT NTS NOT TO SCALE SW SWITCH W WATT OR WIRE BAS BUILDING AUTOMATION SYSTEM ENCL ENCLOSURE KVA KILOVOLT-AMP OC ON CENTER SWBD SWITCHBOARD WP WEATHERPROOF BFC BELOW FINISHED CEILING EP ELECTRIC PNEUMATIC KW KILOWATT PB PULL BOX TEL TELEPHONE XFMR TRANSFORMER BPS BOLTED PRESSURE SWITCH EPO EMERGENCY POWER OFF KWH KILOWATT-HOUR PB PUSHBUTTON TR TAMPER RESISTANT Project No. 2263.001.00 MK JL Date 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description ELECTRICAL TITLE SHEET C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:01:08 PM E000 GENERAL DEMOLITION NOTES: A. DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID SUBMITTAL. B. A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER. C. INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED. D. PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND FEDERAL REGULATIONS. E. IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION. 1 F E D.9 F. MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE TEMPORARY PROVISIONS. G. DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION. DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS. H. DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION. I. EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND BRANCH CIRCUITING. J. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING FOR ELECTRICAL WORK. K. PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS. SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER SYSTEMS. 1 1 L. D C.9 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES AND JUNCTION BOXES. M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE. N. C.3 RSP Architects O. MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF PROJECT. PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS REMAINING AT END OF PROJECT. C STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 B.8 KEY NOTES: B.2 1 IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES, ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION BOXES, SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION DEVICES, CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.), MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS, UNLESS NOTED OTHERWISE. 2 DEMOLISH EXISTING PANELBOARD. 3 REMOVE EXTERIOR WALL MOUNTED LIGHT FIXTURE. TURN LIGHT FIXTURE OVER TO OWNER. B 2 A 1 Project No. Drawn By AA 0 1 2 3 3 3 4 4.2 4.5 4.8 5 CL MMK Checked By Date 3 2263.001.00 5.55.6 66.2 6.7 7 3 8 9 10 11 JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions FIRST FLOOR DEMOLITION PLAN 2 1/8" = 1'-0" No. Date Description FIRST LEVEL DEMOLITION PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:05:53 PM ED101 GENERAL NOTES: 2 A. DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND ELECTRICAL DRAWINGS MUST BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID SUBMITTAL. B. A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY OF EXISTING SITE CONDITIONS, HOWEVER, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES WHICH OCCUR UNDERGROUND. AS CONSTRUCTION PROGRESSES, PERFORM MINOR FIELD MODIFICATIONS AND ADDITIONS AS NECESSARY TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR COMPLETION OF NEW WORK WITH NO ADDITIONAL COST TO THE OWNER. C. SEQUENCE ALL WORK IN ACCORDANCE WITH THE CONSTRUCTION MANAGERS REQUIREMENTS. D. MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE OPERATIONS OF SYSTEMS. PERMANENTLY RE-FEED EXISTING BRANCH CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE TEMPORARY PROVISIONS. J O-B1B /17 1 LCP-B1/11 RIVERVIEW AA4 N-B1/ 13 E. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING FOR ELECTRICAL WORK. F. WARNING: VERIFY LOCATIONS OF UNDERGROUND UTILITIES PRIOR TO ANY SITE WORK. UTILIZE A SURVEY SERVICE TO PROVIDE ADDITIONAL INFORMATION REGARDING EXISTING ELECTRICAL AND COMMUNICATION CABLING LOCATED ON THIS SITE. G. SEE LIGHTING PLANS FOR BUILDING MOUNTED LIGHTING. RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 AA2 N-B1/ 13 GEN 13' - 2" LCP-B1/10 XFMR 7' - 11 27/32" 8' - 0" 2' - 0" 8' - 0" MAIN CIRCUIT BREAKER ENCLOSURE KEY NOTES: 2 J O-B1B /12 SEE ONE-LINE DIAGRAM FOR SIZES, AND REFER TO SHEET 200 FOR PROPOSED CONDUIT ROUTING 1 NEW ELECTRICAL FEED TO SITE LIGHTING. 2 REFEED EXISTING BLUE LIGHT CALL STATION WITH INDICATED CIRCUIT. PROVIDE 1-1/4"C FROM DATA ROOM IN BASEMENT. 3 NEW CONCRETE ENCLASED DUCT BANK FOR MEDIUM VOLTAGE DISTRIBUTION FROM SWITCH TO NEW TRANSFORMER LOCATION. REFER TO RISER DIAGRAM FOR CONDUIT AND FEEDER SIZE. FEEDER SHALL NOT BE ROUTED IN EXISTING TUNNEL. 4 3' - 7" EASTMAN 3 REFER TO LIGHTING CONTROL SEQUENCE SCHEDULE FOR ADDITIONAL INFORMATION ON EXTERIOR LIGHTING CONTROLS. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number 50358 Date 07/24/15 Project For EXISTING MEDIUM VOLTAGE TRANSFORMER SHALL REMAIN TO FEED RIVERVIEW EXISTING MV FEEDERS IN TUNNEL EXISTING S&C PME-9 PAD MOUNTED SWITCH SHALL REMAIN STUDENT HEALTH AND ACADEMIC RENOVATION LCP-B1/10 AA2 N-B1/ 13 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 LCP-B1/12 LCP-B1/9 WP NR-B1B /1 AA5 N-B1/ 9 LCP-B1/9 NR-B1B /1 WP 4 LCP-B1/9 LC 08 AA5 N-B1/ 9 AA5 N-B1/ 9 NR-B1B /3 WP AA5 N-B1/ 9 WP NR-B1B /3 BB4 N-B1/ 11 LCP-B1/9 2 J O-B1A /8 1ST AVENUE SOUTH 1ST AVENUE SOUTH Project No. 2263.001.00 Drawn By MMK Checked By Date ELECTRICAL SITE PLAN - NEW 1 1/16" = 1'-0" FIXTURE DESCRIPTION TYPE LAMPS/ LIGHT ENGINE BALLAST/ DRIVER VOLTAGE MAX VA CONTROL MEDIA (LENS/LOUVER) MANUFACTURER SERIES NUMBERS DESCRIPTION POLE LENGTH POLE SHAPE © Copyright RSP Architects 2015. All rights reserved. BASE DESCRIPTION POLE DESCRIPTION MOUNTING 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. SITE LIGHTING FIXTURE SCHEDULE LETTER JL POLE POLE MATERIAL COLOR/FINISH FIXTURE MOUNT SUPPORTS SUPPORTS INTEGRAL CCTV FLAG OR DUPLEX VIBRATION CAMERA BANNER RECEPTACLE DAMPERS FOUNDATION BASE HEIGHT BASE HEIGHT ABOVE BELOW GRADE GRADE Revisions BASE DIAMETER VERTICAL BARS TIES NOTES No. AA2 AREA POLE LIGHT ONE HEAD RECTANG. ARM LED 4000K 7700 LUMENS MIN ELECTRONIC 120/277V 97W MAX TYPE II DISTRIBUTION BEACON #VPS SERIES NO SUBSTITUTIONS DIE CAST ALUMINUM HOUSING. HINGED DOOR. BRONZE TEXTURED FINISH. 12' ROUND STEEL BRONZE ARM NO NO YES NO CONCRETE BASE 4" 4'-6" 24" #4 #3 1 AA4 AREA POLE LIGHT ONE HEAD RECTANG. ARM LED 4000K 7700 LUMENS MIN ELECTRONIC 120/277V 97W MAX TYPE IV DISTRIBUTION BEACON #VPS SERIES NO SUBSTITUTIONS DIE CAST ALUMINUM HOUSING. HINGED DOOR. BRONZE TEXTURED FINISH. 12' ROUND STEEL BRONZE ARM NO NO YES NO CONCRETE BASE 4" 4'-6" 24" #4 #3 1 AA5 AREA POLE LIGHT ONE HEAD RECTANG. ARM LED 4000K 7700 LUMENS MIN ELECTRONIC 120/277V 97W MAX TYPE V RECTANGULAR DISTRIBUTION BEACON #VPS SERIES NO SUBSTITUTIONS DIE CAST ALUMINUM HOUSING. HINGED DOOR. BRONZE TEXTURED FINISH. 12' ROUND STEEL BRONZE ARM NO NO YES NO CONCRETE BASE 4" 4'-6" 24" #4 #3 1 BB4 AREA POLE LIGHT TWO HEADS RECTANG. ARM LED 4000K 14400 LUMENS MIN ELECTRONIC 120/277V 194W MAX TYPE IV DISTRIBUTION BEACON #VPS SERIES NO SUBSTITUTIONS DIE CAST ALUMINUM HOUSING. HINGED DOOR. BRONZE TEXTURED FINISH. 22' ROUND TAPERED STEEL BRONZE ARM NO NO NO YES CONCRETE BASE 3' 6' 24" #4 #3 1 Date Description GENERAL NOTES: A. SEE SPECIFICATIONS FOR ADDITIONAL LIGHT FIXTURE REQUIREMENTS. B. MINIMUM LUMENS LISTED FOR SOLID STATE LIGHT FIXTURES ARE DELIVERED LUMENS BASED ON PHOTOMETRIC TESTING COMPLETED IN ACCORDANCE WITH IES LM-79 STANDARDS. NOTES: 1. OWNER'S CAMPUS STANDARD EXTERIOR LIGHT FIXTURE MANUFACTURER, NO SUBSTITUTIONS. C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:06:20 PM ELECTRICAL SITE PLAN - NEW E001 GENERAL NOTES: A. DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND ELECTRICAL DRAWINGS MUST BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID SUBMITTAL. B. A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY OF EXISTING SITE CONDITIONS, HOWEVER, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES WHICH OCCUR UNDERGROUND. AS CONSTRUCTION PROGRESSES, PERFORM MINOR FIELD MODIFICATIONS AND ADDITIONS AS NECESSARY TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR COMPLETION OF NEW WORK WITH NO ADDITIONAL COST TO THE OWNER. C. SEQUENCE ALL WORK IN ACCORDANCE WITH THE CONSTRUCTION MANAGERS REQUIREMENTS. D. MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE OPERATIONS OF SYSTEMS. PERMANENTLY RE-FEED EXISTING BRANCH CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE TEMPORARY PROVISIONS. RSP Architects E. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING FOR ELECTRICAL WORK. F. WARNING: VERIFY LOCATIONS OF UNDERGROUND UTILITIES PRIOR TO ANY SITE WORK. UTILIZE A SURVEY SERVICE TO PROVIDE ADDITIONAL INFORMATION REGARDING EXISTING ELECTRICAL AND COMMUNICATION CABLING LOCATED ON THIS SITE. G. SEE LIGHTING PLANS FOR BUILDING MOUNTED LIGHTING. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 2 KEY NOTES: 1 REMOVE LIGHT FIXTURE AND TURN OVER TO OWNER. 2 DEMOLISH ELECTRICAL FEED TO SITE LIGHTING. FIXTURES TO REMAIN AND BE REFED. SEE NEW ELECTRICAL SITE PLAN FOR ADDITIONAL INFORMATION. TEMPORARILY REFEED DURING CONSTRUCTION TO INSURE THAT WALKWAY LIGHTS ARE ON DURING CONSTRUCTION. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For 1 STUDENT HEALTH AND ACADEMIC RENOVATION EXISTING MV FEEDERS DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 EXISTING MEDIUM VOLTAGE TRANSFORMER SHALL REMAIN TO FEED RIVERVIEW EXISTING PMH SWITCH SHALL REMAIN 1 1 1 Project No. Drawn By 2263.001.00 MMK Checked By Date 1ST AVENUE SOUTH 1ST AVENUE SOUTH JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. 1 Date Description ELECTRICAL SITE PLAN - DEMOLITION 1/16" = 1'-0" ELECTRICAL SITE PLAN - DEMOLITION C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:02:14 PM ED001 GENERAL DEMOLITION NOTES: A. DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID SUBMITTAL. B. A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER. C. INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED. D. PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND FEDERAL REGULATIONS. E. IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION. 1 F DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION. DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS. H. DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION. I. EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND BRANCH CIRCUITING. J. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING FOR ELECTRICAL WORK. Signature K. PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS. SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER SYSTEMS. Registration Number I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Date James A. LeClaire 50358 07/24/15 Project For SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES AND JUNCTION BOXES. L. M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE. N. C.3 Dunham Job #: 415134 G. 1 612.677.7100 612.677.7499 fax www.rsparch.com Consultants MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE TEMPORARY PROVISIONS. 1 D C.9 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 F. 2 E D.9 RSP Architects O. MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF PROJECT. PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS REMAINING AT END OF PROJECT. STUDENT HEALTH AND ACADEMIC RENOVATION C DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 B.8 2 3 4 B.2 5 B A 1 KEY NOTES: 1 IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES, ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION BOXES, SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION DEVICES, CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.), MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS, UNLESS NOTED OTHERWISE. 2 REMOVE EXISTING ELECTRICAL DISTRIBUTION. TURN EQUIPMENT OVER TO OWNER. 3 REMOVE EXISTING FACP. 4 EXISTING 800A DISCONNECT FEEDING RIVERVIEW TO REMAIN. 5 REMOVE EXISTING 600A DISCONNECT SERVING EASTMAN HALL. UTILIZE DISCONNECT FOR TEMPORARY POWER DURING CONSTRUCTION. Project No. 2263.001.00 Drawn By MMK Checked By Date AA 0 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions LOWER LEVEL DEMOLITION PLAN 1 1/8" = 1'-0" No. Date Description LOWER LEVEL DEMOLITION PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:05:43 PM ED100 GENERAL DEMOLITION NOTES: A. DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID SUBMITTAL. B. A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER. C. INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED. D. PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND FEDERAL REGULATIONS. E. IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION. 1 F E D.9 DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION. DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS. H. DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION. I. EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND BRANCH CIRCUITING. J. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING FOR ELECTRICAL WORK. Signature K. PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS. SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER SYSTEMS. Registration Number I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Date James A. LeClaire 50358 07/24/15 Project For SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES AND JUNCTION BOXES. M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE. N. C.3 Dunham Job #: 415134 G. L. 612.677.7100 612.677.7499 fax www.rsparch.com Consultants MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE TEMPORARY PROVISIONS. 2 D C.9 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 F. 1 2 RSP Architects O. MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF PROJECT. PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS REMAINING AT END OF PROJECT. STUDENT HEALTH AND ACADEMIC RENOVATION C DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 B.8 KEY NOTES: 2 B.2 1 IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES, ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION BOXES, SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION DEVICES, CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.), MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS, UNLESS NOTED OTHERWISE. 2 DEMOLISH EXISTING PANELBOARD. B 1 A Project No. 2263.001.00 Drawn By MMK 1 Checked By Date AA 0 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 SE COND FLOOR DEMOLITION PLAN 1/8" = 1'-0" Revisions No. Date Description SECOND LEVEL DEMOLITION PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:06:02 PM ED102 GENERAL DEMOLITION NOTES: A. DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID SUBMITTAL. B. A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER. C. INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED. D. PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND FEDERAL REGULATIONS. E. IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION. 1 F E D.9 F. MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE TEMPORARY PROVISIONS. G. DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION. DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS. H. DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION. I. EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND BRANCH CIRCUITING. J. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING FOR ELECTRICAL WORK. K. PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS. SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER SYSTEMS. 1 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE. N. C.3 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES AND JUNCTION BOXES. L. D C.9 RSP Architects MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF PROJECT. O. PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS REMAINING AT END OF PROJECT. STUDENT HEALTH AND ACADEMIC RENOVATION C DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 B.8 1 B.2 B A KEY NOTES: 1 IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES, ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION BOXES, SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION DEVICES, CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.), MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS, UNLESS NOTED OTHERWISE. Project No. 2263.001.00 Drawn By 1 MMK Checked By Date AA 0 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. THIRD FLOOR DEMOLITION PLAN 2 1/8" = 1'-0" Revisions No. Date Description THIRD LEVEL DEMOLITION PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:06:11 PM ED103 GENERAL LIGHTING NOTES: UP H1 E-B1/ 21 CIRCUIT TO N-B1 UNO STORAGE A. WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES SHALL ALWAYS BE “ON”. B. VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES. C. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. D. REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM. E. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE PLACEMENT IN GYP BOARD AND ACT CEILING. F. WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL, ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM RATING. RSP Architects G. PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH BOXES. Consultants H. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. I. VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION. CIRCUIT TO N-B2 UNO 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Dunham Job #: 415134 054 F LC 04 E1 E-B1/ 2 S D1 E-B1/ 18 SHOWER/ RESTROOM D1 E-B1/ 18 J2 2 10 LC 07 R OS EM MENS LOCKER ROOM 008 D1 10 LC 07 COS1 D1 2 A3 E-B1/ 18 D1 2 EM D1 E-B1/ 18 J1 1 004 1 F1 14 S LCP-B1/13 COS1 S B1 E-B1/ 3 3 LC 06 ATS-E F1 8 022 ATS-R ATS-O RD-B1 LCP-B1 O-B1A NR-B1A NR-B1B O-B1B F1 8 F1 8 N-B1 LCP-B1/2 B1 6 F1 E-B1/ 1 E-B1 G F1 E-B1/ 1 NRD-B1 EM OS D1 E-B1/ 19 D1 12 LC 07 LC 06 F1 8 F1 E-B1/ 1 UNISEX TOILET/SHOWER LCP-B1/13 F1 2 J2 12 B1 E-B1/ 3 F1 2 R1 F1 8 F1 3 021 F1 8 CIRCUIT TO N-B1 UNO F1 1 R F1 1 F1 1 C.3 BUILDING SUPPORT F1 3 F1 3 50358 07/24/15 STUDENT HEALTH AND ACADEMIC RENOVATION 018 F1 2 F1 2 LC 05 OS LCP-B1/2 B1 6 F1 3 LC 05 James A. LeClaire F1 1 F1 E-B1/ 1 2 R EM ND-B1 NR-B2 C N-B2 E3 E-B1/ 2 LCP-B1/2 B1 6 LCP-B1/13 B1 E-B1/ 3 COS1 B.8 STAIR B S002 B.2 B F1 3 COS1 COS1 033 F1 3 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 LC 04 H1 E-B1/ 7 E1 E-B1/ 2 COS1 Signature D C.9 EM LC 06 CUSTODIAN SHOWER/ RESTROOM F1 3 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Project For F1 E-B1/ 1 EM D1 E-B1/ 19 DATA ROOM F1 8 2 R LCP-B1/2 COS1 B1 6 F1 1 LC 06 SW R EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU-200 EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL. 032 2 R EM 014 D1 E-B1/ 19 J2 LC 12 07 D1 12 J2 12 013 F1 1 3 MSB ELECTRICAL ROOM LCP-B1/2 B1 6 S 001 R OS E2 E-B1/ 2 LC LCP-B1/2 B1 04 6 COS1 2 Registration Number MECHANICAL ROOM 016 CORRIDOR LCP-B1/2 B1 6 B1 E-B1/ 3 2 2 S F1 14 COS1 LCP-B1/13 D1 5 E1 OS MECHANICAL ROOM F1 2 EM SHOWER/ RESTROOM D1 1 LC 07 LCP-B1/1 PASSENGER ELEVATOR CIRCUIT FIXTURE IN ELEVATOR PIT TO SAME 120V CIRCUIT AS RECEPTACLE(S) WITHIN PIT. DO NOT CONNECT LIGHT TO LOAD SIDE OF GFI RECEPTACLE. COORDINATE LOCATION OF LIGHT FIXTURE WITH ELEVATOR CONTRACTOR. Date 052 S LC 06 PASS./SERV. ELEV. EQUIP. ROOM R D1 12 COS1 F1 1 RESISTANCE TRAINING D1 E-B1/ 19 051 A3 1 S F1 14 D1 1 A3 E-B1/ 19 LCP-B1/1 B1 5 005 R 050 2 E D.9 F1 1 F1 1 LC 07 J2 1 RESTROOM WOMANS LOCKER ROOM S J2 2 2 F1 1 035 OS SHOWER/ D1 1 F1 1 S8 4 A1 3 D1 LC 07 055 SHOWER OS RESTROOM F1 1 CVS1 R1 R F1 E-B1/ 1 LC 02 COS1 2 R EM CORRIDOR D1 A1 3 A1 3 D1 1 LCP-B1/1 B1 5 A3 2 LC 07 D D1 LC 02 RC0-1 R R3 A3 2 R1 D A1 3 S 006 R LCP-B1/1 B1 5 B1 5 LC 04 OS F1 7 010 CVS1 003 D1 10 EXAM/ CONSULT 011 S EM D1 10 R S8 4 EXAM/ CONSULT COS1 S 2 S8 4 COS1 B1 E-B1/ 3 WAITING LC 07 LC 03 S8 4 LCP-B1/13 B1 5 F1 7 J2 10 1 009 LCP-B1/1 007 S8 4 EXERCISE/TRAINING E2 SHOWER/ RESTROOM F1 7 COS1 LCP-B1/1 KEY NOTES: F1 E-B1/ 1 S 1 03A B1 5 S8 4 S SERVICE ELEVATOR S8 4 S COS1 LCP-B1/1 B1 5 CORRIDOR B1 4 OS S S J1 2 E1 E-B1/ 2 LCP-B1/13 B1 E-B1/ 3 LC 05 S E1 E-B1/ 2 F1 E-B1/ 1 2 R EM F1 3 F1 3 MECHANICAL ROOM F1 3 019 CIRCUIT TO N-B2 UNO F1 3 LC 06 F1 E-B1/ 1 A Project No. 2263.001.00 Drawn By MMK Checked By JL Date AA 0 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 LOWER LEVEL LIGHTING PLAN 1/8" = 1'-0" Revisions No. Date Description LOWER LEVEL LIGHTING PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:01:18 PM E100 GENERAL LIGHTING NOTES: 144" LCP-B1/24 W2 E1 E-B1/ 27 E-B1/ 5 A1 1 c A1 1 R c R3 c CVS1 d S R CVS1 C4 3 R3 D5 D A1 5 d COS1 P1 A1 5 d A1 5 A4 5 d d A1 5 f f C1 2 LCP-11/2 D1 3 LC 07 LCP-11/3 LCP-11/5 LCP-11/5 D1 D1 7 7 PASS ELEVATOR A4 5 115 C4 2 a R3 C4 D D5 2 a R LCP-11/5 D1 7 COS1 OS 1 R D1 E-B1/ 25 C6 3 COS1 S S LCP-11/28 C3 E2 E-B1/ 4 E-B1/ 5 LCP-11/9 LCP-11/9 C3 7 1 LC 07 EM B1 E-B1/ 4 d P1 A1 6 S CVS1 D D1 R1 A1 R 6 CVS1 A1 8 COS1 LCP-11/28 EM C2 D1 1 E-B1/ 25 COS2 R D1 1 LC 07 LC 02 LC 04 107 126 0 1 2 LCP-B1/14 W1 72" E-B1/ 10 3 PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH BOXES. H. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. I. VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 D1 E-B1/ 25 B1 21 COS1 C4 7 R R1 A1 8 D D1 CVS1 A1 8 PC P1 R C4 LCP-11/9 7 E1 E-B1/ 6 RESEARCH DIRECTOR 125 LC 01 LC 04 H1 E-B1/ 7 LCP-11/8 D1 7 CVS1 R1 A1 8 A1 8 PC P1 R Consultants UCHOOSE & RC 121 LC 01 R1 A1 8 A1 8 PC P1 UCHOOSE & RC 120 EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU200 EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature 07/24/15 STUDENT HEALTH AND ACADEMIC RENOVATION LC 01 STAIR A B A1 6 R3 A1 6 b a c B1 6 A1 6 P1 HEALTH ED & PROMOTION COORD LC 01 c A1 6 A1 6 b a PC LCP-11/28 P2 RECOVERY C4 E-B1/ 4 C4 7 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 B.2 D D1 E1 E-B1/ 6 PC COMMUNITY RESOURCE AREA A1 6 LCP-11/29 P2 SOUTH ENTRY E-B1/ 8 c A1 6 134 b A1 6 144" LCP-B1/8 W2 O-B1A/ 21 Project No. A a LC 04 LCP-B1/14 72" W1 E-B1/ 10 4.8 5 CL 5.55.6 66.2 6.7 7 LCP-B1/14 72" W1 E-B1/ 10 8 MMK Checked By CVS1 Date 109 LCP-B1/14 72" W1 E-B1/ 10 2263.001.00 Drawn By JL 2/19/16 NORTH ENTRY 4.5 50358 H1 E-B1/ 7 LCP-11/8 D1 7 LCP-11/8LCP-11/8LCP-11/8 D1 D1 D1 7 7 7 COS1 LCP-11/29 P2 PC E-B1/ 8 4.2 James A. LeClaire S102 R D D1 CVS1 C B.8 E1 E-B1/ 6 C3 7 LCP-11/9 LCP-11/9 LC 01 F1 3 LCP-B1/8 W2 O-B1A/ 21 144" COS1 LCP-11/28 LCP-11/9 C3 C5 E-B1/ 4 N-11/ 7 C3 N-11/ 7 F1 3 L6 LCP-11/4 11 LCP-11/5 D1 7 LCP-11/5 D1 7 LCP-11/9 D D1 CVS1 C.3 RADIOLOGY (COMMUNITY PARTNER) 119 4 612.677.7100 612.677.7499 fax www.rsparch.com D C.9 LC 06 110 LC 02 F1 3 LCP-11/6 112 RESEARCH DATA G. RSP Architects Registration Number 118 C1 1 MENS RESTROOM INFO/KIOSK 122 E1 E-B1/ 5 CVS1 WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL, ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM RATING. 108 GRAD ASSIST R N-12 F1 3 C2 1 A1 8 CVS1 D D1 R1 A1 8 PC LCP-11/9 C4 E-B1/ 4 S A1 6 LC 01 S 127 D1 D PC RESEARCH COORDINATOR A1 6 S A1 6 R1 F. Date B1 21 S R R A1 6 COS1 LC 04 R1 REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE PLACEMENT IN GYP BOARD AND ACT CEILING. LCP-11/6 D1 2 CVS1 LCP-11/5 D1 7 S R1 S R LCP-11/7 LCP-11/7 LCP-11/7 D1 D1 D1 7 7 7 E. Project For CVS1 S A1 6 LC 01 R1 D D1 136 A1 8 S 144" LCP-B1/8 W2 O-B1A/ 21 R D1 D INFO/KIOSK A1 8 R1 D D1 A1 8 F1 3 C4 2 S 128 R C4 7 S P1 LCP-11/9 COS1 REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM. COS1 S PC LCP-11/9 C3 7 S S A1 6 LC 02 A1 6 124 F1 3 3 S A1 6 RESEARCHER 129 E D.9 CIRCULATION C1 1 LCP-11/9 C3 N-11/ 7 C3 7 LCP-B1/8 W2 O-B1A/ 21 144" LC 06 F1 LCP-11/27 ASST. CVS1 NR-12B NR-12A C4 2 P1 2 b UNISEX TOILET LCP-11/9 C3 7 F1 3 SHELL SPACE L6 9 LCP-11/9 COS1 LC 04 P1 2 b D2 2 c LCP-11/1 D1 N-11/ 3 COS1 LCP-11/3 a L5 LCP-11/10 10 LCP-11/5 LCP-11/5 LCP-11/5 D1 D1 D1 7 7 7 LC COS1 04 LCP-11/12 R C3 7 D. 1 LCP-11/6 B1 21 C4 2 a CVS1 132 111 D D5 ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. KEY NOTES: LCP-11/6 R3 LC 02 C5 3 C5 E-B1/ 4 DIRECTORY COS1 C4 a 2 R C5 3 R B1 21 117 LCP-11/26LCP-11/26 EM D1 E-B1/ 23 COS1 C5 3 COS1 E2 E-B1/ 5 C4 E-B1/ 4 B1 21 UCHOOSE STUDENT STAFF WORK C5 LCP-11/3 LCP-11/3 3 1 C2 2 LCP-11/7 D1 R R1 LC 7 106 LCP-11/7 LCP-11/7 04 CIRCULATION D1 D1 COS1 D 105 7 7 P1 F3 D1 PC H1 7 LC E-B1/ 7 STAIR A 04 S101 LC CVS1 RESEARCH 01 R5 LACTATION ROOM LCP-11/3 LCP-11/3 C4 3 C4 3 COS1 104 E1 E-B1/ 5 L5 10 LCP-11/10 C4 3 C1 2 D1 2 103 S f CVS1 A1 5 C1 2 WOMENS RESTROOM D1 E-B1/ 23 STORAGE S A1 5 C5 3 C2 2 LC 05 e LCP-11/3 LCP-11/3 LCP-11/3 A4 5 A1 5 d A1 5 C5 3 COS1 C4 3 S A1 5 LCP-11/26 LCP-11/3 LCP-11/3 123 CVS1 d PC d SHHS INTERDISCIPLINARY A1 5 e R d LC 02 A1 5 A1 5 C4 E-B1/ 4 B1 E-B1/ 4 e L5 10 LCP-11/10 LC 04 S e A1 5 S A1 5 C4 3 LCP-11/3 LCP-11/3 C4 3 D D5 R4 A1 5 LCP-11/3 LCP-11/2 D1 3 S b OS LCP-11/26LCP-11/26 C4 C5 E-B1/ 4 E-B1/ 4 133 102 C. F 3 LCP-11/27 P1 f P1 P1 P1 P1 P1 2 e 2 e 2 e 2 e 2 CVS1 C4 a a 2 PEER ED/ VENDING STORAGE c A1 1 LC 05 A1 1 PC C5 2 S c LC 06 F1 4 VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES. S A1 1 L5 3 COS1 LCP-11/11 LCP-11/2 D1 3 S b A1 1 A1 1 116 A1 1 LC 06 114 C5 3 f S HEALTH ED INTERDISCIPLINARY LC 09 A1 1 F1 NR-11B 4 131 C4 3 E1 E-B1/ 6 LCP-11/6 S c SERVICE ELEVATOR S c S b A1 1 DATA LCP-11/3 LCP-11/3 S A1 1 F1 4 NR-11A LCP-11 P2 LCP-11/2 D1 3 F1 4 P1 A1 1 PC LCP-11/1 E1 LCP-11/30 PC E-B1/ 5 P1 P2 E-B1/ 11 S N-11 PC B1 E-B1/ 4 130 a COS1 CVS1 C5 2 135 S D5 D a ELECTRICAL VESTIBULE S a A1 1 B1 COS1 3 LCP-B1/24 144" W2 E-B1/ 27 E1 COS1 E-B1/ 6 144" LCP-B1/24 W2 E-B1/ 27 S A1 1 LCP-11/2 D1 3 LCP-11/25 144" LCP-B1/24 W2 E1 E-B1/ 27 E-B1/ 5 S S A1 1 B1 3 LCP-11/1 144" LCP-B1/24 W2 L5 E-B1/ 27 LCP-11/10 10 S E1 E-B1/ 5 E1 E-B1/ 5 R5 H1 E-B1/ 21 S R 113 B. Dunham Job #: 415134 S CVS1 H1 E-B1/ 21 S S100 CIRCULATION WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES SHALL ALWAYS BE “ON”. CIRCUIT TO N-12 UNO S STAIR D CIRCUIT TO N-11 UNO S UP LCP-B1/8 W2 144" O-B1A/ 21 LCP-B1/8 W2 144" O-B1A/ 21 S 144" LCP-B1/8 W2 O-B1A/ 21 A. AA CIRCUIT TO N-12 UNO CIRCUIT TO N-11 UNO 9 10 11 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 FIRST LEVEL LIGHTING PLAN 1/8" = 1'-0" Revisions No. Date Description FIRST LEVEL LIGHTING PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:01:32 PM E101 GENERAL LIGHTING NOTES: A. WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES SHALL ALWAYS BE “ON”. B. VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES. C. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. D. REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM. E. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE PLACEMENT IN GYP BOARD AND ACT CEILING. F. WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL, ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM RATING. G. PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH BOXES. H. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. I. VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION. RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants H1 E-21/ 31 CIRCUIT TO N-21 UNO S200 O-21A R3 WOMENS RESTROOM A1 2 A1 2 A1 2 L2 COS1 E-21/ 16 D1 E-21/ 32 D1 12 U2 5 WAITING CIRCULATION COS1 C1 12 CVS1 U2 5 LC 02 260 A1 2 LCP-21/14 CVS1 L1 E-21/ 16 L1 E-21/ 16 E2 E-21/ 1 LCP-21/14 D3 6 LCP-11/5 B1 6 P1 PC A2 6 R A2 6 PHARMACY A2 6 A2 6 A2 6 A2 6 CVS1 CVS1 R1 A1 9 D D1 S A2 6 LC 01 242 R2 A2 6 PC A2 6 R R1 R A1 9 PC A1 9 LCP-21/6 HALLWAY 266 A2 O-21A/ 5 256 A2 O-21A/ 5 B1 O-21A/ 6 R R1 D D1 PC CVS1 A1 9 P1 R PC LCP-21/15 R1 D1 D A1 O-21A/ 6 P1 P1 LCP-21/6 A1 9 CIRCUIT TO N-22 UNO CASHIER STUDENT INSURANCE ADVOCATE REFERRAL COORDINATOR OFFICE SUB WAITING 244 245 247 248 249 LC 01 LC 01 LC 01 LC 01 B1 O-21A/ 6 R LCP-21/6 S 1 2 3 A2 O-21A/ 5 4 4.2 4.5 4.8 5 OS CL 5.55.6 LC 04 COS1 B1 E-21/ 3 230 P1 R R1 R R1 227 A1 7 PC R1 LC 02 Project For LC 02 A1 7 270 A1 7 PC NP OFFICE P1 C.3 NURSING MANAGER 228 CVS1 A1 7 REF. N-22 A1 7 LC 02 C B.8 CLEAN SUPPLY DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 234 B.2 B CVS1 R2 A2 O-21A/ 3 A2 O-21A/ 3 D D1 R CVS1 A2 O-21A/ 3 A2 O-21A/ 3 LABORATORY A2 O-21A/ 3 LC 01 A2 O-21A/ 3 251 A2 O-21A/ 3 PC P1 A2 O-21A/ 3 A2 O-21A/ 3 Project No. A CVS1 LAB TOILET PHLEBOTOMY 6.7 7 STUDENT HEALTH AND ACADEMIC RENOVATION LC 02 2263.001.00 Drawn By MMK Checked By 250 LC 07 66.2 07/24/15 H1 E-21/ 8 S202 LC 01 268 50358 D C.9 A1 7 P1 PC D1 D B1 O-21A/ 6 LCP-21/15 NR-22A OS LC NR-22B 05 LC 04 MED/ NOURISH ROOM D D5 JL Date A2 O-21A/ 3 0 CVS1 James A. LeClaire R1 A1 7 CVS1 Signature Date MD OFFICE NP OFFICE D1 D D D1 A2 O-21A/ 3 BUSINESS MANAGER R I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Registration Number PC R1 LCP-21/6 A2 O-21A/ 5 A1 7 P1 LCP-21/15 255 A2 O-21A/ 5 H1 E-21/ 8 PC C2 O-21A/ 3 A1 7 224 STAFF TOILET LC 05 E D.9 CVS1 R LC 02 A1 7 CVS1 D1 D E2 D1 E-21/ 2 E-21/ 10 C1 E-21/ 10 223 C1 E-21/ 11 COS1 OS D1 O-21A/ 3 R1 A1 7 P1PC EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU200 EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL. STAIR B LC 07 OS D1 C1 E-21/ 11 E-21/ 11 LCP-21/6 LC 05 B1 O-21A/ 6 LC 04 LC 02 A1 7 R OS PROCESS ROOM A2 O-21A/ 5 E1 B1 E-21/ 2 O-21A/ 6 B1 E-21/ 3 B1 A1 O-21A/ 6 E-21/ 3 CVS1 LCP-21/6 B1 E-21/ 3 LCP-21/6 A1 9 A1 9 LCP-21/6 PATIENT TOILET 267 271 LC 07 A2 O-21A/ 5 O-21A /9 A2 O-21A/ 5 J B1 O-21A/ 1 B1 OS O-21A/ 1 3 CVS2 R2 CVS1 A1 9 D D1 P1 LC 04 STORAGE A1 9 D3 NURSE STATION O-21A/ 1 231 E2 E-21/ 2 LCP-21/15 B1 O-21A/ 6 B1 O-21A/ 1 D3 O-21A/ 1 EXAM ROOM 225 B1 232 O-21A/ 1 BP 5 A2 6 CIRCUIT TO N-21 UNO A2 6 CVS1 P1 241 A2 6 CVS1 A1 9 CVS2 S D1 A2 6 A1 9 B1 6 A1 9 PRESCRIPTION PICK-UP/DROP-OFF D R LCP-11/5 S S CVS1 LCP-11/5 COS1 B1 6 LCP-21/6 LC 04 269 LC 02 TREATMENT ROOM EXAM ROOM B1 O-21A/ 6 COS1 D D1 3 D3 O-21A/ 1 A2 O-21A/ 4 LC 04 LCP-21/6 R U2 3 229 R D D1 LC 03 246 S LC 01 P1 PC R1 D1 D S A1 6 S 239 R A1 6 243 R1 D D1 COS1 B1 O-21A/ 6 A2 O-21A/ 4 R1 D1 D B1 O-21A/ 6 D3 O-21A/ 1 LCP-21/6 F2 15 LC 03 RECEPTION 240 U2 5 CVS1 D3 6 WORK OTC SALES CONSULTATION AREA D3 6 U2 5 EXAM ROOM S H1 E-21/ 8 S H1 E-21/ 8 COS1 LCP-21/14 COS1 S S201 A2 O-21A/ 4 LCP-21/15 COS1 B1 E-21/ 3 226 S STAIR A R EXAM ROOM CVS1 238 LC 02 D3 O-21A/ 1 B1 O-21A/ 6 LC 02 A2 O-21A/ 4 R1 D1 D A2 O-21A/ 4 LC 04 CVS1 R D1 D E1 E-21/ 1 U2 5 LC 02 A2 O-21A/ 4 PASS ELEVATOR 207 LC 04 LC U2 02 5 CVS1 S 203 C1 12 A1 2 LC 02 265 R3 CVS1 S R A2 O-21A/ 4 HALLWAY INJECTION ROOM S S P1 219 D1 D R1 LC A2 02 O-21A/ 4 R R1 R S S 205 R1 A2 O-21A/ 4 D1 D A2 O-21A/ 4 S CONFERENCE PC D1 D R EXAM ROOM C1 12 A2 O-21A/ 4 D1 A2 R1 D O-21A/ 7 R CVS1 A2 O-21A/ 7 LC R R1 02 A2 D D1 O-21A/ 7 REF. A2 O-21A/ 4 S LC 01 D1 D R R1 A2 O-21A/ 7 LCP-21/6 217 U2 3 A2 O-21A/ 7 OBSERVATION (IVS) - EKG EXAM ROOM U2 3 B1 O-21A/ 6 HALLWAY D1 D 259 1 S LCP-21/14 D1 D EXAM ROOM S EM D1 E-21/ 32 LC 07 R D1 D A2 O-21A/ 2 CVS1 LC 02 A2 O-21A/ 7 LC 02 LCP-21/6 233A D1 216 A2 A2 A2 D HALLWAY O-21A/ 2 O-21A/ 2 O-21A/ 2 258 LCP-21/15 LCP-21/15 LCP-21/6 EXAM ROOM EXAM ROOM LC COS1 221 220 B1 B1 B1 04 HALLWAY E2 E-21/ 3 E-21/ 3 O-21A/ 6 264 E-21/ 2 S 1 A1 2 A2 O-21A/ 2 U2 3 CVS1 CVS1 222 MD OFFICE CVS1 U2 3 MEDICAL DIRECTOR OFFICE P1 R1 R S A2 O-21A/ 2 S A1 2 R1 U2 4 U2 3 CVS1 S LCP-21/1 R S B1 8 R1 LCP-21/6 A2 O-21A/ 7 S B1 COS1 E-21/ 4 LCP-21/13 HALLWAY R1 U2 4 LC 02 R CVS1 EXAM ROOM E2 E-21/ 1 R U2 4 LC 02 S C1 12 R1 PC COS1 A2 O-21A/ 7 S S A1 2 LC 02 LC 02 R KEY NOTES: REF. A1 7 D D1 S C1 12 C2 12 A1 2 R1 U2 4 LC 02 CVS1 L1 E-21/ 16 D1 D CVS1 R 218 B1 8 261 LC 02 R1 D D1 S S COS1 LC 04 B1 8 LCP-21/1 COS1 LC 07 201 LCP-21/1 S S A1 2 B1 8 LCP-21/1 S S P1 LC 01 MENS RESTROOM R1 S C2 12 R R LC 02 A2 O-21A/ 7 LC 02 B1 O-21A/ 6 LC 04 B1 O-21A/ 6 R S D1 OS 12 COS1 1 R EM A1 D1 10 E-21/ 32 OS LC 07 OS 1 S CUSTODIAN U2 4 U2 4 C2 12 EM D1 E-21/ 32 S PC 210 F1 10 CVS1 214 S 202 B1 8 R1 A1 D1 2 D UNISEX RESTROOM CVS1 S LC 05 LCP-21/1 CVS1 LC R 02 R1 A2 O-21A/ 7 A2 O-21A/ 7 LCP-21/6 D D1 CVS1 S A1 10 EXAM ROOM COS1 A2 O-21A/ 2 S COS1 R SHS ASST DIRECTOR E-21 212 A1 2 CVS1 254 R1 D R D1 S 209 DATA A2 O-21A/ 7 236 S 211 206 237 E2 E-21/ 2 215 A2 O-21A/ 2 A2 O-21A/ 2 257 LCP-21/15 B1 CONSULT ROOM (CAPS) O-21A/ 6 B1 235 E-21/ 3 S 262 F1 10 P1 213 SERVICE ELEVATOR F1 10 TRIAGE ROOM S HALLWAY P1 F1 10 O-21B LARGE CENTRAL SUPPLY PC A2 O-21A/ 2 A2 D1 D O-21A/ 2 ISOLATION EXAM HALLWAY LCP-21/6 CONSULT ROOM (E-EXAM) B1 O-21A/ 6 S R1 A1 D1 2 D NR-21A LCP-21 LC NR-21B F1 10 06 LC 05 LCP-21/13 A3 B1 10 E-21/ 4 PC SHS DIRECTORS A3 10 LCP-21/14 F1 10 N-21 B1 O-21A/ 6 A2 D1 D O-21A/ 2 D1 D EXAM ROOM LCP-21/6 S LC 04 R LC 01 OS COS1 B1 E-21/ 3 S B1 8 R1 R 253 COS1 B1 LCP-21/15 E-21/ 3 LCP-21/6 LC PC P1 04 S A1 2 LC 06 B1 8 LCP-21/1 LCP-21/15 S D1 D 208 ELECTRICAL E1 E-21/ 1 L1 E-21/ 16 S P1 B1 8 S PC 252 263 S A1 2 LC 01 UCHOOSE ADMINISTRATOR E1 E-21/ 1 LCP-21/1 LC LCP-21/13 04 B1 COS1 E-21/ 4 HALLWAY LCP-21/1 SOILED HOLD Dunham Job #: 415134 F E2 E-21/ 1 S S CVS1 CIRCUIT TO N-22 UNO S STAIR D S H1 E-21/ 31 S UP UP 8 A2 O-21A/ 3 A2 O-21A/ 3 9 AA A2 O-21A/ 3 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 SECOND LEVEL LIGHTING PLAN 1/8" = 1'-0" Revisions No. Date Description SECOND LEVEL LIGHTING PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:01:48 PM E102 GENERAL LIGHTING NOTES: STAIR D CIRCUIT TO N-31 UNO S300 CVS1 D D1 A1 A1 R R1 5 5 LC 02 S STORAGE 302 H1 E-21/ 8 L3 E-21/ 17 L3 COS1 E-21/ 17 E2 E-21/ 7 F2 5 A1 4 D1 11 LC 01 CVS1 422 P1 11 CVS1 419 B1 11 A1 11 D1 11 ? A1 4 FILE & ARCHIVE 321 385 LC 01 A1 9 A1 E-21/ 5 A1 4 A1 4 D D5 CONFERENCE /GROUP ROOM LCP-31/4 AOD COUNSELOR PC R A1 2 374 COS1 LC 01 NR-32A NR-32B A1 7 C.3 P1 LCP-31/15 B1 E-21/ 5 A1 4 G. PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH BOXES. Consultants H. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. I. VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION. R 612.677.7100 612.677.7499 fax www.rsparch.com 5.55.6 66.2 6.7 7 KEY NOTES: EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU200 EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire THERAPIST OFFICE CVS1 50358 07/24/15 STUDENT HEALTH AND ACADEMIC RENOVATION C R1 375 B.8 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 B CVS1 LCP-31/4 B1 11 LC 04 B1 11 CVS1 A1 4 388 D D1 P1 PC A1 4 R R1 D D1 R1 A1 4 A1 4 P1 A1 4 A PC CL 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 A1 2 LC 01 CASE MANAGER OFFICE R1 D1 D CIRCUIT TO N-32 UNO 4.8 5 RSP Architects PC A1 2 B1 E-21/ 5 376 387 R S 4.5 WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL, ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM RATING. D C.9 CASE MANAGER INTERN LC 02 LC 01 -1 4.2 F. H1 E-21/ 8 V SN 4 REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE PLACEMENT IN GYP BOARD AND ACT CEILING. LC 01 LC 04 N-1 VS 3 E. B.2 N-1 VS 2 REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM. Project For CAPS DIRECTOR OFFICE 8 389 9 Project No. 2263.001.00 Drawn By MMK Checked By JL Date AA 1 D. P1 R1 CVS1 0 ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. Date COS1 R CIRCUIT TO N-31 UNO B1 2 B1 2 CVS1 LC A1 04 2 P1PC D1 R R1 LCP-31/4 D B1 THERAPIST OFFICE 11 THERAPIST OFFICE H1 E-21/ 8 320 A1 11 R1 D1 D E1 E-21/ 6 WORK ROOM 359 E D.9 R1 LC 01 LCP-31/15 D1 D LC 02 LC 02 A1 7 A1 4 VS D1 11 A1 7 E2 E-21/ 6 A1 9 ADMIN SUPPORT/ RECEPTION R CVS1 LCP-31/4 B1 11 A1 4 R1 CVS1 LCP-31/4 B1 B1 E-21/ 5 11 LCP-31/15 LC 05 D1 7 A1 7 378 HALLWAY A1 9 A1 4 A1 4 A1 11 D D5 LC 04 COS1 A1 4 PRIVATE WAITING AREA KITCHEN P1 11 A1 11 D1 D A1 11 B1 11 S A1 11 D1 11 S A1 11 D1 11 A1 11 D1 11 P1 11 1 E1 E-21/ 6 323 A1 E-21/ 7 STAFF BREAK ROOM 324 CVS1 B1 4 CAPS ENTRY D D1 LC 01 B1 E-21/ 5 R D D1 B1 11 A1 5 OS A1 7 R1 R 360 381 D5 D COS1 LCP-31/14 LCP-31/14 E1 E-21/ 7 A1 11 F2 5 LC 05 D1 D LC 04 LCP-31/4 R1 STORAGE/AV S S301 A1 11 THERAPIST R PREDOCTORAL 379 S STAIR A D1 5 A1 5 VS S H1 E-21/ 8 LC 02 D1 5 B1 11 R LC 02 361 C1 7 377 D D1 R B1 11D1 B1 E-21/ 5 STAFF TOILET AOD COUNSELOR VS N-1 S LC 04 A1 5 LC 02 A1 5 D1 5 A1 5 380 COS1 VS CVS1 LCP-31/4 B1 11 COS1 A1 7 LC 02 A1 2 P1PC D COS1 THERAPIST E2 OFFICE E-21/ 6 373 LCP-31/15 CVS1 LCP-31/4 S 363 THERAPIST PREDOCTORAL CVS1 S PASS ELEVATOR C. Registration Number A1 3 D D1 LCP-31/4 LC B1 04 11 CVS1 S D1 5 E2 E-21/ 6 B1 E-21/ 5 COS1 S 382 A1 2 GROUP THERAPY ROOM LCP-31/15 LC 01 372 LCP-31/4 S RELAXATION ROOM VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES. 1 A1 2 THERAPIST OFFICE A1 3 R1 CVS1 A1 2 D D1 S COS1 R1 A1 3 S 384 C1 4 LC 05 A1 8 397 HALLWAY S S S SHHS FACULTY COMMAND CENTER C1 4 B1 5 R 303 D1 R R1 D S A1 2 LC 02 D1 4 D1 E-21/ 7 CVS1 A1 5 B1 11 S S COS1 CVS1 A1 A1 2 LCP-31/13 D R 2 R1 D1 A1 D B1 2 R1 D1 E-21/ 7 COS1 CVS1 D D1 D D5 D1 R2 D1 5 5 A1 A1 5 5 CVS1 S 396 LCP-31/14 355 LC 02 S SHHS FACULTY COMMAND CENTER LC 02 R1 A1 5 LC 04 WOMENS RESTROOM D1 E-21/ 7 S LC 07 C1 4 A1 5 E1 E-21/ 6 R A1 3 S S R C2 4 383 LCP-31/15 A1 3 LC 02 R1 B1 E-21/ 5 LCP-31/4 A1 3 R S 340 LCP-31/4 B1 LC 11 04 B1 E-21/ 5 RELAXATION ROOM D1 D A1 3 LC 02 B1 11 A1 1 R 370 S LCP-31/1 E1 E-21/ 6 COS1 352 E2 E-21/ 7 R1 CVS1 398 S S R B2 6 D1 D R LCP-31/15 OPEN STUDY S LC 01 C1 4 B2 COS1 E-21/ 7 A1 2 CVS1 A1 1 367 A1 3 CAPS INTERN OFFICE LC 01 A1 2 B1 D R R1 E-21/ 5 THERAPIST D1 OFFICE PC LCP-31/15 371 P1 COS1 S 394 A1 1 CVS1 D1 D R R1 L4 E-21/ 17 A1 B1 2 6 D D1 LCP-31/1 368 A1 3 PRACTICUM INTERN OFFICE COS1 LCP-31/4 PRACTICUM THERAPY LC 02 A1 3 A1 3 LC 04 A1 1 CVS1 CVS1 S SHHS CLINICAL P1 ROOM A1 2 S A1 2 CVS1 LCP-31/14 HALLWAY D1 D 369 COS1 PRACTICUM THERAPY LC 02 S A1 2 P1 PC C1 4 LCP-31/13 B1 E-21/ 7 COS1 PRACTICUM THERAPY B1 11 A1 1 LC 02 A1 1 S R1 393 PC LC 04 D1 E-21/ 7 A1 1 R1 366 A1 1 S SHHS CLINICAL R ROOM 301 L4 E-21/ 17 COS1 LC 07 B1 6 D1 E-21/ 7 LCP-31/1 LCP-31/13 B1 6 E1 E-21/ 7 B1 2 LC 01 LCP-31/1 OS UNISEX RESTROOM 365 D D1 A1 3 R COS1 N-32 S B1 2 S D D1 R1 R S LC 01 CVS1 R1 D1 D A1 1 PRACTICUM LC THERAPY 02 B1 11 COS1 LC 04 S S 392 R 354 D1 E-21/ 7 S PC B1 2 MENS RESTROOM LC 07 A1 10 395 R A1 1 S B1 2 P1 SHHS GROUP THERAPY ROOM A1 COS1 10 F2 10 C1 4 D1 D R CVS1 R1 A1 1 PRACTICUM LC THERAPY LCP-31/4 02 R1 C2 4 341 LC 02 D1 D CVS1 B2 E-21/ 5 S A1 10 R COS1 S CVS1 F1 12 CLOSET A1 10 L7 13 399 R1 CVS1 A1 PRACTICUM 1 THERAPY LC 02 364 362 DATA ROOM D1 D 356 B1 11 LCP-31/4 S F1 12 A1 2 LCP-31/1 B1 6 CVS1 SHHS CLINICAL ROOM LC 06 LCP-21 NR-31A F1 12 NR-31B B1 E-21/ 5 LCP-31/15 CIRCULATION S LC 05 LCP-31/14 SERVICE ELEVATOR F1 12 E1 E-21/ 6 S A1 2 F1 12 L3 E-21/ 17 COS1 S PC R1 D1 D LC 06 F1 12 N-31 LCP-31/4 LC 04 S P1 R B1 E-21/ 7 LC 04 COS1 LCP-31/15 COS1 B1 LCP-31/4 11 S 391 LC 01 S SHHS CLINICAL ROOM LCP-31/13 B1 6 E2 E-21/ 7 300 D R1 R B1 LCP-31/1 6 B1 E-21/ 7 ELECTRICAL ROOM S S D1 PC 353 E1 E-21/ 7 LCP-31/1 LC 04 S LC 01 LCP-31/13 B1 LCP-31/1 6 COS1 CUSTODIAN S A1 2 P1 E1 E-21/ 7 F S CVS1 A1 2 390 B. Dunham Job #: 415134 S SHHS CLINICAL ROOM H1 E-21/ 31 WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES SHALL ALWAYS BE “ON”. CIRCUIT TO N-32 UNO S DN H1 E-21/ 31 A. 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 THIRD LEVEL LIGHTING PLAN 1/8" = 1'-0" Revisions No. Date Description THIRD LEVEL LIGHTING PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:02:04 PM E103 GENERAL POWER NOTES: A. VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH ARCHITECTURAL ELEVATIONS. B. ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. C. MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6” ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL ELEVATIONS FOR COUNTER HEIGHTS. D. REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT. E. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. F. REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL SYSTEMS. G. COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING. H. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. I. PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET. J. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. RSP Architects 1 UP STAIR D CIRCUIT TO NR-B1A UNO S001 CIRCUIT TO NR-B2 UNO F 1 TO EXTERIOR ENCLOSED CIRCUIT BREAKER ENCLOSURE 16 15 17 4 18 12 CORRIDOR PROPOSED CONDUIT ROUTE (6) 3-1/2"C, 4#400KCMIL + #250 GND (2 ROWS OF 3) 2 009 E2 13 60" 3 13 AHUR 03 AHUS 03 3 E D.9 O-B1A /17 13 11 J 19 AC 5 20 10 12 WAITING 007 8 60" 12 19 AC 003 EXAM/ CONSULT 056 10 8 N-B1 /26,28 J 8 8 SHOWER RESTROOM 14 RD-B1 /15 11 12 12 J J J 13 RD-B1 /13 RD-B1 /17 PASS./SERV. ELEV. EQUIP. ROOM 11 6 J TF 01 3 36" 1 2 3 AC N-B1 /19,21 J 013 032 8 8 J 7 SHOWER/ RESTROOM CUSTODIAN 014 018 M001 6 PULLBOX 2 21 O-B1B /1 G ATS-E 22 24 ATS-R ATS-O LCP-B1 O-B1B O-B1A B.8 STAIR B B.2 NR-B1A /4 5 B SCP 01 1 BUILDING SUPPORT DATA ROOM 021 O-B1B /9 O-B1A /5 J NR-B1A 5 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature 9 HWP 01 UH 001 O-B1B /5 GFS 01 23 O-B1B /11 HWP 02 Registration Number Date 07/24/15 Project For 9 120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER. 10 WIREWAY OF ENCLOSED CIRCUIT BREAKERS FOR GENERATOR DISTRIBUTION AND SYSTEM SEPARATION TO TRANSFER SWITCHES, REFER TO RISER DIAGRAM FOR ADDITIONAL INFORMATION. 11 120V, 30A LOCKABLE FUSED DISCONNECT FOR ELEVATOR CAB EQUIPMENT. CIRCUIT SHALL BE FUSED AT 15A. 12 120V POWER CONNECTION FOR ELEVATOR CONTROLLER. COORDINATE FINAL LOCATION IN FIELD. 13 BUSSMAN POWER MODULE SWITCH ELEVATOR DISCONNECT RATED AT 100A. FUSE PER ELEVATOR MANUFACTURER RECOMMENDATIONS.1-1/4"C, 3#3 & 1#6G. 14 120V POWER FOR SHUNT TRIP POWER ON PANEL. 15 BUSSMAN POWER MODULE SWITCH ELEVATOR DISCONNECT RATED AT 200A. FUSE PER ELEVATOR MANUFACTURER RECOMMENDATIONS.1-1/2"C, 3#1/0 & 1#6G. STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 MECHANICAL ROOM 1 DWP 01 CIRCUIT TO NR-B2 UNO UH 002 Project No. A Drawn By MMK JL 1 Date AA 2 2263.001.00 Checked By 1 1 50358 SWH 01 019 CIRCUIT TO NR-B1A UNO 0 James A. LeClaire 5 033 O-B1B /3 RD-B1 NR-B1B INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL CONTRACTOR) AT SHOWN LOCATION, 208V CONNECTION TO HAND DRYER. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHT. REFER TO PANELBOARD SCHEDULE FOR ADDITIONAL INFORMATION REGARDING CIRCUIT BREAKER SIZE AND TYPE. NR-B1A /4 O-B1B /13 O-B1B /7 6 8 S002 25 NRD-B1 N-B1 5 O-B1A /9 J 3 2 C O-B1B /15 10 6 ND-B1 2 E-B1 /14 E-B1 120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS (TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/ WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS. PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22. TRANSFORMERS LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH DIV. 22 CONTRACTOR. C.3 3 022 G MECHANICAL ROOM 7 AHUR 01 J N-B1 /22,24 AC 7 ELECTRICAL ROOM 6 ELECTRICAL CONNECTION TO EMS PANEL. VERIFY LOCATION IN THE FIELD. ELECTRICAL CONNECTION TO SMOKE GUARD. UH 003 4 6 AHUS 01 2 001 MSB 120V CONNECTION FOR LIGHTS AND RECEPTACLES PROVIDED WITH AIR HANDLING UNIT. PROVIDE CONDUIT AND WIRING BETWEEN DEVICES. COORDINATE LOCATIONS WITH MANUFACTURES EQUIPMENT. 6 D C.9 4 8 016 CORRIDOR 3 RECEPTACLE FOR ELECTRIC WATER COOLER. PROVIDE GFCI BREAKER AT INDICATED CIRCUIT. COORDINATE RECEPTACLE MOUNTING HEIGHT WITH EQUIPMENT ACCESS IN THE FIELD. 3 AC 7 8 AHUR 02 2 MECHANICAL ROOM UNISEX TOILET/SHOWER E1 GENERATOR ANNUNCIATOR PANEL 3 5 J N-B2 /6 N-B1 /23,25 AC 8 E-B1 /13 PASSENGER ELEVATOR 004 J N-B2 /8 AHUS 02 SHOWER/ RESTROOM J J J RD-B1 /1,3,5 J RD-B1 /9 J RD-B1 /11 14 8 J AC 9 N-B1 /14,16 10 9 J RD-B1 /7 050 WOMANS LOCKER ROOM J O-B1A /3 051 AC GFI PIT RECEPTACLE. CONNECT TO PIT LIGHTING CIRCUIT. VERIFY LOCATION WITH ELEVATOR CONTRACTOR. 4 035 AC 7 SHOWER/ RESTROOM 055 7 2 J O-B1A /3 MENS LOCKER ROOM 005 LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD. 4 8 7 1 052 CORRIDOR 15 3 AC 20 008 RD-B1 /2,4,6 13 MECHANICAL ROOM 9 8 J N-B1 /15,17 RESISTANCE TRAINING 20 010 19 J N-B1 /18,20 006 AC 19 20 011 SHOWER/ RESTROOM SUMP ROOM EXAM/ CONSULT N-B2 12 SHOWER/ RESTROOM NR-B2 SP 01 COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. KEY NOTES: EXERCISE/TRAINING 11 Dunham Job #: 415134 13 SERVICE ELEVATOR 2 Consultants J N-B2 /10 03A 36" 612.677.7100 612.677.7499 fax www.rsparch.com 054 6 J E-B1 /15 14 STORAGE 12 K. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 LOWER LEVEL POWER PLAN 1/8" = 1'-0" Revisions No. Date Description LOWER LEVEL POWER PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:02:25 PM E200 GENERAL POWER NOTES: UP CUH 103 MAIN CIRCUIT BREAKER ENCLOSURE A. VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH ARCHITECTURAL ELEVATIONS. B. ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. C. MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6” ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL ELEVATIONS FOR COUNTER HEIGHTS. D. REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT. E. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. RSP Architects F. REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL SYSTEMS. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 G. COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING. H. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. I. PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET. J. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. CIRCUIT TO NR-12A UNO DN F K. REFRIG 1 XFMR 12 CIRCULATION 113 10 4 2 18 AC MICRO CUH 104 FCU 102 7 19 19 ELECTRICAL 130 7 6 3 DATA SERVICE ELEVATOR 131 114 J 5 7 6 3 3 102 FSD 1 124 13 12 13 VENDING 13 133 PEER ED/ UCHOOSE STUDENT STAFF WORK 6 3 60" 14 N-12 /4 J N-12 /4 J 1 1 LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD. 2 120V CONNECTION TO AUTOMATIC DOOR OPENER. VERIFY LOCATIONS AND MOUNTING HEIGHT WITH ARCHITECTURAL PLANS. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 3 MOUNT DEVICES HORIZONTALLY UNDERNEATH PERIMETER FIN TUBE RADIATION. Signature 4 120V CONNECTION TO ELECTRIC FIREPLACE. 5 120V CONNECTION TO ALL SHOWN FIRE/SMOKE DAMPERS IN THIS AREA. CIRCUIT ALL FIRE/SMOKE DAMPERS ON THIS PLAN TO THE INDICATED CIRCUIT. COORDINATE WITH MECHANICAL CONTRACTOR FOR LOCATIONS. REFER TO FIRE ALARM DETAILS SHEET FOR ADDITIONAL INFORMATION. 14 117 K 11 E D.9 5 12 5 GEN KEY NOTES: 8 2 SHELL SPACE 12 2 N-11 /16 J STORAGE 1 1 4 N-11 /14 116 FVAV 101 AC 16 16 15 AC 15 AC 16 15 AC HEALTH ED INTERDISCIPLINARY J 8 AC 14 14 14 14 6 120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS (TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/ WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS. PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22. TRANSFORMERS LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH DIV. 22 CONTRACTOR. 9 3 6 7 INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL CONTRACTOR) AT SHOWN LOCATION, 208V CONNECTION TO HAND DRYER. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHT. REFER TO PANELBOARD SCHEDULE FOR ADDITIONAL INFORMATION REGARDING CIRCUIT BREAKER SIZE AND TYPE. 6 J O-B1A /1 103 J O-B1A /1 9 11 3 STORAGE 11 AC 104 9 7 3 J N-11 /13,15 8 8 3 108 C.3 AC 4 14 AC 4 2 C E-B1 /16 PASS ELEVATOR 8 N-12 /5,7 132 14 J RADIOLOGY (COMMUNITY PARTNER) 107 UNISEX TOILET J N-11 /17,19 10 1 J J N-12 /9,11 14 MENS RESTROOM N-12 /12,14 J 7 7 8 D C.9 2 J O-B1A /1 WOMENS RESTROOM SHHS INTERDISCIPLINARY 1 CIRCULATION 118 14 123 1 DIRECTORY 115 2 111 3 B.8 15 LACTATION ROOM 15 CIRCULATION 106 3 Date 50358 07/24/15 8 STUB THREE (3) 3/4" CONDUITS UP TO ACCESSIBLE CEILING SPACE IN CORRIDOR FOR FUTURE USE. 9 120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER. STUDENT HEALTH AND ACADEMIC RENOVATION 10 ELECTRICAL CONNECTION TO SMOKE GUARD. 11 POWER FOR MOTORIZED PARTITION. KEYED SWITCHES AND PUSH BUTTON PROVIDED BY OTHERS. ELECTRICAL CONTRACTOR SHALL PROVIDE REQUIRED SINGLE GANG BACK BOXES, CONDUIT AND CABLING BETWEEN CONTROL BOX AND ASSOCIATED KEYED SWITCHES AND PUSH BUTTON. DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 STAIR A 3 3 S102 STAIR A S101 9 15 9 21 15 16 17 GRAD ASSIST 136 122 10 INFO/KIOSK 9 20 8 6 7 11 5 RESEARCH 7 6 UCHOOSE & RC 121 18 20 RESEARCH DIRECTOR 8 N-11 /25 J 2 18 RESEARCH COORDINATOR 120 7 137 5 UCHOOSE & RC 6 119 134 3 HEALTH ED & PROMOTION COORD 11 5 125 N-12 /19 J 2 A 19 127 CUH 101 RESEARCH DATA 18 126 19 NORTH ENTRY 112 2 19 J N-11 /26 SOUTH ENTRY CIRCUIT TO NR-11A UNO CIRCUIT TO NR-12A UNO 109 J J N-11 /23 N-12 /17 2 J 2 13 12 12 2 3 4 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 Date J N-12 /15 8 MMK JL 60" AA 2 J N-12 /13 4.2 2263.001.00 Checked By 1 N-11 /27 Project No. Drawn By CUH 102 1 1 RECOVERY COMMUNITY RESOURCE AREA 11 AC 60" 8 17 B 11 11 10 17 20 3 16 128 AC 20 110 16 129 RESEARCHER B.2 21 AC INFO/KIOSK RESEARCH ASST. XFMR 0 Registration Number 12 120V CONNECTION TO FIRE ALARM NAC PANEL. 105 PMH SWITCH James A. LeClaire Project For N-11 /18,20,22 K 9 3 COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. 19 FSD 6 3 NR-11A /10 WP FCU 101 J E-B1 /17 17 135 Dunham Job #: 415134 N-12 2 E201 NR-12B 1 3 NR-12A 5 VESTIBULE FSD 3 Consultants 1 CIRCUIT TO NR-11A UNO STAIR D S100 5 612.677.7100 612.677.7499 fax www.rsparch.com 9 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 FIRST LEVEL POWER PLAN 1/8" = 1'-0" Revisions No. NR-11A /4 O-B1B /6 G N-11 9 Description NR-11A /21 O-B1B /10 J O-B1A /6 ELECTRICAL 130 NR-11A /24 NR-11A 12 NR-11B Date E-B1 /12 J O-B1B /2 NR-11A /22 O-B1B /8 O-B1B /4 DATA J 131 E-B1 /9 2 2 FIRST FLOOR ELECTRICAL AND DATA ROOMS 1/4" = 1'-0" C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:02:38 PM 3 FIRST LEVEL POWER PLAN E201 GENERAL POWER NOTES: A. VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH ARCHITECTURAL ELEVATIONS. B. ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. C. MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6” ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL ELEVATIONS FOR COUNTER HEIGHTS. D. REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT. E. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. F. REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL SYSTEMS. G. COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING. H. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. I. PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET. J. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. RSP Architects 1 UP UP STAIR D S200 CIRCUIT TO NR-21A UNO CIRCUIT TO NR-22A UNO NR-22B /10 12 27 J 27 E-21 /19 NR-21B /7 3 SOILED HOLD ELECTRICAL DATA 252 253 254 206 SHS DIRECTORS J N-21 /11,13 212 J 7 LARGE CENTRAL SUPPLY 3 NR-21B /2,4 5 7 UNISEX RESTROOM 202 201 N-21 /7,9 8 5 210 EXAM ROOM EXAM ROOM 218 AC 13 20 48" 16 48" 16 48" 15 4 48" 48" 31 29 WOMENS RESTROOM 15 3 258 N-21 /15,17 AC 8 J 11 WAITING CIRCULATION EXAM ROOM EXAM ROOM 6 219 AC O-21B /25 220 O-21B /25 2 AC 31 AC 260 8 48" 12 48" 12 EXAM ROOM 10 221 AC O-21B /26 6 AC AC 18 14 J N-21 /16,18 J 14 12 O-21B /27 O-21B /27 18 39 EXAM ROOM 48" EXAM ROOM 225 269 48" 226 16 PASS ELEVATOR EXAM ROOM 20 AC 15 13 31 16 48" AC 26 O-21B /13 48" 24 48" 20 HALLWAY NP OFFICE 259 227 27 AC D C.9 29 8 31 N-21 /14 J 10 17 STAIR A 13 S201 15 O-21B /23 13 O-21B /2313 N-22 /4,6 31 30 J AC O-21B /15 -1 V SN VSN-1 5 25 1 NR-21B /1 PRESCRIPTION PICK-UP/DROP-OFF 7 245 BUSINESS MANAGER PHARMACY P 244 23 241 1 3 5 STUDENT INSURANCE ADVOCATE 247 J SUB WAITING 5 PROCESS ROOM O-21A /11 30 35 7 NURSING MANAGER 228 NR-22B 9 N-22 33 33 3REF. NR-31B /2 3 NR-22B /20 AC 2 NR-22B /2 PHLEBOTOMY NR-22B /18 250 AC AC NR-22B /18 NR-22B /6 NR-22B /18 LABORATORY 251 NR-22B /4 48" 21 21 NR-21B /1 42 1 42 CIRCUIT TO NR-21A UNO CIRCUIT TO NR-22A UNO 1 NR-22B /26 J 5 42 B.8 42 19 2119 21 NR-22B /22 NR-22B /24 NR-22B /22 NR-22B /24 NR-22B /22 NR-22B /24 NR-22B /22 NR-22B /24 NR-22B /22 NR-22B /24 NR-22B /22 A 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 11 120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER. 12 ELECTRICAL CONNECTION TO SMOKE GUARD. 13 120V CONNECTION TO AUTOMATIC DOOR OPENER. VERIFY LOCATIONS AND MOUNTING HEIGHT WITH ARCHITECTURAL PLANS. 14 120V CONNECTION TO FIRE ALARM NAC PANEL. 07/24/15 Project For STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 8 9 Project No. 2263.001.00 Drawn By MMK Checked By JL Date 10 2 ALL RECEPTACLES SHOWN WITHIN DASHED LINE SHALL BE HOSPITAL GRADE DEVICE, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. Date B AA 1 10 C 19 21 0 STUB THREE (3) 3/4" CONDUITS UP TO ACCESSIBLE CEILING SPACE IN CORRIDOR FOR FUTURE USE. 50358 3 NR-21B /1 23 9 1 AC NR-22B /8 J 268 17 INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL CONTRACTOR) AT SHOWN LOCATION, 208V CONNECTION TO HAND DRYER. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHT. REFER TO PANELBOARD SCHEDULE FOR ADDITIONAL INFORMATION REGARDING CIRCUIT BREAKER SIZE AND TYPE. 3 NR-22A 9 B.2 N-22 /11,13 NR-22B /18 7 17 8 C.3 33 S202 NR-22B /8 AC LAB TOILET 249 120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS (TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/ WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS. PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22. TRANSFORMERS LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH DIV. 22 CONTRACTOR. Registration Number J O-B1A /19 O-B1A /2 8 248 CASHIER 17 17 REFERRAL COORDINATOR OFFICE 3 1 242 7 17 7 STAIR B 60" 11 120V CONNECTION TO ALL SHOWN FIRE/SMOKE DAMPERS IN THIS AREA. CIRCUIT ALL FIRE/SMOKE DAMPERS ON THIS PLAN TO THE INDICATED CIRCUIT. COORDINATE WITH MECHANICAL CONTRACTOR FOR LOCATIONS. REFER TO FIRE ALARM DETAILS SHEET FOR ADDITIONAL INFORMATION. James A. LeClaire Signature NR-22B /20 NR-22B /2 O-21B /21 3 AC 243 25 O-21B /19 17 17 6 31 AC 40 N-22 /8,10 256 246 19 239 19 9 RECEPTION 240 VSN-1 O-21B /23 J PATIENT TOILET 267 11 AC 11 AC 120V CONNECTION TO FUME HOOD. NP OFFICE O-21B /17 WORK OTC SALES CONSULTATION AREA 40 STORAGE 5 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 40 8 NR-22B /28 19 7 O-B1A /2 J 266 MOUNT DEVICES HORIZONTALLY UNDERNEATH PERIMETER FIN TUBE RADIATION. J 37 J 17 4 29 N-21 /1 13 HALLWAY POWER CONNECTION AND SWITCH FOR LAB TOILET WATER SHUTT OFF. SWITCH SHALL HAVE AN INDICATOR LIGHT AND BE LABELED AS "LIGHT ON VALVE ON" AND "LIGHT OFF VALVE OFF" 29 7 AC 229 36 NR-22B /16 AC 36 32 O-21B /10 MED/ NOURISH 38 ROOM AC AC O-21B /12 230 O-21B /16 28 CLEAN SUPPLY 38 234 O-21B /14 32 AC AC 32 32 O-21B /13 207 13 231 O-21B /11 NR-22B /14 AC 26 48" 24 3 270 26 NR-32B /5 NR-32B /5 22 AC RECEPTACLE FOR ELECTRIC WATER COOLER. PROVIDE GFCI BREAKER AT INDICATED CIRCUIT. COORDINATE RECEPTACLE MOUNTING HEIGHT WITH EQUIPMENT ACCESS IN THE FIELD. 224 AC STAFF TOILET 34 232 NURSE STATION AC O-21B /31 O-21B /26 TREATMENT ROOM O-21B /11 41 2 AC 22 O-21B /15 MD OFFICE 35 48" 255 AC 10 27 48" 35 28 2 27 271 37 AC 26 E D.9 25 O-B1A /7 J LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD. 223 25 AC EXAM ROOM 33 35 265 MD OFFICE 35 1 25 O-21B /29 AC 38 48" 38 NR-21A /40 O-21B /11 10 AC AC AC E-21 /18 3 13 48" 8 AC 29 15 205 HALLWAY 264 AC 33 AC HALLWAY 29 60" 203 15 238 24 48" 8 48" 4 2 13 AC 38 38 48" 48" 40 48" NR-21B /5 HALLWAY 35 29 15 40 24 48" 20 48" J O-B1A /2 13 1 OBSERVATION (IVS) - EKG KEY NOTES: 23 235 O-21B /29 36 AC O-21B /30 233A 216 36 AC 236 INJECTION ROOM E-21 /9 6 EXAM ROOM 217 7 CONFERENCE 22 AC 222 CONSULT ROOM (CAPS) O-21B /28 30 AC O-21B /30 MEDICAL DIRECTOR OFFICE 23 34 48" CONSULT ROOM (E-EXAM) O-21B /28 26 AC NR-21B /3 N-22 /2 N-22 /2 J J 34 30 AC 237 COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. 3 48" 27 261 AC 26 AC 215 18 O-21B /22 AC HALLWAY 5 TRIAGE ROOM AC 22 O-21B /24 48" Dunham Job #: 415134 23 48" 32 32 28 28 48" EXAM ROOM O-21B /22 10 AC AC 18 48" N-22 /2 J N-22 /2 O-21B /20 6 AC O-21B /24 31 J O-B1A /2 7 J O-B1A /2 J SHS ASST DIRECTOR 14 AC 10 AC 214 AC AC 14 31 MENS RESTROOM AC 9 31 FSD 8 211 6 O-21B /20 2 AC 9 AC 8 J EXAM ROOM 213 STAIR C S203 N-21 /3 N-21 /3 J CUSTODIAN 209 2 AC 6 262 48" ISOLATION EXAM HALLWAY 3 27 48" 12 12 48" 8 8 K. Consultants Mini Fridge NR-21B /3 REF. 27 FSD 1 SERVICE ELEVATOR 48" 4 4 48" J F 612.677.7100 612.677.7499 fax www.rsparch.com 3 REF. Low for microwave 257 NR-21B /3 48" 1 23 HALLWAY 6 N-21 /19 13 J FSD 3 263 FSD FVAV 201 1 208 2 E202 FSD 1 AC HALLWAY 1 FSD UCHOOSE ADMINISTRATOR 1 NR-22B /12 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 SECOND LEVEL POWER PLAN 1/8" = 1'-0" Revisions No. NR-21B /7 Date Description G NR-21B /9 N-21 O-21B /3 E-21 /13 J 14 NR-21A O-21B /5 J O-21B O-21A /8 O-21B /1 11 J E-21 NR-11A /23 O-21B /7 O-21B /9 FSD O-21A NR-21B /11 NR-21B /15 253 NR-21B DATA 254 ELECTRICALE-21 /12 3 SECOND FLOOR ELECTRICAL AND DATA ROOMS 2 1/4" = 1'-0" C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:02:58 PM SECOND LEVEL POWER PLAN E202 GENERAL POWER NOTES: A. VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH ARCHITECTURAL ELEVATIONS. B. ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. C. MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6” ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL ELEVATIONS FOR COUNTER HEIGHTS. D. REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT. E. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. F. REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL SYSTEMS. G. COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING. H. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. I. PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET. J. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. 1 CUH 303 J 1 1 SHHS CLINICAL ROOM 1 21 10 J 1 1 CUSTODIAN 300 353 2 362 399 34 4 PRACTICUM THERAPY 364 3 2 NR-31B /3 21 3 SHHS CLINICAL ROOM 4 CLOSET 11 391 11 J SHHS GROUP THERAPY ROOM 5 11 11 SHHS CLINICAL ROOM 11 PRACTICUM THERAPY 369 4 6 12 14 14 AC USB 8 10 8 PRACTICUM THERAPY PRACTICUM THERAPY 368 367 10 12 20 20 AC USB AC USB AC USB 8 26 28 7 34 AC USB 372 32 NR-31B /7 340 393 396 13 7 NR-32A /12 NR-32A /12 WOMENS RESTROOM NR-31B /7 21 9 303 12 GROUP THERAPY ROOM 14 37 9 J 1 N-31 /20,22 J 10 397 RELAXATION ROOM PASS ELEVATOR 382 30 37 30 THERAPIST OFFICE 15 381 375 376 11 THERAPIST PREDOCTORAL 8 25 1 C 11 11 J 15 N-31 /24 STAIR A J N-31 /5 25 S301 15 23 23 ADMIN SUPPORT/ RECEPTION 23 323 23 25 33 2 385 35 27 AC CASE MANAGER INTERN 10 35 AC 31 AC 2 4 388 29 29 2 4 35 4 10 31 33 VS N-1 N-1 VS CIRCUIT TO NR-31A UNO A CIRCUIT TO NR-32A UNO CAPS DIRECTOR OFFICE -1 33 2 389 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 31 2 2263.001.00 Drawn By Date AA 9 Project No. MMK Checked By V SN N-1 VS 23 1 2 120V CONNECTION TO AUTOMATIC DOOR OPENER. VERIFY LOCATIONS AND MOUNTING HEIGHT WITH ARCHITECTURAL PLANS. 320 2 1 11 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 29 1 0 ELECTRICAL CONNECTION TO SMOKE GUARD. WORK ROOM 31 2 10 27 27 2 23 120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER. STUDENT HEALTH AND ACADEMIC RENOVATION 35 29 31 23 9 Project For CASE MANAGER OFFICE 419 AC ALL RECEPTACLES SHOWN WITHIN DASHED LINE SHALL BE HOSPITAL GRADE DEVICE, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 07/24/15 AC 6 422 KITCHEN 33 8 Date 50358 B 27 FILE & ARCHIVE 321 6 PRIVATE WAITING AREA 4 35 359 STAFF BREAK ROOM 324 CONFERENCE /GROUP ROOM 35 STUB THREE (3) 3/4" CONDUITS UP TO ACCESSIBLE CEILING SPACE IN CORRIDOR FOR FUTURE USE. Registration Number B.2 387 AC 7 James A. LeClaire S302 360 CAPS ENTRY INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL CONTRACTOR) AT SHOWN LOCATION, 208V CONNECTION TO HAND DRYER. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHT. REFER TO PANELBOARD SCHEDULE FOR ADDITIONAL INFORMATION REGARDING CIRCUIT BREAKER SIZE AND TYPE. Signature HALLWAY AC 35 4 23 35 18 4 6 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. STAIR B 10 AC 6 35 35 60" 35 120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS (TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/ WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS. PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22. TRANSFORMERS LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH DIV. 22 CONTRACTOR. 379 8 8 5 15 B.8 11 120V CONNECTION TO ALL SHOWN FIRE/SMOKE DAMPERS IN THIS AREA. CIRCUIT ALL FIRE/SMOKE DAMPERS ON THIS PLAN TO THE INDICATED CIRCUIT. COORDINATE WITH MECHANICAL CONTRACTOR FOR LOCATIONS. REFER TO FIRE ALARM DETAILS SHEET FOR ADDITIONAL INFORMATION. C.3 25 378 STORAGE/AV 1 THERAPIST OFFICE AOD COUNSELOR 7 1 12 363 9 7 60" 3 4 23 15 NR-31A /26 11 3 3 120V CONNECTION TO FIRE ALARM NAC PANEL. THERAPIST OFFICE 23 15 9 7 1 E-21 /20 STORAGE 302 5 384 SHHS FACULTY COMMAND CENTER 14 SHHS CLINICAL ROOM N-31 /19,21 AC 6 J NR-31B /1 3 374 10 HALLWAY 9 J 5 380 6 J AC 13 377 9 MOUNT DEVICES HORIZONTALLY UNDERNEATH PERIMETER FIN TUBE RADIATION. D C.9 23 N-32 /8,10 O-B1A /4 AOD COUNSELOR 1 15 355 13 5 6 361 1 383 2 21 5 3 LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD, OFFSET FROM ROOF PENETRATION INTO FURRED OUT WALL. 21 21 THERAPIST PREDOCTORAL 1 373 26 3 RELAXATION ROOM SHHS FACULTY COMMAND CENTER HALLWAY 7 19 STAFF TOILET 1 E D.9 THERAPIST OFFICE 32 NR-31B /9 NR-31B /9 28 19 THERAPIST OFFICE 20 20 AC USB COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. KEY NOTES: USB 16 16 Dunham Job #: 415134 1 19 CAPS INTERN OFFICE 370 Consultants 371 22 22 32 32 612.677.7100 612.677.7499 fax www.rsparch.com THERAPIST OFFICE 17 AC USB 24 32 26 J O-B1A /4 21 1 AC USB 22 22 7 24 20 20AC 398 AC USB OPEN STUDY 5 21 394 PRACTICUM INTERN OFFICE 16 16 8 24 24 K. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 17 17 18 18 AC USB 18 18 AC USB AC USB 6 26 352 5 SHHS CLINICAL ROOM 14 14 NR-31B /3 O-B1A /4 J 5 O-B1A /4 J AC 17 366 10 354 6 365 12 MENS RESTROOM J 301 5 392 J PRACTICUM THERAPY NR-31B /3 J N-31 /7 N-31 /15,17 UNISEX RESTROOM 395 AC C PRACTICUM THERAPY 2 N-31 /7 N-31 /16,18 FSD N-31 /23,25 FVAV 301 3 J 6 6 4 17 FSD 341 26 26 SERVICE ELEVATOR DATA ROOM F N-32 /6 FSD E-21 /21 NR-31B /3 ELECTRICAL ROOM J 356 42 390 4 N-32 /6 FSD CIRCULATION 21 2 E203 4 CIRCUIT TO NR-32A UNO NR-32A DN CIRCUIT TO NR-31A UNO N-32 S300 NR-32B STAIR D RSP Architects 10 11 JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 THIRD LEVEL ELECTRICAL PLAN 1/8" = 1'-0" Revisions No. Date Description NR-31A /38 NR-31A /42 G J O-21A /10 N-31 O-21B /4 9 ELECTRICAL ROOM NR-31A O-21B /6 300 E-21 /14 NR-31A /19 J 3 NR-31B NR-31A /36 E-21 /15 DATA ROOM 399 O-21B /2 J O-21B /8 NR-21B /13 NR-31A /40 2 2 THIRD FLOOR ELECTRICAL AND DATA ROOMS 1/4" = 1'-0" C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:03:16 PM 3 THIRD LEVEL POWER PLAN E203 GENERAL POWER NOTES: A. VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH ARCHITECTURAL ELEVATIONS. B. ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. C. MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6” ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL ELEVATIONS FOR COUNTER HEIGHTS. D. REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT. E. ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS. F. REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL SYSTEMS. G. COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING. H. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. I. PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET. J. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. K. COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION. RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 KEY NOTES: F 1 FREE STANDING STEEL CHANNEL RACK TO MOUNT DISCONNECTS AND/OR RECEPTACLES. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. EF 02 WP 36" NR-32B /1 Signature James A. LeClaire Registration Number 1 E D.9 Date 50358 07/24/15 Project For EF 01 36" NR-31B /5 WP 1 D C.9 C.3 STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 C B.8 B.2 B EF 03 WP NR-32B /3 36" Project No. 2263.001.00 Drawn By 1 MMK Checked By Date A AA JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. 0 1 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 Date Description 11 ROOF POWER PLAN 1/8" = 1'-0" ROOF POWER PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:06:31 PM E204 GENERAL SIGNAL NOTES: A. DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT, BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS NOTED OTHERWISE. B. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. C. ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES. D. ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS. RSP Architects E. REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING FIRE ALARM SYSTEM. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 F. MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS. G. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. 612.677.7100 612.677.7499 fax www.rsparch.com Consultants KEY NOTES: UP F SMOKE DETECTOR FOR ELEVATOR RECALL. 2 EZ PATH 44 SERIES. 3 FIRE ALARM HORN/STROBE ABOVE SIAMESE CONNECTION. VERIFY LOCATION WITH PLUMBING PLANS. 4 FLOW AND TAMPER SWITCHES LOCATED AT WATER AND FIRE ENTRANCES. COORDINATE EXACT LOCATIONS WITH MECHANICAL. 5 FIRE ALARM CONNECTION TO SMOKE GUARD. F 1 5 1 F P F CM S STORAGE S F Dunham Job #: 415134 054 CORRIDOR 03A SERVICE ELEVATOR EXERCISE/TRAINING 009 E2 F F S S P P F S F F P F FS E D.9 S F FS S F WAITING SHOWER/ RESTROOM EXAM/ CONSULT EXAM/ CONSULT RESISTANCE TRAINING 011 010 035 003 Signature James A. LeClaire Registration Number 50358 Date 007 MECHANICAL ROOM 07/24/15 Project For 052 SHOWER/ RESTROOM SHOWER/ RESTROOM 050 006 FS I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. MENS LOCKER ROOM FS D C.9 008 F F CORRIDOR S 055 WOMANS LOCKER ROOM S FS 051 P SHOWER/ RESTROOM F SHOWER RESTROOM F 005 S F FS MECHANICAL ROOM 013 S FS P P P F F F 032 C.3 STUDENT HEALTH AND ACADEMIC RENOVATION PASS./SERV. ELEV. EQUIP. ROOM 5 004 P F P E1 1 FS F SHOWER/ RESTROOM CUSTODIAN 001 P S 018 014 CORRIDOR C R FS 016 PASSENGER ELEVATOR F UNISEX TOILET/SHOWER F CM P S F F S F F S F F FS P S F S F F B.8 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 S F STAIR B 2 S002 F S F S F B.2 FS FACP B DATA ROOM 021 P P F F F BUILDING SUPPORT P P F F P 033 S F F P ELECTRICAL ROOM 022 MECHANICAL ROOM 019 F TS TS TS P F F FS F F FS F TS F F FS F TS TS F F FS 4 3 F A Project No. 2263.001.00 Drawn By MMK Checked By JL Date AA 0 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 LOWER LEVEL SYSTEMS PLAN 1/8" = 1'-0" Revisions No. Date Description LOWER LEVEL SYSTEMS PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:03:27 PM E300 GENERAL SIGNAL NOTES: A. DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT, BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS NOTED OTHERWISE. B. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. C. ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES. D. ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS. E. REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING FIRE ALARM SYSTEM. F. MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS. G. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants UP KEY NOTES: STAIR D S100 DN Dunham Job #: 415134 CIRCULATION VESTIBULE S F 113 S F 4 2 S F P CM F F 135 REF. F P 2 EZ PATH 44 SERIES. 3 FIRE ALARM CONNECTION TO SHOWN FIRE/SMOKE DAMPERS NEAR THIS LOCATIONS. COORDINATE WITH MECHANICAL CONTRACTOR FOR LOCATIONS. REFER TO FIRE ALARM DETAIL SHEET REGARDING FIRE ALARM INTERFACE. REFER TO POWER PLANS FOR 120VAC CONNECTION. 4 FIRE ALARM CONNECTION TO SMOKE GUARD. 5 ROUGH-IN FOR FUTURE CARD READER AND ELECTRONIC LOCK SET AT INDICATED DOOR. F S F P F SMOKE DETECTOR FOR FIRE ALARM RECALL. P S F 1 1 5 F ELECTRICAL DATA 130 131 P F F NAC 114 2 3 F SD VENDING CM F FSD 133 102 124 E D.9 117 P F S F CM F F SD 3 S F S CM F F SD F Signature James A. LeClaire 50358 FS P F I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Registration Number FSD STORAGE SHELL SPACE PEER ED/ UCHOOSE STUDENT STAFF WORK 116 FSD HEALTH ED INTERDISCIPLINARY SERVICE ELEVATOR P S F S F Date 5 07/24/15 Project For F S P 5 F FS CIRCULATION D C.9 118 P F MENS RESTROOM S F RADIOLOGY (COMMUNITY PARTNER) 107 SHHS INTERDISCIPLINARY UNISEX TOILET FS 123 S F 132 WOMENS RESTROOM 108 C.3 S F FS 103 STUDENT HEALTH AND ACADEMIC RENOVATION P F STORAGE S 104 4 F CM F DIRECTORY 111 C PASS ELEVATOR F P 1 115 LACTATION ROOM CIRCULATION P F S F P 105 F 106 B.8 S F S F S F FS S F DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 STAIR A S102 STAIR A S101 B.2 S F B GRAD ASSIST 122 INFO/KIOSK RESEARCH ASST. INFO/KIOSK 129 136 S F S F 110 RECOVERY COMMUNITY RESOURCE AREA RESEARCHER P 128 P F S F F F S F P RESEARCH DIRECTOR UCHOOSE & RC UCHOOSE & RC HEALTH ED & PROMOTION COORD 125 121 120 119 134 S F FS RESEARCH COORDINATOR A 127 126 NORTH ENTRY SOUTH ENTRY 112 109 Date AA 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 MMK Checked By FAAP 1 2263.001.00 Drawn By RESEARCH DATA 0 Project No. 8 9 10 11 JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 FIRST LEVEL SYSTEMS PLAN 1/8" = 1'-0" Revisions No. Date Description FIRST LEVEL SYSTEMS PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:03:37 PM E301 GENERAL SIGNAL NOTES: STAIR D S200 F F 263 4 2 208 S F CM F S F S S F ELECTRICAL FP 253 HALLWAY SOILED HOLD 262 252 P NAC F SERVICE ELEVATOR DATA 206 254 SHS DIRECTORS CUSTODIAN 209 212 LARGE CENTRAL SUPPLY F Low for microwave S TRIAGE ROOM CONSULT ROOM (E-EXAM) CONSULT ROOM (CAPS) 213 214 215 237 236 235 F SD SD 3 F CM F FSD P CM F F SD S F 202 MENS RESTROOM S F 201 EXAM ROOM EXAM ROOM EXAM ROOM 218 217 216 F F F S OBSERVATION (IVS) - EKG INJECTION ROOM EXAM ROOM 233A 238 271 MD OFFICE 223 E D.9 224 P P 261 P F F F HALLWAY S F F F F S 264 S P HALLWAY S F 265 EXAM ROOM EXAM ROOM EXAM ROOM REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING FIRE ALARM SYSTEM. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 F. MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS. G. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. 612.677.7100 612.677.7499 fax www.rsparch.com Consultants 1 SMOKE DETECTOR FOR ELEVATOR RECALL. 2 EZ PATH 44 SERIES. 3 FIRE ALARM CONNECTION TO SHOWN FIRE/SMOKE DAMPERS NEAR THIS LOCATIONS. COORDINATE WITH MECHANICAL CONTRACTOR FOR LOCATIONS. REFER TO FIRE ALARM DETAIL SHEET REGARDING FIRE ALARM INTERFACE. REFER TO POWER PLANS FOR 120VAC CONNECTION. 4 FIRE ALARM CONNECTION TO SMOKE GUARD. Dunham Job #: 415134 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature Bryan Schmidt 26566 07/24/15 HALLWAY S 259 NP OFFICE D C.9 219 220 221 S STAFF TOILET TREATMENT ROOM F NP OFFICE 255 270 232 S WOMENS RESTROOM F 203 S F F S F 260 F E. Project For 258 WAITING CIRCULATION 205 RSP Architects Date HALLWAY F F ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS. 227 P CONFERENCE D. Registration Number S HALLWAY ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES. MD OFFICE S SHS ASST DIRECTOR S C. 222 F F DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. Mini Fridge MEDICAL DIRECTOR OFFICE S 210 B. REF. SD CM F F 3 UNISEX RESTROOM 211 F F S EXAM ROOM FSD CM F 257 EXAM ROOM FSD F S P F F P ISOLATION EXAM 2 P HALLWAY SD CM F F 3 P CM F F SD F P F F FSD S UCHOOSE ADMINISTRATOR P F FSD F F P F P FSD 1 DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT, BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS NOTED OTHERWISE. KEY NOTES: UP UP HALLWAY A. S S F F NURSE STATION S 231 PROCESS ROOM F P C.3 229 STUDENT HEALTH AND ACADEMIC RENOVATION S F S 4 EXAM ROOM EXAM ROOM 226 225 269 230 F P 1 PASS ELEVATOR 207 NURSING MANAGER MED/ NOURISH ROOM 228 C REF. CLEAN SUPPLY REF. F CM EXAM ROOM 234 P B.8 F P P F S F STAIR A F F S F F HALLWAY S 266 P F F S S FS S201 F STORAGE P 240 F F RECEPTION WORK F 243 246 S S 239 S B.2 S F F VSN-1 -1 V SN S202 256 B OTC SALES VSN-1 STAIR B PATIENT TOILET 267 CONSULTATION AREA DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 S F PRESCRIPTION PICK-UP/DROP-OFF 242 CASHIER 244 245 REFERRAL COORDINATOR OFFICE 247 248 P F F SUB WAITING S S F P PHLEBOTOMY LAB TOILET 249 S F PHARMACY F BUSINESS MANAGER STUDENT INSURANCE ADVOCATE F 250 268 241 LABORATORY S 251 Project No. A S F 2263.001.00 Drawn By MMK Checked By JL Date AA 0 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 SECOND LEVEL SYSTEMS PLAN 1/8" = 1'-0" Revisions No. Date Description SECOND LEVEL SYSTEMS PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:03:51 PM E302 GENERAL SIGNAL NOTES: A. DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT, BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS NOTED OTHERWISE. B. DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. C. ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES. D. ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS. RSP Architects E. REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING FIRE ALARM SYSTEM. 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 F. MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS. G. PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK. S300 Dunham Job #: 415134 DN 3 P S F SHHS CLINICAL ROOM 4 S CM F F F 1 S F P SHHS CLINICAL ROOM NAC 353 PRACTICUM THERAPY PRACTICUM THERAPY PRACTICUM THERAPY 364 365 366 S F S F S F F S S THERAPIST OFFICE FSD CLOSET F CM F CM 341 3 SD F SD FFSD FS F MENS RESTROOM FS PRACTICUM THERAPY PRACTICUM THERAPY PRACTICUM THERAPY 369 368 367 S F S F S F PRACTICUM INTERN OFFICE CAPS INTERN OFFICE 398 370 F S 373 P P P F 352 P F F F F S S S F F F S F 340 P GROUP THERAPY ROOM Project For S S 384 397 377 THERAPIST OFFICE S STAFF TOILET 374 361 P F P F P HALLWAY 394 303 F F FS SHHS FACULTY COMMAND CENTER AOD COUNSELOR F S SHHS CLINICAL ROOM THERAPIST PREDOCTORAL 380 355 S F F 07/24/15 D C.9 383 WOMENS RESTROOM 396 F 50358 F F S S RELAXATION ROOM SHHS FACULTY COMMAND CENTER HALLWAY James A. LeClaire P SHHS CLINICAL ROOM 393 Signature Date OPEN STUDY F I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. THERAPIST OFFICE 301 392 FIRE ALARM CONNECTION TO SMOKE GUARD. Registration Number S 354 S F SHHS CLINICAL ROOM 4 F UNISEX RESTROOM 395 E D.9 372 F SHHS GROUP THERAPY ROOM FIRE ALARM CONNECTION TO SHOWN FIRE/SMOKE DAMPERS NEAR THIS LOCATIONS. COORDINATE WITH MECHANICAL CONTRACTOR FOR LOCATIONS. REFER TO FIRE ALARM DETAIL SHEET REGARDING FIRE ALARM INTERFACE. REFER TO POWER PLANS FOR 120VAC CONNECTION. P F F P 391 S 3 F F S EZ PATH 44 SERIES. 371 399 S F 2 S DATA ROOM F SMOKE DETECTOR FOR ELEVATOR RECALL. S 362 F CUSTODIAN S F F SERVICE ELEVATOR P F P F P F 1 THERAPIST OFFICE S P SD F FSD FSD F SD 356 S F F CM F ELECTRICAL ROOM 300 3 F CM P 390 S F CIRCULATION P F P F F Consultants KEY NOTES: STAIR D F 612.677.7100 612.677.7499 fax www.rsparch.com F S F C.3 F S STUDENT HEALTH AND ACADEMIC RENOVATION S THERAPIST OFFICE S F CM F 4 STORAGE PASS ELEVATOR 302 RELAXATION ROOM P F 363 THERAPIST PREDOCTORAL AOD COUNSELOR 379 378 376 THERAPIST OFFICE F 375 S C 382 1 STORAGE/AV HALLWAY 381 360 B.8 P F F S F P STAIR A F S301 F F S S S P DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 F FS F S B ADMIN SUPPORT/ RECEPTION F S F CAPS ENTRY S 323 B.2 P F 321 CASE MANAGER INTERN 387 STAFF BREAK ROOM 324 F PRIVATE WAITING AREA S 422 KITCHEN CONFERENCE /GROUP ROOM 419 359 FILE & ARCHIVE P F CASE MANAGER OFFICE 385 F 388 S F P S F WORK ROOM 320 F S CAPS DIRECTOR OFFICE VS N-1 S 389 N-1 VS F A Project No. 2263.001.00 Drawn By MMK V SN -1 N-1 VS Checked By JL Date AA 0 1 2 3 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. 1 THIRD LEVEL SYSTEMS PLAN 1/8" = 1'-0" Revisions No. Date Description THIRD LEVEL SYSTEMS PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:04 PM E303 GENERAL NOTES: 1/E405 4/E405 4/E405 4/E405 4/E405 A. REFER TO NFPA-780 INSTALLATION OF LIGHTNING PROTECTION SYSTEMS, FOR FURTHER INFORMATION. B. THE TIP OF AN AIR TERMINAL SHALL BE NOT LESS THAN 10 INCHES ABOVE THE OBJECT OR AREA IT IS TO PROTECT. C. THE DISTANCE BETWEEN STRIKE TERMINATION DEVICES AND EDGES OR OUTSIDE CORNERS OF ROOF, SHALL NOT EXCEED 2 FEET. D. STRIKE TERMINATION DEVICES SHALL BE PLAED AROUND THE PERIMETER OF ROOFS. AT INTERVALS NOT EXCEEDING 20 FEET. E. THE MAIN ROOF CONDUCTOR SHALL BE RUN ADJACENT TO THE VERTICAL ROOF MEMBERS SO THAT THE SINGLE CABLE FROM THE STRIKE TERMINATION DEVICE IS AS SHORT AS POSSIBLE AND IN NO CASE LONGER THAN 16 FEET. F. EACH DOWN CONDUCTOR SHALL TERMINATE AT A GROUNDING ELECTRODE DEDICATED TO THE LIGHTNING PROTECTION SYSTEM. 2/E405 1/E405 4/E405 1 4/E405 4/E405 4/E405 4/E405 4/E405 4/E405 4/E405 4/E405 4/E405 2/E405 2/E405 1/E405 4/E405 2/E405 2/E405 1 1 2/E405 6/E405 6/E405 F 1/E405 1 7/E4045 4/E405 4/E405 4/E405 4/E405 7/E405 3 E D.9 G. GROUNDING ELECTRODES SHALL BE INSTALLED BELOW THE FROST LINE WHERE POSSIBLE. H. GROUND RODS SHALL BE NOT LESS THAN 3/4" IN DIAMETER AND 8' LONG. I. THE GROUND RODS SHALL EXTEND VERTICALLY NOT LESS THAN 10 FEET INTO THE EARTH. J. WHERE MULTIPLE GROUND RODS ARE USED. THE SEPERATION BETWEEN ANY TWO GROUND RODS SHALL BE AT LEAST THE SUM OF THEIR DRIVEN DEPTHS, WHERE PRACTIBLE. K. ALL GROUNDING MEDIA AND BURIED METALLIC CONDUCTORS THAT CAN ASSIST IN PROVIDING A PATH FOR LIGHTNING CURRENTS IN OR ON A STRUCTURE SHALL BE INTERCONNECTED TO PROVIDE A COMMON GROUND POTENTIAL. THIS INTERCONNECTION SHALL INCLUDE LIGHTNING PROTECTON, ELECTRIC SERVICE, COMMUNICATIONS, AND ANTENNA SYSTEM GROUNDS, AS WELL AS UNDERGROUND METALLIC PIPING SYSTEMS. 3 RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 4 4/E405 4 4/E405 4 4 6/E405 4/E405 4/E405 D C.9 KEY NOTES: 4/E405 4/E405 2/E405 C.3 1/E405 4/E405 4/E405 2/E405 C 2/E405 1 1/E405 1 6/E405 4/E405 4/E405 4/E405 4/E405 B.8 1 DOWNLEAD CONDUCTOR FROM ROOF DOWN THROUGH NEW ROOF PENETRATION, AND THEN THROUGH NEW INTERIOR STUD WALLS TO GROUND ROD LOCATION. SEE SHEETS E200, E201, E202, E203 FOR CONTINUATION OF DOWNLEAD CONDUCTORS. 2 BOND TO ROOF HATCH. 3 BOND TO LADDER 4 BOND TO ROOF DRAIN. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For 6/E404 B.2 4/E405 4 4/E405 4/E405 B 4 2 4 4 STUDENT HEALTH AND ACADEMIC RENOVATION 7/E405 4/E405 4/E405 2/E405 2/E405 4/E405 4/E405 4/E405 4/E405 4/E405 4/E405 4/E405 A 6/E405 1 1 4/E405 4/E405 4/E405 1 2 3 AA 4/E405 4/E405 1/E405 1/E405 1 6/E405 2/E405 2/E405 0 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 4 4.2 4.5 4.8 5 CL 5.55.6 66.2 6.7 7 8 9 10 11 LIGHTNING PROTECTION PLAN 1/8" = 1'-0" Project No. 2263.001.00 Drawn By DM Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description LIGHTNING PROTECTION PLAN C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:05:33 PM E404 28str x 14Ga BARE Cu CONDUCTOR SOLID Alum BLUNT TIP AIR TERMINAL 1" PVC CONDUIT BY ELECTRICAL CONTRACTOR SEE AIR TERMINAL DETAIL NOTES: 1. DEPTH OF GROUNDING PER CONTRACT ST UB REQUIREMENTS OR CODE. BE C LO ON W DU GR IT AD OU EO TA R P PP ER ROX CO IMA NT TE RA LY CT 6" RE - 12 QU " IR EM EN TS BARE CONDUCTOR BARE Alum CONDUCTOR CABLE FROM HIGH ROOF DOWN TO LOW ROOF RSP Architects SEE ROOF PENETRATION DETAIL 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 SEE AIR TERMINAL DETAIL STUB OUT ABOVE LOW ROOF COUNTER-FLASHING SINCE CAP IS EITHER GALVANIZED OR ALUMINUM, ALL LIGHTNING PROTECTION SYSTEM MATERIALS MUST BE OF ALUMINUM CONSTRUCTION FOR CODE COMPLIANCE AND ELECTROLYTIC COMPATIBILITY. 1" PVC CONDUIT - BY ELECTRICAL CONTRACTOR GRADE 6" - 1'-0" MAX. 3/4" GROUND ROD CLAMP 2' MIN. SEE GROUND ROD DETAIL CROSS RUN CABLE CLAMP 0" MI N. 3/4" x 10' COPPER-CLAD GROUND ROD 1 GROUND ROD - CONDUIT TO CROSS RUN CLAMP DETAIL NO SCALE 2 612.677.7100 612.677.7499 fax www.rsparch.com Consultants CABLE FROM ROOF DOWN TO GROUND 2' - Alum ADHESIVE FLAT MOUNT POINT BASE ADHESIVE CABLE HOLDER @ 3'-0" O/C DOWNLEAD ROUTING IN CONDUIT - TWO LEVEL WITH PARAPET DETAIL NO SCALE REFER TO INSPEC ROOFING DETAILS FOR ROOF PENETRATION REQUIREMENTS 3 ROOF PENETRATION DETAIL NO SCALE 4 SINCE MECHANICAL EQUIPMENT IS EITHER GALVANIZED OR ALUMINUM, ALL LIGHTNING PROTECTION SYSTEM MATERIALS MUST BE OF ALUMINUM CONSTRUCTION FOR CODE COMPLIANCE AND ELECTROLYTIC COMPATIBILITY. SINCE MECHANICAL EQUIPMENT IS EITHER GALVANIZED OR ALUMINUM, ALL LIGHTNING PROTECTION SYSTEM MATERIALS MUST BE OF ALUMINUM CONSTRUCTION FOR CODE COMPLIANCE AND ELECTROLYTIC COMPATIBILITY. Dunham Job #: 415134 AIR TERMINAL - PARAPET TOP MOUNT DETAIL NO SCALE TYPICAL BONDING AND SPLICING M S = MAIN, FULL SIZE CABLE = SECONDARY SIZE CABLE I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature Alum BLUNT TIP AIR TERMINAL James A. LeClaire Registration Number 50358 SOLID Alum BLUNT TIP AIR TERMINAL Date MECHANICAL EQUIPMENT POINT BASE - Alum SOLID Alum BLUNT TIP AIR TERMINAL FLAT MOUNT POINT BASE - Alum Project For M No. 800: BONDING STRAP M No. 240 or 240X: BONDING CLAMP SWIVEL POINT ADAPTER BARE Alum CONDUCTOR ADHESIVE CABLE HOLDER @ 3'-0" O/C M ADHESIVE FLAT MOUNT POINT BASE No. 142X: SECONDARY SIZE BONDING CLAMP No. 702: BONDING PLATE S BOND PLATE No. 423B: PARALLEL CABLE SPLICER BARE Alum CONDUCTOR M BARE Alum CONDUCTOR No. 551: BONDING LUG ALUM PARALLEL CABLE SPLICER 07/24/15 STUDENT HEALTH AND ACADEMIC RENOVATION M Alum PARALLEL CABLE SPLICER No. 561: BONDING LUG M S No. 143: CABLE SPLICER M M No. 142HD: FLAT METAL BONDING CLAMP DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 S AIR TERMINAL - SWIVEL POINT ADAPTER DETAIL 5 NO SCALE AIR TERMINAL - MECHANICAL VENT - PARALLEL CABLE DETAIL 6 NO SCALE AIR TERMINAL - MECHANICAL EQUIPMENT - PARALLEL CABLE DETAIL 7 NO SCALE 8 TYPICAL BONDING & SPLICING DETAILS NO SCALE Project No. Drawn By Checked By Date 2263.001.00 Author Checker 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description LIGHTNING PROTECTION DETAILS C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:07:00 PM E405 NAME: MSB ELECTRICAL PANEL NOMENCLATURE VOLTAGE: 120/208 PHASE: 3 WIRE: 4 EQUIPMENT OPTIONS: FR, SPD, M, 200% NEUTRAL MAIN OCPDTYPE: MLO MAIN OCPD OPTIONS: NOT APPLICABLE MINIMUM BUS SIZE: 1600 A MAIN SIZE: MAIN SETTING: LHD - B1 PANEL NUMBER N - NORMAL BRANCH E - EMERGENCY BRANCH R - LEGALLY REQUIRED O - OPTIONAL STANDBY 42,654A CALCULATED A.F.C. R - RECEPTACLE CKT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 B - BASEMENT 1 - 1ST FLOOR 2 - 2ND FLOOR 3 - 3RD FLOOR PM D - DISTRIBUTION 91.5 TRANSFER SWITCH SCHEDULE ATS NAME ATS-E ATS-O ATS-R VOLTAGE 208 V 208 V 208 V SIZE 100 A 200 A 400 A SWITCH TYPE AUTOMATIC AUTOMATIC AUTOMATIC TRANSFER POLES 4-POLE 4-POLE 4-POLE TRANSITION OPEN OPEN OPEN MOUNTING WALL WALL WALL ACCESS FRONT FRONT FRONT OPTIONS ECM, SCM ECM, SCM, LSR ECM, SCM, ECC, ESR NOTES 24.00 BI - BYPASS ISOLATION DO - DRAW OUT ECC - ELEVATOR CONTROL CONTACTS ECM - ETHERNET COMMUNICATIONS MODULE ON - OVERSIZED NEUTRAL PM - POWER MANAGER RA - REMOTE ANNUNCIATOR SCM - SERIAL COMMUNICATION MODULE SMDR - SEQUENTIAL MOTOR DISCONNECT RELAY ESR - ELEVATOR/ESCALATOR PRE-TRANSFER IPM - IN-PHASE MONITOR LSR - LOAD SHED RELAY MDR - MOTOR DISCONNECT RELAY 1.5 42.00 42.00 36.00 GENERAL NOTES A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. TRANSFER SWITCH SHALL HAVE HIGHER SHORT-CIRCUIT CURRENT RATING THAN CALCULATED VALUE SHOWN ON RISER DIAGRAM. 36.00 78.00 ELECTRICAL NOTES: 2 MSB ELEVATION AND FLOOR PLAN NO SCALE OCPD FRAME... TRIP RATING A B C 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 225 A 225 A 1200 A 100 A 400 A 225 A 1000 A 225 A 400 A 225 A 225 A 100 A 100 A 100 A 225 A 225 A 225 A 225 A 1000 A 100 A 300 A 225 A 1000 A 225 A 400 A 225 A 225 A 100 A 100 A 100 A 225 A 225 A 4213 VA 4855 VA 38423 VA 3680 VA 25182 VA 18757 VA 54768 VA 10559 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 3634 VA 4108 VA 38423 VA 3788 VA 25686 VA 18158 VA 46800 VA 9354 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 3554 VA 3376 VA 38423 VA 2155 VA 24990 VA 17177 VA 45320 VA 9054 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA TOTAL CONN. LOAD: 160436 VA TOTAL AMPS: 1345 A DEMAND FACTOR LOAD DEMAND (VA) 125% 40383 VA 10 KVA @ 100%, REMAINING @... 80030 VA 100% 100% 100% 227704 VA 100% 125% 227704 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, REMAINING @... 100% 40200 VA 100% 149950 VA 1257 A 144048 VA 1200 A N-22 N-B2 NRD-B1 ATS-E ATS-R ATS-O NRD-B1 N-B1 SPARE SPARE SPARE SPARE SPARE SPARE FUTURE COMMUNITY PARTNER FUTURE COMMUNITY PARTNER LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) LARGEST MOTOR - PROJECT (DA_LPM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) TRANSFER SWITCH OPTIONS: # OF POLES CIRCUIT DESCRIPTION CONNECTED LOAD (VA) 32306 VA 150060 VA 227704 VA 227704 VA 40200 VA OCPD TYPE OCPD OPTIONS NOTES MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM ET, AIT, TM TOTAL CONN. LOAD: 454435 VA TOTAL EST. DEMAND: TOTAL CONN. CURRENT: 1261 A TOTAL EST. DEMAND... 1089 A NOTES: 1. PROVIDE ARC ENERGY REDUCTION MAINTENANCE SWITCH WITH LOCAL INDICATOR LIGHT AND BEACON LIGHT AT THE MAIN ENTRY TO THE ROOM. 2. PROVIDE DIGITAL METERING AND ASSOCIATED CT'S FOR METERING. 3. 4. MCCB TM - THERMAL MAGNETIC BREAKER ET - ELECTRONIC TRIP CL - CURRENT LIMITING IF - INTERNALLY FUSED GFEP - GROUND FAULT EQUIPMENT GFCI - GROUND FAULT CIRCUIT INTERRUPTION AIT - ADJUSTABLE INSTANTANEOUS TRIP ICCB FB - FIXED BREAKER (5) 4"C, 3#400KCMIL + 2#400KCMIL N + #4/0 G 2 1-1/4"C, 3#3 + #3/0 N + #8 G 3 (4) 3"C, 3#250KCMIL + 2#250KCMIL N + #2/0 G 4 (2) 3-1/2"C, 3#350KCMIL + 2#350KCMIL N + #1 G 5 (2) 3"C, 3#3/0 + #600KCMIL N + #3 G 6 3"C, 3#4/0 + #700KCMIL N + #6 G 7 3-1/2"C, 3#350KCMIL + 2#350KCMIL N + #4 G DOB - DRAW OUT BREAKER SWITCH BPS - BOLTED PRESSURE SWITCH EQUIPMENT OPTIONS SE - SERVICE ENTRANCE RATED LS - LOAD SHEDDING KEY NOTES: 1 LSI MOLDED CASE CIRCUIT BREAKER WITH ARC FLASH MAINTENANCE (AMS) SWITCH. 2 100A/3P ENCLOSED THERMAL MAGNETIC CIRCUIT BREAKER WITH ELECTRONIC TRIP AND ADJUSTABLE INSTANTEOUS TRIP. 3 400A/3P ENCLOSED THERMAL MAGNETIC CIRCUIT BREAKER WITH ELECTRONIC TRIP AND ADJUSTABLE INSTANTEOUS TRIP. 4 225A/3P ENCLOSED THERMAL MAGNETIC CIRCUIT BREAKER WITH ELECTRONIC TRIP AND ADJUSTABLE INSTANTEOUS TRIP. 2 2 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number 50358 Date 07/24/15 OCPD TYPE OPTIONS: OCPD TYPES: 1 RSP Architects TOTALS GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. EQUIPMENT SHALL HAVE STANDARD SHORT-CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. FEEDER SCHEDULE 1, 2 FS - FUSED SWITCH M - METER SR - SERIES RATED GFP - GROUND FAULT PROTECTION CC - COMMUNICATIONS CAPABILITIES UT - UNDERVOLTAGE TRIP KI - KIRK KEY INTERLOCK ZI - ZONE SELECTIVE INTERLOCKING ST - SHUNT TRIP AU - AUXILARY CONTACTS BL - BREAKER LOCK ZI - ZONE SELECTIVE INTERLOCKING KI - KIRK KEY INTERLOCK RT - REMOTE TRIP CC - COMMUNICATIONS CAPABILITIES BL - BREAKER LOCK GFP - GROUND FAULT PROTECTION SRVR - SERVICE RATED BL - BREAKER LOCK H - STRIP HEATERS FR - FULLY RATED EO - EMERGENCY OFF REQUIREMENTS SPD - SURGE PROTECTION DEVICE C - COMPARTMENTALIZED Project For STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 ROOF 3RD FLOOR NORTHEAST ELECTRICAL ROOM SECOND FLOOR N-31 NR-31A NR-31B 8724A 11764A 11608A GENERATOR 600A FRAME 540A TRIP ET, AIT, MCCB C3 C2 FIRST FLOOR C4 2ND FLOOR SOUTHWEST 6 5 NR-32B 5457A 7792A 7722A 6 5 6 Project No. N-21 EXTERIOR PAD MOUNTED OIL FILLED TRANSFORMER RATED AT 500KVA 12.47KV PRIMARY, 208/120V SECONDARY NR-21A NR-21B O-21B O-21A E-21 N-22 NR-22A NR-22B 2263.001.00 Drawn By MMK Checked By 9367A 12675A 6 5 12494A 1ST FLOOR NORTHEAST ELECTRICAL ROOM ENCLOSED CIRCUIT BREAKER - SERVICE ENTRANCE RATED (NEMA 3R) 1600A NR-32A 5 2ND FLOOR NORTHEAST ELECTRICAL ROOM 150KW DIESEL GAS GENERATOR WITH WEATHER PROOF SOUND ATTENUATED ENCLOSURE N-32 M 6 EXISTING PMH SWITCH UTILIZE SPARE FEEDER COMPARTMENT (C4) 5 METERING FOR B3 PLUG LOADS THIRD FLOOR UNDERGROUND PRIMARY TAP FEEDERS - 3-1/0 AWG COPPER, 15KV CABLE AND 1-1/0 AWG COPPER NEUTRAL, FEEDERS SHALL BE CONCRETE ENCASED 3RD FLOOR SOUTHWEST 5 8678A 8817A 6 3346A 7423A 1ST FLOOR SOUTHEAST 8 6 6908A 6822A 5 6 6 N-11 NR-11A NR-11B N-12 NR-12A NR-12B 10109A 10943A 10733A 5628A 9163A 9067A Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. TRANSFORMER 1 C1 BUILDING METER Revisions 6 1 © Copyright RSP Architects 2015. All rights reserved. EXTERIOR 6 EXISTING PRIMARY TAP FEEDERS - 3-1/0 AWG COPPER, 15KV CABLE AND 11/0 AWG COPPER NEUTRAL BASEMENT MECHANICAL ROOM BASEMENT NORTHWEST GEN DISTRIBUTION ELECTRICAL ROOM BASEMENT NORTHWEST MAIN ELECTRICAL ROOM No. Date Description 5 TO RIVERVIEW 6 1 EXISTING PRIMARY LOOP FEEDERS - 3-4/0 AWG COPPER, 15KV CABLE AND 14/0 AWG COPPER NEUTRAL METERING FOR B3 PLUG LOADS 6 7 2 M 6 3 2 6 BASEMENT N-B1 ELECTRICAL RISER DIAGRAM NO SCALE C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:15 PM NRD-B1 NR-B1A 6 NR-B1B 25533A 24477A 21814A 21100A RD-B1 E-B1 DIST 22191A 2 6 2 MSB - SWITCHBOARD 208/120V, 3PH, 4W, 1600A 1 6 6 M INCOMING MAIN LUG AND DIST SECTION 7 4 ATS-E 13410A 2 11854A ATS-R 20147A 7 19269A ATS-O 20311A O-B1A O-B1B 18677A 18120A 3 4 NR-B2 N-B2 ND-B1 7760A 8162A 19660A 6 INCOMING M 6 M GEN DIST ELECTRICAL RISER DIAGRAM METERING FOR B3 PLUG LOADS E500 LUMINAIRE SCHEDULE FIXTURE LETTER FIXTURE TYPE VOLTAGE MOUNTING LAMPS CONTROL MEDIA (LENS, LOUVER, ETC.) MANUFACTURER'S SERIES NUMBERS LUMINAIRE SCHEDULE LUMINAIRE DESCRIPTION NOTES A1 2X4 RECESSED LED TROFFER 120V RECESSED LAY-IN GRID INVERTED TEE LED 4000 LUMENS MIN 35W 3500K FROSTED ACRYLIC LENS METALUX #24CZ SERIES COLUMBIA #LCAT24 SERIES STEEL HOUSING. 0-10V DIMMING DRIVER. WHITE ENAMEL FINISH. STEEL HATCHES. SAFETY-LOCK HINGES. 2 A2 2X4 RECESSED LED TROFFER 120V RECESSED LAY-IN GRID INVERTED TEE LED 7500 LUMENS MIN 75W 3500K FROSTED ACRYLIC LENS METALUX #24CZ SERIES COLUMBIA #LCAT24 SERIES STEEL HOUSING. 0-10V DIMMING DRIVER. WHITE ENAMEL FINISH. STEEL HATCHES. SAFETY-LOCK HINGES. - A3 2X4 RECESSED LED TROFFER 120V RECESSED GYP BOARD LED 4000 LUMENS MIN 35W 3500K FROSTED ACRYLIC LENS METALUX #24CZ SERIES COLUMBIA #LCAT24 SERIES STEEL HOUSING. 0-10V DIMMING DRIVER. WHITE ENAMEL FINISH. STEEL HATCHES. SAFETY-LOCK HINGES. 2 A4 B1 B2 C1 C2 C3 C4 C5 2X4 LENSED TROFFER 2X2 RECESSED TROFFER 2X2 RECESSED TROFFER 4' RECESSED LINEAR 6' RECESSED LINEAR 8' RECESSED LINEAR 6' RECESSED LINEAR 4' RECESSED LINEAR 120V 120V 120V 120V 120V 120V 120V 120V RECESSED LAY-IN GRID INVERTED TEE 2-F32 T8 4100K .125" MINIMUM ACRYLIC LENS RECESSED LAY-IN GRID INVERTED TEE LED 2400 LUMENS MIN 23W 3500K FROSTED ACRYLIC LENS RECESSED GYP BOARD LED 2400 LUMENS MIN 23W 3500K FROSTED ACRYLIC LENS LED 3500K 440 LMNS/FT 7W/FT SATIN LENS LED 3500K 440 LMNS/FT 7W/FT SATIN LENS LED 3500K 515 LMNS/FT MIN 9W/FT MAX SATIN LENS LED 3500K 515 LMNS/FT MIN 9W/FT MAX SATIN LENS LED 3500K 515 LMNS/FT MIN 9W/FT MAX SATIN LENS RECESSED SHEET ROCK FLANGED RECESSED SHEET ROCK FLANGED RECESSED RECESSED RECESSED COLUMBIA #ST824 SERIES LITHONIA #2SP8 SERIES METALUX #2GC8 SERIES DAY-BRITE #2DPG SERIES LIGHTOLIER #SPS2 SERIES WILLIAMS #50G-S24 SERIES SPRING LATCHES. POST PAINTED STEEL HOUSING. FLUSH WHITE ALUM. MITERED CORNERED DOOR FRAME, GASKETED AND/OR WITH METAL LIGHT BAFFLES. DOOR CAN BE LATCHED FROM EITHER SIDE OF HOUSING. ONE ELECTRONIC BALLASTS. - METALUX #22CZ SERIES COLUMBIA #LCAT22 SERIES STEEL HOUSING. 0-10V DIMMING DRIVER. WHITE ENAMEL FINISH. STEEL HATCHES. SAFETY-LOCK HINGES. - STEEL HOUSING. 0-10V DIMMING DRIVER. WHITE ENAMEL FINISH. STEEL HATCHES. SAFETY-LOCK HINGES. - METALUX #22CZ SERIES COLUMBIA #LCAT22 SERIES NEORAY #22DR SERIES AXIS #BRLED SERIES NEORAY #22DR SERIES AXIS #BRLED SERIES EXTRUDED ALUMINUM HOUSING. WHITE POWDER COAT FINISH. 0-10V DIMMING. EXTRUDED ALUMINUM HOUSING. WHITE POWDER COAT FINISH. 0-10V DIMMING. EXTRUDED ALUMINUM HOUSING. WHITE POWDER COAT FINISH. 0-10V DIMMING. NEORAY #23DR SERIES AXIS #BMRLED SERIES EXTRUDED ALUMINUM HOUSING. WHITE POWDER COAT FINISH. 0-10V DIMMING. EXTRUDED ALUMINUM HOUSING. WHITE POWDER COAT FINISH. 0-10V DIMMING. LED 3000K 900 LUMEN 20W L1 3FT DECORATIVE RING 120V SURFACE L2 4FT DECORATIVE RING 120V SURFACE 3FT DECORATIVE RING PENDANT 120V 4FT DECORATIVE RING PENDANT 120V PENDANT PENDANT CONTROL MEDIA (LENS, LOUVER, ETC.) ACRYLIC LENS MANUFACTURER'S SERIES NUMBERS LUMINAIRE DESCRIPTION NOTES TECH LIGHTING #700BCMET SERIES SATIN NICKEL FINISH. - LED 3500K 8600 LUMENS MIN 108W MAX ADVENT #AIP11847 SERIES 5IN. HEIGHT. 0-10V DIMMING. INTEGRAL POWER SUPPLY. MATTE OPAL ACRYLIC FINISH. - LED 3500K 12000 LUMENS MIN 150W MAX ADVENT #AIP11848 SERIES 5IN. HEIGHT. 0-10V DIMMING. INTEGRAL POWER SUPPLY. MATTE OPAL ACRYLIC FINISH. - LED 3500K 8600 LUMENS MIN 108W MAX ADVENT #AIP11847 SERIES LED 3500K 12000 LUMENS MIN 150W MAX ADVENT #AIP11848 SERIES RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 5IN. HEIGHT. 0-10V DIMMING. INTEGRAL POWER SUPPLY. MATTE OPAL ACRYLIC FINISH. - 5IN. HEIGHT. 0-10V DIMMING. INTEGRAL POWER SUPPLY. MATTE OPAL ACRYLIC FINISH. - 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 L5 LED TAPE LIGHT 120V SURFACE/COVE LED 3500K 207 LMNS/FT 3W/FT WAC LIGHTING #LED-T24 SERIES ACCLAIM #FLEX2I SERIES L6 COLORED LINEAR FIXTURE 120V RECESSED LED ACCLAIM #FTA SERIES - FLEXIBLE SILICONE CASED. DIMMING. - - - WALL GRAZE 120V RECESSED - DECORATIVE PENDANT 120V PENDANT - LED 3500K 657 LMNS/FT 12.5W/FT 10° X 60° BEAM ANGLE, POLYCARBONATE LENS LED 3000K 370 LUMENS 4W PRESSED GLASS DIFFUSER PHILIPS #EW FUSE POWERCORE SERIES ARDRON LED #ECO COVE INTEGRAL SERIES ECOSENSE #TROV L50 SERIES END-TO-END LOCKING POWER CONNECTORS. DIE-CAST ALUMINUM HOUSING. WHITE POWDER COAT FINISH. EUREKA LIGHTING #4005-CLC SERIES 0-10V DIMMING. - I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature - James A. LeClaire Registration Number Date 50358 07/24/15 Project For P2 DECORATIVE PENDANT 120V PENDANT LED 3000K 840 LUMENS 10W S8 LINEAR PENDANT 120V SUSPENDED LED 3500K 5000 LUMENS 46W ACRYLIC LENS ACRYLIC LENS EUREKA LIGHTING #4404B SERIES 0-10V DIMMING. - CORELITE MB SERIES EXTRUDED ALUMINUM HOUSING. 0-10V DIMMING. WHITE POWDER COAT FINISH. PROVIDE CONTINUOUS ROW AS INDICATED ON PLANS. - - 120V RECESSED LED 3500K 515 LMNS/FT MIN 9W/FT MAX SATIN LENS NEORAY #23DR SERIES AXIS #BMRLED SERIES EXTRUDED ALUMINUM HOUSING. WHITE POWDER COAT FINISH. 0-10V DIMMING. - D1 RECESSED LED DOWNLIGHT 120V RECESSED LED 3500K 1500 LUMENS 23W SPECULAR CLEAR PORTFOLIO #LD6A SERIES PRESCOLITE #LC6LED SERIES 0-10V DIMMING. ALUMINUN HOUSING. EXTRUDED ALUMINUM HEAT SINK. ALUMINUM REFLECTORS. SELF-FLANGED. - D2 RECESSED LED DOWNLIGHT - WALL WASH 120V RECESSED LED 3500K 1500 LUMENS 23W SPECULAR CLEAR PORTFOLIO #LD6A SERIES 0-10V DIMMING. ALUMINUN HOUSING. EXTRUDED ALUMINUM HEAT SINK. ALUMINUM REFLECTORS. SELF-FLANGED. SINGLE WALL WASH REFLECTOR. - D3 RECESSED LED DOWNLIGHT 120V RECESSED LED 3500K 1500 LUMENS 25W CYLINDRICAL GLASS, POLISHED FROSTED SHAPER #340-6 LED DL SERIES WITH PORTFOLIO #LD615 SERIES SPECTRUM #SGE6LEDOS SERIES 0-10V DIMMING. ALUMINUN HOUSING. EXTRUDED ALUMINUM HEAT SINK. - D4 LACTATION ROOM 120V SURFACE 0-10V DIMMING. - E1 EXIT SIGN SINGLE FACE EDGE LIT LED DIE CAST HOUSING 120V RECESSED CLEAR FACE WITH MIRROR BACKGROUND, CONFIRM ARROW ORIENTATION WITH FLOOR PLANS, BRUSHED ALUMINUM COVERPLATE, FULLY RECESSED HOUSING, AC ONLY. - SURE-LITES #EUX6 SERIES LAMPS WALL L4 3' RECESSED LINEAR RED LETERS STENCIL FACE MOUNTING 120V P1 NEORAY #23DR SERIES AXIS #BMRLED SERIES VOLTAGE 2' LINEAR SCONCE L7 NEORAY #23DR SERIES AXIS #BMRLED SERIES FIXTURE TYPE J2 L3 C6 LED FIXTURE LETTER U2 2' UNDERCABINET LIGHT 120V SURFACE LED 3500K 800 LUMENS 9W W1 EXTERIOR WALL SCONCE 120V WALL LED W2 EXTERIOR WALL SCONCE 120V WALL LED 4000K 55W MAX 3800 LUMENS TYPE 4 DISTRIBUTION FAIL-SAFE #UCL SERIES GARDCO #101L SERIES NO SUBSTITUTIONS STEEL HOUSING. WHITE POWDER COAT FINISH. INTEGRAL ROCKER SWITCH. - CUSTOM FIXTURE TO MATCH EXISTING. - TRAPEZOID LED FIXTURE. WET LOCATION. VERIFY FINISH WITH ARCHITECT. 1 GENERAL NOTES: KEY NOTES: A. SEE SPECIFICATION FOR ADDITIONAL LIGHT FIXTURE REQUIREMENTS B. MINIMUM LUMENS LISTED FOR SOLID STATE LIGHT FIXTURES ARE DELIVERED LUMENS BASED ON PHOTOMETRIC TESTING COMPLETED IN ACCORDANCE WITH IES LM-79 STANDARD. 1. OWNER'S CAMPUS STANDARD EXTERIOR LIGHT FIXTURE MANUFACTURER, NO SUBSTITUTIONS. 2. VERIFY CEILING TYPE PRIOR TO ORDERING AND INSTALLING FIXTURES. STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 Project No. 2263.001.00 Drawn By MMK Checked By E2 E3 EXIT SIGN DOUBLE FACE EDGE LIT LED DIE CAST HOUSING EXIT SIGN SINGLE FACE LED DIE CAST HOUSING 120V 120V RECESSED UNIVERSAL LED LED RED LETERS STENCIL FACE RED LETERS STENCIL FACE SURE-LITES #EUX6 SERIES DUAL-LITE #SE SERIES SURE-LITES #CX SERIES LIGHTALARMS #XLD SERIES CLEAR FACE WITH MIRROR BACKGROUND, CONFIRM ARROW ORIENTATION WITH FLOOR PLANS, BRUSHED ALUMINUM COVERPLATE, FULLY RECESSED HOUSING, AC ONLY. - DIFFUSING OVERLAY, BLACK DIE CAST ALUMINUM HOUSING, BRUSHED ALUMINUM FACEFLATE, UNIVERSAL ARROWS, AC ONLY. - Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:07:09 PM E4 BATTERY PACK 120V UNIVERSAL LED SURE-LITES #LEM SERIES WHITE FINISH. PLASTIC HOUSING. - F1 4' INDUSTRIAL 120V SURFACE/CHAIN 2-F32 T8 HUNG 4100K COLUMBIA #KL SERIES METALUX #DMF SERIES WILLIAMS #82 SERIES STEEL CHANNEL, WHITE POWDER COAT WIRE GAURD, ONE ELECTRONIC BALLAST. - F2 2' WRAPAROUND 120V SURFACE LED 3500K 2000 LUMEN 23W METALUX #SLWP SERIES STEEL CHANNEL, WHITE POWDER COAT WIRE GAURD, ONE ELECTRONIC BALLAST. - F3 4' WRAPAROUND 120V SURFACE LED 3500K 3900 LUMENS 40W METALUX #SLWP SERIES STEEL CHANNEL, WHITE POWDER COAT WIRE GAURD, ONE ELECTRONIC BALLAST. - H1 STAIR LIGHT 120V SURFACE LED 3500K 4000 LUMENS 41W FROSTED LENS METALUX #SWLED SERIES COLUMBIA #LBIL SERIES INTEGRAL OCCUPANCY SENSOR. STEEL HOUSING. POST PAINTED FINISH. ONE DRIVER. - J1 4' WALL BRACKET 120V SURFACE 2-F32 T8 4100K #12 ARCYLIC PRISMATIC DIFFUSER COLUMBIA #W SERIES METALUX #BC SERIES WILLIAMS #20 SERIES POST PAINTED STEEL HOUSING. WHITE INJECTED MOLDED END CAPS. HEAT SINK EMBOSSMENTS IN BODY FOR BALLAST COOLING. FIXTURE PAINTED WHITE. 1 - 2 LAMP ELECTRONIC BALLAST. - APERATURED REFLECTOR WITH 20% UP LIGHT No. Date Description ELECTRICAL SCHEDULES E600 LIGHTING CONTROL PANEL SCHEDULE LIGHTING CONTROL DEVICE SCHEDULE SWITCH TYPE COS1 COS2 CVS1 CVS2 D1 D5 EM OS P1 P2 R1 R2 R3 R4 R5 SW VS DEVICE DESCRIPTION CEILING MOUNT DLM DIGITAL ULTRASONIC OCCUPANCY SENSOR CEILING MOUNT STAND-ALONE LINE VOLTAGE DUAL TECHNOLOGY OCCUPANCY SENSOR CEILING CORNER MOUNT DLM DIGITAL DUAL TECHNOLOGY VACANCY SENSOR CEILING MOUNT DLM DIGITAL DUAL TECHNOLOGY VACANCY SENSOR SINGLE BUTTON DLM DIGITAL DIMMING SWITCH FIVE BUTTON DLM DIGITAL SCENE SELECTOR SWITCH WITH MANUAL RAISE/LOWER SWITCH EMERGENCY LIGHTING CONTROL UNIT WALL MOUNT OCCUPANCY SENSOR SWITCH DIGITAL DLM DIMMING SINGLE ZONE PHOTOSENSOR DIGITAL DLM DIMMING MULI-ZONE PHOTOSENSOR DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROL - 1 RELAY DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROL - 2 RELAY DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROL - 3 RELAY DIGITAL PARTITION INTERFACE - INDICATES TO LIGHTING CONTROLS WHEN ROOM PARTITION IS OPEN/CLOSED SERIAL DATA INTERFACE - RS-232 INTERFACE TO CONNECT LIGHTING CONTROL SYSTEM TO 3RD PARTY AV CONTROL SYSTEM DIGITAL WALL SWITCH WALL MOUNT VACANCY SENSOR SWITCH MANUFACTURER SERIES NUMBER LMUC-100-2 DT-355 LMDX-100 LMDC-100 LMDM-101 LMSW-105 ELCU-200 DW-100 LMLS-400 LMLS-500 LMRC-211 LMRC-212 LMRC-213 LMIO-102 NOTES 3 1 1 1 LMDI-100 LMSW-100 DW-100 3 GENERAL NOTES: A. SYSTEM IS DESIGNED AROUND A WATTSTOPPER DLM SERIES SYSTEM. DOCUMENTS INDICATE CONTROL DEVICES, SEQUENCE OF OPERATION, AND OVERRIDE CONTROL LOCATIONS. CONTRACTOR SHALL PROVIDE ALL REQUIRED POWER PACKS, DIMMING POWER PACKS, BRIDGES, GATEWAYS, AND PROGRAMMING AS REQUIRED TO ACCOMPLISH THE CONTROL SEQUENCES INDICATED. NOT ALL PARTS AND PIECES ARE SHOWN ON PLAN. CONTRACTOR SHALL PROVIDE ADDITIONAL COMPONENTS FOR A COMPLETE SYSTEM. ELECTRICAL NOTES: 1. MOUNT ROOM CONTROLLER IN ACCESSIBLE CEILING SPACE ABOVE ENTRY DOOR (TYPICAL FOR SMALLER ENCLOSED SPACES). 2. MOUNT PLUG LOAD CONTROLLER NEXT TO ASSOCIATED ROOM CONTROLLER IN ACCESSIBLE CEILING. 3. TURN OFF 'AUTO SET' FUNCTION PRIOR TO INSTALLATION. LIGHTING CONTROL SEQUENCE SCHEDULE LC # LIGHTING CONTROL SEQUENCE SYMBOL FOUND ON LIGHTING PLAN(S). LIGHTING NETWORK CONTROL CONTROL EMS/BAS SEQUENCE CAPABILITIES SYSTEM LC 01 NO NO LC 02 NO NO LC 03 YES YES LC 04 YES YES LC 05 NO NO LC 06 NO NO LC 07 NO NO LC 08 YES YES LC 09 NO NO TIME CLOCK NO NO YES YES NO NO NO YES NO AUTO OFF TIME VACANCY OCCUPANCY (MINUTES) SENSOR SENSOR YES NO 15 YES NO 15 NO YES 30 NO YES 30 YES NO 5 NO NO NA NO YES 20 NO NO NA YES NO 15 DIMMING TYPE 0-10V 0-10V 0-10V 0-10V NA NA NA NA 0-10V DIMMING LEVEL 10% 10% 10% 10% NA NA NA NA 10% SIDELIGHT DAYLIGHT HARVEST (AUTOMATIC/ AFTERHOURS OVERRIDE SWITCHED) OVERRIDE DURATION AUTOMATIC NA NA NA NA NA NA YES 2 HOURS AUTOMATIC YES 2 HOURS NA NA NA NA NA NA NA NA NA NA NO NA AUTOMATIC NA NA LIGHTING CONTROL PANEL RELAY NUMBER LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-11 LCP-21 LCP-21 LCP-21 LCP-21 LCP-21 LCP-21 LCP-21 LCP-31 LCP-31 LCP-31 LCP-31 LCP-31 LCP-31 LCP-31 LCP-31 LCP-B1 LCP-B1 LCP-B1 LCP-B1 LCP-B1 LCP-B1 RELAY DESCRIPTION CONTROL DESCRIPTION PANEL CIRCUIT NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 25 26 27 28 29 30 CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING - EMERGENCY CORRIDOR LIGHTING - EMERGENCY CORRIDOR LIGHTING - EMERGENCY CORRIDOR LIGHTING - EMERGENCY ENTRY VESTIBULE - EMERGENCY. ENTRY VESTIBULE - EMERGENCY. TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING N-11 N-11 N-11 N-11 3 3 3 11 N-12 N-11 N-11 N-11 N-11 N-11 N-11 E-B1 E-B1 E-B1 E-B1 E-B1 E-B1 21 7 7 7 10 3 9 4 4 4 4 8 11 1 2 6 13 14 15 CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING - OPTIONAL CORRIDOR LIGHTING - EMERGENCY CORRIDOR LIGHTING - EMERGENCY CORRIDOR LIGHTING - EMERGENCY TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING N-21 N-21 O-21A E-21 E-21 E-21 8 5 6 4 16 3 1 2 3 4 13 14 15 CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING CORRIDOR LIGHTING - EMERGENCY CORRIDOR LIGHTING - EMERGENCY CORRIDOR LIGHTING - EMERGENCY TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING N-31 N-31 N-31 N-31 E-21 E-21 6 9 13 11 7 17 1 2 8 9 10 CORRIDOR LIGHTING CORRIDOR LIGHTING EXTERIOR WALL PACKS FRONT ENTRY LIGHTING POLES EXTERIOR POLES BETWEEN EASTMAN AND RIVERVIEW EXTERIOR POLE IN NE PARKING LOT EXTERIOR POLE IN SOUTH PARKING LOT CORRIDOR LIGHTING - EMERGENCY EXTERIOR WALL PACKS EMERGENCY EXTERIOR WALL PACKS EMERGENCY TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING ENERGY MANAGEMENT SYSTEM ENERGY MANAGEMENT SYSTEM ENERGY MANAGEMENT SYSTEM N-B1 N-B1 O-B1A N-B1 N-B1 5 6 21 9 13 ENERGY MANAGEMENT SYSTEM ENERGY MANAGEMENT SYSTEM N-B1 N-B1 13 11 TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING ENERGY MANAGEMENT SYSTEM E-B1 E-B1 3 10 ENERGY MANAGEMENT SYSTEM E-B1 27 LCP-B1 LCP-B1 11 12 LCP-B1 LCP-B1 13 14 LCP-B1 24 NOTES 1 1 RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 1 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number Date NOTES 1 1 GENERAL NOTES: A. BASIS OF DESIGN MANUFACTURER - DOUGLAS LIGHTING CONTROLS #LITEPAK. EQUAL BY LC&D, WATTSTOPPER, OR LEVITON WITH ENGINEER PRIOR APPROVAL. B. PANEL TO HAVE DIGITAL ASTRO TIME CLOCK AND COMPARTMENTS FOR SEPARATION OF DUAL VOLTAGE/SERVICE BRANCHES. C. ALL LIGHTING CONTROL PANELS SHALL BE NETWORKED TOGETHER FOR SINGLE STATION MONITORING. D. ALL TIME OF DAY SETTING, PUSH BUTTON FUNCTIONS, LIGHT LEVEL SETTINGS, AND OCCUPANCY SENSOR OVERRIDES SHALL BE COORDINATED AND REVIEWED WITH OWNER, CAMPUS FACILITY STAFF, AND ELECTRICAL ENGINEER IN A PRE-INSTALLATION/PRE-PROGRAMMING MEETING WITH A FACTORY REPRESENTATIVE PRESENT FROM LIGHTING CONTROL SYSTEM MANUFACTURER. DIV. 26 CONTRACTOR RESPONSIBLE FOR COORDINATING AND FACILITATING MEETING. E. EMERGENCY RELAY SHALL MEET NEC (NFPA 70) UL 924 REQUIREMENTS FOR EMERGENCY LIGHTING CONTROL. UPON LOSS OF NORMAL POWER, EMERGENCY LIGHTING SHALL TURN ON TO FULL BRIGHTNESS. 50358 07/24/15 Project For ELECTRICAL NOTES: 1. EMERGENCY RELAY REQUIRED. 1 STUDENT HEALTH AND ACADEMIC RENOVATION GENERAL NOTES: A. PROVIDE ALL COMPONENTS, WIRING AND PROGRAMMING NECESSARY TO MAKE A FUNCTIONAL LIGHTING CONTROL SYSTEM WITH CONTROLS AS NOTED ABOVE. B. CONTROLS MANUFACTURER OR REPRESENTATIVE SHALL PROVIDE COMPLETE WIRING DIAGRAM IN SHOP DRAWING SUBMITTAL. C. IF DIMMING IS CALLED FOR IN SCHEDULE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY AND PROVIDE ALL NECESSARY PARTS, BALLASTS, DRIVERS, ETC. TO PROVIDE THE DIMMING FUNCTION. D. CONTRACTOR TO PROVIDE ALL WIRING NECESSARY INCLUDING ANY 0-10V CONTROL WIRING AS REQUIRED. E. CONTRACTOR SHALL REVIEW ALL COMPONENTS AND REQUIRED WIRING METHODS WITH CONTROLS MANUFACTURER OR REPRESENTATIVE PRIOR TO BID. F. ALL TIME OF DAY SETTING, PUSH BUTTON FUNCTIONS, LIGHT LEVEL SETTINGS, AND OCCUPANCY SENSOR OVERRIDES SHALL BE COORDINATED AND REVIEWED WITH OWNER, CAMPUS FACILITY STAFF, AND ELECTRICAL ENGINEER IN A PRE-INSTALLATION/PRE-PROGRAMMING MEETING WITH A FACTORY REPRESENTATIVE PRESENT FROM LIGHTING CONTROL SYSTEM MANUFACTURER. DIV. 26 CONTRACTOR RESPONSIBLE FOR COORDINATING AND FACILITATING MEETING. DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 ELECTRICAL NOTES: 1. 2. LOCAL DIMMER SWITCH SHALL OVERRIDE AUTOMATIC DAYLIGHTING CONTROLS WITHIN ROOM. DAYLIGHTING PHOTOSENSOR SHALL TAKE CONTROL AFTER NEXT OCCUPANCY SENSOR TIME OUT. ROOMS SHALL FUNCTION AS TWO SEPERATE SPACES WHEN THE PARTITION IS CLOSED, AND SHALL FUNCTION AS ONE SPACE WHEN PARTITION IS OPEN. CONTROL SWITCHES AT ENTRY POINTS SHALL AUTOMATICLLY ADJUST SCENE CONTROL BASE ON PARTITION INTERFACE DEVICE. LIGHTING SHALL INTERFACE WITH 3RD PARTY AV SYSTEM. REFER TO FLOOR PLANS FOR ADDITIONAL INFORMATION RELATED TO CONTROL DEVICES. Project No. 2263.001.00 Drawn By MMK Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description ELECTRICAL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:23 PM E601 NAME: NRD-B1 NAME: NR-B1A VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION MIN. BUS RATING: 1000 A MAIN SIZE: 1000 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES NR-B1A --NR-11A --NR-21A --Spare --Spare --Spare --Spare 1 --1 --1 --------- 39 -- -- 41 -- -- 225 A --225 A --400 A --400 A --400 A --200 A --100 A 3 --3 --3 --3 --3 --3 --3 -- -- A B C MOUNTING: SURFACE POLES TRIP NOTES 5528... 1260... 3420... 720 VA 3420... 0 VA 4320... 10840... 3240... 12240... 4140... 1008... 1926... 13560... 16740... 10440... 16020... 1166... 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA --TOTAL LOAD: 54768 VA 46800 VA TOTAL AMPS: 458 A 392 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LIGHTING LOAD (DA_L) 128 VA 125% RECEPTACLE LOAD (DA_R) 129600 VA 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% MOTOR LOAD TOTALS 0 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 17160 VA 100% SPARE CAPACITY (DA_SP) 100% 0 VA 0 VA VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT NR-B2 --NR-22A --NR-12A --Spare --Spare --Spare --Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION NOTES TRIP POLES A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 225 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 244 VA 244 VA -- -- 3 --3 --3 --3 --3 --3 --3 225 A --400 A --225 A --200 A --100 A --100 A --200 A 1 --1 --1 --- -- -- -- -- 40 39 -- -- -- -- -- -- 42 41 -- -- 45320 VA 378 A LOAD DEMAND (VA) 160 VA 69800 VA ------- TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 146888 VA 87120 VA 408 A 242 A 0 VA 0 VA 17160 VA ELEV PIT RECEPT & LIGHT DA_R ELEVATOR EQUIPMENT ROOM 004 DA_R BUILDING SUPPORT 033 DA_R UNISEX TOILET 016 MENS LOCKER ROOM 015 ELECTRIC WATER COOLERS EXERCISE/TRAINING 009 TREADMILL TREADMILL DA_R EXAM/ CONSULT 011 DATA ROOM 021 DATA ROOM 021 DATA ROOM 021 Spare Spare Spare Spare Spare NR-B1B B C MOUNTING: SURFACE POLES TRIP NOTES CIRCUIT DESCRIPTION 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ELEV PIT RECEPT & LIGHT DA_R MECHANICAL ROOM 019 DA_R ELECTRICAL ROOM 022 WOMANS LOCKER ROOM 051 DA_R SHOWER/RESTROOM 007 DA_R CORRIDOR 008 TREADMILL TREADMILL TREADMILL DA_R EXAM/CONSULT 010 DATA ROOM 021 DATA ROOM 021 Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 20 A Spare 40 --0 VA 0 VA 1 20 A TOTAL LOAD: 5528 VA 3420 VA 3420 VA TOTAL AMPS: 46 A 29 A 29 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 128 VA 125% 160 VA RECEPTACLE LOAD (DA_R) 12240 VA 10 KVA @ 100%, Remaining @ 50% 11120 VA MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 0 VA 0 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 100% SPARE CAPACITY (DA_SP) 100% Spare 42 1 720 VA 540 VA 540 VA 900 VA 720 VA 900 VA 540 VA 540 VA 360 VA 900 VA 900 VA 180 VA 180 VA 180 VA 180 VA 180 VA 900 VA 900 VA 180 VA 180 VA 180 VA 180 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 360 VA 0 VA 0 VA 360 VA 0 VA TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 12368 VA 11280 VA 34 A 31 A GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. PROVIDE THERMAL MAGNETIC MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP WITH ADJUSTABLE INSTANTANEOUS SETTING. 2. 3. 4. NOTES: 1. PROVIDE GFCI BREAKER. 2. 3. 4. CIRCUIT DESCRIPTION MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES POLE MOUNTED RECEPTACLES POLE MOUNTED RECEPTACLES Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 39 Spare 41 Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 1 A 360 VA B C 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 720 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA POLES TRIP NOTES 0 VA 360 VA 0 VA MOUNTING: SURFACE I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 360 VA 360 VA 3A 3A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA 0 VA 0 VA 720 VA NOTES TRIP POLES A L - WOMEN'S LOCKER ROOM AND... LIGHTING - EXAM/CONSULT 011 AND 010 LIGHTING - CORRIDOR 001 LIGHTING - SUMP ROOM 056 FRONT SITE LIGHTING PARKING LOT LIGHTING SIDE SITE LIGHTING HAND DRYER - SHOWER/ RESTROOM 006 -HAND DRYER - UNISEX TOILET/SHOWER... -HAND DRYER - SHOWER/ RESTROOM 013 -Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A -20 A -20 A -20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 2 -2 -2 -1 1 1 1 1 1 232 VA 208 VA 20 A 1 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 1 20 A Spare 40 39 Spare 1 20 A Spare 42 41 Spare TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 720 VA 720 VA 2A 2A 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL CIRCUIT DESCRIPTION Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 0 VA 0A LOAD DEMAND (VA) Date CKT 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A B C CIRCUIT DESCRIPTION CKT L - MENS LOCKER ROOM AND... LIGHTING - EXERCISE/TRAINING 009 LIGHTING - CORRIDOR 034 LIGHTING - ELECTRICAL AND DATA... LIGHTING - SHOWER/ RESTROOM 006 LIGHTING - UNISEX TOILET/SHOWER 016 HAND DRYER - SHOWER RESTROOM 005 -HAND DRYER - SHOWER/ RESTROOM 007 -HAND DRYER - SHOWER/ RESTROOM 014 -HAND DRYER - SHOWER/ RESTROOM 050 -Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 20 A 20 A 20 A 20 A 20 A 20 A 20 A -20 A -20 A -20 A -20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 20 A 1 0 VA 0 VA 1 20 A TOTAL LOAD: 10559 VA 9354 VA 9054 VA TOTAL AMPS: 88 A 78 A 75 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 13009 VA 125% 16261 VA RECEPTACLE LOAD (DA_R) 720 VA 10 KVA @ 100%, Remaining @ 50% 720 VA MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 3216 VA 100% 3216 VA LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 3216 VA 3216 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 9180 VA 100% 9180 VA SPARE CAPACITY (DA_SP) 100% Spare 42 ---- 172 VA 140 VA 192 VA 448 VA 400 VA 224 VA 440 VA 288 VA 300 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 0 VA 0 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA ----- STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 28967 VA 32219 VA 80 A 89 A Project No. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. Drawn By NOTES: 1. 2. 3. 4. NOTES: 1. 2. 3. 4. Date VOLTAGE: 120/208 PHASE: 3 WIRE: 4 1 3 5 7 9 11 13 15 17 CIRCUIT DESCRIPTION PASSENGER ELEVATOR E1 --PASSENGER ELEVATOR CONTROLLER PASSENGER ELEVATOR SHUNT TRIP PASSENGER ELEVATOR CAB SERVICE ELEVATOR CONTROLLER SERVICE ELEVATOR SHUNT TRIP SERVICE ELEVATOR CAB MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES A B C MMK JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. MOUNTING: SURFACE © Copyright RSP Architects 2015. All rights reserved. Revisions POLES TRIP NOTES 110 A 3 9391... 14411... 3 175 A ---9391... 14411... -----9391... 1441... --20 A 1 180 VA 828 VA 3 20 A 20 A 1 180 VA 828 VA --20 A 1 180 VA 828 VA --20 A 1 180 VA 192 VA 1 20 A 20 A 1 180 VA 696 VA 1 20 A 20 A 1 180 VA 0 VA 1 20 A TOTAL LOAD: 25182 VA 25686 VA 24990 VA TOTAL AMPS: 210 A 214 A 208 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 192 VA 125% 240 VA RECEPTACLE LOAD (DA_R) 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 74585 VA 100% 74585 VA LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 74585 VA 74585 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 1080 VA 100% 1080 VA SPARE CAPACITY (DA_SP) 100% ----- CIRCUIT DESCRIPTION CKT SERVICE ELEVATOR E2 --SP 01 --LIGHTING - ELEVATOR EQUIPMENT ROO... TF 01 Spare 2 4 6 8 10 12 14 16 18 No. Date Description TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 75857 VA 75905 VA 211 A 211 A GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. 2263.001.00 Checked By NAME: RD-B1 C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:29 PM 07/24/15 Project For POLES TRIP NOTES 160 VA 916 VA 50358 MOUNTING: SURFACE 1 1 1 1 1 1 2 -2 -2 -2 -1 1 1 1 1 CKT James A. LeClaire Registration Number CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Signature VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 Dunham Job #: 415134 NAME: N-B1 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 RSP Architects TOTALS GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. CKT CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 NAME: NR-B1B 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, 200% NEUTRAL PANEL SCHEDULES E602 NAME: O-B1A NAME: O-B1B VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 CIRCUIT DESCRIPTION MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL NOTES TRIP POLES A B C MOUNTIN... SURFACE POLES TRIP NOTES DA_MI MENS RESTROOM 107 DA_MI CORRIDOR 002 DA_MI DATA ROOM 021 PUPLIC LAV/URINAL SENSOR EMS PANEL HWP-01 --DA_MI MECHANICAL ROOM 052 LAB TOILET WATER SHUT OFF DA_L Spare Spare Spare Spare 20 A 1 540 VA 900 VA 1 20 A 20 A 1 360 VA 720 VA 1 20 A 1 20 A 1 180 VA 180 VA 1 20 A 20 A 1 180 VA 180 VA 1 20 A 20 A 1 180 VA 3036... 3 50 A 50 A 3 3036... 3036... -----3036... 3036... -----3036... 1320... 3 25 A 20 A 1 180 VA 1320... --20 A 1 180 VA 1320... --20 A 1 700 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A TOTAL LOAD: 18757 VA 18158 VA 17177 VA TOTAL AMPS: 158 A 153 A 143 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 4852 VA 125% 6065 VA RECEPTACLE LOAD (DA_R) 19560 VA 10 KVA @ 100%, Remaining @ 50% 14780 VA MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 24771 VA 100% 24771 VA LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 24771 VA 24771 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 4860 VA 100% 4860 VA SPARE CAPACITY (DA_SP) 100% 1 ----- VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION DA_MI HALLWAY 266 DA_MI ACCESS CONTROL POWER SUPPLY BLUE LIGHT CALL STATION HWP-02 --SCP 01 --Spare Spare Spare Spare Spare CKT CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... CIRCUIT DESCRIPTION RACK - DATA ROOM 021 RACK - DATA ROOM 021 RACK - DATA ROOM 021 DATA ROOM 021 DATA ROOM 021 DATA ROOM 021 DATA ROOM 021 DATA ROOM 021 DA_MI Spare Spare Spare Spare Spare Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 54092 VA 50525 VA 150 A 140 A MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL NOTES TRIP POLES 1 1 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) A B C 360 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 0 VA 180 VA 0 VA 0 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 0 VA 0 VA 1080 VA 9A LOAD DEMAND (VA) CIRCUIT DESCRIPTION RACK - DATA 131 RACK - DATA 131 DATA 131 DATA 131 DATA 131 BLUE LIGHT CALL STATION Spare Spare Spare Spare Spare Spare Spare Spare Spare CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 3240 VA 3600 VA 3600 VA 10 A 10 A Dunham Job #: 415134 0 VA 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% 360 VA 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 360 VA 360 VA 1260 VA 1260 VA 11 A 11 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 3240 VA POLES TRIP NOTES 360 VA 360 VA 180 VA MOUNTIN... SURFACE 360 VA GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER. 2. 3. 4. NOTES: 1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER. 2. 3. 4. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For NAME: E-B1 NAME: ND-B1 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 MIN. BUS RATING: 100 A MAIN SIZE: 100 A MAIN OPTIONS: MLO, FEED THRU LUGS, 200% NEUTRAL CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A B 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 BACK OF HOUSE EMERGENCY CORRIDOR EMERGENCY FIRST FLOOR EXIT LIGHTS STAIR LIGHTING FIRST FLOOR NAC PANEL - ELECTRICAL... VESTIBULE 135 SMOKE GUARD SMOKE GUARD SMOKE GUARD LIGHTING - WOMANS LOCKER ROOM 051 LIGHTING - STAIR D S001 LIGHTING - WOMENS RESTROOM 103 LIGHTING - UNISEX TOILET 132 DA_L Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 640 VA 35 VA 20 A 1 C MOUNTING: SURFACE POLES TRIP NOTES VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT EXIT LIGHTS DA_L OPEN/GATHERING 101 FIRST FLOOR EXIT LIGHTS NORTH ENTRY 112 EXTERIOR WALL SCONCE FIRST FLOOR NAC PANEL - ELECTRICAL... FACP SMOKE GUARD LIGHTING - SHOWER/ RESTROOM 007 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION NOTES TRIP POLES A 60 A --60 A --175 A --100 A --100 A --100 A --60 A 3 --3 --3 --3 --3 --3 --3 3864... 7452... -- -- 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 39 -- -- 20 A 1 0 VA 0 VA 1 20 A TOTAL LOAD: 3680 VA 3788 VA 2155 VA TOTAL AMPS: 33 A 34 A 18 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 6155 VA 125% 7694 VA RECEPTACLE LOAD (DA_R) 180 VA 10 KVA @ 100%, Remaining @ 50% 180 VA MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 0 VA 0 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 2700 VA 100% 2700 VA SPARE CAPACITY (DA_SP) 100% Spare 42 41 -- -- 39 Spare 1 41 Spare 120 VA 501 VA 60 VA 25 VA 256 VA 64 VA 180 VA 400 VA 32 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 136 VA 168 VA 0 VA 192 VA 0 VA 64 VA 96 VA 500 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1 1 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 9623 VA 11162 VA 27 A 31 A AHUS 01 --AHUR 01 --AHUS 03 --Spare --Spare --Spare --Spare MIN. BUS RATING: 1200 A MAIN SIZE: 1200 A MAIN OPTIONS: MCB, 200% NEUTRAL LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) ------------- B C 3864... 7452... 3864... 3036... 3864... 3036... 3864... 3036... 1441... 5796... 14411... 5796... 14411... 5796... 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA --TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 115268 VA POLES TRIP NOTES 3864... 7452... 0 VA 38423 VA 38423 VA 320 A 320 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 115268 VA 0 VA MOUNTING: SURFACE 0 VA 3 --3 --3 --3 --3 --3 --3 100 A --50 A --90 A --100 A --200 A --30 A --60 A -- -- -- -- 38423 VA 320 A LOAD DEMAND (VA) 115268 VA 0 VA 115268 VA CIRCUIT DESCRIPTION CKT AHUS 02 --AHUR 02 --AHUR 03 --Spare --Spare --Spare --Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 -- -- 40 -- -- 42 ------------- STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 115268 VA 115268 VA 320 A 320 A DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER. 2. 3. 4. NOTES: 1. 2. 3. 4. Project No. 2263.001.00 Drawn By MMK Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description PANEL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:36 PM E603 NAME: NR-B2 NAME: NR-12A VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, 200% NEUTRAL NOTES TRIP POLES A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 360 VA 900 VA 20 A 1 DA_R MECHANICAL ROOM 019 DA_R BLDG MECHANICAL 052 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 39 Spare 41 Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) B 720 VA C 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 0 VA 1260 VA 720 VA 11 A 7A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 1980 VA POLES TRIP NOTES 0 VA 0 VA 0 VA MOUNTING: SURFACE 0 VA VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A DA_R PHYSICAL THERAPY (COMMUNITY... DA_R DA_R HEALTH ED & PROMOTION COORD... DA_R UCHOOSE & RC 121 GRAD ASSIST 122 DA_R RECOVERY COMMUNITY RESOUR... COFFEE MAKER DA_R PEER ED/ UCHOOSE STUDENT... REFRIGERATOR DA_MI PEER ED/ UCHOOSE STUDENT... DA_R GRAD ASSIST 122 Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 540 VA 900 VA 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A DA_R STAIR S002 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 1 20 A Spare 40 39 Spare 1 20 A Spare 42 41 Spare 0 VA 0A LOAD DEMAND (VA) TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 1980 VA LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 1980 VA 1980 VA 5A 5A 0 VA 0 VA 0 VA MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% B C 720 VA 720 VA 720 VA 720 VA 540 VA 540 VA 1080... 540 VA 1800... 900 VA 1080... 540 VA 360 VA 1400... 1760... 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 0 VA 13560 VA 10440 VA 115 A 87 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 29700 VA 0 VA CIRCUIT DESCRIPTION CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A DA_R CIRCULATION 118 DA_R UNISEX TOILET 132 DA_R UCHOOSE & RC 120 DA_R RESEARCH DIRECTOR 125 DA_R DA_R RECOVERY COMMUNITY RESOUR... DA_R PEER ED/ UCHOOSE STUDENT... DA_R PEER ED/ UCHOOSE STUDENT... MICROWAVE DA_R RECOVERY COMMUNITY RESOUR... Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 20 A Spare 40 1 20 A Spare 42 11660 VA 99 A LOAD DEMAND (VA) TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 19850 VA RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 35660 VA 25810 VA 99 A 72 A 0 VA 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% 5960 VA POLES TRIP NOTES 1080... 360 VA 360 VA MOUNTING: RECESSED 5960 VA GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. NOTES: 1. 2. 3. 4. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For NAME: N-B2 NAME: N-12 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION BLDG MECHANICAL 052 MECHANICAL ROOM 019 & BUILDING... SWH 01 DWP 01 -UH 002 UH 003 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL NOTES TRIP POLES A B 20 A 20 A 20 A 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 2 -1 1 1 1 1 1 1 1 1 1 1 1 1 1 704 VA 320 VA 20 A 1 C MOUNTING: SURFACE POLES TRIP NOTES VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A MENS RESTROOM COMMUNITY PARTNERS HAND DRYER - MENS RESTROOM 107 -HAND DRYER - UNISEX TOILET 132 -AUTO DOOR OPENER AUTO DOOR OPENER - SOUTH ENTRY 109 AUTO DOOR OPENER - SOUTH ENTRY 109 AUTO DOOR OPENER LIGHTING - CIRCULATION 118 Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A -20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 2 -2 -1 1 1 1 1 1 1 1 1 1 1 1 1 228 VA 747 VA 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 25 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A BLDG JANITOR 018 & MECH ROOM 32 UH 001 AHU LIGHTS AND RECEPTACLES AHU LIGHTS AND RECEPTACLES AHU LIGHTS AND RECEPTACLES GFS 01 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 1 20 A Spare 40 39 Spare 20 A 1 0 VA 0 VA 1 20 A TOTAL LOAD: 4855 VA 4108 VA 3376 VA TOTAL AMPS: 41 A 35 A 28 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 2954 VA 125% 3693 VA RECEPTACLE LOAD (DA_R) 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 6048 VA 100% 6048 VA LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 6048 VA 6048 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 2700 VA 100% 2700 VA SPARE CAPACITY (DA_SP) 100% Spare 42 41 Spare 39 Spare 41 Spare -- 704 VA 300 VA 180 VA 180 VA 960 VA 180 VA 960 VA 180 VA 300 VA 1656... 300 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 12339 VA 13078 VA 34 A 36 A MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, 200% NEUTRAL B C MOUNTING: RECESSED POLES TRIP NOTES 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 20 A Spare 40 20 A 1 0 VA 0 VA 1 20 A TOTAL LOAD: 2391 VA 1964 VA 1060 VA TOTAL AMPS: 21 A 18 A 9A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 1226 VA 125% 1533 VA RECEPTACLE LOAD (DA_R) 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 1392 VA 100% 1392 VA LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 1392 VA 1392 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 2160 VA 100% 2160 VA SPARE CAPACITY (DA_SP) 100% Spare 42 --- 180 VA 340 VA 180 VA 696 VA 180 VA 696 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 180 VA 0 VA 100 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 20 A 20 A 20 A 20 A 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 CKT PEER ED/ UCHOOSE STUDENT STAFF... FIRE/SMOKE DAMPERS RECOVERY COMMUNITY RESOURCE... CUH-102 CUH-104 HAND DRYER - MENS RESTROOM 107 -Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 448 VA 360 VA 1 1 1 1 1 2 -1 1 1 1 1 1 1 1 1 1 1 1 CIRCUIT DESCRIPTION -- STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 5415 VA 5722 VA 15 A 16 A GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. NOTES: 1. 2. 3. 4. Project No. 2263.001.00 Drawn By MMK Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description PANEL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:42 PM E604 NAME: NR-12B NAME: N-11 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 39 Spare 20 A 1 41 Spare 20 A 1 LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) A 0 VA B C 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 5860 VA 5940 VA 49 A 50 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A HEALTH ED INTERDISCIPLINARY 116 &... CIRCULATION 113 & VESTIBULE SHHS INTERDISCIPLINARY 123 &... CIRCULATION COLORED STRIP COLORED STRIP HAND DRYER - WOMENS RESTROOM 103 -HAND DRYER - WOMENS RESTROOM 103 -CUH-101 AUTO DOOR OPENER - NORTH ENTRY 112 AUTO DOOR OPENER AUTO DOOR OPENER Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A -20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 2 -2 -1 1 1 1 1 1 1 1 1 600 VA 277 VA 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 1 20 A Spare 40 39 Spare 20 A 1 1 20 A Spare 42 41 Spare 20 A 1 --- B C 720 VA 400 VA 1317... 480 VA 49 VA 196 VA 49 VA 600 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 18640 VA 14820 VA 52 A 41 A 0 VA 0 VA 1000 VA 0 VA 0 VA 696 VA 0 VA 180 VA 696 VA 180 VA 180 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA MOUNTING: SURFACE POLES TRIP NOTES 1065... 256 VA 0 VA TOTAL LOAD: 8279 VA 6754 VA TOTAL AMPS: 70 A 56 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LIGHTING LOAD (DA_L) 8889 VA 125% RECEPTACLE LOAD (DA_R) 720 VA 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 3216 VA 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% MOTOR LOAD TOTALS 3216 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 6660 VA 100% SPARE CAPACITY (DA_SP) 100% TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 13820 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6840 VA 57 A LOAD DEMAND (VA) 0 VA 1000 VA POLES TRIP NOTES 0 VA TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 17640 VA MOUNTING: RECESSED CIRCUIT DESCRIPTION CKT WOMENS RESTROOM 103 ELECTRICAL AND DATA ROOMS RESEARCH AREA OFFICES AND GRAD ASSISTANTS COVE - OPEN/GATHERING 101 FCU 01 & FCU 02 FIREPLACE FIRE/SMOKE DAMPER MOTORIZED PARTITION --CUH-103 AUTO DOOR OPENER - NORTH ENTRY 112 Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 1 1 1 1 1 1 1 3 --1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 15 A 20 A 20 A 20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 1 20 A Spare 42 7294 VA 61 A LOAD DEMAND (VA) 11111 VA 720 VA 3216 VA 0 VA 3216 VA --- 612.677.7100 612.677.7499 fax www.rsparch.com Consultants TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 22327 VA 24549 VA 62 A 68 A I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 6660 VA GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. NOTES: 1. 2. 3. 4. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For NAME: NR-11B VOLTAGE: 120/208 PHASE: 3 WIRE: 4 MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 VENDING MACHINE VENDING MACHINE DA_R HEALTH ED INTERDISCIPLINARY 116 DA_R HEALTH ED INTERDISCIPLINARY 116 DA_R SHHS INTERDISCIPLINARY 123 DA_R WOMENS RESTROOM 103 DA_R DA_R LACTATION ROOM 106 DA_R RESEARCHER 128 DA_R RESEARCH DATA 126 DATA 131 DATA 131 Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 180 VA 180 VA 39 Spare 20 A 1 41 Spare 20 A 1 LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 Dunham Job #: 415134 GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NAME: NR-11A RSP Architects B C 540 VA 720 VA 540 VA 900 VA 720 VA 180 VA 360 VA 720 VA 540 VA 1080... 720 VA 720 VA 720 VA 720 VA 540 VA 360 VA 180 VA 180 VA 180 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 11700 VA POLES TRIP NOTES 180 VA 360 VA 0 VA 4320 VA 3240 VA 37 A 27 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA MOUNTING: SURFACE 0 VA VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT CIRCUIT DESCRIPTION MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, 200% NEUTRAL NOTES TRIP POLES 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A VENDING MACHINE DA_R CIRCULATION 113 DA_R HEALTH ED INTERDISCIPLINARY 116 DA_R SHHS INTERDISCIPLINARY 123 EXTERIOR RECEPTACLE DA_R DA_R DA_R RESEARCH ASST. 129 DA_R RESEARCH COORDINATOR 127 DA_R DATA 131 DATA 131 Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A Spare 40 39 Spare 20 A 1 1 20 A Spare 42 41 Spare 20 A 1 4140 VA 36 A LOAD DEMAND (VA) 10850 VA TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 11700 VA 10850 VA 32 A 30 A 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) A 0 VA B 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA POLES TRIP NOTES 0 VA 0 VA 0 VA C MOUNTING: SURFACE 0 VA 0 VA 0 VA 0 VA TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 0 VA 0 VA 0A 0A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA CIRCUIT DESCRIPTION CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 20 A Spare 40 1 20 A Spare 42 0 VA 0A LOAD DEMAND (VA) STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 0 VA 0 VA 0A 0A 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. NOTES: 1. 2. 3. 4. Project No. 2263.001.00 Drawn By MMK Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description PANEL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:49 PM E605 NAME: NR-22A NAME: N-22 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL NOTES TRIP POLES A B C EXAM ROOMS 237, 234, 235, 271, 238, 233 EXAM ROOMS 221, 220, 219, 226, 225, 269 OFFICES 222, 223, 224, 227, 270, 228 243, 244, 245, 246, 248, 247 RECEPTION... HAND DRYER - LAB TOILET 268 -HALLWAY 266 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 2 -1 1 1 1 1 1 1 1 1 1 1 1 39 Spare 20 A 1 41 Spare 20 A 1 -- 102 VA 180 VA 102 VA 180 VA 520 VA 180 VA 480 VA 180 VA 180 VA 180 VA 0 VA 0 VA 20 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA TOTAL LOAD: 4213 VA 3634 VA TOTAL AMPS: 35 A 30 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LIGHTING LOAD (DA_L) 5016 VA 125% RECEPTACLE LOAD (DA_R) 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 3816 VA 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% MOTOR LOAD TOTALS 3816 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 2520 VA 100% SPARE CAPACITY (DA_SP) 100% CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A FIRE/SMOKE DAMPERS HAND DRYER - STAFF TOILET 255 -HAND DRYER - PATIENT TOILET 256 -Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 BUSINESS MANAGER 244 CASHIER 245 STUDENT INSURANCE ADVOCATE 247 REFERRAL COORDINATOR OFFICE 248 COPIER/PRINTER - WORK 246 GENERAL RECEPTACLES Room 246, 266,... RECEPTION 243 RECEPTION 243 GENERAL RECEPTACLES SUB WAITING... WIREMOLD - LABORATORY 251 WIREMOLD - LABORATORY 251 MEDICAL DIRECTOR OFFICE 222 MD OFFICE 223 MD OFFICE 224 NP OFFICE 227 NP OFFICE 270 NURSING MANAGER 228 CORRIDOR 259 & 265 DA_R TREATMAN ROOM 232 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 720 VA 360 VA 0 VA CIRCUIT DESCRIPTION 1 2 -2 -1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A -20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 39 ICE MAKER - HALLWAY 258 1 20 A Spare 42 41 ELECTRIC WATER COOLER - HALLWAY 258 --- 3554 VA 30 A LOAD DEMAND (VA) 6270 VA LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 3816 VA 0 VA 3816 VA 11401 VA 12655 VA 32 A 35 A 2520 VA 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 1 20 A 1 B C 720 VA 360 VA 720 VA 360 VA 1000... 360 VA 540 VA 360 VA 360 VA 360 VA 180 VA 360 VA 1260... 360 VA 540 VA 360 VA 540 VA 360 VA 900 VA 360 VA 720 VA 720 VA 720 VA 360 VA 720 VA 360 VA 720 VA 720 VA 720 VA 180 VA 720 VA 360 VA 360 VA 360 VA 1560... 540 VA 180 VA 720 VA 10840 VA 12240 VA 91 A 103 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 25920 VA CIRCUIT DESCRIPTION 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A EXAM ROOM 219 EXAM ROOM 219 EXAM ROOM 220 EXAM ROOM 220 EXAM ROOM 221 EXAM ROOM 221 EXAM ROOM 226 EXAM ROOM 226 EXAM ROOM 225 EXAM ROOM 225 EXAM ROOM 269 EXAM ROOM 269 NURSE STATION 231 NURSE STATION 231 DA_R TREATMAN ROOM 232 MED/ NOURISH ROOM 230 STAFF TOILET 255 PROCESSING ROOM 229 CLEAN SUPPLY 236 1 20 A HALLWAY 258 & 266 & STAIR S202 40 1 20 A REFRIGERATOR - LABORATORY 251 42 TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 17960 VA MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, 200% NEUTRAL NOTES TRIP POLES Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 39 Spare 20 A 1 41 Spare 20 A 1 A 0 VA B C 0 VA 1400... 0 VA 1440... 0 VA 1080... 0 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 900 VA 1200... 0 VA 0 VA 720 VA 360 VA 0 VA 0 VA 360 VA 1000... 0 VA 0 VA 180 VA 540 VA 0 VA 0 VA POLES TRIP NOTES 180 VA 0 VA 0 VA MOUNTING: RECESSED 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 3460 VA 4280 VA 31 A 37 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA 3960 VA 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 7240 VA Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For NAME: N-21 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 5940 VA 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 0 VA 0 VA NOTES: 1. PROVIDE GFCI BREAKER. 2. 3. 4. LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) RSP Architects 33160 VA 25200 VA 92 A 70 A NOTES: 1. 2. 3. 4. CIRCUIT DESCRIPTION 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 TOTALS GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. CKT CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 10080 VA 84 A LOAD DEMAND (VA) 0 VA 7240 VA POLES TRIP NOTES 720 VA 360 VA TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) MOUNTING: RECESSED GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NAME: NR-22B 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL CKT POLES TRIP NOTES 720 VA VOLTAGE: 120/208 PHASE: 3 WIRE: 4 MOUNTING: RECESSED DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% 0 VA CIRCUIT DESCRIPTION CKT CKT ELECTRIC WATER COOLERS DA_R LABORATORY 251 DA_R LABORATORY 251 DA_R LABORATORY 251 MICROWAVE - MEDICAL DIRECTOR... MINI FRIDGE - MEDICAL DIRECTOR OFFI... PRINTER - NURSE STATION 231 AUTOCLAVE - PROCESSING ROOM 229 PHLEBOTOMY 250 REC LAB TOILET 268 REC DA_R LABORATORY 251 DA_R LABORATORY 251 FUME HOOD - LABORATORY 251 SCALE - HALLWAY 266 Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION NOTES TRIP POLES A 20 A 20 A 20 A 20 A -20 A -20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 2 -2 -2 -1 1 1 1 1 1 1 1 1 1 180 VA 600 VA 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 39 Spare 20 A 1 1 20 A Spare 42 41 Spare 20 A 1 5940 VA TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 9900 VA 9900 VA 27 A 27 A 0 VA 0 VA 3960 VA AUTO DOOR OPENER - HALLWAY 266 FIRE/SMOKE DAMPERS DA_L WAITING CIRCULATION 260 HAND DRYER - UNISEX RESTROOM 202 -HAND DRYER - MENS RESTROOM 201 -HAND DRYER - WOMENS RESTROOM 203 -AUTO DOOR OPENER - WAITING... Spare Spare Spare Spare Spare Spare Spare Spare Spare MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2160 VA 18 A LOAD DEMAND (VA) 1 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 ---- B C POLES TRIP NOTES 360 VA 102 VA 673 VA 1016... 180 VA 160 VA 180 VA 544 VA 180 VA 456 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA TOTAL LOAD: 4705 VA 3952 VA TOTAL AMPS: 40 A 33 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LIGHTING LOAD (DA_L) 5489 VA 125% RECEPTACLE LOAD (DA_R) 720 VA 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 1224 VA 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% MOTOR LOAD TOTALS 1224 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 4860 VA 100% SPARE CAPACITY (DA_SP) 100% MOUNTING: SURFACE 1 1 1 1 1 1 1 2 -1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 CIRCUIT DESCRIPTION CKT 208, 209, 210, 205 EXAM ROOMS 214, 215, 213, 218, 217, 216 PHARMACY AREA WAITING CIRCULATION 260 STORAGE, JANITOR, ELECTRICAL AND... RESTROOMS AUTO DOOR OPENER - WAITING... HAND DRYER - WOMENS RESTROOM 203 -Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 20 A Spare 40 20 A Spare 42 4469 VA 38 A LOAD DEMAND (VA) 6861 VA 720 VA 1224 VA 0 VA 1224 VA STUDENT HEALTH AND ACADEMIC RENOVATION -- DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 13126 VA 14498 VA 36 A 40 A Project No. Drawn By GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. PROVIDE GFCI BREAKER. 2. 3. 4. NOTES: 1. 2. 3. 4. MMK Checked By Date 4860 VA 2263.001.00 JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description PANEL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:04:56 PM E606 NAME: NR-21A NAME: NR-21B VOLTAGE: 120/208 PHASE: 3 WIRE: 4 MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 UCHOOSE ADMINISTRATOR 208 SHS DIRECTORS 209 SHS ASST DIRECTOR 210 Room 211, 212 Room 201, 202 WOMENS RESTROOM 203 CONFERENCE 205 CONFERENCE 205 Room 260, S201 CONSULTATION AREA 239 PHARMACY 241 PHARMACY 241, 240 OTC SALES 240 GENERAL RECEPTACLES Room 260, 262,... WAITING CIRCULATION 260 WAITING CIRCULATION 260 EXAM ROOM 271 EXAM ROOM 271 Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 720 VA 360 VA 20 A 1 39 Spare 41 Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) B 720 VA 360 VA 540 VA 360 VA 360 VA 360 VA 180 VA 360 VA 1080... 360 VA 1080... 360 VA 360 VA 360 VA 720 VA 360 VA 540 VA 360 VA 540 VA 360 VA 720 VA 360 VA 900 VA 360 VA 720 VA 360 VA 1080... 360 VA 360 VA 360 VA 360 VA 360 VA 0 VA 720 VA 0 VA 720 VA 0 VA 19260 VA 16740 VA 161 A 140 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 540 VA VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A ISOLATION EXAM 213 ISOLATION EXAM 213 EXAM ROOM 214 EXAM ROOM 214 EXAM ROOM 215 EXAM ROOM 215 EXAM ROOM 218 EXAM ROOM 218 EXAM ROOM 217 EXAM ROOM 217 Room 216 EXAM ROOM 216 TRIAGE ROOM 237 TRIAGE ROOM 237 CONSULT ROOM (E-EXAM) 234 CONSULT ROOM (E-EXAM) 234 CONSULT ROOM (CAPS) 235 CONSULT ROOM (CAPS) 235 INJECTION ROOM 238 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 1 20 A OBSERVATION (IVS) - EKG 233 40 39 Spare 1 20 A DA_R PHARMACY 241 42 41 Spare 29030 VA TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 52020 VA 32990 VA 144 A 92 A 3960 VA MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 540 VA 180 VA 20 A 1 DA_R PHARMACY 241 HALLWAY 257 & 258 SCALE - HALLWAY 258 ELECTRICAL 253 & JANITOR 252 DATA 254 DATA 254 DATA 254 DATA 254 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% CIRCUIT DESCRIPTION 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 16020 VA 134 A LOAD DEMAND (VA) 0 VA 3960 VA POLES TRIP NOTES 720 VA 360 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 48060 VA C MOUNTING: SURFACE B C 360 VA 180 VA 0 VA 0 VA 0 VA 180 VA 0 VA 0 VA 0 VA 180 VA 180 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 11520 VA 9900 VA 97 A 83 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA 2 -1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 CIRCUIT DESCRIPTION 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 20 A Spare 40 20 A Spare 42 18950 VA TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 3960 VA 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 SECOND FLOOR EXIT LIGHTS DA_L HALLWAY 257 DA_L THIRD FLOOR EXIT LIGHTS CRASH CART - HALLWAY 258 PATIENT TOILET 256 - LIGHTING SECOND FLOOR NAC PANEL -... THIRD FLOOR NAC PANEL - ELECTRICAL... DA_L OPEN STUDY 352 SMOKE GUARD SMOKE GUARD Spare Spare Spare Spare Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For NAME: O-21A MIN. BUS RATING: 100 A MAIN SIZE: 100 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES Consultants 0 VA 0 VA NOTES: 1. 2. 3. 4. CIRCUIT DESCRIPTION 612.677.7100 612.677.7499 fax www.rsparch.com 31860 VA 22910 VA 88 A 64 A NOTES: 1. 2. 3. 4. CKT 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 TOTALS GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. VOLTAGE: 120/208 PHASE: 3 WIRE: 4 RSP Architects Dunham Job #: 415134 GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NAME: E-21 CKT DA_MI MENS RESTROOM 201 -Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare -- 10440 VA 88 A LOAD DEMAND (VA) 0 VA 3960 VA POLES TRIP NOTES 540 VA 180 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 27900 VA MOUNTING: SURFACE A B C MOUNTING: SURFACE POLES TRIP NOTES 20 A 1 45 VA 50 VA 1 20 A 20 A 1 220 VA 60 VA 1 20 A 20 A 1 260 VA 55 VA 1 20 A 20 A 1 350 VA 512 VA 1 20 A 20 A 1 180 VA 81 VA 1 20 A 20 A 1 130 VA 180 VA 1 20 A 1 20 A 1 180 VA 180 VA 1 20 A 1 20 A 1 180 VA 634 VA 1 20 A 20 A 1 673 VA 180 VA 1 20 A 20 A 1 180 VA 180 VA 1 20 A 20 A 1 180 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A TOTAL LOAD: 2061 VA 1535 VA 1478 VA TOTAL AMPS: 17 A 13 A 12 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 3307 VA 125% 4134 VA RECEPTACLE LOAD (DA_R) 180 VA 10 KVA @ 100%, Remaining @ 50% 180 VA MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 0 VA 0 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 1440 VA 100% 1440 VA SPARE CAPACITY (DA_SP) 100% 1 1 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT CIRCUIT DESCRIPTION SECOND FLOOR EXIT LIGHTS DA_L WAITING CIRCULATION 260 THIRD FLOOR EXIT LIGHTS DA_L STAIR S202 STAFF TOILET - LIGHTING SECOND FLOOR NAC PANEL -... THIRD FLOOR NAC PANEL - ELECTRICAL... DA_L WAITING CIRCULATION 260 SMOKE GUARD SMOKE GUARD Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 LIGHTING - NURSE STATION LIGHTING - PHLEBOTOMY 250 LIGHTING - TREATMENT, MED/NOURISH,... LIGHTING - INJECTION ROOM 238 OVERHEAD SURGICAL LIGHT - TREATMA... EXAM TABLE - TREATMAN ROOM 232 FVAV-101 FVAV-301 Spare Spare Spare Spare Spare Spare Spare TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 5074 VA 5901 VA 14 A 16 A MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL NOTES TRIP POLES A B C MOUNTIN... SURFACE POLES TRIP NOTES 20 A 1 240 VA 720 VA 1 20 A 20 A 1 921 VA 720 VA 1 20 A 20 A 1 480 VA 400 VA 1 20 A 20 A 1 720 VA 180 VA 1 20 A 20 A 1 180 VA 180 VA 1 20 A 20 A 1 180 VA 865 VA 1 20 A 20 A 1 865 VA 0 VA 1 20 A 20 A 1 865 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A 20 A 1 0 VA 0 VA 1 20 A TOTAL LOAD: 8125 VA 7546 VA 8165 VA TOTAL AMPS: 68 A 63 A 69 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LOAD DEMAND (VA) LIGHTING LOAD (DA_L) 4152 VA 125% 5190 VA RECEPTACLE LOAD (DA_R) 16320 VA 10 KVA @ 100%, Remaining @ 50% 13160 VA MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 2595 VA 100% 2595 VA LARGEST MOTOR - BRANCH (DA_LBM) 125% 0 VA MOTOR LOAD TOTALS 2595 VA 2595 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 720 VA 100% 720 VA SPARE CAPACITY (DA_SP) 100% 1 1 CIRCUIT DESCRIPTION DA_L ISOLATION EXAM 213 DA_L EXAM ROOM 219 CORRIDOR ACCESS CONTROL POWER SUPPLY ACCESS CONTROL POWER SUPPLY FVAV-201 Spare Spare Spare Spare Spare Spare Spare Spare Spare CKT 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 23836 VA 21714 VA 66 A 60 A GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER. 2. 3. 4. NOTES: 1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER. 2. 3. 4. Project No. Drawn By Checked By Date 2263.001.00 Author Checker 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description PANEL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:06:40 PM E607 NAME: O-21B NAME: NR-32A VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES RACK - DATA 254 DATA 254 DATA 254 DATA 254 DATA 254 DA_R NURSE STATION 231 DA_R NURSE STATION 231 DA_R TREATMAN ROOM 232 DA_R TREATMAN ROOM 232 PHARMACY REFRIGERATOR PHARMACY REFRIGERATOR RECEPTION 243 DA_R EXAM ROOM 219 DA_R EXAM ROOM 225 DA_R CONSULT ROOM (CAPS) 235 DA_R HALLWAY 258 Spare Spare Spare 1 39 Spare 41 Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 1 A B C POLES TRIP NOTES 360 VA 360 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 720 VA 1080... 1560... 720 VA 360 VA 360 VA 180 VA 180 VA 360 VA 720 VA 720 VA 720 VA 720 VA 540 VA 720 VA 720 VA 720 VA 720 VA 720 VA 720 VA 720 VA 360 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 0 VA 5400 VA 4680 VA 46 A 39 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 16320 VA MOUNTING: SURFACE 0 VA 1 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT RACK - DATA ROOM 399 DATA ROOM 399 DATA ROOM 399 DATA ROOM 399 REFRIGERATOR - MED/NOURISH ROOM... ICE MAKER MED/NOURSIH ROOM 230 UC REFRIG - MED/NOURISH ROOM 230 DA_R CLEAN SUPPLY 236 DA_R ADMIN SUPPORT/ RECEPTION 321 DA_R ISOLATION EXAM 213 DA_R EXAM ROOM 215 DA_R EXAM ROOM 218 DA_R EXAM ROOM 221 DA_R TRIAGE ROOM 237 DA_R INJECTION ROOM 238 Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 39 Spare 1 20 A Spare 42 41 Spare 6240 VA 53 A LOAD DEMAND (VA) TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 13160 VA 16320 VA 13160 VA 45 A 37 A DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% NOTES TRIP POLES A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1260... 1000... 20 A 1 Room 383, 382 GROUP THERAPY ROOM 380 THERAPIST PREDOCTORAL 303 THERAPIST PREDOCTORAL 379 AOD COUNSELOR 377 AOD COUNSELOR 378 STAFF TOILET 361 THERAPIST OFFICE 376 THERAPIST OFFICE 371 THERAPIST OFFICE 372 THERAPIST OFFICE 373 THERAPIST OFFICE 374 THERAPIST OFFICE 375 CASE MANAGER INTERN 387 CASE MANAGER OFFICE 388 CAPS DIRECTOR OFFICE 389 CAPS DIRECTOR OFFICE 389 FILE & ARCHIVE 385 Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 0 VA 0 VA 0 VA CIRCUIT DESCRIPTION MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL B C 720 VA 900 VA 720 VA 360 VA 720 VA 720 VA 720 VA 720 VA 0 VA 720 VA 720 VA 720 VA 0 VA 720 VA 0 VA 900 VA 0 VA 0 VA 0 VA 0 VA 360 VA 0 VA 0 VA 0 VA 720 VA 720 VA 720 VA 0 VA 720 VA 720 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 0 VA 5860 VA 5940 VA 49 A 50 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 17640 VA 0 VA CIRCUIT DESCRIPTION 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A COPIER/PRINTER DA_R DA_R DA_R DA_R DA_R OPEN STUDY 352 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 20 A Spare 40 1 20 A Spare 42 Consultants 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 1000 VA NOTES: 1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER. 2. 3. 4. NOTES: 1. 2. 3. 4. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For NAME: N-31 VOLTAGE: 120/208 PHASE: 3 WIRE: 4 MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, 200% NEUTRAL CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 Room 364, 365, 366, 367, 368, 369 THERAP... Room 398, 370 INTERN OFFICES Room379, 303, 380, 383, 382 RELAXATION... Room 376, 378, 377, 361 COUNSELOR,... DA_L Room 359, 360, 134 EF 02 --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 3 --1 1 1 1 1 1 1 1 1 1 480 VA 360 VA 20 A 1 41 Spare 612.677.7100 612.677.7499 fax www.rsparch.com 18640 VA 14820 VA 52 A 41 A GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. 39 Spare 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 13820 VA RSP Architects Dunham Job #: 415134 GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NAME: N-32 CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 6840 VA 57 A LOAD DEMAND (VA) 0 VA 1000 VA POLES TRIP NOTES 900 VA 900 VA 180 VA MOUNTING: RECESSED --- B C POLES TRIP NOTES 480 VA 620 VA 732 VA 360 VA 321 VA 180 VA 120 VA 180 VA 728 VA 828 VA 444 VA 828 VA 444 VA 828 VA 444 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA MOUNTING: RECESSED 0 VA CIRCUIT DESCRIPTION CKT CKT Room 371, 372, 373, 374, 375 OFFICES Room 389, 388, 387 FIRE/SMOKE DAMPERS HAND DRYER - STAFF TOILET 361 -EF 03 --Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION A 20 A 15 A 20 A 20 A 20 A 20 A 20 A 20 A -20 A -20 A -- 1 1 1 1 1 1 1 2 -2 -2 -- 696 VA 640 VA Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 20 A 1 20 A 20 A 20 A 20 A -20 A --20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 39 Spare 1 20 A Spare 42 41 Spare 0 VA 3092 VA 26 A LOAD DEMAND (VA) 4740 VA 3816 VA 0 VA 3816 VA ---- TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 8377 VA 9325 VA 23 A 26 A 720 VA MIN. BUS RATING: 225 A MAIN SIZE: 225 A MAIN OPTIONS: MCB, 200% NEUTRAL NOTES TRIP POLES 1 1 1 2 -3 --1 1 1 1 1 1 1 1 1 1 1 0 VA 20 A 1 TOTAL LOAD: 2613 VA 2672 VA TOTAL AMPS: 22 A 22 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LIGHTING LOAD (DA_L) 3792 VA 125% RECEPTACLE LOAD (DA_R) 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 3816 VA 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% MOTOR LOAD TOTALS 3816 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 720 VA 100% SPARE CAPACITY (DA_SP) 100% VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CUH-303 EF-01 AUTO DOOR OPENER - CAPS ENTRY 323 FIRE/SMOKE DAMPERS OPEN STUDY - LTG PRIVATE WAITING - LTG Lighting HAND DRYER - UNISEX RESTROOM 301 -HAND DRYER - WOMENS RESTROOM 355 -HAND DRYER - MENS RESTROOM 354 -- ---- B C POLES TRIP NOTES 528 VA 424 VA 180 VA 160 VA 360 VA 40 VA 554 VA 180 VA 340 VA 384 VA 49 VA 720 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: 3045 VA 2406 VA TOTAL AMPS: 26 A 21 A LOAD CLASSIFICATION CONNECTED LOAD (VA) DEMAND FACTOR LIGHTING LOAD (DA_L) 2330 VA 125% RECEPTACLE LOAD (DA_R) 720 VA 10 KVA @ 100%, Remaining @ 50% MOTOR LOAD - HEATING (DA_HM) 100% MOTOR LOAD - COOLING (DA_CM) 100% MOTOR LOAD - GENERAL (DA_M) 1224 VA 100% LARGEST MOTOR - BRANCH (DA_LBM) 125% MOTOR LOAD TOTALS 1224 VA KITCHEN LOAD (DA_K) DEMAND PER NEC ELECTRONIC LOAD (DA_EL) 100% ELECTRIC HEATING (DA_E) 100% DWELLING UNIT - GENERAL LOAD (DA_D) 10 KVA @ 100%, Remaining @ 40% MISCELLANEOUS LOAD (DA_MI) 2520 VA 100% SPARE CAPACITY (DA_SP) 100% 0 VA MOUNTING: SURFACE 0 VA CIRCUIT DESCRIPTION CKT Room 390, 391, 392, 393, 394, 396, 397 Restrooms DA_L OPEN STUDY 352 DA_L DA_L SHHS GROUP THERAPY ROOM 395 DA_L DATA ROOM 399 DA_R SHHS FACULTY COMMAND CENTE... HAND DRYER - MENS RESTROOM 354 -HAND DRYER - WOMENS RESTROOM 355 -AUTO DOOR OPENER - OPEN STUDY 352 Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 1 1 1 1 1 1 2 -2 -1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A -20 A -20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 20 A Spare 40 1 20 A Spare 42 1784 VA 15 A LOAD DEMAND (VA) 2913 VA 720 VA 1224 VA 0 VA 1224 VA --- STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 7235 VA 7818 VA 20 A 22 A Project No. Drawn By Checked By Date 2520 VA GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. NOTES: 1. 2. 3. 4. 2263.001.00 Author Checker 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description PANEL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:06:46 PM E608 NAME: NR-32B NAME: NR-31A VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CKT 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 CIRCUIT DESCRIPTION MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MLO, 200% NEUTRAL NOTES TRIP POLES ROOF RECEPTACLE ROOF RECEPTACLE DA_R HALLWAY 258 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 39 Spare 41 Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 1 A 180 VA B C 0 VA 720 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 1080 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA POLES TRIP NOTES 0 VA 180 VA 0 VA MOUNTING: RECESSED 180 VA 180 VA 2A 2A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA 0 VA 0 VA VOLTAGE: 120/208 PHASE: 3 WIRE: 4 CIRCUIT DESCRIPTION CKT CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A SHHS CLINICAL ROOM 390 SHHS CLINICAL ROOM 391 SHHS CLINICAL ROOM 392 SHHS CLINICAL ROOM 393 SHHS CLINICAL ROOM 394 SHHS GROUP THERAPY ROOM 395 SHHS FACULTY COMMAND CENTER 396 GENERAL REC Room 352, 302, S301 UNISEX RESTROOM 301 REC DATA ROOM 399 GENERAL REC Room 352, 340 STAFF BREAK ROOM 360 REFRIGERATO,R KITCHEN 134 REFRIGERATOR, KITCHEN 134 COFFEE MAKER, KITCHEN 134 KITCHEN 134 KITCHEN 134 CONFERENCE /GROUP ROOM 359 DA_R SHHS FACULTY COMMAND CENTE... 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 540 VA 540 VA 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 1 20 A Spare 40 39 Spare 1 20 A Spare 42 41 Spare 720 VA 6A LOAD DEMAND (VA) 1080 VA TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 1080 VA 1080 VA 3A 3A 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) B C 540 VA 540 VA 540 VA 540 VA 540 VA 540 VA 900 VA 540 VA 720 VA 720 VA 720 VA 720 VA 360 VA 720 VA 180 VA 1080... 1080... 720 VA 1440... 720 VA 720 VA 1260... 720 VA 720 VA 1800... 720 VA 360 VA 900 VA 360 VA 360 VA 1080... 180 VA 720 VA 180 VA 180 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 0 VA 10260 VA 8820 VA 87 A 74 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 25560 VA 360 VA CIRCUIT DESCRIPTION CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A PRACTICUM THERAPY 364 PRACTICUM THERAPY 365 PRACTICUM THERAPY 366 PRACTICUM THERAPY 367 PRACTICUM THERAPY 368 PRACTICUM THERAPY 369 PRACTICUM INTERN OFFICE 398 PRACTICUM INTERN OFFICE 398 PRACTICUM INTERN OFFICE 398 PRACTICUM INTERN OFFICE 398 CAPS INTERN OFFICE 370 CAPS INTERN OFFICE 370 GENERAL RECEPTACLES CIRCULATION... DA_R SHHS FACULTY COMMAND CENTE... DA_R SHHS FACULTY COMMAND CENTE... DA_R CAPS INTERN OFFICE 370 DA_R PRACTICUM INTERN OFFICE 398 DATA ROOM 399 DATA ROOM 399 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 20 A DATA ROOM 399 40 1 20 A DA_R JANITOR 353 42 10080 VA 86 A LOAD DEMAND (VA) RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 17780 VA 29160 VA 21380 VA 81 A 59 A 0 VA 0 VA 0 VA DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% 3600 VA POLES TRIP NOTES 540 VA 540 VA 0 VA MOUNTING: SURFACE I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. 3600 VA GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. NOTES: 1. 2. 3. 4. Signature James A. LeClaire Registration Number Date 50358 07/24/15 Project For NAME: NR-31B VOLTAGE: 120/208 PHASE: 3 WIRE: 4 MIN. BUS RATING: 400 A MAIN SIZE: 400 A MAIN OPTIONS: MLO, 200% NEUTRAL CKT CIRCUIT DESCRIPTION NOTES TRIP POLES A 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 WOMENS RESTROOM 355 REC DA_R OPEN STUDY 352 ROOF RECEPTACLE DA_R SHHS FACULTY COMMAND CENTE... DA_R OPEN STUDY 352 Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 180 VA 360 VA 20 A 1 39 Spare 41 Spare LOAD CLASSIFICATION LIGHTING LOAD (DA_L) RECEPTACLE LOAD (DA_R) MOTOR LOAD - HEATING (DA_HM) MOTOR LOAD - COOLING (DA_CM) MOTOR LOAD - GENERAL (DA_M) LARGEST MOTOR - BRANCH (DA_LBM) MOTOR LOAD TOTALS KITCHEN LOAD (DA_K) ELECTRONIC LOAD (DA_EL) ELECTRIC HEATING (DA_E) DWELLING UNIT - GENERAL LOAD (DA_D) MISCELLANEOUS LOAD (DA_MI) SPARE CAPACITY (DA_SP) B 720 VA 720 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 1260 VA 1080 VA 12 A 10 A DEMAND FACTOR 125% 10 KVA @ 100%, Remaining @ 50% 100% 100% 100% 125% 0 VA 360 VA 0 VA 0 VA 20 A 1 TOTAL LOAD: TOTAL AMPS: CONNECTED LOAD (VA) 2160 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 180 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA 0 VA POLES TRIP NOTES 0 VA 360 VA 0 VA C MOUNTING: SURFACE DEMAND PER NEC 100% 100% 10 KVA @ 100%, Remaining @ 40% 100% 100% 0 VA 0 VA CIRCUIT DESCRIPTION CKT 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A 20 A UC REFRIGERATOR - NURSING MANAGE... Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare Spare 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 1 20 A Spare 40 1 20 A Spare 42 180 VA 2A LOAD DEMAND (VA) 2160 VA DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 TOTALS TOTAL CONN. LOAD: TOTAL EST. DEMAND: TOTAL CONN. CURRENT: TOTAL EST. DEMAND... 2520 VA 2520 VA 7A 7A 0 VA 0 VA Project No. Drawn By Checked By Date 360 VA GENERAL NOTES: A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM. NOTES: 1. 2. 3. 4. STUDENT HEALTH AND ACADEMIC RENOVATION 2263.001.00 Author Checker 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description PANEL SCHEDULES C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:06:53 PM E609 THERMOSTAT BY TEMP. CONTROL CONTRACTOR 1 1/2" TYP. DETAIL NOTES DIMMER SWITCH (WHERE INDICATED ON PLANS) 1 #12 WIRE TO FIXTURE(S) OR AS INDICATED. PROVIDE IN-LINE FUSE AND FUSE HOLDER WITH BREAKAWAY CAPABILITY, FERRAZ SHAMUT FEY, COOPER HEB SERIES, (4)(20)(XX) AMPERE BUSSMAN TYPE KTK OR PRE-APPROVED EQUAL. 2 PROVIDED BUSHED RIGID CONDUITS. CONDUIT STUBBED UP ADJACENT TO HANDHOLE; NUMBER AND SIZE AS REQUIRED. CAP SPARE CONDUITS. 3 COPPER EQUIPMENT GROUNDING CONDUCTOR ATTACH TO INTERNAL LUG WELDED TO INTERIOR OF POLE. CONDUCTOR TO BE SAME SIZE AND TYPE AS SUPPLY PHASE CONDUCTOR. 6 1 3 8 2 7 6 1 4 INSULATED COPPER GROUNDING CONDUCTOR ATTACHED TO INTERNAL LUG WELDED TO INTERIOR OF POLE. SIZE PER NFPA 70. EXOTHERMIC WELD TO DRIVEN GROUND ROD. 5 3/4"x10' COPPER GROUND ROD (MIN 6" BELOW GRADE). 6 FIXTURE POLE - REFER TO SITE LIGHTING FIXTURE SCHEDULE AND LIGHTING STANDARD DETAILS. 7 SET TOP OF CONCRETE FOUNDATION ABOVE GRADE AS INDICATED ON SITE LIGHTING FIXTURE SCHEDULE. 8 PROVIDE DOUBLE ANCHOR BOLT NUTS ABOVE AND BELOW POLE BASE. ADJUST TO PLUMB POLE. ANCHOR BOLT ASSEMBLY SHALL BE PROVIDED BY POLE MFG. INSTALL ACCORDING TO MFG TEMPLATE. USE SHRINK PROOF GROUT ON BASE. FURNISH BASE COVER FOR POLES. 9 REINFORCED ROUND CONCRETE FOUNDATION BASE. CONCRETE 5-7% AIR ENTRAINED 4000 PSI MINIMUM. 3 INCH MINIMUM CONCRETE COVER ON BARS AND TIES. FINISH CONCRETE ABOVE GRADE LEVEL AND BEVEL EDGE 45 DEGREES. FOOTING SHALL BE FORMED WHERE SOIL CONDITIONS REQUIRE. CHAMFER ALL EDGES OF CONCRETE BASE 1/2". TREAT EXPOSED CONCRETE WITH PROSOCO SALT-GUARD WATER-BASED OR PRE-APPROVED EQUAL. 3 8 4 10 10 36" MIN 36" MIN 5 9 5 9 11 11 12 ~ ~ ~ ~ ~ ~ THERMOSTAT BY TEMP. CONTROL CONTRACTOR 12 15 MOTORIZED SHADE SWITCH BY OTHERS (WHERE INDICATED ON PLANS) 15 13 13 14 "Y" 14 "Y" 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 SIDE CLOSEST TO DOOR Consultants 10 FULLY COMPACTED BACKFILL. 11 CIRCUIT CONDUCTORS AND CONDUIT TO POWER SOURCE OR NEXT POLE. 12 #4 BARS VERTICAL AT 6" EACH FACE (UNLESS NOTED OTHERWISE ON SITE LIGHTING FIXTURE SCHEDULE). Dunham Job #: 415134 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature "X" 4'-0" A.F.F. STD. MULTI - GANG BRUSHED STAINLESS STEEL SWITCH PLATE BASE HEIGHT NOTES BASE HEIGHT SCHEDULE 1. POLE HEIGHT "Y" DEPTH (FEET) "X" WIDTH (INCHES) 2. NOTES: ALL DEVICES AND COVER PLATES SHALL HAVE THE SAME COLOR. SWITCH PLATE COVER DETAIL NO SCALE DETAIL B 13 #3 BARS AT 12" ON CENTER HORIZONTALLY (UNLESS NOTED OTHERWISE ON SITE LIGHTING FIXTURE SCHEDULE). 14 REFER TO SITE LIGHTING FIXTURE SCHEDULE FOR DEPTH "Y" AND WIDTH "X" DIMENSIONS. 15 PROVIDE A MINIMUM ONE INCH RACEWAY FOR SECURITY DEVICES (AND CCTV CAMERAS). RACEWAY SHALL EXTEND TO SECURITY SYSTEM HEADEND UNLESS NOTED OTHERWISE. LIGHT SWITCHES MACHINE ENGRAVED BLACK FILLED LETTERS 1 14 DETAIL A SHADES 1. "X" 14 DIMMER SWITCH (WHERE INDICATED ON PLANS) 3. 2 BASE HEIGHT IS TYPICAL FOR SEDIMENTARY AND FOLIATED ROCK SOIL, ROUND TAPERED, POLES EXPOSED TO WINDS OF 70MPH, WITH ONE LIGHT FIXTURE. CONFIRM WITH STRUCTURAL ENGINEER FOR BASE WIDTH AND DEPTH REQUIREMENTS IF ENVIRONMENTAL VARIABLES DIFFER FROM ABOVE. [REFER TO POLE DEPTH CALCULATION FOR ADDITIONAL INFORMATION]. DESIGNER SHALL CHOOSE THE MOST APPLICABLE DETAIL, A OR B, FOR THE PROJECT. THE PRIMARY DIFFERENCE IS HEIGHT OF FOUNDATION ABOVE GROUND. EXTERIOR POLE BASE DETAIL WITH GROUNDING NO SCALE 612.677.7100 612.677.7499 fax www.rsparch.com 7 2 4 OR RSP Architects REBAR <14' 5 16 (4)#5 REBAR <14' 4.5 24 (4)#5 REBAR 15'-29' 6 24 (6)#5 REBAR 30'-40' 8 24 (8)#5 REBAR 30'-40' 6 30 (8)#5 REBAR James A. LeClaire Registration Number 50358 Date 07/24/15 Project For STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 Project No. 2263.001.00 Drawn By MMK Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description LIGHTING DETAILS C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:05:02 PM E700 DETAIL NOTES: 1. TYPICAL, CONNECTIONS TO OTHER SYSTEMS, PIPING, BUILDING STEEL, LIGHTNING PROTECTION, AND OTHER SYSTEMS. WALL 2" MIN GROUND LUG TWO HOLE COMPRESSION TYPICAL, SEE NOTE 5 GROUND BUSBAR SEE NOTE 4 REFER TO TYPICAL SERVICE GROUNDING DETAIL AND GROUNDING RISER DIAGRAM FOR ADDITIONAL INFORMATION. MAXIMUM O.D. OF CONDUIT MAXIMUM OPENING SIZE MINIMUM PUTTY THICKNESS FIRE RATING OF ASSEMBLY 5" 6 1/4 INCH 1/2 INCH 2 HOUR 10" 12 1/4 INCH 1 INCH 3 HOUR O.D. OF CONDUIT 2. BUS BAR SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION. 3. PROVIDE ELECTRO-TIN PLATED, CU BUSBAR WITH HOLES FOR USE WITH CORRECTLY MATCHED LISTED LUGS AND HARDWARE. 4. BUSBAR SHALL BE A MINIMUM OF 0.25" THICK BY 2 INCHES WIDE AND 24 INCHES IN LENGTH FOR ELECTRICAL GROUNDING BUSBARS. 5. MAKE CONNECTIONS WITH UL LISTED COMPRESSION OR MECHANICAL CONNECTORS. 6. GROUNDING ELECTRODE CONDUCTORS, BONDING CONDUCTORS AND JUMPERS, TYPICAL. PUTTY THICKNESS SEE TABLE ABOVE ANNULAR SPACE 3/4" MAX. FIRE RATED CONCRETE FLOOR RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 METAL CONDUIT SEE NOTE 6 24" AFF PHENOLIC STANDOFF INSULATOR Consultants NOTES: TO NEUTRAL BUS IN SERVICE ENTRANCE EQUIPMENT OR SEPARATELY DERIVED SYSTEMS EQUIPMENT OPENING SIZE SEE TABLE ABOVE FINISHED FLOOR SIDE VIEW SECTION 1 2 GROUNDING EQUALIZER (IF REQUIRED) SEE NOTE 5, NOTE 9 3M RECOMMENDATIONS ARE BASED ON U.L. FIRESTOP SYSTEM 202. 3. 3M FIRE BARRIER MP MOLDABLE PUTTY INSTALLED FLUSH TO BOTH SURFACES OF THE WALL. PENETRATION FIRESTOP FOR CONDUIT THROUGH CONCRETE FLOOR (2,3 HOUR) DETAIL NO SCALE 1. REFER TO TYPICAL SERVICE GROUNDING DETAIL AND GROUNDING RISER DIAGRAM FOR ADDITIONAL INFORMATION. 2. BUS BAR SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION. 3. PROVIDE ELECTRO-TIN PLATED, CU BUSBAR WITH HOLES FOR USE WITH CORRECTLY MATCHED LISTED LUGS AND HARDWARE. BUSBAR SHALL BE A MINIMUM OF 0.25" THICK BY 2 INCHES WIDE AND 18 INCHES IN LENGTH. O.D. OF CONDUIT BONDING CONDUCTOR SIZE VS LENGTH (TABLE 1) LINEAR LENGTH (FEET) PHENOLIC STANDOFF INSULATOR GROUND LUG TWO HOLE COMPRESSION TYPICAL, SEE NOTE 4 7'-0" AFF 5. 6. SEE NOTE 3 7. SEE NOTE 7 FINISHED FLOOR 14-20 MAXIMUM OPENING SIZE MINIMUM PUTTY THICKNESS FIRE RATING OF ASSEMBLY 5" 6 1/4 INCH 1/2 INCH 2 HOUR 10" 12 1/4 INCH 1 INCH 3 HOUR SIZE (AWG) PUTTY THICKNESS SEE TABLE ABOVE 6 Signature Registration Number 8. 9. MAKE CONNECTIONS WITH UL LISTED, IRREVERSIBLE, COMPRESSION OR MECHANICAL CONNECTORS. 21-26 3 SIZE BONDING CONDUCTORS PER ANSI-607-B. REFER TO TABLE 1, THIS DETAIL. 27-33 2 34-41 1 42-52 1/0 TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR SHALL BE A MINIMUM OF #6AWG CU. James A. LeClaire 4 4. WALL NEAREST ELECTRICAL GROUND BUS OR TELECOMMUNICATIONS BONDING BACKBONE (IF APPLICABLE) SEE NOTE 5 LESS THAN 13 MAXIMUM O.D. OF CONDUIT I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. METAL CONDUIT Date PROVIDE CONNECTION TO STRUCTURAL STEEL WITH A # 6AWG CU CONDUCTOR, MINIMUM. 53-66 2/0 ALL CONDUCTORS SHALL BE GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR. 67-84 3/0 50358 07/24/15 Project For ANNULAR SPACE 3/4" MAX. FIRE RATED CONCRETE OR CONCRETE BLOCK WALL NOTES: OPENING SIZE SEE TABLE ABOVE GROUNDING EQUALIZERS CONNECT MULTIPLE TMGB AND TGB ON THE SAME FLOOR. SIDE VIEW CROSS-SECTION VIEW 1. MAXIMUM ANNULAR SPACE BETWEEN CONDUIT AND OPENING SHALL NOT EXCEED 3/4 INCH. 2. 3M RECOMMENDATIONS ARE BASED ON U.L. FIRESTOP SYSTEM 202. 3. 3M FIRE BARRIER MP MOLDABLE PUTTY INSTALLED FLUSH TO BOTH SURFACES OF THE WALL. STUDENT HEALTH AND ACADEMIC RENOVATION ELEVATION SECTION TELECOMMUNICATIONS GROUND BAR DETAIL (TGB) NO SCALE 4 GROUNDING EQUALIZER (IF REQUIRED) SEE NOTE 5, NOTE 9 4" MIN (TMGB) TYPICAL, SEE NOTE 6 GROUND LUG TWO HOLE COMPRESSION TYPICAL, SEE NOTE 4 PHENOLIC STANDOFF INSULATOR PENETRATION FIRESTOP FOR CONDUIT THROUGH CONCRETE WALL (2,3 HOUR) DETAIL NO SCALE DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 DETAIL NOTES: 1. GROUND BUSBAR REFER TO TYPICAL SERVICE GROUNDING DETAIL AND GROUNDING RISER DIAGRAM FOR ADDITIONAL INFORMATION. 2. BUS BAR SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION. 3. PROVIDE ELECTRO-TIN PLATED, CU BUSBAR WITH HOLES FOR USE WITH CORRECTLY MATCHED LISTED LUGS AND HARDWARE. BUSBAR SHALL BE A MINIMUM OF 0.25" THICK BY 4 INCHES WIDE AND 18 INCHES IN LENGTH. BONDING CONDUCTOR SIZE VS LENGTH (TABLE 1) 1 HOUR RATED GYPSUM WALL LINEAR LENGTH (FEET) SIZE (AWG) LESS THAN 13 6 14-20 4 MAKE CONNECTIONS WITH UL LISTED, IRREVERSIBLE, COMPRESSION OR MECHANICAL CONNECTORS. 21-26 3 SIZE BONDING CONDUCTORS PER ANSI-607-B. REFER TO TABLE 1, THIS DETAIL. 27-33 2 34-41 1 42-52 1/0 PROVIDE CONNECTION TO STRUCTURAL STEEL WITH A # 6AWG CU CONDUCTOR, MINIMUM. 53-66 2/0 ALL CONDUCTORS SHALL BE GREEN OR MARKED WITH A DISTINCTIVE GREEN COLOR. 67-84 3/0 4. WALL 7'-0" AFF 5. 6. SEE NOTE 3 7. TO NEAREST ELECTRICAL GROUND BUS SEE NOTE 5 SEE NOTE 7 8. 9. TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR SHALL BE A MINIMUM OF #6AWG CU. 1/4" MINIMUM DIAMETER BEAD OF 3M FIRE BARRIER CP25N/S CAULK (TYPICAL) NOTES: METAL CONDUIT GROUNDING EQUALIZERS CONNECT MULTIPLE TMGB AND TGB ON THE SAME FLOOR. THE CAULK SHALL BE FORCED INTO THE ANNULAR SPACE TO THE MAXIMUM EXTENT POSSIBLE, FLUSH WITH THE EXTERIOR OF PENETRATION SURFACE. 2. FINISH CAULKING WITH 1/4" MINIMUM BEAD OF CP25N/S CAULK APPLIED TO THE PERIMETER OF THE CONDUIT AT ITS EGRESS FROM THE WALL. 3. THE MAXIMUM ANNULAR SPACE SHALL NOT EXCEED 3/16" INSTALL 3M FIRESTOP ON BOTH SIDES OF THE WALL. 3M RECOMMENDATION ARE BASED ON ASTM E-814 (UL 1479) FIRE TEST AND U.L. THROUGH -PENETRATION FIRESTOP SYSTEM #147. Project No. 2263.001.00 Drawn By MMK Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. ELEVATION TELECOMMUNICATIONS GROUND BAR DETAIL (TMGB) NO SCALE 1. 4. FINISHED FLOOR 5 2. CROSS-SECTION VIEW DETAIL NOTES: SEE NOTE 6 SECTION MAXIMUM ANNULAR SPACE BETWEEN CONDUIT AND OPENING SHALL NOT EXCEED 3/4 INCH. Dunham Job #: 415134 ELECTRICAL GROUND BAR DETAIL (SGB/EGB) NO SCALE GROUND BUSBAR 3 1. ELEVATION 2" MIN 612.677.7100 612.677.7499 fax www.rsparch.com 6 PENETRATION FIRESTOP FOR CONDUIT THROUGH GYPSUM WALL (1 HOUR) DETAIL NO SCALE © Copyright RSP Architects 2015. All rights reserved. Revisions No. Date Description ELECTRICAL DETAILS C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:05:09 PM E701 DETAIL KEY NOTES: TO ADDITIONAL EQUIPMENT XFMR TO OTHER SYSTEMS TGB XFMR GEC TO OTHER SYSTEMS TO OTHER MAIN SERVICE DISCONNECTING MEANS TO OTHER SEPARATELY DERIVED SYSTEMS TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB) G 2 TELDATA ROOM B. ALL BONDING BACKBONE CABLING WORK BY DIVISION 26. C. DIVISION 26 TO PROVIDE PULL STRING IN ALL CONDUIT RUNS. D. REFER TO GROUNDING DETAILS FOR ADDITIONAL DIRECTION. TO METAL GAS PIPING THIRD FLOOR THIRD FLOOR DATA 254 1/A GROUND ROD GROUNDING ELECTRODE; PROVIDE GROUND ROD GROUNDING ELECTRODES WHERE CODE COMPLIANT WATER PIPE, METAL FRAME STRUCTURE, AND CONCRETE ENCASED GROUNDING ELECTRODES DO NOT EXIST. PROVIDE DRIVEN GROUND RODS IN ACCORDANCE WITH NEC 250.52(A)(5), 250.53(A), 250.53(B), AND 250.53(G). KEY NOTES: 1 MOUNT DEVICE AT 7'-0" AFF. RSP Architects COMMON GROUNDING ELECTRODE CONDUCTOR; PROVIDE #3/0 CU, MINIMUM, IN ACCORDANCE WITH NEC 250.30(A). CONDUCTOR SHALL BE CONTINUOUS. CONNECTIONS SHALL BE MADE AT A EQUIPMENT GROUNDING BUSBAR. TGB G 2 MULTIPLE SERVICE DISCONNECTS; PROVIDE COMMON GROUNDING ELECTRODE IN ACCORDANCE WITH NEC 250.58, SIZE GROUNDING ELECTRODE CONDUCTOR, FOR MULTIPLE SERVICES, IN ACCORDANCE WITH NEC 250.64(D). G 1 MAIN SERVICE EQUIPMENT TO OTHER SYSTEMS DATA 131 NEUTRAL BUSBAR METER GEC MAIN BONDING JUMPER AND SYSTEM BONDING JUMPERS; PROVIDE JUMPER IN ACCORDANCE WITH NEC 250.28(A) THROUGH 250.28(C). SIZE JUMPER ACCORDANCE WITH NEC 250.28(D)(1) THROUGH 250.28(D)(3), AND NO SMALLER THAN THOSE SPECIFIED IN TABLE 250.102(C)(1). PROVIDE GROUNDING AND BONDING FOR SEPARATELY DERIVED (GROUNDED) SYSTEMS IN ACCORDANCE WITH NEC 250.30.(A). SERVICE EQUIPMENT BONDING; PROVIDE BONDING JUMPER IN ACCORDANCE WITH NEC 250.92 AND SIZED IN ACCORDANCE WITH NEC 250.102(C). TGB TO SERVICE TRANSFORMER BOND METAL WATER PIPES IN ACCORDANCE WITH NEC 250.104(A). SIZE BONDING JUMPERS IN ACCORDANCE WITH NEC 250.66. GEC GEC GEC METAL WATER SERVICE PIPES BURIED TO 10'-0"MIN ELECTRICAL ROOM 022 TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB). PROVIDED AND INSTALLED BY DIVISION 26. SEE DETAILS FOR ADDITIONAL DIRECTION. G 2 TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) PROVIDED AND INSTALLED BY DIVISION 26. SEE DETAILS FOR ADDITIONAL DIRECTION. G 3 ELECTRICAL ROOM GROUNDING BUS BAR (EGB) PROVIDED AND INSTALLED BY DIVISION 26. SEE DETAILS FOR ADDITIONAL DIRECTION. G 4 SERVICE GROUNDING BUS BAR (SGB) PROVIDED AND INSTALLED BY DIVISION 26. SEE DETAILS FOR ADDITIONAL DIRECTION. DATA ROOM 021 1. THE DETAIL REPRESENTS A TYPICAL GROUNDING AND BONDING INSTALLATION. ALL NECESSARY ACCESSORIES AND REQUIREMENTS ARE NOT SHOWN. NOT ALL COMPONENTS AND EQUIPMENT SHOWN MAY BE UTILIZED IN THE PROJECT. 2. ALL CONDUCTOR SIZES SHOWN ARE BASED ON CU. REVISE CONDUCTOR SIZES PER NEC IF ALUMINUM CONDUCTORS ARE PROVIDED. 3. INSTALL EQUIPMENT GROUNDING CONDUCTORS, GROUNDING ELECTRODE CONDUCTORS (GEC), AND BONDING JUMPERS IN ACCORDANCE WITH NEC 250.8. 4. INSTALL GROUNDING ELECTRODE CONDUCTORS (GEC) IN ACCORDANCE WITH NEC 250.64. INSTALL GROUNDING ELECTRODE CONDUCTORS AT BUSBAR LOCATIONS IN ACCORDANCE WITH NEC 250.64(B) AND 250.64(C). 5. MAKE SPLICES OF WIRE TYPE GEC WITH LISTED IRREVERSIBLE COMPRESSION OR MECHANICAL-TYPE CONNECTORS OR BY EXOTHERMIC WELD. 6. MAKE GROUNDING ELECTRODE CONDUCTOR (GEC) AND BONDING JUMPER CONNECTIONS IN ACCORDANCE WITH NEC 250.68 AND 250.70. 7. SIZE GROUNDING ELECTRODE CONDUCTORS (GEC) AND TAPS IN ACCORDANCE WITH NEC 250.66, UNLESS INDICATED OTHERWISE. 8. GROUND AND BOND ALL METALLIC UNDERGROUND PIPING. Dunham Job #: 415134 CABLE TYPE CALLOUT CABLE QUANTITIES BOND UNGROUNDED STRUCTURAL METAL IN ACCORDANCE WITH NEC 250.104(C). SIZE JUMPERS CONDUCTORS IN ACCORDANCE WITH NEC 250.66. #/A 1/A BOND LIGHTNING PROTECTION SYSTEMS (IF AVAILABLE) IN ACCORDANCE WITH NEC 250.106 AND NFPA 780. DETAIL NOTES #/A 1/A SGB ELEC ROOM BOND OTHER SYSTEMS (CATV, ANTENNA, FIBER OPTIC, TELECOMMUNICATIONS SYSTEMS) TO THE ELECTRICAL GROUND SYSTEM WITH A #6AWG CU CONDUCTOR, MINIMUM, IN ACCORDANCE WITH NEC 250.94, UNLESS INDICATED OTHERWISE. INDIVIDUAL DEVICE CALLOUT CABLE TYPE: FIRST FLOOR FIRST FLOOR BOND OTHER METAL PIPING IN ACCORDANCE WITH NEC 250.104(B). SIZE BONDING JUMPERS IN ACCORDANCE WITH NEC 250.122. Consultants DEVICE TYPE CALLOUT G 1 G 2 TELDATA ROOM SIZE BONDING JUMPER PER NEC 250.122, WHERE GROUNDING ELECTRODE CONDUCTOR IS CONNECTED SUPPLY SIDE OF WATER METER. 612.677.7100 612.677.7499 fax www.rsparch.com SECOND FLOOR SECOND FLOOR SERVICE NEUTRAL CONDUCTOR; DO NOT PROVIDE EQUIPMENT GROUNDING CONDUCTOR IN CONDUITS FROM SERVICE EQUIPMENT (TRANSFORMERS). 1/A TO LIGHTNING PROTECTION SYSTEM 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 EQUIPMENT: TELDATA ROOM TO METAL WATER PIPING ELECTRICAL GROUND BUSBAR 1 A. ALL CABLING SHALL BE INDEPENDENTLY SUPPORTED FROM STRUCTURE. GROUND RING TYPE GROUNDING ELECTRODE; ELECTRODE SHALL BE COMPLIANT WITH NEC 250.52(A)(4) AND 250.53(F). GROUND ELECTRODE CONDUCTOR SHALL BE THE SAME SIZE CONDUCTOR AS RING CONDUCTOR IN ACCORDANCE WITH NEC 250.66(C), A MINIMUM OF #2/0AWG CU. ELECTRICAL GROUNDING BUSBAR (EGB) GENERAL NOTES: DATA 399 CONCRETE ENCASED GROUNDING ELECTRODE; ELECTRODE SHALL BE COMPLIANT WITH NEC 250.52(A)(3). TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TGB) GROUNDED METAL BUILDING FRAME UNDERGROUND METAL WATER PIPE GROUNDING ELECTRODE; PIPE MUST BE BURIED A MINIMUM OF 10'-0" IN ACCORDANCE WITH NEC 250.52(A)(1) AND INSTALLED PER NEC 250.53(D). METAL FRAME OF BUILDING OR STRUCTURE USED AS GROUNDING ELECTRODE; ELECTRODE SHALL BE COMPLIANT WITH NEC 250.52(A)(2). GEC UNGROUNDED METAL BUILDING FRAME ROOF LEVEL G 4 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. #3/0 AWG CABLE [TELECOMMUNICATION BONDING]. G 1 TMGB IT ROOM Signature James A. LeClaire Registration Number 50358 LOWER LEVEL Date REFER TO ELECTRICAL GROUNDING BUSBAR (EGB) DETAIL FOR ADDITIONAL INFORMATION. 07/24/15 Project For REFER TO TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB) DETAIL FOR ADDITIONAL INFORMATION. 2 GROUNDING RISER DIAGRAM NO SCALE REFER TO TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) DETAIL FOR ADDITIONAL INFORMATION. NOTES: 1. ROOFING CONTRACTOR TO FLASH AND SEAL ROOF PENETRATIONS PER ARCHITECTURAL SPECIFICATIONS AND APPLICABLE CODES. LOCATE UL LABEL ADJACENT TO EZ-PATH ASSEMBLY (TYP) TYPICAL SERVICE GROUNDING DETAIL - (BASED ON 2014 NEC) NO SCALE MOUNT DUPLEX OUTLET TO UNISTRUT UL LABEL EZ-PATH SERIES "44" PATHWAY MODULE UNISTRUT - MIN. 26" ABOVE FINISHED ROOF TO TOP DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 SERIES "44" MODULAR GRID SYSTEM WP IN-USE COVER STUDENT HEALTH AND ACADEMIC RENOVATION WELD UNISTRUT TO STEEL PLATE SOLID 1" HOLE FOR CONDUIT 3 NOTES: 6"X6"X1/4" STEEL PLATE. BOLT TO ROOF DECK IN 4 PLACES ROOFTOP RECEPTACLE DETAIL - UNISTRUT MOUNTED NO SCALE 4 1. INSTALL PER MANUFACTURER'S INSTALLATION INSTRUCTIONS. 2. PART NUMBERS LISTED FOR REFERENCE AND MAY NOT REPRESENT ALL REQUIRED COMPONENTS FOR A COMPLETE INSTALLATION. SEE SPECIFICATIONS. FIRE STOP DETAIL - CORRIDOR PENETRATION NO SCALE Project No. 2263.001.00 Drawn By MMK Checked By Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. SPD Revisions No. Date Description PM 91.50 35.50 1.5 24.00 36.00 24.00 36.00 60.00 5 2000A ENCLOSED CIRCUIT BREAKER ELEVATION AND FLOOR PLAN NO SCALE ELECTRICAL DETAILS C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:05:16 PM E702 ROOF GENERAL NOTES ACCESS CTRL RELEASE TAMPER FLOW SWITCH SWITCH F F #/C #/E TYP F F F sF F F SB #/C #/C F MM S ES S ML CM F #/C F P FH F F F MC FR F TYP F RL F B. THE SYSTEM DIAGRAM IS BASED ON A DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM. C. 3 sF THE WIRING DIAGRAM IS CONCEPTUAL ONLY AND DOES NOT INDICATE ALL DEVICES, DEVICE TYPES OR QUANTITY OF LOOPS. REFER TO FLOOR PLANS FOR DEVICE QUANTITIES AND LOCATIONS. F P FH F P FH F MC F F MM MM A. S EL #/C D. DIGITAL VOICE EVAC/PAGING AMPLIFIER 4 C NAC DH F TO ADDITIONAL DOOR HOLDERS DH F #/B (DATA ROOM) 4 C TO ADDITIONAL SMOKE, FIRE/SMOKE DAMPERS D D 5 #/C #/C #/C #/E TYP F F F F MM sF F F SB F F F MC FR F TYP F I/O F I/O R G KEY NOTES DIGITAL VOICE EVAC/PAGING AMPLIFIER 4 C NAC DH F TO ADDITIONAL DOOR HOLDERS DH F TO ADDITIONAL SMOKE, FIRE/SMOKE DAMPERS #/B (DATA ROOM) D 1 RELOCATED FIRE ALARM CONTROL PANEL. 2 DIGITAL VOICE EVACUATION AND PAGING SYSTEM INTERFACE WITH TELEPHONE SYSTEM. 3 EMS CONNECTION, COORDINATE WITH CONTROLS CONTRACTOR FOR FINAL CONNECTION REQUIREMENTS 4 LIFE SAFETY BRANCH CIRCUIT (REFER TO POWER PLAN DWGS). 5 FIRE/SMOKE AND SMOKE DAMPER MOTORS ARE SHOWN ON MECHANICAL PLANS. VERIFY QUANTITIES AND LOCATIONS. PROVIDE FIRE ALARM CONNECTIONS TO RELAY SO THAT THE FIRE/SMOKE AND SMOKE DAMPERS CLOSE UPON LOSS OF POWER. (DIVISION 26 SHALL PROVIDE RELAY AND CIRCUITING. SEE POWER PLANS FOR 120V CIRCUITING, RELAY LOCATIONS, ETC.) PROVIDE ONE (1) FIRE ALARM CONTROL MODULE PER FIRE/SMOKE DAMPER GROUP ON EACH FLOOR OF EAST AND WEST BUILDINGS. 4 C D 5 SECOND FLOOR ACCESS CTRL RELEASE TAMPER FLOW SWITCH SWITCH F F #/E TYP F WP FIRE DEPARTMENT +10' AFG CM F F CONNECTOIN (FDC) F F F MM sF F F SB #/C #/C #/C S ES S ML CM F #/C F P FH F F P FH F P FH F MC F F MM MM S EL F F MC FR F TYP 6 F RL F AHU sF AHU 4 C NAC DH F TO ADDITIONAL DOOR HOLDERS DH F TO ADDITIONAL SMOKE, FIRE/SMOKE DAMPERS #/B (DATA ROOM) 4 C D ID TAG NOTATION #/A 5 CABLE TYPE BRANCH CIRCUIT #/C CONTROL CIRCUIT #/D FIBER OPTIC CONNECTION #/E SIGNAL LINE CIRCUIT #/F TWO-HOUR RATED PRIMARY BACKBONE (CLASS A) #/G TWO-HOUR RATED REDUNDANT BACKBONE (CLASS A) #/H FUTURE FIRE FIGHTERS TELEPHONE HOMERUN #/ J AUDIO INPUT REMOTE INDICATOR/TEST STATION, FURNISHED BY FIRE/SMOKE DAMPER MANUFACTURE IN ACCORDANCE WITH DIVISION 23, INSTALLED AND WIRED BY DIVISION 26. SHALL HAVE RED LED FOR CLOSED, GREEN FOR OPEN, AND KEYED TEST SWITCH. REFER TO FIRE/SMOKE DAMPER SCHEDULE AND PLANS FOR LOCATION RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 VFD FIRE ALARM OUTPUT MODULE (1 FOR EACH AHU). PROVIDED BY DIVISION 26. I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature James A. LeClaire Registration Number BMS FACP BUILDING MANAGEMENT SYSTEM (BMS) FACP #/B K BMS DATA LINK BMS INITIATING LINE CIRCUIT G FIRE ALARM CONTROL PANEL (FACP). REFER TO FIRE ALARM CONTROL MATRIX FOR PROGRAMMING OF FA SYSTEM. CABLE TYPE CALLOUT #/A K FIRE ALARM DATA LINK FIRE ALARM DATA LINK CABLE QUANTITIES FIRST FLOOR R RELAY WIRING, PROVIDED BY DIVISION 23 FIRE ALARM OUTPUT MODULE (1 FOR EACH AHU). PROVIDED BY DIVISION 26. BUILDING MANAGEMENT SYSTEM (BMS) D FSD BMS INPUT MODULE, PROVIDED BY DIVISION 23 (1 PER AHU) BMS DATA LINK DIGITAL VOICE EVAC/PAGING AMPLIFIER F I/O F CM RELAY WIRING, PROVIDED BY DIVISION 23 #/C FIRE ALARM ADDRESSABLE I/O RELAY MODULE WITH EOL FOR DUCT DETECTOR "SUPERVISORY" SIGNAL AND DUCT DETECTOR RESET FIRE/SMOKE DAMPER, AS SPECIFIED; WITH 120V MOTOR, FURNISHED AND INSTALLED IN ACCORDANCE WITH DIVISION 23, WIRED BY DIVISION 26 VFD BMS INPUT MODULE, PROVIDED BY DIVISION 23 (1 PER AHU) 3 F I/O F R F CM PHONE CONNECTION TO PHONE SWITCH. MR G REMOTE INDICATOR/ RESET STATION, FURNISHED BY FIRE/ SMOKE DAMPER MANUFACTURE IN ACCORDANCE WITH DIVISION 23, INSTALLED AND WIRED BY DIVISION 26. SHALL HAVE RED LED FOR TROUBLE, GREEN FOR NORMAL, AND A RESET SWITCH. REFER TO FIRE/ SMOKE DAMPER SCHEDULE AND PLANS FOR LOCATION. #/C FIRE ALARM ADDRESSABLE I/O RELAY MODULE WITH EOL FOR DUCT DETECTOR "TROUBLE" SIGNAL AND DUCT DETECTOR RESET J PHOTOELECTRIC DUCT SMOKE DETECTOR FURNISHED AND FACTORY INSTALLED WITH FIRE/SMOKE DAMPER IN ACCORDANCE WITH DIVISION 23. FIRE ALARM ADDRESSABLE I/O RELAY MODULE WITH EOL FOR DUCT DETECTOR "SUPERVISORY" SIGNAL AND DUCT DETECTOR RESET. F RL F 3 sF F PHOTOELECTRIC DUCT SMOKE DETECTOR FURNISHED AND FACTORY INSTALLED WITH FIRE/SMOKE DAMPER IN ACCORDANCE WITH DIVISION 23. REFER TO FIRE ALARM CONTROL MATRIX FOR ALL CONTROL REQUIREMENTS. H. F P FH F P FH F MC F F MM MM S EL #/C F P FH FIRE ALARM ADDRESSABLE I/O RELAY MODULE WITH EOL FOR DUCT DETECTOR "TROUBLE" SIGNAL AND DUCT DETECTOR RESET. 120V POWER WIRING, BY DIVISION 26. REFER TO PLANS FOR CIRCUITING INFORMATION ALL SPRINKLER HEADS, LOCATED IN ELEVATOR SHAFTS AND ELEVATOR EQUIPMENT ROOMS, ARE TO HAVE A HEAT DETECTOR MOUNTED WITHIN TWO (2) FEET OF HEAD FOR ACTIVATION OF SHUNT TRIP POWER DEVICE. VERIFY QUANTITY ON SITE. G. S ES S ML CM F PROVIDE MOTOR RATED TOGGLE SWITCH FOR EACH DAMPER MOTOR PROVIDE ALL CONTROL WIRING FROM FIRE ALARM CONTROLLER AND/OR DEVICES TO HVAC CONTROLLERS. F. ACCESS CTRL RELEASE TAMPER FLOW SWITCH SWITCH F F THE INSTALLATION SHALL BE FROM DRAWINGS THAT HAVE BEEN SUBMITTED, REVIEWED AND APPROVED BY THE AUTHORITIES HAVING JURISDICTION. EACH SIGNALLING CIRCUIT SHALL ALLOW 15% SPARE CAPACITY TO ADD ADDITIONAL AUDIO, VISUAL OR COMBINATION AUDIO/VISUAL SIGNALING DEVICES TO ANY OF THESE CIRCUITS. E. THIRD FLOOR ALL WIRING AND CABLING SHALL BE IN CONDUIT (MINIMUM 3/4" C.) EMT CONDUIT USED FOR FIRE ALARM WIRING SHALL INCLUDE FACTORYAPPLIED RED TOPCOAT UL-LISTED FOR FIRE ALARM USE. 120V POWER WIRING, BY DIVISION 26. REFER TO PLANS FOR CIRCUITING INFORMATION FIRE ALARM CONTROL PANEL (FACP). REFER TO FIRE ALARM CONTROL MATRIX FOR PROGRAMMING OF FA SYSTEM Date 50358 07/24/15 Project For STUDENT HEALTH AND ACADEMIC RENOVATION ACCESS CTRL RELEASE #/E TYP F F F F ELEV CONTROLLER F TAMPER FLOW SWITCH SWITCH F F #/C sF sF #/C F MM #/C #/C F F MM MM 3 S EL #/C F P FH F F P FH F P FH F MC F CM ELEV RECALL S ES S ML CM F F F MC 2 FR F TYP F RL F DUCT DETECTOR DETAIL NO SCALE 3 #/C LOUVER DIGITAL VOICE EVAC/PAGING AMPLIFIER 1 RELOCATED FACP 4 C DH F TO ADDITIONAL DOOR HOLDERS DH F #/B (MAIN ELECTRICAL ROOM) #/B OWNER LAN CONNECTION #/D BACNET IP GATEWAY COMMUNICATION CONNECTIONS TO ENERGY MANAGMENT SYSTEM AND LIGHTING CONTROL SYSTEM #/H #/A 4 #/ J 6 4 C TO ADDITIONAL SMOKE, FIRE/SMOKE DAMPERS D F D F P TOP OF SHAFT DACT IP DIGITAL ALARM COMMUNICATION TRANSMITTER F 3RD FLOOR LOBBY F P SUPERVISED MANUAL SHUT-OFF VALVE IN SPRINKLER LINE BY DIV 21. IF INSTALLED, DIV 26 TO CONNECT TO FA SYSTEM FOR SUPERVISED STATUS. BASEMENT 135 HEAT DETECTOR, FIXED RATE, SET AT 135° SPRINKLER HEAD SET AT 212° 212° SUPERVISED FLOW SWITCH BY DIV 21. DIV 26 TO CONNECT TO FA SYSTEM DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 F P SMOKE DETECTOR J F 135 F 5 2 #/B FIRE/SMOKE DAMPER - DUCT DETECTOR DIAGRAM NO SCALE 2ND FLOOR LOBBY F P 1ST FLOOR LOBBY F P K FIRE ALARM CABLING RISER DIAGRAM NO SCALE 1 FIRE ALARM CONTROL MATRIX ACTION SEND ALARM SIGNAL TO FACP 1 SEND SUPERVISORY SIGNAL TO FACP 1 SEND TROUBLE SIGNAL TO FACP 1 MANUAL PULL STATION XX PATIENT AREA ROOM HEAT SMOKE SMOKE DETECTOR DETECTOR DETECTOR XX XX ACTIVATE NOTIFICATION DEVICES ON FLOOR OF ACTIVATION, FLOOR ABOVE, AND FLOOR BELOW RELEASE DOOR HOLDS, POWERED FIRE DOORS, AND POWERED SECURITY DOORS THROUGHOUT BUILDING RELEASE DOOR HOLDS, POWERED FIRE DOORS, AND POWERED SECURITY DOORS IN SMOKE COMPARTMENT OF INITIATION ONLY RECALL CORRESPONDING ELEVATOR/ELEVATOR BANK TO PRIMARY LEVEL RECALL CORRESPONDING ELEVATOR/ELEVATOR BANK TO ALTERNATE LEVEL(S) ACTIVATE CORRESPONDING ELEVATOR/ELEVATOR BANK SHUNT TRIP 5 ELEVATOR LOBBY SMOKE DETECTOR HEAT PRIMARY ALTERNATE SMOKE LEVEL LEVEL DETECTOR DETECTOR XX XX ELEVATOR EQUIPMENT ROOM AND ELEVATOR SHAFT XX XX XX FLOW SWITCH XX ZONE WATER FLOW SWITCH XX MAIN WATER FLOW SWITCH POST SPRINKLER INDICATOR SYSTEM VALVE TAMPER TAMPER SWITCH FA PHONE LINE LOSS XX XX XX XX SPEAKER PRIMARY & FIRE ALARM AMP OR SECONDARY PANEL/ GENERATOR TONE POWER CIRCUIT MONITOR GENERATOR MONITOR TROUBLE TROUBLE F F F P MACHINE ROOM PHASE ONE RECALL TO MAIN FLOOR OR ALTERNATE IF OVER 25 FT OF TRAVEL AS PER ANSI A17.1 SECTION 211.3 XX XX XX XX XX XX XX 3 PHASE FEED XX POWER SHUT DOWN SHUNT TRIP DEVICE MMK Checked By F 135 212° 2263.001.00 Drawn By 212° XX XX 5 XX XX SHUT DOWN ENTIRE SMOKE COMPARTMENT SUPPLY, RETURN, AND EXHAUST FANS; & CLOSE ASSOCIATED SMOKE DAMPERS ACTIVATE NOTIFICATION DEVICES ON ALL FLOORS DEDICATED F/S DOOR AHU DAMPER HOLD DUCT DUCT SMOKE DETECTOR DETECTOR DETECTOR Project No. F P PIT FIRE ALARM DEVICE NOTES NOTES: F 135 3 PHASE ELEVATOR CONTROLLER Date JL 2/19/16 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. XX XX Revisions XX 4 ELEVATOR FIRE ALARM CONTROL RISER DIGRAM NO SCALE No. Date Description XX XX XX XX XX XX XX 10 XX XX 10 2,4 4,15 7 4 4 12 12 12 XX XX 9,12 11,12 6 17 3 14 8,16 GENERAL NOTES: A. REFER TO DIVISION 28 SPECIFICATIONS FOR ADDITIONAL FIRE ALARM SYSTEM REQUIREMENTS. B. ALL ACTIONS SHALL INDICATE A SPECIFIC DEVICE AND LOCATION TO THE CONTROL PANEL(S), ANNUNCIATOR PANEL(S), DACT, AND SYSTEM PRINTER. C. NOT ALL DEVICES MAY BE REQUIRED. REFER TO PLANS FOR ACTUAL DEVICES. SPECIFIC NOTES: 1. SEND SIGNAL TO REMOTE ALARM RECEIVING STATION. 2. IN SOME ROOMS, AREA SMOKE DETECTORS SHALL BE PROGRAMMED SO THAT UPON ACTIVATION OF THE FIRST SMOKE DETECTOR, A SUPERVISORY SIGNAL IS SENT. UPON ACTIVATION OF A SECOND SMOKE DETECTOR AN ALARM SIGNAL WILL BE SENT. REFER TO PLANS FOR DUAL SMOKE DETECTOR LOCATIONS AND ZONING. 3. FACP SHALL SWITCH TO SECOND PHONE LINE AND SEND TROUBLE SIGNAL TO REMOTE ALARM RECEIVING STATION. 4. FOR SMOKE TYPE DETECTORS FOR SMOKE DAMPER CONTROL, FACP SHALL SEND SIGNAL TO BUILDING MANAGEMENT SYSTEM TO SHUT DOWN ONLY SUPPLY, RETURN, AND EXHAUST FANS FOR ENTIRE AFFECTED SMOKE COMPARTMENT (10) SECONDS PRIOR TO CLOSING ASSOCIATED FIRE/SMOKE DAMPERS. REFER TO AHU ZONING PLANS. 5. ACTIVATE ALL EXTERIOR NOTIFICATION DEVICES. 6. ACTIVATE STAND-ALONE EXTERIOR NOTIFICATION DEVICE LOCATED ABOVE SIAMESE CONNECTION. 7. RELEASE DOOR HOLD FOR ASSOCIATED DOOR ONLY. REFER TO PLANS FOR DEDICATED DOOR HOLD SMOKE DETECTOR LOCATIONS. 8. FOR OVERHEAD COILING DOORS, PROVIDE TIME DELAY OF AT LEAST 15 SECONDS AFTER LOSS OF POWER BEFORE DOOR HOLDS ARE RELEASED. 9. LOCATE DEVICE WITHIN 2' OF EACH SPRINKLER HEAD. HEAT DETECTORS SHALL HAVE A LOWER RESPONSE TIME INDEX (RTI) THAN THE SPRINKLER HEAD IN THAT AREA. 10. ELEVATOR RECALL SHALL NOT RECALL ELEVATOR/ELEVATOR BANK TO SAME FLOOR AS FLOOR WITH ACTIVATED INITIATING DEVICE. 11. DEVICE(S) SHALL ACTIVATE SHUNT TRIP IMMEDIATELY UPON OR PRIOR TO DISCHARGE OF WATER. 12. ACTION SHALL BE MANUALLY RESET ONLY. ELEVATOR SMOKE DETECTORS ARE NOT ALLOWED TO PERFORM ALARM VERIFICATION. 13. MONITOR FOR PUMP RUNNING, PHASE REVERSAL, AND FAILURE. 14. GENERATOR FAILED START SHALL SEND TROUBLE SIGNAL. UPON GENERATOR START, FACP AND REMOTE FAAP'S SHALL INDICATE GENERATOR IN "RUN" MODE. 15. SMOKE DETECTOR SHALL HAVE AUXILIARY CONTACTS FOR CONNECTION TO PATIENT ROOM NURSE CALL LIGHT, WIRING BY OTHERS. 16. DACT PRIMARY POWER TROUBLE SIGNAL SHALL BE SENT WHEN BATTERY CAPACITY IS BETWEEN 25 & 50%. 17. SEND SIGNAL ON BOTH OFF-NORMAL POSITION AND RETURN TO NORMAL POSITION. 18. UPON ACTIVATION OF MAIN WATER FLOW SWITCH, FA SHALL SEND SIGNAL TO CONTROL MODULE AT MATER SERVICE EMERGENCY CONTROL VALVE TO CLOSE DOMESTIC WATER SUPPLY TO THE REST OF THE BUILDING. COORDINATE WITH MECHANICAL CONTRACTOR. 5 FIRE ALARM CONTROL MATRIX NO SCALE C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt 2/18/2016 4:05:24 PM FIRE ALARM DETAILS E703 PLUMBING FIXTURE SCHEDULE FIXTURE TAG P-1 FIXTURE DESCRIPTION WATER CLOSET MOUNTING WALL ADA NO P-1A WATER CLOSET WALL YES P-2 URINAL WALL NO P-2A URINAL WALL YES P-3 LAVATORY SEMI-COUNTER TOP YES P-3A LAVATORY COUNTER DROP IN NO P-3B LAVATORY WALL YES P-4 ICE MAKER CONNECTION BOX WALL NA P-5 SERVICE SINK FLOOR NA P-5A SERVICE SINK WALL NA P-6 DOUBLE BOWL SINK COUNTER DROP IN NO P-7 SHOWER P-8 WALL WALL HYDRANT FIXTURE AMERICAN STANDARD AFWALL 3351.101, ELONGATED BOWL, WALL MOUNTED WITH TOP SPUD, WHITE, EVERCLEAN SURFACE. AMERICAN STANDARD AFWALL 3351.101, ELONGATED BOWL, WALL MOUNTED WITH TOP SPUD, WHITE, EVERCLEAN SURFACE. AMERICAN STANDARD WASHBROOK 6590.001, ELONGATED 14" RIM, WALL MOUNTED WITH TOP SPUD, WASHOUT FLUSH, STRAINER, WHITE. AMERICAN STANDARD WASHBROOK 6590.001, ELONGATED 14" RIM, WALL MOUNTED WITH TOP SPUD, WASHOUT FLUSH, STRAINER, WHITE. AMERICAN STANDARD MEZZO SEMI-COUNTERTOP, SINGLE HOLE WALL VENT (IN) 2 CW (IN) 1 1/2 HW (IN) NA RO (IN) NA FLOOR SET VERTICALLY ADJUSTABLE WITH AUXILIARY SUPPORT ASSEMBLY (4 FEET SUPPORTS). 4 NA 2 1 1/2 NA NA PROVIDE OPEN FRONT WHITE SEAT EQUAL TO OLSONITE 95SSCT. FLUSH VALVE HANDLE TO BE ON THE APPROACH SIDE OF WATER CLOSET. FLOOR MOUNTED, HANGER PLATE, ADJUSTABLE SUPPORTING RODS, STRUCTURAL UPRIGHTS AND WELDED FEET. FLOOR MOUNTED, HANGER PLATE, ADJUSTABLE SUPPORTING RODS, STRUCTURAL UPRIGHTS AND WELDED FEET. NA 2 NA 1-1/2 3/4 NA NA ALL URINALS TO BE INSTALLED WITH MANUFACTURERS STAINLESS STEEL NON-REMOVEABLE DRAIN STRAINER 2 NA 1-1/2 3/4 NA NA ALL URINALS TO BE INSTALLED WITH MANUFACTURERS STAINLESS STEEL NON-REMOVEABLE DRAIN STRAINER 1-1/2 1-1/4 1-1/2 1/2 1/2 NA PROVIDE CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8 FITTINGS) TRAP INTEGRAL CARRIER FLOOR SET VERTICALLY ADJUSTABLE WITH AUXILIARY SUPPORT ASSEMBLY (4 FEET SUPPORTS). SLOAN MANUAL FLUSHOMETER MODEL ROYAL 111-1.28, 1-1/2" SPUD INTEGRAL ANGLE STOP ON FLUSH VALVE. INTEGRAL SLOAN FLUSHOMETER MODEL ROYAL OPTIMA SMOOTH 186-1.0-HW, HARDWIRED SIDE MOUNT SENSOR OPERATED, 1.0 GPF LOW CONSUMPTION, ANGLE STOP, 3/4" IPS, TOP SPUD, POLISHED CHROME. SLOAN FLUSHOMETER MODEL ROYAL OPTIMA SMOOTH 186-1.0-HW, HARDWIRED SIDE MOUNT SENSOR OPERATED, 1.0 GPF LOW CONSUMPTION, ANGLE STOP, 3/4" IPS, TOP SPUD, POLISHED CHROME. CHICAGO FAUCETS 116.706.AB.1, HARDWIRED SENSOR OPERATED, DECK MOUNTED, SINGLE HOLE, 0.5 GPM, POLISHED CHROME. INTEGRAL ANGLE STOP ON FLUSH VALVE. INTEGRAL INTEGRAL ANGLE STOP ON FLUSH VALVE. INTEGRAL CHICAGO 1025-ABCP QUARTER TURN POLISHED C.P. CAST BRASS ANGLE VALVE KITS, LOOSE KEY, FLEXIBLE RISERS, ESCUTCHEON CHICAGO 1025-ABCP QUARTER TURN POLISHED C.P. CAST BRASS ANGLE VALVE KITS, LOOSE KEY, FLEXIBLE RISERS, ESCUTCHEON CHICAGO 1025-ABCP QUARTER TURN POLISHED C.P. CAST BRASS ANGLE VALVE KITS, LOOSE KEY, FLEXIBLE RISERS, ESCUTCHEON 1-1/4" PVC TRAP, EXT TO WALL, W/ ESCUTCHEON W/ GRID STRAINER CHICAGO FAUCETS 540-LD897SWXFXKCP, WALL CRANE/FIAT MSB 2424 MOP SERVICE BASIN, 24" X 24" X 10" DEEP, MOLDED MOUNTED, 5-3/4" VACUUM BREAKER SPOUT WITH HOSE STONE, STAINLESS STEEL DRAIN WITH THREAD, PAIL HOOK & WALL BRACE, LEVER HANDLES, CERAMIC CARTRIDGE, POLISHED CHROME. COMBINATION DOME STRAINER & LINT BASKET. CHICAGO FAUCETS 305-VBXKCP, WALL MOUNTED, 2-3/8" AMERICAN STANDARD LAKEWELL 7692.008, DRILLED BACK 2 HOLES ON 8" VACUUM BREAKER SPOUT WITH HOSE THREAD & PAIL CENTERS, WALL HANGER, RIM GUARD, HOOK, ADJUSTABLE ARMS, LEVER HANDLES, CERAMIC CARTRIDGE, POLISHED CHROME. ENAMELED CAST IRON, WHITE. ELKAY LR1919, 18 GAUGE, TYPE 304 CHICAGO FAUCETS 786-E29XKABCP, DECK MOUNTED, STAINLESS STEEL, 19-1/2" X 19" X 7-1/2" 5-1/4" RIGID/SWING GOOSENECK SPOUT, 8" CENTERS, DEEP, 3 HOLE, UNDERCOATED. WRISTBLADE HANDLES, CERAMIC CARTRIDGE, 2.2 GPM LAMINAR FLOW OUTLET, POLISHED CHROME. CHICAGO FAUCETS 1905-VOCCP PRESSURE BALANCING AQUATIC 1363BFSC 36X36X75" SHOWER VALVE, ACCESSIBLE SHOWER WITH VERTICAL AND HORIZONTAL GRAB BARS, AND FOLD UP SEAT, AND HAND-HELD SHOWER ASSEMBLY WITH SLIDE BAR ZURN ECOLOTROL CERAMIC DISK WALL HYDRANT, ENCASED, NON-FREEZE, ANTI-SIPHON, AUTOMATIC DRAINING MECHANICAL NOTES PROVIDE OPEN FRONT WHITE SEAT EQUAL TO OLSONITE 95SSCT. 1-1/2" PVC TRAP, EXT TO WALL, W/ ESCUTCHEON W/ GRID STRAINER NA 1-1/2 1-1/4 1-1/2 1/2 1/2 NA PROVIDE CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8 FITTINGS) 1-1/4" PVC TRAP, EXT TO WALL, W/ ESCUTCHEON W/ GRID STRAINER FLOOR MOUNTED, CONCEALED ARMS, LEVELING AND SECURING SCREWS, STRUCTURAL UPRIGHTS AND WELDED FEET. 1-1/2 1-1/4 1-1/2 1/2 1/2 NA PROVIDE AMERICAN STANDARD 0059.020EC SHROUD/KNEE CONTACT GUARD, EVERCLEAN SURFACE. PROVIDE McGUIRE CAST BRASS CHROME PLATED TAILPIECE & OPEN GRID STRAINER, ALL METAL PARTS TREATED INSIDE & OUTSIDE WITH SANIGUARD, PROVIDE CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8 FITTINGS) NA NA NA NA NA NA 1/2 NA NA COORDINATE LOCATION & MOUNTING HEIGHT OF WALL BOX WITH CASEWORK & EQUIPMENT REQUIREMENTS. ACCESSIBLE CHECK VALVES & SHUTOFFS ON HOT & COLD SUPPLIES. 3" 'P' TRAP NA 3 3 1-1/2 3/4 3/4 NA PROVIDE CRANE/FIAT 832-AA HOSE & HOSE BRACKET, 889-CC MOP HANGER, (2) E-88-AA STAINLESS STEEL BUMPERGUARD, (2) MSG2424 STAINLESS STEEL WALL GUARD. SEE DETAIL FOR ALL PIPING REQUIREMENTS. CHICAGO FAUCETS 786-E29XKABCP, DECK MOUNTED, 5-1/4" RIGID/SWING GOOSENECK SPOUT, 8" CENTERS, WRISTBLADE HANDLES, CERAMIC CARTRIDGE, 2.2 GPM LAMINAR FLOW OUTLET, POLISHED CHROME. CHICAGO FAUCETS 786-E29XKABCP, DECK MOUNTED, AMERICAN STANDARD MURRO 5-1/4" RIGID/SWING GOOSENECK SPOUT, 8" CENTERS, 0958.908EC, WALL HUNG FOR WRISTBLADE HANDLES, CERAMIC CARTRIDGE, 2.2 GPM CONCEALED ARMS SUPPORT, 8" LAMINAR FLOW OUTLET, POLISHED CHROME. CENTERS, LESS OVERFLOW, VITREOUS CHINA, WHITE, EVERCLEAN SURFACE. NA GUY GRAY MIB1AB, RECESSED, WHITE POWDER COATED STEEL ICE MAKER OUTLET BOX, WITH BRASS PLATED, QUARTER TURN, LEAD-FREE COMPLIANT BALL VALVE. NA TRAP (IN) NA STOP INTEGRAL ANGLE STOP ON FLUSH VALVE. ELKAY LR1919, 18 GAUGE, TYPE 304 STAINLESS STEEL, 19-1/2" X 19" X 7-1/2" DEEP, 3 HOLE, UNDERCOATED. YES WASTE (IN) 4 TRIM SLOAN MANUAL FLUSHOMETER MODEL ROYAL 113-1.28, 1-1/2" SPUD 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants Dunham Job #: 415134 Certification I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. ACCESSIBLE CHECK VALVES & SHUTOFFS ON HOT & COLD SUPPLIES. AMERICAN STANDARD 7798.030, 3" CAST IRON 'P' TRAP STANDARD TO WALL & STRAINER FOR 3" IRON PIPE. WALL HANGER SUPPLIED WITH FIXTURE. 3 3 1-1/2 3/4 3/4 NA PROVIDE CHICAGO FAUCET #952 AND BACKFLOW PREVENTOR. CHICAGO 1025-ABCP QUARTER TURN POLISHED C.P. CAST BRASS ANGLE VALVE KITS, LOOSE KEY, FLEXIBLE RISERS, ESCUTCHEON CHICAGO 1771-ABCP QUARTER TURN POLISHED 1-1/2" 'P' TRAP NA 2 2 1-1/2 1/2 1/2 NA PROVIDE CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8 FITTINGS) ENCASED, KEY-OPERATED RSP Architects Signature Bryan Schmidt Registration Number NA INTEGRAL NA NA 2 NA 2 NA NA NA 1/2 NA 1/2 3/4 NA NA INCLUDE SHOWER CURTAIN AND ROD, ADD VERTICAL GRAB BAR, ADD FLEXIBLE DAM NA Date 26566 07/24/15 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. ALL FROST PROOF HYDRANTS SHALL BE INSTALLED IN A SLEEVE Signature James A. LeClaire Registration Number THERMOSTATIC MIXING VALVE SCHEDULE EQUIPMENT TAG TMV-1 TMV-2 MINIMUM FLOW (GPM) 1.5 0.5 MAXIMUM FLOW (GPM) 10.5 20 COLD WATER BYPASS (GPM) 2.3 0 Date EMERGENCY PLUMBING FIXTURE SCHEDULE PRESSURE DROP AT MAXIMUM FLOW (PSI) 60 125 OUTLET TEMPERATURE (F) INLET TEMPERATURE (F) 140 85 140 110 CW INLET (IN) 1/2" 1/2" HW INLET (IN) 1/2" 1/2" OUTLET (IN) 1/2" 1/2" MANUFACTURER BRADLEY CHICAGO FAUCETS MODEL NUMBER S-19-2000 122-ABNF EQUIPMENT TAG EP-1 MECHANICAL NOTES 1,2 - EP-2 FIXTURE DESCRIPTION EMERGENCY EYE / FACEWASH MOUNTING WALL ADA YES EMERGENCY EYEWASH / FAUCET COMBINATION COUNTER NO MECHANICAL NOTES: 1. SEE DETAIL FOR ADDITIONAL PIPING REQUIREMENTS 2. PROVIDE INLET CHECK VALVES ON MIXING VALVE. FIXTURE SPEAKMAN SE-1000, YELLOW PLASTIC BOWL, WITH TAIL PIECE STAINLESS STEEL PUSH HANDLE, UNIVERSAL EMERGENCY SIGN SPEAKMAN SEF-1800-CA, EYESAVER LABORATORY WIDESPREAD FAUCET WITH INTEGRATED EYEWASH STOP BALL VALVE TRAP 1-1/4 WASTE (IN) 1-1/2 TRAP (IN) 1-1/4 VENT (IN) 1-1/2 CW (IN) NA HW (IN) NA TW (IN) 1/2 MECHANICAL NOTES 1 BALL VALVE NA NA NA NA 1/2 1/2 1/2 1 50358 07/24/15 Project For MECHANICAL NOTES: 1. INSTALL TMV-1 WITH EMERGENCY EQUIPMENT. FLOOR SINK SCHEDULE EQUIPMENT TAG FS-1 SIZE (IN) 3" MANUFACTURER JOSAM STUDENT HEALTH AND ACADEMIC RENOVATION STEAM WATER HEATER SCHEDULE - SEMI-INSTANTANEOUS MODEL NUMBER 49503-LF-NB MECHANICAL NOTES - MECHANICAL (223500) WATER EQUIPMENT TAG SWH 01 MECHANICAL NOTES: APPLICATION LOWER LEVEL STORAGE CAPACITY (GAL) 215 RECOVERY RATE (GPH) 600 TEMPERATURE RISE (F) 80 PRESSURE BEFORE CONTROL VALVE (PSIG) 8-10 STEAM CONTROL VALVE PRESSURE DROP (PSIG) 5 STEAM PRESSURE AT BUNDLE (PSIG) 3-5 STEAM CAPACITY (LBS/HR) 410 DOUBLE WALL HEAT EXCHANGER (YES/NO) YES MANUFACTURER PVI INDUSTRIES MODEL NUMBER 600 L 215A-QSD MECHANICAL NOTES 1 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 MECHANICAL NOTES: 1. SET LEAVING WATER TEMPERATURE TO 140F ELECTRICAL FLOOR DRAIN SCHEDULE EQUIPMENT TAG FD-1 FD-2 SIZE (IN) SEE FLOOR PLAN SEE FLOOR PLAN MANUFACTURER JOSAM JOSAM MODEL NUMBER 30000-A 30000-A EQUIPMENT TAG SWH 01 MECHANICAL NOTES 1 1,2 MECHANICAL NOTES: 1. ROUND NIKALOY FINISH TOP, LESS BACKWATER VALVE 2. DRY PAN DRAIN HP/LOAD 20A CKT VOLTAGE PHASE 120 V 1 TYPE CP CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 22/DIV. 22 INTEGRAL CTRL WIRE BY DIV. 22 AMPS/TYPE MRS DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE 1 DIV. 26/DIV. 26 LOCATION AT UNIT PANEL N-B2 CIRCUIT NUMBER 5 CONDUIT/FEEDER SIZE 3/4" C, 2#12, 1#12G ELECTRICAL NOTES GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) ELECTRICAL NOTES: ELECTRIC WATER COOLER SCHEDULE EQUIPMENT TAG EWC-1 FIXTURE DESCRIPTION DUAL ELECTRIC WATER COOLER MOUNTING WALL ADA YES SUMP PUMP SCHEDULE FIXTURE EZH20 BOTTLE FILLING STATION, BI-LEVEL, MODELS EZSTL8WS & EZSTLDDWS STOP INTEGRAL TRAP SEE PLAN FOR SIZE WASTE (IN) 1-1/2" TRAP (IN) 1-1/4" VENT (IN) 1-1/2" CW (IN) 1/2" MECHANICAL NOTES 1 MECHANICAL NOTES: MECHANICAL (221429) EQUIPMENT TAG SP 01 APPLICATION ELEVATOR SUMP Project No. TYPE SUBMERSIBLE GPM 100 DISCHARGE HEAD (FT) 22 NUMBER OF PUMPS 1 BASIN DIAMETER DEPTH (IN) (IN) 30 114 MOTOR RPM (EACH) 1750 Drawn By MANUFACTURER WEIL MODEL NUMBER 2445 - 1.5HP MECHANICAL NOTES PROVIDE WITH CONTROL PANEL 8153 Checked By 1. REFER TO ELECTRICAL PLANS FOR RECEPTACLE LOCATION. Date EQUIPMENT TAG SP 01 AREA DRAIN SCHEDULE MECHANICAL (221319) EQUIPMENT TAG AD-1 SIZE (IN) 3 MECHANICAL NOTES: MANUFACTURER JOSAM MODEL NUMBER 22083 MECHANICAL NOTES - HP/LOAD 1.5 HP VOLTAGE PHASE 208 V 3 TYPE MAGS CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 26/DIV. 26 SEE PLANS DISCONNECT AT MOTOR CTRL WIRE BY DIV. 23 AMPS/TYPE SEE STARTER SCHEDULE FUSE SIZE (AMPS) SEE STARTER SCHEDULE NEMA TYPE SEE STARTER SCHEDULE FURNISHED BY/ INSTALLED BY SEE STARTER SCHEDULE LOCATION AT UNIT GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL PANEL RD-B1 CIRCUIT NUMBER 8,10,12 CONDUIT/FEEDER SIZE 3/4" C, 3#12, 1#12G ELECTRICAL NOTES Nick U Nic I 2/19/2016 MECHANICAL NOTES: ELECTRICAL 2263.001.00 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. Revisions MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) No. Date Description ELECTRICAL NOTES: DOMESTIC WATER PUMP SCHEDULE MECHANICAL (221123) EQUIPMENT TAG DWP 1 APPLICATION HOT WATER RECIRCULATION TYPE HORIZONTAL GPM 17 DISCHARGE NPSHR HEAD (FT) (FT) 22 2 RPM 2100 BHP 1.0 SUCTION SIZE (IN) 1-1/2 DISCHARGE SIZE (IN) 1-1/2 VFD (YES/NO) YES MANUFACTURER BELL AND GOSSET MODEL NUMBER ECOCIRC XL B 65-130 MECHANICAL NOTES 1 MECHANICAL NOTES: 1. PUMP SIZED FOR 17GPM WHICH INCLUDES FUTURE SHELL SPACE PIPING. ELECTRICAL EQUIPMENT TAG DWP 01 HP/LOAD 1 HP TYPE CP CTRL WIRE BY DIV. 22 AMPS/TYPE MRS DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE 1 DIV. 26/DIV. 26 LOCATION AT UNIT PANEL N-B2 CIRCUIT NUMBER 7,9 GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. VFD - VARIABLE FREQUENCY MOTOR CONTROLLER MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL ELECTRICAL NOTES: C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt 2/18/2016 3:49:51 PM VOLTAGE PHASE 208 V 1 CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 22/DIV. 22 INTEGRAL CONDUIT/FEEDER SIZE 3/4" C, 2#12, 1#12G ELECTRICAL NOTES MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) PLUMBING ELECTRICAL SCHEDULES M901 AIR HANDLING UNIT SCHEDULE MECHANICAL (237313, 237316, 237333, 237339) EQUIPMENT TAG AHU 01 AHU 02 AHU 03 APPLICATION HEATING/COOLING HEATING/COOLING HEATING/COOLING FACE & BYPASS DAMPERS (YES/NO) YES (HX) NO NO MIXING BOX (YES/NO) NO NO NO MINIMUM OUTDOOR AIR CFM 7400 2000 6500 COOLING COIL AHUCC 01 AHUCC 02 AHUCC 03 HEATING COIL AHUHC 01 AHUHC 02 AHUHC 03 HEAT RECOVERY COIL HX 01 NO NO AIR FILTER AHUAF 01 AHUAF 02 AHUAF 03 AIR PRE-FILTER AHUPF 01 AHUPF 02 AHUPF 03 AIR FINAL-FILTER AHUFF 01 AHUFF 02 AHUFF 03 HUMIDIFIER NO NO NO AIR BLENDER NO AHUAB 02 AHUAB 03 SUPPLY FAN AHUS 01 AHUS 02 AHUS 03 PREHEAT COIL AHUPHC-01 NO NO RETURN FAN AHUR 01 AHUR 02 AHUR 03 MANUFACTURER DAIKIN-MCQUAY DAIKIN-MCQUAY DAIKIN-MCQUAY MODEL NUMBER VISION VISION VISION MECHANICAL NOTES MECHANICAL NOTES: ELECTRICAL EQUIPMENT TAG HP/LOAD VOLTAGE PHASE CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION TYPE CTRL WIRE BY DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE AMPS/TYPE LOCATION CIRCUIT NUMBER PANEL CONDUIT/FEEDER SIZE ELECTRICAL NOTES RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. VFD - VARIABLE FREQUENCY MOTOR CONTROLLER MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) 612.677.7100 612.677.7499 fax www.rsparch.com Consultants ELECTRICAL NOTES: AIR HANDLING UNIT - SUPPLY FAN SCHEDULE Dunham Job #: 415134 MECHANICAL (233416) EQUIPMENT TAG AHUS 01 AHUS 02 AHUS 03 NUMBER OF FANS 1 1 1 AHU SERVED AHU 01 AHU 02 AHU 03 TYPE CENTRIFUGAL-PLENUM CENTRIFUGAL-PLENUM CENTRIFUGAL-PLENUM CLASS 2 2 2 CFM PER FAN 7400 13000 26000 TOTAL CFM 7400 13000 26000 ESP (IN W.C.) 2.5 3.0 3.0 TOTAL SP (IN W.C.) 4.33 4.64 4.59 Certification WHEEL DIAMETER (IN) 20.0 24.5 44.5 VFD (YES/NO) YES YES YES FAN RPM 2337 2014 903 BHP 5.34 14.23 27.28 DRIVE TYPE (BELT/DIRECT) BELT BELT BELT MODEL NUMBER NA NA NA MANUFACTURER DAIKIN-MCQUAY DAIKIN-MCQUAY DAIKIN-MCQUAY MECHANICAL NOTES I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. Signature Bryan Schmidt MECHANICAL NOTES: Registration Number Date ELECTRICAL EQUIPMENT TAG AHUS 01 AHUS 02 AHUS 03 AIR HANDLING UNIT - AIR BLENDER SCHEDULE EQUIPMENT TAG AHUAB 02 AHUAB 03 AHU SERVED AHU 02 AHU 03 MINIMUM CFM 6500 13000 DESIGN CFM 13000 26000 DESIGN APD (IN W.C.) 0.14 0.15 DESIGN VELOCITY (FPM) 977 1036 HP/LOAD 10 HP 20 HP 40 HP CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 23/DIV. 26 SEE PLANS DIV. 23/DIV. 26 SEE PLANS DIV. 23/DIV. 26 SEE PLANS TYPE VFD VFD VFD VOLTAGE PHASE 208 V 3 208 V 3 208 V 3 CTRL WIRE BY DIV. 23 DIV. 23 DIV. 23 AMPS/TYPE 60A/FUSED 100A/FUSED 200A/FUSED DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE PER MANUF. 1 DIV. 23/DIV. 26 PER MANUF. 1 DIV. 23/DIV. 26 PER MANUF. 1 DIV. 23/DIV. 26 LOCATION SEE PLANS SEE PLANS SEE PLANS CIRCUIT NUMBER 1,3,5 2,4,6 13,15,17 PANEL ND-B1 ND-B1 ND-B1 GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. VFD - VARIABLE FREQUENCY MOTOR CONTROLLER MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL CONDUIT/FEEDER SIZE 3/4" C, 3#8, 1#10G 1 1/4" C, 3#4, 1#6G 1 1/2" C, 3#1/0, 1#6G ELECTRICAL NOTES 1,2 1,2 1,2 07/24/15 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. James A. LeClaire Signature Registration Number MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) 50358 Date 07/24/15 ELECTRICAL NOTES: MECHANICAL (237313 & 237316) MINIMUM VELOCITY (FPM) 488 518 26566 Project For 1. DISCONNECT IS INTERGRAL TO VFD WITH OVERCURRENT PROTECTION. 2. PROVIDE 120V POWER FOR LIGHTS AND RECEPTACLES WITHIN ENCLOSURE. MANUFACTURER BLENDER PRODUCTS BLENDER PRODUCTS MODEL NUMBER IV IV MECHANICAL NOTES AIR HANDLING UNIT - RETURN FAN SCHEDULE MECHANICAL NOTES: MECHANICAL (233416) EQUIPMENT TAG AHUR 01 AHUR 02 AHUR 03 NUMBER OF FANS 1 1 1 AHU SERVED AHU 01 AHU 02 AHU 03 TYPE CENTRIFUGAL-PLENUM CENTRIFUGAL-PLENUM CENTRIFUGAL-PLENUM CLASS 2 2 2 CFM PER FAN 9000 11000 20000 TOTAL CFM 9000 11000 20000 TOTAL SP (IN W.C.) 3.54 1.67 1.66 ESP (IN W.C.) 2.5 1.50 1.50 WHEEL DIAMETER (IN) 22.25 24.5 33.0 VFD (YES/NO) YES YES YES FAN RPM 1988 1525 1113 BHP 8.09 5.53 9.79 DRIVE TYPE (BELT/DIRECT) BELT BELT BELT MANUFACTURER DAIKIN-MCQUAY DAIKIN-MCQUAY DAIKIN-MCQUAY MODEL NUMBER NA NA NA MECHANICAL NOTES MECHANICAL NOTES: AIR HANDLING UNIT - PREFILTER SCHEDULE MECHANICAL (234100) EQUIPMENT TAG AHUPF 01 AHUPF 02 AHUPF 03 AHU SERVED AHU 01 AHU 02 AHU 03 TYPE PLEATED PLEATED PLEATED CFM 7400 13000 26000 NUMBER OF MODULES 6 3/6 12/6/5 SIZE PER MODULE (H"xL"xD") 20"x24"x2" 24"x24"x2"/20"x24"x2" 24"x20"x2"/20"x20"x2"/12"x24"x2" STUDENT HEALTH AND ACADEMIC RENOVATION MERV RATING 7 7 7 APD CLEAN (IN W.C.) 0.27 0.31 0.29 APD AT 50% LOADING (IN W.C.) 0.63 0.66 0.65 MANUFACTURER NA NA NA MODEL NUMBER NA NA NA MECHANICAL NOTES ELECTRICAL EQUIPMENT TAG AHUR 01 AHUR 02 AHUR 03 MECHANICAL NOTES: HP/LOAD 10 HP 7.5 HP 15 HP VOLTAGE PHASE 208 V 3 208 V 3 208 V 3 CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 23/DIV. 26 SEE PLANS DIV. 23/DIV. 26 SEE PLANS DIV. 23/DIV. 26 SEE PLANS TYPE VFD VFD VFD CTRL WIRE BY DIV. 23 DIV. 23 DIV. 23 AMPS/TYPE 60A/FUSED 60A/FUSED 100A/FUSED DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE PER MANUF. 1 DIV. 23/DIV. 26 PER MANUF. 1 DIV. 23/DIV. 26 PER MANUF. 1 DIV. 23/DIV. 26 LOCATION SEE PLANS SEE PLANS SEE PLANS CIRCUIT NUMBER 7,9,11 8,10,12 14,16,18 PANEL ND-B1 ND-B1 ND-B1 GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. VFD - VARIABLE FREQUENCY MOTOR CONTROLLER MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL CONDUIT/FEEDER SIZE 3/4" C, 3#8, 1#10G 3/4" C, 3#8, 1#10G 1" C, 3#6, 1#8G ELECTRICAL NOTES 1,2 1,2 1,2 DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) ELECTRICAL NOTES: 1. DISCONNECT IS INTERGRAL TO VFD WITH OVERCURRENT PROTECTION. 2. PROVIDE 120V POWER FOR LIGHTS AND RECEPTACLES WITHIN ENCLOSURE. AIR HANDLING UNIT - AIR FILTER SCHEDULE MECHANICAL (234100) EQUIPMENT TAG AHUAF 01 AHUAF 02 AHUAF 03 AHU SERVED AHU 01 AHU 02 AHU 03 TYPE CARTRIDGE CARTRIDGE CARTRIDGE CFM 7400 13000 26000 NUMBER OF MODULES 6 3/6 12/6/5 SIZE PER MODULE (H"xL"xD") 20"x24"x4" 24"x24"x4"/20"x24"x4" 24"x20"x4"/20"x20"x4"/12"x24"x4" MERV RATING 13 13 13 APDP CLEAN (IN W.C.) 0.34 0.40 0.37 APD AT 50% LOADING (IN W.C.) 0.92 0.95 0.94 MANUFACTURER VARICEL VARICEL VARICEL MODEL NUMBER II MH II MH II MH MECHANICAL NOTES AIR HANDLING UNIT - COOLING COIL SCHEDULE - CHILLED WATER MECHANICAL (238216) COIL EQUIPMENT TAG AHUCC 01 AHUCC 02 AHUCC 03 MECHANICAL NOTES: AHU SERVED AHU 01 AHU 02 AHU 03 CFM 7400 13000 26000 NUMBER EACH COIL SIZE OF COILS (W"xH") 1 36"x67" 2 30"x67" 2 36"X106" AIR ROWS 8 8 8 FINS PER INCH 10 10 10 EAT DB WB (F) (F) 80.1 73.1 79.5 68.0 79.5 68.0 LAT DB WB (F) (F) 52.6 52.4 51.0 50.8 51.0 50.8 WATER FACE VELOCITY (FPM) 442 466 477 EWT (F) 42 42 42 APD (IN W.C.) 0.42 0.46 0.48 LWT (F) 54 54 54 GPM 84 113 226 GLYCOL TYPE NONE NONE NONE GLYCOL % 0 0 0 WPD (FT) 14.0 13.9 18.6 SENSIBLE CAPACITY (MBH) 222.317 405.510 811.363 TOTAL CAPACITY (MBH) 500.773 678.125 1357.423 MANUFACTURER DAIKIN-MCQUAY DAIKIN-MCQUAY DAIKIN-MCQUAY MODEL NUMBER 5WS1008A 5WS1008A 5WM1008A MECHANICAL NOTES Project No. 2263.001.00 Drawn By Bryan S Checked By Nic I Date NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. AIR HANDLING UNIT - HEATING COIL SCHEDULE - HEATING WATER MECHANICAL (238216) COIL EQUIPMENT TAG AHUHC 01 AHUHC 02 AHUHC 03 AHU SERVED AHU 01 AHU 02 AHU 03 HEATING CFM 7400 13000 26000 NUMBER OF COILS 1 2 2 EACH COIL SIZE (W"xH") 36"x64" 30"x64" 36"x106" ROWS 1 1 1 FINS PER INCH 6 6 6 EAT (F) 51.2 40.0 40.0 LAT (F) 64.8 52 52 AIR FACE VELOCITY (FPM) 463 488 491 2/19/2016 WATER © Copyright RSP Architects 2015. All rights reserved. MAX. APD (IN W.C.) 0.1 0.1 0.1 EWT (F) 180.0 180.0 180.0 LWT (F) 160 160 160 GPM 12.0 18.3 36.6 GLYCOL TYPE PROPYLENE PROPYLENE PROPYLENE GLYCOL % 35 35 35 WPD (FT) 0.40 0.60 1.80 CAPACITY (MBH) 110,242 168,000 336,000 MANUFACTURER DAIKIN-MCQUAY DAIKIN-MCQUAY DAIKIN-MCQUAY MODEL NUMBER 5WB0601B 5WB0601C 5WB0601C MECHANICAL NOTES Revisions No. Date Description AIR HANDLING UNIT - PREHEAT COIL SCHEDULE - HEATING WATER MECHANICAL (238216) COIL EQUIPMENT TAG AHUPHC 01 DESCRIPTION PREHEAT COIL CFM 7400 NUMBER OF COILS 1 EACH COIL SIZE (W"xH") 64" X 36" ROWS 1 FINS PER INCH 7 EAT (F) -20 LAT (F) 10 AIR FACE VELOCITY (FPM) 463 WATER APD (IN W.C.) 0.07 EWT (F) 180 LWT (F) 160 GPM 25 GLYCOL TYPE PROPYLENE GLYCOL % 30 WPD (FT) 5 CAPACITY (MBH) 250 MANUFACTURER DAIKIN MODEL NUMBER 5WB0701B MECHANICAL NOTES FIXED-PLATE AIR-TO-AIR HEAT EXCHANGER SCHEDULE MECHANICAL (237200) EQUIPMENT TAG HX 001 UNIT SERVED AHU-01 RETURN AIR ENTERING DB RH (F) (%) CFM 75.0 54 9000 MECHANICAL NOTES: WINTER PERFORMANCE OUTDOOR AIR ENTERING OUTDOOR/SUPPLY AIR LEAVING DB RH DB RH (F) (%) (F) (%) CFM CFM -20.0 0 7400 51.2 32 7400 ENERGY RECOVERED (MBH) 569.326 RETURN AIR ENTERING DB RH (F) (%) CFM 75 54 9000 SUMMER PERFORMANCE OUTDOOR AIR ENTERING OUTDOOR/SUPPLY AIR LEAVING DB RH DB RH (F) (%) (F) (%) CFM CFM 91.0 54 7400 80.1 74 7400 ENERGY RECOVERED (MBH) 89.581 APD (IN W.C.) 1.04 MANUFACTURER DAIKIN-MCQUAY MODEL NUMBER XLT-H 50(24)-60 MECHANICAL NOTES 1 MECHANICAL ELECTRICAL SCHEDULES 1. PROVIDE SUPPLY AIR FACE AND BYPASS DAMPER C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt 2/18/2016 3:50:35 PM M902 FAN POWERED VARIABLE AIR VOLUME BOX SCHEDULE - HEATING WATER MECHANICAL (233600) EQUIPMENT TAG FVAV 101 FVAV 201 FVAV 301 PRIMARY AIR MAXIMUM MINIMUM CFM CFM 800 0 800 0 800 0 INLET SIZE (IN) 14x8 14x8 14x8 TYPE PARALLEL PARALLEL PARALLEL FAN CFM 800 800 800 HEATING COIL ESP (IN W.C.) 0.2 0.2 0.2 HEATING CFM 0 0 0 EAT (F) LAT (F) CAPACITY (MBH) EWT (F) LWT (F) GPM GLYCOL TYPE MAXIMUM WPD (FT) GLYCOL % MAXIMUM COIL RADIATED NC ROWS 40 40 40 MODEL NUMBER DFLP DFLP DFLP MANUFACTURER TITUS TITUS TITUS MECHANICAL NOTES MECHANICAL NOTES: ELECTRICAL EQUIPMENT TAG FVAV 101 FVAV 201 FVAV 301 HP/LOAD 1/3 HP 1/3 HP 1/3 HP CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 26/DIV. 26 AT UNIT DIV. 26/DIV. 26 AT UNIT DIV. 26/DIV. 26 AT UNIT TYPE MRS MRS MRS VOLTAGE PHASE 120 V 1 120 V 1 120 V 1 CTRL WIRE BY DIV. 23 DIV. 23 DIV. 23 DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE 1 DIV. 26/DIV. 26 1 DIV. 26/DIV. 26 1 DIV. 26/DIV. 26 AMPS/TYPE MRS MRS MRS LOCATION AT UNIT AT UNIT AT UNIT PANEL O-21A O-21A O-21A CIRCUIT NUMBER 13 12 15 CONDUIT/FEEDER SIZE 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. VFD - VARIABLE FREQUENCY MOTOR CONTROLLER MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL ELECTRICAL NOTES RSP Architects 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) 612.677.7100 612.677.7499 fax www.rsparch.com Consultants ELECTRICAL NOTES: Dunham Job #: 415134 UNIT HEATER SCHEDULE - HEATING WATER Certification I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. MECHANICAL (238239) FAN EQUIPMENT TAG CUH 101 CUH 102 CUH 103 CUH 104 CUH 303 UH 001 UH 002 UH 003 APPLICATION HEATING HEATING HEATING HEATING HEATING HEATING HEATING HEATING TYPE WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE HORIZONTAL HORIZONTAL HORIZONTAL CFM 620 620 620 620 620 1120 1120 1120 COIL MOTOR HP 1/10 1/10 1/10 1/10 1/10 1/10 1/10 1/10 EAT (F) 60 60 60 60 60 60 60 60 COIL ROWS 2 2 2 2 2 1 1 1 EWT (F) 180 180 180 180 180 180 180 180 LWT (F) 160 160 160 160 160 160 160 160 GPM 7.3 7.3 7.3 7.3 7.3 4.7 4.7 4.7 GLYCOL TYPE PROPYLENE PROPYLENE PROPYLENE PROPYLENE PROPYLENE PROPYLENE PROPYLENE PROPYLENE GLYCOL % 35 35 35 35 35 35 35 35 MAX. WPD (FT) 5 5 5 5 5 5 5 5 CAPACITY (MBH) 60 60 60 60 60 40 40 40 MANUFACTURER RITTLING RITTLING RITTLING RITTLING RITTLING RITTLING RITTLING RITTLING MODEL NUMBER RWI-300-06 RWI-300-06 RWI-300-06 RWI-300-06 RWI-300-06 RH-63 RH-63 RH-63 MECHANICAL NOTES Signature Bryan Schmidt Registration Number 26566 Date 07/24/15 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. MECHANICAL NOTES: James A. LeClaire Signature ELECTRICAL EQUIPMENT TAG CUH 101 CUH 102 CUH 103 CUH 104 CUH 303 UH 001 UH 002 UH 003 Registration Number HP/LOAD 1/4 HP 1/4 HP 1/4 HP 1/4 HP 1/4 HP 1/10 HP 1/10 HP 1/10 HP CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 23/DIV. 23 INTEGRAL DIV. 23/DIV. 23 INTEGRAL DIV. 23/DIV. 23 INTEGRAL DIV. 23/DIV. 23 INTEGRAL DIV. 23/DIV. 23 INTEGRAL DIV. 26/DIV. 26 AT UNIT DIV. 26/DIV. 26 AT UNIT DIV. 26/DIV. 26 AT UNIT TYPE MRS MRS MRS MRS MRS MRS MRS MRS VOLTAGE PHASE 120 V 1 120 V 1 120 V 1 120 V 1 120 V 1 120 V 1 120 V 1 120 V 1 CTRL WIRE BY DIV. 23 DIV. 23 DIV. 23 DIV. 23 DIV. 23 DIV. 23 DIV. 23 DIV. 23 DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE 1 DIV. 23/DIV. 23 1 DIV. 23/DIV. 23 1 DIV. 23/DIV. 23 1 DIV. 23/DIV. 23 1 DIV. 23/DIV. 23 1 DIV. 26/DIV. 26 1 DIV. 26/DIV. 26 1 DIV. 26/DIV. 26 AMPS/TYPE MRS MRS MRS MRS MRS MRS MRS MRS LOCATION INTEGRAL INTEGRAL INTEGRAL INTEGRAL INTEGRAL AT UNIT AT UNIT AT UNIT CIRCUIT NUMBER 21 8 24 10 1 4 11 13 PANEL N-11 N-12 N-11 N-12 N-31 N-B2 N-B2 N-B2 GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL CONDUIT/FEEDER SIZE 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G ELECTRICAL NOTES 1,2 1,2 1,2 1,2 1,2 MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) ELECTRICAL NOTES: 1. ROUTE TO SINGLE POINT CONNECTION AT FACTORY MOUNTED DISCONNECT. 2. MRS LISTED UNDER CONTROLLER AND DISCONNECT ARE THE SAME SWITCH. 50358 Date 07/24/15 Project For STUDENT HEALTH AND ACADEMIC RENOVATION DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 FAN COIL UNIT SCHEDULE - CHILLED AND HEATING WATER MECHANICAL (238219) FAN COOLING COIL WATER EQUIPMENT TAG FCU 101 FCU 102 APPLICATION HEATING HEATING TYPE HIDE AWAY HIDE AWAY NUMBER OF FANS 2 2 MOTOR HP RPM TOTAL (EACH) (EACH) CFM 1/10 1155 550 1/10 1155 550 ESP (IN W.C.) 0.3 0.3 EWT (F) LWT (F) GPM GLYCOL TYPE GLYCOL WPD % (FT) EAT DB (F) EAT WB (F) HEATING COIL AIR LAT LAT DB WB (F) (F) FILTER WATER FACE VELOCITY (FPM) SENSIBLE TOTAL CAPACITY CAPACITY (MBH) (MBH) EWT (F) 180 180 LWT (F) 160 160 GPM 4.5 4.5 AIR GLYCOL TYPE PROPYLENE PROPYLENE GLYCOL WPD % (FT) 35 5 35 5 EAT (F) 65 65 LAT (F) 135 135 CAPACITY (MBH) 41 41 TYPE THROWAWAY THROWAWAY MERV RATING 4 4 MANUFACTURER DAIKIN DAIKIN MODEL MECHANICAL NUMBER NOTES THINLINE S04 THINLINE S04 MECHANICAL NOTES: ELECTRICAL EQUIPMENT TAG FCU 101 FCU 102 HP/LOAD 1/10 HP 1/10 HP VOLTAGE PHASE 120 V 1 120 V 1 TYPE CP CP CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 23/DIV. 23 INTEGRAL DIV. 23/DIV. 23 INTEGRAL CTRL WIRE BY DIV. 23 DIV. 23 DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE 1 DIV. 26/DIV. 26 1 DIV. 26/DIV. 26 AMPS/TYPE MRS MRS LOCATION AT UNIT AT UNIT PANEL N-11 N-11 CIRCUIT NUMBER 12 12 CONDUIT/FEEDER SIZE 3/4" C, 2#12, 1#12G 3/4" C, 2#12, 1#12G ELECTRICAL NOTES Project No. GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) 2263.001.00 Drawn By Bryan S Checked By ELECTRICAL NOTES: Nic I Date 2/19/2016 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. © Copyright RSP Architects 2015. All rights reserved. FAN SCHEDULE Revisions MECHANICAL (233413, 233416, 233423) EQUIPMENT TAG EF 01 EF 02 EF 03 TF 01 APPLICATION EXHAUST EXHAUST EXHAUST TRANSFER TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL CFM 160 500 1500 1,000 ESP (IN W.C.) 0.5 0.75 0.75 0.25 BHP .04 0.45 1.3 0.11 FAN RPM 1466 2341 3372 1357 DRIVE TYPE DIRECT BELT BELT DIRECT SOUND 7.2 SONES 65 DB 76 DB 7.9 SONES VFD (YES/NO) NO NO NO NO MANUFACTURER GREENHECK GREENHECK GREENHECK GREENHECK No. MODEL NUMBER G-080-VG VK-H-10-5 VK-H-10-9 SQ-100-VG Date Description MECHANICAL NOTES ECM MOTOR 1 2 ECM MOTOR MECHANICAL NOTES: 1. FAN SHALL HAVE 5" DISCHARGE NOZZE WITH MIN. 3,000 FT/MIN OUTLET VELOCITY AND A MINIMUM PLUME HEIGHT OF 15' @ 10 MPH WIND 2. FAN SHALL HAVE 9" DISCHARGE NOZZE WITH MIN. 3,000 FT/MIN OUTLET VELOCITY AND A MINIMUM PLUME HEIGHT OF 15' @ 10 MPH WIND, ELECTRICAL CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 26/DIV. 26 AT UNIT DIV. 26/DIV. 26 SEE PLANS EQUIPMENT TAG EF 01 EF 02 HP/LOAD 1/6 HP 3/4 HP EF 03 1.5 HP 208 V 3 MAGS DIV. 26/DIV. 26 SEE PLANS TF 01 1/4 HP 120 V 1 CP DIV. 23/DIV. 23 INTEGRAL VOLTAGE PHASE 120 V 1 208 V 3 TYPE MRS MAGS DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE CTRL WIRE BY AMPS/TYPE DIV. 23 MRS 1 DIV. 26/DIV. 26 DIV. 23 SEE STARTER SEE STARTER SEE STARTER SEE STARTER SCHEDULE SCHEDULE SCHEDULE SCHEDULE DIV. 23 SEE STARTER SEE STARTER SEE STARTER SEE STARTER SCHEDULE SCHEDULE SCHEDULE SCHEDULE DIV. 23 MRS 1 DIV. 26/DIV. 26 LOCATION AT UNIT SEE PLANS PANEL N-31 N-32 CIRCUIT NUMBER 3 13,15,17 CONDUIT/FEEDER SIZE 3/4" C, 2#12, 1#12G 3/4" C, 3#12, 1#12G SEE PLANS N-32 12,14,16 3/4" C, 3#12, 1#12G AT UNIT RD-B1 16 3/4" C, 2#12, 1#12G GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. VFD - VARIABLE FREQUENCY MOTOR CONTROLLER MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL ELECTRICAL NOTES MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) ELECTRICAL NOTES: MECHANICAL ELECTRICAL SCHEDULES C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt 2/18/2016 3:50:04 PM M903 HYDRONIC PUMP SCHEDULE MECHANICAL (232123) EQUIPMENT TAG HWP 01 HWP 02 APPLICATION HEATING WATER HEATING WATER TYPE BASE MOUNTED BASE MOUNTED GPM 200 200 DISCHARGE GLYCOL HEAD (FT) GLYCOL TYPE % 70 PROPYLENE 30 70 PROPYLENE 30 NPSHR (FT) 3 3 RPM 1760 1760 SUCTION SIZE (IN) 3 3 BHP 5.1 5.1 DISCHARGE SIZE (IN) 2.5 2.5 VFD (YES/NO) YES YES MANUFACTURER TACO TACO MODEL NUMBER FI2509C FI2509C MECHANICAL NOTES MECHANICAL NOTES: ELECTRICAL EQUIPMENT TAG HWP 01 HP/LOAD 7.5 HP HWP 02 7.5 HP TYPE MAGS VOLTAGE PHASE 208 V 3 208 V 3 MAGS CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 26/DIV. 26 SEE PLANS DIV. 26/DIV. 26 SEE PLANS DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE CTRL WIRE BY AMPS/TYPE DIV. 23 SEE STARTER SEE STARTER SEE STARTER SEE STARTER SCHEDULE SCHEDULE SCHEDULE SCHEDULE DIV. 23 SEE STARTER SEE STARTER SEE STARTER SEE STARTER SCHEDULE SCHEDULE SCHEDULE SCHEDULE LOCATION SEE PLANS PANEL O-B1A CIRCUIT NUMBER 11,13,15 SEE PLANS O-B1A 10,12,14 RSP Architects CONDUIT/FEEDER SIZE 3/4" C, 3#8, 1#10G 3/4" C, 3#8, 1#10G ELECTRICAL NOTES 1220 Marshall Street NE Minneapolis Minnesota 55413-1036 612.677.7100 612.677.7499 fax www.rsparch.com Consultants GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. VFD - VARIABLE FREQUENCY MOTOR CONTROLLER MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) ELECTRICAL NOTES: Dunham Job #: 415134 Certification I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. STEAM CONDENSATE PUMP SCHEDULE MECHANICAL (232223) PUMP EQUIPMENT TAG SCP 01 APPLICATION STEAM CONDENSATE TYPE DUPLEX NUMBER OF PUMPS 2 MOTOR HP (EACH) 1.5 RPM 3500 DISCHARGE PRESSURE (PSIG) 50 GPM 12 Signature TANK CAPACITY (GAL) 14 MANUFACTURER DOMESTIC MODEL NUMBER MECHANICAL NOTES Registration Number 07/24/15 I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly licensed Professional Engineer under the laws of the State of Minnesota. ELECTRICAL HP/LOAD (2) 1.5 HP 26566 Date MECHANICAL NOTES: EQUIPMENT TAG SCP 01 Bryan Schmidt VOLTAGE PHASE 208 V 3 TYPE CP CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 23/DIV. 23 INTEGRAL CTRL WIRE BY DIV. 23 AMPS/TYPE 30A/FUSED DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE PER MANUF. 1 DIV. 26/DIV. 26 LOCATION AT UNIT PANEL O-B1A GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL CIRCUIT NUMBER 16,18,20 CONDUIT/FEEDER SIZE 3/4" C, 3#12, 1#12G ELECTRICAL NOTES 1 MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) James A. LeClaire Signature Registration Number 50358 Date 07/24/15 Project For ELECTRICAL NOTES: 1. SINGLE POINT ELECTRICAL CONNECTION. STUDENT HEALTH AND ACADEMIC RENOVATION GLYCOL FILL STATION SCHEDULE MECHANICAl (232113) EQUIPMENT TAG GFS 01 APPLICATION HEATING WATER NUMBER OF PUMPS 1 GPM (EACH) 5 DISCHARGE HEAD (FT) 140 PUMP MOTOR HP (EACH) 3/4 RPM (EACH) 3600 VOLTAGE/PHASE (EACH) 120/1 TANK CAPACITY (GAL) 55 GAL MANUFACTURER BELL & GOSSETT MODEL NUMBER GMU-60 MECHANICAL NOTES DESIGN DEVELOPMENT ISSUE DATE 2/19/2016 MECHANICAL NOTES: ELECTRICAL EQUIPMENT TAG GFS 01 HP/LOAD 3/4 HP VOLTAGE PHASE 120 V 1 TYPE CP CONTROLLER FURNISHED BY/ INSTALLED BY LOCATION DIV. 23/DIV. 23 INTEGRAL CTRL WIRE BY DIV. 23 DISCONNECT AT MOTOR FURNISHED BY/ FUSE SIZE INSTALLED BY (AMPS) NEMA TYPE 1 DIV. 26/DIV. 26 AMPS/TYPE MRS LOCATION AT UNIT PANEL N-B2 GENERAL ELECTRICAL NOTES: CONTROLLER TYPES: A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION. MMS - MANUAL MOTOR STARTER (WITH OVERLOADS) CP - CONTROL PANEL CIRCUIT NUMBER 12 CONDUIT/FEEDER SIZE 3/4" C, 2#10, 1#10G ELECTRICAL NOTES MAGS - MAGNETIC STARTER MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS) ELECTRICAL NOTES: Project No. VARIABLE FREQUENCY MOTOR CONTROLLER SCHEDULE Drawn By MECHANICAL/ELECTRICAL (230923) EQUIPMENT TAG VOLTAGE PHASE AHUR 01 208 V 3 AHUR 02 208 V 3 AHUR 03 208 V 3 AHUS 01 208 V 3 AHUS 02 208 V 3 AHUS 03 208 V 3 ENCLOSURE PLENUM RATED CALCULATED ENCLOSURE TYPE (YES/NO) AFC (NEMA 1/4X/12) 5303A 1 NO 4037A 1 NO 3720A 1 NO 3850A 1 NO 6653A 1 NO 9160A 1 NO HARMONIC CONTROL SEISMIC BRACING (YES/NO) NO NO NO NO NO NO 2263.001.00 VARIABLE TORQUE/ INPUT AC LINE OUTPUT AC (YES/NO) LINE (YES/NO) CONSTANT TORQUE VARIABLE NO NO VARIABLE NO NO VARIABLE NO NO VARIABLE NO NO VARIABLE NO NO VARIABLE NO NO BYPASS (YES/NO) NO NO NO NO NO NO VFD BYPASS BYPASS TYPE BYPASS CONTROL MOTOR STARTING IN (CONTACTOR/ TYPE (MANUAL/ BYPASS MODE VFD) AUTOMATIC) (FULL/REDUCED VOLTAGE) NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA NA MULTIPLE MOTOR CONTROL (YES/NO) NO NO NO NO NO NO ESSENTIAL DAMPER CONTROL SERVICE/ FIRE LEED CIRCUIT FIGHTER MODE REQUIREMENTS (YES/NO) (YES/NO) (YES/NO) NOTES NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO NO Bryan S Checked By Nic I Date 2/19/2016 NOTICE: The designs shown and described herein including all technical drawings, graphics, and models thereof, are proprietary and cannot be copied, duplicated or commercially exploited, in whole or in part, without express written permission of RSP Architects. These are available for limited review and evaluation by clients, consultants, contractors, government agencies, vendors and office personnel only in accordance with this Notice. GENERAL NOTES: © Copyright RSP Architects 2015. All rights reserved. A. FOR VFD'S WITH BYPASS PROVISIONS, SEPARATE MOTOR OVERLOAD PROTECTION REQUIRED FOR EACH MOTOR, WHEN IN THE BYPASS POSITION. B. VFD EQUIPMENT SHALL HAVE STANDARD SHORT-CIRCUIT CURRENT RATING HIGHER THAN THE CALCUALTED VALUE SHOWN IN THE SCHEDULE. C. ALL VFDS SHALL HAVE INTEGRAL DISCONNECT WITH OVERCURRENT PROTECTION UNLESS NOTED OTHERWISE. Revisions No. Date Description NOTES: MAGNETIC STARTER SCHEDULE STARTER EQUIPMENT TAG VOLTAGE PHASE EF 02 208 V 3 EF 03 208 V 3 HWP 01 208 V 3 HWP 02 208 V 3 SP 01 208 V 3 TYPE FVNR FVNR FVNR FVNR FVNR SIZE 00 00 1 1 00 CONTROL VOLTAGE 24V 24V 24V 24V 24V AMPS/TYPE 30A/FUSED 30A/FUSED 60A/FUSED 60A/FUSED 30A/FUSED FUSE SIZE (AMPS) PER MANUF PER MANUF PER MANUF PER MANUF PER MANUF FURNISHED BY/ INSTALLED BY DIV. 26/DIV. 26 DIV. 26/DIV. 26 DIV. 26/DIV. 26 DIV. 26/DIV. 26 DIV. 26/DIV. 26 NOTES GENERAL NOTES: STARTER TYPES: A. REFER TO ENCLOSED CONTROLLER SPECIFICATION FOR ACCESSORIES/MODIFIERS. B. REFER TO MOTOR SCHEDULE FOR DISCONNECT REQUIRED AT MOTOR WHEN STARTER/DISCONNECT COMBINATION DOES NOT SATISFY THE REQUIREMENT. FVNR - FULL VOLTAGE NON-REVERSING FVR - FULL VOLTAGE REVERSING RVS - REDUCED VOLTAGE STARTER MULTI - MULTIPLE SPEED MAGNETIC STARTER NOTES: C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt 2/18/2016 3:50:17 PM ENCLOSURE (NEMA TYPE) 3R 3R 1 1 1 DISCONNECT AT STARTER DISCONNECT (COMBINATION/ EXTERNAL) COMBINATION COMBINATION COMBINATION COMBINATION COMBINATION MECHANICAL ELECTRICAL SCHEDULES M904