Electrical Draw.. - Terra General Contractors

SYMBOL
DESIGNATIONS
SYMBOL
DESIGNATIONS
SYMBOL SCHEDULE NOTES
A
#
B. MOUNTING HEIGHTS INDICATED ARE STANDARD. DIMENSIONAL
NUMBERS INDICATED AT DEVICES SHALL OVERRIDE THESE
STANDARDS. MOUNTED HEIGHTS ARE TO THE CENTER OF THE DEVICE,
UNLESS NOTED OTHERWISE.
b
D. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.
LIGHT FIXTURE ID - REFER TO LT FIXT SCHEDULE
(FIXT SCHEDULE OVERRIDES SYMBOL ABBREVIATION)
A - INDICATES LIGHT FIXTURE TYPE
# - INDICATES CIRCUIT NUMBER
b - INDICATES SWITCHING
TROFFER TYPE LIGHT FIXTURE, SIZE AS INDICATED CEILING MOUNT
48"
2
DOUBLE POLE TOGGLE SWITCH
48"
3
THREE WAY TOGGLE SWITCH
48"
4
FOUR WAY TOGGLE SWITCH
48"
a
TOGGLE SWITCH - "a" INDICATES SWITCHING
48"
PILOT LIGHT TOGGLE SWITCH
48"
ILLUMINATED TOGGLE - TOGGLE SWITCH
48"
K
KEYED SWITCH
48"
MC
MOMENTARY CONTACT TOGGLE SWITCH
48"
TS
TIMER SWITCH
48"
MUTLI SWITCH, MULTI GANG BOX
48"
DIMMER SWITCH (# = WATTAGE)
48"
DOWNLIGHT CLG FIXT, RECESSED OR SURFACE MOUNT
HEAVY DASHED LINE WEIGHT INDICATES EXISTING
ITEM TO BE REMOVED.
#
CEILING WALL WASH FIXT, AIMED AS INDICATED
SMALL MOUNT FIXTURE OR SCONCE
LIGHT SOLID LINE WEIGHT INDICATES EXISTING
ITEM TO REMAIN.
HEAVY SOLID LINE WEIGHT INDICATES NEW ITEM
OR NEW LOCATION.
REMOVE EXISTING ITEM
D
VERIFY
LINEAR RECESSED , LENGTH AS INDICATED
VERIFY
LINEAR WALL MOUNT FIXT, LENGTH AS INDICATED
VERIFY
S
EXISTING ITEM TO REMAIN
NL
NEW LOCATION FOR RELOCATED ITEM
OCCUPANCY SENSOR WALL SWITCH
PHOTO ELECTRIC CELL
UNDER CABINET FIXTURE, LENGTH AS INDICATED
TC
TIME CLOCK
60"
TRACK FIXTURE, NUMBER OF HEADS AS INDICATED
C
CONTACTOR
60"
R
RELAY
EMERGENCY BATTERY LIGHT - WALL CLG MNT
VERIFY
EXIT LIGHT, FILLED QUADRANT INDICATES FACES WALL/CEILING MOUNT
VERIFY
KEYNOTE
MISCELLANEOUS NOTE
#
RACEWAYS
CONDUIT CONCEALED IN CEILING OR WALLS
#
CONDUIT EXPOSED ON THE CEILING OR WALLS
CONDUIT BURIED UNDERGROUND (# = DEPTH)
MMS
P
J
I
SMOKE DETECTOR (P=PHOTOELEC, I=IONIZATION)
B-T
BEAM DET (B-T=TRANSMITTER, B-R=RECEIVER)
RS
F
F RS
TRANSFORMER
VERIFY
RL
F
F
MOTOR OR MOTOR CONNECTION
VERIFY
F
MOTOR CONTROLLER, STARTER OF VFD
VERIFY
F
F
VERIFY
F
VERIFY
MANUAL MOTOR STARTER SW W/THERM OVERLOAD
18"
QUADPLEX RECEPTACLE - WALL MOUNT
18"
CONDUIT WITH BREAK OR CONTINUATION
EMERGENCY QUADPLEX RECEPTACLE - WALL MOUNT
18"
CIRCUIT HOME RUN
- L1 INDICATES PANEL
- NUMBER
GFI RECEPTACLE, DUPLEX/QUADPLEX - WALL MOUNT
18"
SPECIAL PURPOSE RECEPTACLE - WALL/CLG MNT
18"
CONDUCTOR COUNT - UNLESS NOTED OTHERWISE
/ SHORT HASH INDICATES 1#12 LINE
/ LONG HASH INDICATES 1#12 NEUTRAL
/ HASH W/DOT INDICATES 1#12 GROUND
EMERGENCY SPECIAL PURPOSE RECEPT - WALL/CLG
18"
MM
CM
SD
DH
VERIFY
#
S
WIREWAY, DUCT BANK, OR FLOOR DUCT AS NOTED
MONITOR MODULE
CONTROL MODULE
FIRE/SMOKE DAMPER CONNECTION
DOOR HOLD OR DOOR HOLD CONNECTION
VERIFY
BELL - WALL/CEILING MOUNT
82"
F
F
BELL/STROBE - WALL/CLG MOUNT (# = CANDELA)
82"
F
F
CHIME - WALL/CEILING MOUNT
82"
F
CHIME/STROBE - WALL/CLG MOUNT (# = CANDELA)
82"
F
HORN - WALL/CEILING MOUNT
82"
F
HORN/STROBE - WALL/CLG MOUNT (# = CANDELA)
82"
#
#
F
GROUND REFERENCE BUS - AS NOTED - WALL/CLG MNT
TAMPER SWITCH
F
#
F
#
S
FLOW SWITCH
82"
F
S
72"
STROBE - WALL/CLG MNT (# = CANDELA)
F
POWER POLE - DEVICES AS INDICATED
REMOTE INDICATOR LAMP - WALL/CLG MOUNT
F
#
FLOOR BOX - DEVICES AS INDICATED
72"
48"
#
F
#
REMOTE STATION - WALL/CLG MOUNT
FIREMAN'S STATION - WALL MOUNT
FS
#
#
JUNCTION BOX - WALL/CEILING MOUNT
RL
TS
F
VERIFY
COMBINATION SMOKE DETECTOR AND ALARM
FS
F
VERIFY
CONDUIT WITH BUSHED END
SA
F
VERIFY
18"
G
F
DUCT MOUNTED PHOTOELECTRIC DETECTOR
F
EMERGENCY DUPLEX RECEPT - WALL/CLG MNT
G
P
HEAT DETECTOR (#=FIXED TEMP, R=RATE OF RISE)
F
CONDUIT WITH BEND UP
PULL BOX, SIZE AS NOTED
B
48"
48"
F
VERIFY
DUPLEX RECEPTACLE - WALL/CEILING MOUNT
P
F
MANUAL PULL STATION
EQUIPMENT CABINET
MOTOR RATED TOGGLE
CONDUIT WITH BEND DOWN
L1
1.3
VERIFY
R
VERIFY
DISCONNECT SWITCH
MR
F
#
BRANCH CIRCUIT PANEL
COMBINATION STARTER & DISCONNECT SWITCH
CONDUIT CONCEALED IN THE FLOOR OR BELOW
UG
F
POWER
ELEC EQUIP CONNECTION TAG - SEE EQUIP SCHEDULE
#
VERIFY
PUSH BUTTON STATION - BUTTONS AS INDICATED
SITE LIGHTING POLE TOP FIXT, ROUND/ RECT HEAD
FEEDER SIZE TAG - SEE POWER RISER SCHEDULE
#/A
48"
PC
SITE LIGHTING POLE FIXT, ROUND/RECTANGLE HEAD
- NUMBER OF HEADS INDICATED
EQUIPMENT IDENTIFICATION TAG - SEE EQUIP SCHEDULES
#
Sheet
Number
Sheet Name
E000
ELECTRICAL TITLE SHEET
ED001
ELECTRICAL SITE PLAN - DEMOLITION
E001
ELECTRICAL SITE PLAN - NEW
ED100
LOWER LEVEL DEMOLITION PLAN
ED101
FIRST LEVEL DEMOLITION PLAN
ED102
SECOND LEVEL DEMOLITION PLAN
ED103
THIRD LEVEL DEMOLITION PLAN
E100
LOWER LEVEL LIGHTING PLAN
E101
FIRST LEVEL LIGHTING PLAN
E102
SECOND LEVEL LIGHTING PLAN
E103
THIRD LEVEL LIGHTING PLAN
E200
LOWER LEVEL POWER PLAN
E201
FIRST LEVEL POWER PLAN
E202
SECOND LEVEL POWER PLAN
E203
THIRD LEVEL POWER PLAN
E204
ROOF POWER PLAN
E300
LOWER LEVEL SYSTEMS PLAN
E301
FIRST LEVEL SYSTEMS PLAN
E302
SECOND LEVEL SYSTEMS PLAN
E303
THIRD LEVEL SYSTEMS PLAN
E404
LIGHTNING PROTECTION PLAN
E405
LIGHTNING PROTECTION DETAILS
E500
ELECTRICAL RISER DIAGRAM
E600
ELECTRICAL SCHEDULES
E601
ELECTRICAL SCHEDULES
E602
PANEL SCHEDULES
E603
PANEL SCHEDULES
E604
PANEL SCHEDULES
E605
PANEL SCHEDULES
E606
PANEL SCHEDULES
E607
PANEL SCHEDULES
E608
PANEL SCHEDULES
E609
PANEL SCHEDULES
E700
LIGHTING DETAILS
E701
ELECTRICAL DETAILS
E702
ELECTRICAL DETAILS
E703
FIRE ALARM DETAILS
M901
PLUMBING ELECTRICAL SCHEDULES
M902
MECHANICAL ELECTRICAL SCHEDULES
M903
MECHANICAL ELECTRICAL SCHEDULES
M904
MECHANICAL ELECTRICAL SCHEDULES
Grand total: 41
FIRE ALARM
NOTES & TAGS
xx
##
Sheet List
OCCUPANCY SENSOR - CLG MOUNT
OS
REMOVE EXISTING ITEM AND RELOCATE AS INDICATED
X
J
SINGLE POLE TOGGLE SWITCH
4
CHANNEL OR INDUSTRIAL, LENGTH AS INDICATED
GENERAL
MTG
HT
DESIGNATIONS
SWITCHES AND CONTROLS
LIGHT FIXTURE CIRCUIT TYPE
- NO HATCH INDICATES NORMAL CIRCUIT
- ANGLED HATCH INDICATES CRITICAL CIRCUIT
- SOLID HATCH INDICATES LIFE SAFETY CIRCUIT
C. MOUNTING HEIGHTS INDICATED ARE FOR STUD WALL CONSTRUCTION.
WHEN BLOCK OR BRICK CONSTRUCTION IS USED, ADJUST MOUNTING
HEIGHTS TO ALIGN DEVICE PLATES WITH RUNNING JOINT.
RL
SYMBOL
LIGHTING
A. THESE SYMBOLS COMPRISE A STANDARD LIST, NOT ALL SYMBOLS
MAY APPEAR ON THESE DRAWINGS.
R
MTG
HT
F
S
F
SPEAKER - WALL/CEILING MOUNT
82"
F
#
S
F
SPEAKER/STROBE - WALL/CLG MOUNT(# = CANDELA)
82"
#
S
AF
COMBINATION FIRE ALARM/MASS NOTIFICATION:
SPEAKER/STROBE - WALL/CLG MOUNT(# = CANDELA)
82"
AF
FACP
CABLE TRAY, TYPE/SIZE AS INDICATED
FIRE ALARM CONTROL PANEL - WALL MOUNT
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
50358
Date
07/24/15
Project For
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
VERIFY
ELECTRICAL ABBREVIATIONS
A, AMP
AMPERES
C
CONDUIT
EWC
ELECTRIC WATER COOLER
MC
MOMENTARY CONTACT
PE
PNEUMATIC ELECTRIC
TSTAT
THERMOSTAT
AA
AUDIBLE ALARM
CAB
CABINET
F
FUSE OR FUSED
MCB
MAIN CIRCUIT BREAKER
PF
POWER FACTOR
TYP
TYPICAL
AC
ABOVE COUNTER
CB
CIRCUIT BREAKER
FA
FIRE ALARM
MLO
MAIN LUG ONLY
PH
PHASE
UC
UNDER COUNTER
Drawn By
ADD
ADDENDUM
CCTV
CLOSED CIRCUIT TV
FACP
FIRE ALARM CONTROL PANEL
MRS
MOTOR RATED SWITCH
PNL
PANEL
UG
UNDERGROUND
Checked By
AFC
AVAILABLE FAULT CURRENT
CKT
CIRCUIT
FSD
FIRE-SMOKE DAMPER
MSB
MAIN SWITCHBOARD
PRI
PRIMARY
UH
UNIT HEATER
AFCI
ARC FAULT CIRCUIT INTERRUPTER
CU
COPPER
FV
FILM VIEWER
MT
EMPTY
RECEPT
RECEPTACLE
UNO
UNLESS NOTED OTHERWISE
AFF
ABOVE FINISHED FLOOR
DN
DOWN
G, GND
GROUND
NC
NORMALLY CLOSED
REFG
REFRIGERATOR
V
VOLT
AHU
AIR HANDLING UNIT
EC
ELECTRICAL CONTRACTOR
GFI
GROUND FAULT INTERRUPTER
NEC
NATIONAL ELECTRICAL CODE
RTU
ROOF TOP UNIT
VA
VOLT-AMP
AL
ALUMINUM
ELEC
ELECTRIC OR ELECTRICAL
IG
ISOLATED GROUND
NIC
NOT IN CONTRACT
SEC
SECONDARY
VAC
VOLTS ALTERNATING CURRENT
ANT
ANTENNA
EM
EMERGENCY
JBOX
JUNCTION BOX
NO
NORMALLY OPEN
SPKR
SPEAKER
VDC
VOLTS DIRECT CURRENT
ATS
AUTOMATIC TRANSFER SWITCH
EMT
ELECTRICAL METALLIC TUBING
KV
KILOVOLT
NTS
NOT TO SCALE
SW
SWITCH
W
WATT OR WIRE
BAS
BUILDING AUTOMATION SYSTEM
ENCL
ENCLOSURE
KVA
KILOVOLT-AMP
OC
ON CENTER
SWBD
SWITCHBOARD
WP
WEATHERPROOF
BFC
BELOW FINISHED CEILING
EP
ELECTRIC PNEUMATIC
KW
KILOWATT
PB
PULL BOX
TEL
TELEPHONE
XFMR
TRANSFORMER
BPS
BOLTED PRESSURE SWITCH
EPO
EMERGENCY POWER OFF
KWH
KILOWATT-HOUR
PB
PUSHBUTTON
TR
TAMPER RESISTANT
Project No.
2263.001.00
MK
JL
Date
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
ELECTRICAL TITLE
SHEET
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:01:08 PM
E000
GENERAL DEMOLITION NOTES:
A.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED
UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR
REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED
CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND
DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT
TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR
TO BID SUBMITTAL.
B.
A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY
OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES
WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE
CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS
TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR
COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER.
C.
INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK
WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR
WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED.
D.
PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND
OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND
TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK
PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER
EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING
BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND
FEDERAL REGULATIONS.
E.
IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR
RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE
DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF
REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION.
1
F
E
D.9
F.
MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO
THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE
OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH
CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE
TEMPORARY PROVISIONS.
G.
DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION.
DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED
BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS.
H.
DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN
WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO
ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE
TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION.
I.
EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE
USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED
SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND
BRANCH CIRCUITING.
J.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING
FOR ELECTRICAL WORK.
K.
PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE
CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY
WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO
MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS.
SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER
SYSTEMS.
1
1
L.
D
C.9
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF
NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES
AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES
AND JUNCTION BOXES.
M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES
WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE.
N.
C.3
RSP Architects
O.
MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING
CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE
CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF
PROJECT.
PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS
REMAINING AT END OF PROJECT.
C
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
B.8
KEY NOTES:
B.2
1
IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES,
ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION BOXES,
SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION DEVICES,
CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.),
MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS,
UNLESS NOTED OTHERWISE.
2
DEMOLISH EXISTING PANELBOARD.
3
REMOVE EXTERIOR WALL MOUNTED LIGHT FIXTURE. TURN LIGHT FIXTURE
OVER TO OWNER.
B
2
A
1
Project No.
Drawn By
AA
0
1
2
3
3
3
4
4.2
4.5
4.8 5
CL
MMK
Checked By
Date
3
2263.001.00
5.55.6
66.2
6.7 7
3
8
9
10
11
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
FIRST FLOOR DEMOLITION PLAN
2
1/8" = 1'-0"
No.
Date
Description
FIRST LEVEL
DEMOLITION PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:05:53 PM
ED101
GENERAL NOTES:
2
A.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED
UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR
REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED
CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND
DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND ELECTRICAL DRAWINGS MUST BE BROUGHT TO THE
ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID
SUBMITTAL.
B.
A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY
OF EXISTING SITE CONDITIONS, HOWEVER, NO ATTEMPT HAS BEEN MADE
TO FIND CHANGES WHICH OCCUR UNDERGROUND. AS CONSTRUCTION
PROGRESSES, PERFORM MINOR FIELD MODIFICATIONS AND ADDITIONS AS
NECESSARY TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW
FOR COMPLETION OF NEW WORK WITH NO ADDITIONAL COST TO THE
OWNER.
C.
SEQUENCE ALL WORK IN ACCORDANCE WITH THE CONSTRUCTION
MANAGERS REQUIREMENTS.
D.
MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO
THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE
OPERATIONS OF SYSTEMS. PERMANENTLY RE-FEED EXISTING BRANCH
CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE
TEMPORARY PROVISIONS.
J
O-B1B /17
1
LCP-B1/11
RIVERVIEW
AA4
N-B1/ 13
E.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING
FOR ELECTRICAL WORK.
F.
WARNING: VERIFY LOCATIONS OF UNDERGROUND UTILITIES PRIOR TO ANY
SITE WORK. UTILIZE A SURVEY SERVICE TO PROVIDE ADDITIONAL
INFORMATION REGARDING EXISTING ELECTRICAL AND COMMUNICATION
CABLING LOCATED ON THIS SITE.
G.
SEE LIGHTING PLANS FOR BUILDING MOUNTED LIGHTING.
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
AA2
N-B1/ 13
GEN
13' - 2"
LCP-B1/10
XFMR
7' - 11 27/32"
8' - 0"
2' - 0"
8' - 0"
MAIN
CIRCUIT
BREAKER
ENCLOSURE
KEY NOTES:
2
J
O-B1B /12
SEE ONE-LINE
DIAGRAM FOR SIZES,
AND REFER TO SHEET
200 FOR PROPOSED
CONDUIT ROUTING
1
NEW ELECTRICAL FEED TO SITE LIGHTING.
2
REFEED EXISTING BLUE LIGHT CALL STATION WITH INDICATED
CIRCUIT. PROVIDE 1-1/4"C FROM DATA ROOM IN BASEMENT.
3
NEW CONCRETE ENCLASED DUCT BANK FOR MEDIUM VOLTAGE
DISTRIBUTION FROM SWITCH TO NEW TRANSFORMER LOCATION.
REFER TO RISER DIAGRAM FOR CONDUIT AND FEEDER SIZE.
FEEDER SHALL NOT BE ROUTED IN EXISTING TUNNEL.
4
3' - 7"
EASTMAN
3
REFER TO LIGHTING CONTROL SEQUENCE SCHEDULE FOR
ADDITIONAL INFORMATION ON EXTERIOR LIGHTING CONTROLS.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
50358
Date
07/24/15
Project For
EXISTING MEDIUM VOLTAGE
TRANSFORMER SHALL REMAIN
TO FEED RIVERVIEW
EXISTING MV
FEEDERS IN
TUNNEL
EXISTING S&C PME-9
PAD MOUNTED
SWITCH SHALL
REMAIN
STUDENT HEALTH AND
ACADEMIC RENOVATION
LCP-B1/10
AA2
N-B1/ 13
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
LCP-B1/12
LCP-B1/9
WP
NR-B1B /1
AA5
N-B1/ 9
LCP-B1/9
NR-B1B /1
WP
4
LCP-B1/9
LC
08
AA5
N-B1/ 9
AA5
N-B1/ 9
NR-B1B /3
WP
AA5
N-B1/ 9
WP
NR-B1B /3
BB4
N-B1/ 11
LCP-B1/9
2
J
O-B1A /8
1ST AVENUE SOUTH
1ST AVENUE SOUTH
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
ELECTRICAL SITE PLAN - NEW
1
1/16" = 1'-0"
FIXTURE DESCRIPTION
TYPE
LAMPS/
LIGHT ENGINE
BALLAST/
DRIVER
VOLTAGE MAX
VA
CONTROL MEDIA
(LENS/LOUVER)
MANUFACTURER
SERIES NUMBERS
DESCRIPTION
POLE
LENGTH
POLE
SHAPE
© Copyright RSP Architects 2015. All rights reserved.
BASE DESCRIPTION
POLE DESCRIPTION
MOUNTING
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
SITE LIGHTING FIXTURE SCHEDULE
LETTER
JL
POLE
POLE
MATERIAL COLOR/FINISH
FIXTURE
MOUNT
SUPPORTS SUPPORTS INTEGRAL
CCTV
FLAG OR
DUPLEX
VIBRATION
CAMERA
BANNER RECEPTACLE DAMPERS
FOUNDATION
BASE HEIGHT BASE HEIGHT
ABOVE
BELOW
GRADE
GRADE
Revisions
BASE
DIAMETER
VERTICAL
BARS
TIES
NOTES
No.
AA2
AREA POLE LIGHT ONE HEAD
RECTANG.
ARM
LED 4000K
7700
LUMENS
MIN
ELECTRONIC 120/277V
97W
MAX
TYPE II
DISTRIBUTION
BEACON #VPS SERIES
NO SUBSTITUTIONS
DIE CAST ALUMINUM HOUSING.
HINGED DOOR. BRONZE TEXTURED
FINISH.
12'
ROUND
STEEL
BRONZE
ARM
NO
NO
YES
NO
CONCRETE BASE
4"
4'-6"
24"
#4
#3
1
AA4
AREA POLE LIGHT ONE HEAD
RECTANG.
ARM
LED 4000K
7700
LUMENS
MIN
ELECTRONIC 120/277V
97W
MAX
TYPE IV
DISTRIBUTION
BEACON #VPS SERIES
NO SUBSTITUTIONS
DIE CAST ALUMINUM HOUSING.
HINGED DOOR. BRONZE TEXTURED
FINISH.
12'
ROUND
STEEL
BRONZE
ARM
NO
NO
YES
NO
CONCRETE BASE
4"
4'-6"
24"
#4
#3
1
AA5
AREA POLE LIGHT ONE HEAD
RECTANG.
ARM
LED 4000K
7700
LUMENS
MIN
ELECTRONIC 120/277V
97W
MAX
TYPE V
RECTANGULAR
DISTRIBUTION
BEACON #VPS SERIES
NO SUBSTITUTIONS
DIE CAST ALUMINUM HOUSING.
HINGED DOOR. BRONZE TEXTURED
FINISH.
12'
ROUND
STEEL
BRONZE
ARM
NO
NO
YES
NO
CONCRETE BASE
4"
4'-6"
24"
#4
#3
1
BB4
AREA POLE LIGHT TWO HEADS
RECTANG.
ARM
LED 4000K
14400
LUMENS
MIN
ELECTRONIC 120/277V
194W
MAX
TYPE IV
DISTRIBUTION
BEACON #VPS SERIES
NO SUBSTITUTIONS
DIE CAST ALUMINUM HOUSING.
HINGED DOOR. BRONZE TEXTURED
FINISH.
22'
ROUND
TAPERED
STEEL
BRONZE
ARM
NO
NO
NO
YES
CONCRETE BASE
3'
6'
24"
#4
#3
1
Date
Description
GENERAL NOTES:
A. SEE SPECIFICATIONS FOR ADDITIONAL LIGHT FIXTURE REQUIREMENTS.
B. MINIMUM LUMENS LISTED FOR SOLID STATE LIGHT FIXTURES ARE DELIVERED LUMENS BASED ON PHOTOMETRIC TESTING COMPLETED IN ACCORDANCE WITH IES LM-79 STANDARDS.
NOTES:
1. OWNER'S CAMPUS STANDARD EXTERIOR LIGHT FIXTURE MANUFACTURER, NO SUBSTITUTIONS.
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:06:20 PM
ELECTRICAL SITE
PLAN - NEW
E001
GENERAL NOTES:
A.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED
UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR
REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED
CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND
DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND ELECTRICAL DRAWINGS MUST BE BROUGHT TO THE
ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR TO BID
SUBMITTAL.
B.
A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY
OF EXISTING SITE CONDITIONS, HOWEVER, NO ATTEMPT HAS BEEN MADE
TO FIND CHANGES WHICH OCCUR UNDERGROUND. AS CONSTRUCTION
PROGRESSES, PERFORM MINOR FIELD MODIFICATIONS AND ADDITIONS AS
NECESSARY TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW
FOR COMPLETION OF NEW WORK WITH NO ADDITIONAL COST TO THE
OWNER.
C.
SEQUENCE ALL WORK IN ACCORDANCE WITH THE CONSTRUCTION
MANAGERS REQUIREMENTS.
D.
MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO
THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE
OPERATIONS OF SYSTEMS. PERMANENTLY RE-FEED EXISTING BRANCH
CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE
TEMPORARY PROVISIONS.
RSP Architects
E.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING
FOR ELECTRICAL WORK.
F.
WARNING: VERIFY LOCATIONS OF UNDERGROUND UTILITIES PRIOR TO ANY
SITE WORK. UTILIZE A SURVEY SERVICE TO PROVIDE ADDITIONAL
INFORMATION REGARDING EXISTING ELECTRICAL AND COMMUNICATION
CABLING LOCATED ON THIS SITE.
G.
SEE LIGHTING PLANS FOR BUILDING MOUNTED LIGHTING.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
2
KEY NOTES:
1
REMOVE LIGHT FIXTURE AND TURN OVER TO OWNER.
2
DEMOLISH ELECTRICAL FEED TO SITE LIGHTING. FIXTURES TO REMAIN
AND BE REFED. SEE NEW ELECTRICAL SITE PLAN FOR ADDITIONAL
INFORMATION. TEMPORARILY REFEED DURING CONSTRUCTION TO INSURE
THAT WALKWAY LIGHTS ARE ON DURING CONSTRUCTION.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
1
STUDENT HEALTH AND
ACADEMIC RENOVATION
EXISTING MV
FEEDERS
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
EXISTING MEDIUM VOLTAGE
TRANSFORMER SHALL REMAIN
TO FEED RIVERVIEW
EXISTING PMH
SWITCH SHALL
REMAIN
1
1
1
Project No.
Drawn By
2263.001.00
MMK
Checked By
Date
1ST AVENUE SOUTH
1ST AVENUE SOUTH
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
1
Date
Description
ELECTRICAL SITE PLAN - DEMOLITION
1/16" = 1'-0"
ELECTRICAL SITE
PLAN - DEMOLITION
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:02:14 PM
ED001
GENERAL DEMOLITION NOTES:
A.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED
UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR
REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED
CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND
DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT
TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR
TO BID SUBMITTAL.
B.
A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY
OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES
WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE
CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS
TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR
COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER.
C.
INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK
WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR
WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED.
D.
PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND
OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND
TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK
PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER
EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING
BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND
FEDERAL REGULATIONS.
E.
IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR
RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE
DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF
REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION.
1
F
DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION.
DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED
BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS.
H.
DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN
WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO
ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE
TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION.
I.
EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE
USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED
SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND
BRANCH CIRCUITING.
J.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING
FOR ELECTRICAL WORK.
Signature
K.
PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE
CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY
WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO
MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS.
SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER
SYSTEMS.
Registration Number
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Date
James A. LeClaire
50358
07/24/15
Project For
SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF
NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES
AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES
AND JUNCTION BOXES.
L.
M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES
WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE.
N.
C.3
Dunham Job #: 415134
G.
1
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO
THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE
OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH
CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE
TEMPORARY PROVISIONS.
1
D
C.9
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
F.
2
E
D.9
RSP Architects
O.
MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING
CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE
CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF
PROJECT.
PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS
REMAINING AT END OF PROJECT.
STUDENT HEALTH AND
ACADEMIC RENOVATION
C
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
B.8
2
3
4
B.2
5
B
A
1
KEY NOTES:
1
IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES,
ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION
BOXES, SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION
DEVICES, CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.),
MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS,
UNLESS NOTED OTHERWISE.
2
REMOVE EXISTING ELECTRICAL DISTRIBUTION. TURN EQUIPMENT OVER
TO OWNER.
3
REMOVE EXISTING FACP.
4
EXISTING 800A DISCONNECT FEEDING RIVERVIEW TO REMAIN.
5
REMOVE EXISTING 600A DISCONNECT SERVING EASTMAN HALL. UTILIZE
DISCONNECT FOR TEMPORARY POWER DURING CONSTRUCTION.
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
AA
0
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
LOWER LEVEL DEMOLITION PLAN
1
1/8" = 1'-0"
No.
Date
Description
LOWER LEVEL
DEMOLITION PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:05:43 PM
ED100
GENERAL DEMOLITION NOTES:
A.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED
UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR
REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED
CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND
DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT
TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR
TO BID SUBMITTAL.
B.
A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY
OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES
WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE
CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS
TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR
COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER.
C.
INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK
WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR
WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED.
D.
PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND
OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND
TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK
PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER
EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING
BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND
FEDERAL REGULATIONS.
E.
IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR
RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE
DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF
REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION.
1
F
E
D.9
DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION.
DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED
BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS.
H.
DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN
WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO
ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE
TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION.
I.
EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE
USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED
SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND
BRANCH CIRCUITING.
J.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING
FOR ELECTRICAL WORK.
Signature
K.
PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE
CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY
WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO
MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS.
SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER
SYSTEMS.
Registration Number
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Date
James A. LeClaire
50358
07/24/15
Project For
SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF
NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES
AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES
AND JUNCTION BOXES.
M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES
WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE.
N.
C.3
Dunham Job #: 415134
G.
L.
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO
THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE
OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH
CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE
TEMPORARY PROVISIONS.
2
D
C.9
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
F.
1
2
RSP Architects
O.
MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING
CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE
CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF
PROJECT.
PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS
REMAINING AT END OF PROJECT.
STUDENT HEALTH AND
ACADEMIC RENOVATION
C
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
B.8
KEY NOTES:
2
B.2
1
IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES,
ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION BOXES,
SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION DEVICES,
CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.),
MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS,
UNLESS NOTED OTHERWISE.
2
DEMOLISH EXISTING PANELBOARD.
B
1
A
Project No.
2263.001.00
Drawn By
MMK
1
Checked By
Date
AA
0
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
SE COND FLOOR DEMOLITION PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
SECOND LEVEL
DEMOLITION PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:06:02 PM
ED102
GENERAL DEMOLITION NOTES:
A.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE PLANNED
UNDER PREVIOUS CONSTRUCTION PROJECTS AND ARE INCLUDED FOR
REFERENCE. ACTUAL CONDITIONS MAY VARY FROM PLANNED
CONDITIONS. EXAMINE THE SITE CONDITIONS PRIOR TO BIDDING AND
DETERMINE ACTUAL CONDITIONS. DISCREPANCIES BETWEEN EXISTING
CONDITIONS AND ELECTRICAL DEMOLITION DRAWINGS TO BE BROUGHT
TO THE ATTENTION OF THE ELECTRICAL ENGINEER AND ARCHITECT PRIOR
TO BID SUBMITTAL.
B.
A FIELD SURVEY WAS CONDUCTED TO VERIFY THE GENERAL ACCURACY
OF EXISTING PLANS, NO ATTEMPT HAS BEEN MADE TO FIND CHANGES
WHICH OCCUR IN CONCEALED AREAS SUCH AS ABOVE INACCESSIBLE
CEILINGS AND IN WALLS. PERFORM MINOR MODIFICATIONS AND ADDITIONS
TO CORRECT FOR THESE HIDDEN CONDITIONS TO ALLOW FOR
COMPLETION OF WORK WITH NO ADDITIONAL COST TO THE OWNER.
C.
INTERRUPTIONS TO SERVICES OR SIGNIFICANT NOISE PRODUCING WORK
WILL BE LIMITED TO NIGHT TIME WORKING HOURS (9:00PM TO 5:00AM) OR
WEEKENDS. OWNER WILL CONFIRM THE AREAS AND SYSTEMS IMPACTED.
D.
PROVIDE A COORDINATION WALK THROUGH WITH THE OWNER AND
OWNER REPRESENTATIVE TO IDENTIFY EQUIPMENT TO BE SALVAGED AND
TURNED OVER PRIOR TO START OF DEMOLITION. REMOVE AND STOCK
PILE EQUIPMENT FOR THE OWNER TO REMOVE FROM SITE. OTHER
EXISTING DEVICES, LIGHT FIXTURES, EQUIPMENT, CONDUIT AND CABLING
BEING DEMOLISHED WILL BE THE RESPONSIBILITY OF THE ELECTRICAL
CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH THE LOCAL AND
FEDERAL REGULATIONS.
E.
IDENTIFY DAMAGE TO EXISTING EQUIPMENT BEING REUSED OR
RELOCATED PRIOR TO THE START OF DEMOLITION. REMOVE AND STORE
DEVICES SHOWN TO BE REUSED OR RELOCATED UNTIL THE TIME OF
REINSTALLATION. REPLACE DEVICES DAMAGED DURING CONSTRUCTION.
1
F
E
D.9
F.
MAINTAIN OPERATION OF ELECTRICAL SYSTEMS IN AREAS ADJACENT TO
THE DEMOLITION AND INSTALL TEMPORARY CONNECTIONS TO CONTINUE
OPERATION OF SYSTEMS. PERMANENTLY FEED EXISTING BRANCH
CIRCUITS AND SYSTEMS REMAINING IN OPERATION AND REMOVE
TEMPORARY PROVISIONS.
G.
DE-ENERGIZE ELECTRICAL EQUIPMENT PRIOR TO DEMOLITION.
DISCONNECT POWER TO MECHANICAL EQUIPMENT AND POWERED
BUILDING EQUIPMENT NOTED FOR DEMOLITION OR REMOVAL BY OTHERS.
H.
DEMOLISH ALL ELECTRICAL DEVICES, CONDUIT, WIRE, AND EQUIPMENT IN
WALLS, CEILINGS, AND FLOORS. REMOVE CONDUIT AND WIRING BACK TO
ELECTRICAL DEVICES THAT REMAIN, BACK TO THE SOURCE OR PROVIDE
TEMPORARY SUPPORT FOR REUSE UPON COMPLETION OF DEMOLITION.
I.
EXISTING CONDUITS AND BOXES MAY BE REUSED WHERE PRACTICAL. THE
USE OF EXISTING OUTLET BOXES WITH BLANK COVERS IN FINISHED
SPACES IS NOT ACCEPTABLE. DEMOLISH THESE BOXES, CONDUIT, AND
BRANCH CIRCUITING.
J.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING
FOR ELECTRICAL WORK.
K.
PROVIDE TIE WRAPS AND SUPPORTS FOR LOOSE CABLES ABOVE
CEILINGS, CABLES LYING ON THE CEILING, AND CABLES ATTACHED TO GUY
WIRE SUPPORTS. PERMANENTLY SUPPORT CABLES ATTACHED TO
MECHANICAL DUCTWORK, PIPING, AND OTHER DEMOLISHED SUPPORTS.
SUPPORT CABLES FROM THE STRUCTURE, INDEPENDENT OF OTHER
SYSTEMS.
1
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
M. COORDINATE THE DISCONNECTION OF LOW VOLTAGE SYSTEMS CABLES
WITH THE OWNER AND REMOVE FROM UTILIZATION POINT TO SOURCE.
N.
C.3
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
SUPPORT CONDUITS NOT SUPPORTED PER THE LATEST VERSION OF
NEC. REPLACE MISSING COVERS ON JUNCTION BOXES, OUTLET BOXES
AND CLOSE UNUSED AND OPEN KNOCKOUTS ON EXISTING PULL BOXES
AND JUNCTION BOXES.
L.
D
C.9
RSP Architects
MAINTAIN OPERATION OF THE FIRE ALARM SYSTEM DURING
CONSTRUCTION. PROTECT EXISTING FIRE ALARM DEVICES IN THE
CONSTRUCTION AREA AND THOROUGHLY CLEAN UPON COMPLETION OF
PROJECT.
O.
PROVIDE BLANK COVER PLATES FOR UNUSED DEVICE OUTLETS
REMAINING AT END OF PROJECT.
STUDENT HEALTH AND
ACADEMIC RENOVATION
C
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
B.8
1
B.2
B
A
KEY NOTES:
1
IN SPACES WITHIN HATCHED GRAY AREA, REMOVE ALL LIGHT FIXTURES,
ELECTRICAL DEVICES/BOXES (RECEPTACLES, UNUSED JUNCTION BOXES,
SWITCHES, FIRE ALARM DEVICES, EXIT SIGNS, COMMUNICATION DEVICES,
CAMERAS, MONITORS, SPEAKERS, VOLUME CONTROLS, ETC.),
MECHANICAL EQUIPMENT AND ASSOCIATED CONDUIT AND CONDUCTORS,
UNLESS NOTED OTHERWISE.
Project No.
2263.001.00
Drawn By
1
MMK
Checked By
Date
AA
0
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
THIRD FLOOR DEMOLITION PLAN
2
1/8" = 1'-0"
Revisions
No.
Date
Description
THIRD LEVEL
DEMOLITION PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:06:11 PM
ED103
GENERAL LIGHTING NOTES:
UP
H1
E-B1/ 21
CIRCUIT TO
N-B1 UNO
STORAGE
A.
WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES
SHALL ALWAYS BE “ON”.
B.
VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING
HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES.
C.
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
D.
REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL
REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM.
E.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE
PLACEMENT IN GYP BOARD AND ACT CEILING.
F.
WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL,
ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER
DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER
PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM
RATING.
RSP Architects
G.
PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH
BOXES.
Consultants
H.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
I.
VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT
FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION.
CIRCUIT TO
N-B2 UNO
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Dunham Job #: 415134
054
F
LC
04
E1
E-B1/ 2
S
D1
E-B1/ 18
SHOWER/
RESTROOM
D1
E-B1/ 18
J2 2
10
LC
07
R
OS
EM
MENS LOCKER
ROOM
008
D1
10
LC
07
COS1
D1
2
A3
E-B1/ 18
D1
2
EM
D1
E-B1/ 18
J1
1
004
1
F1
14
S
LCP-B1/13
COS1
S
B1
E-B1/ 3
3
LC
06
ATS-E
F1
8
022
ATS-R
ATS-O
RD-B1
LCP-B1
O-B1A
NR-B1A
NR-B1B
O-B1B
F1
8
F1
8
N-B1
LCP-B1/2
B1
6
F1
E-B1/ 1 E-B1
G
F1
E-B1/ 1
NRD-B1
EM
OS
D1
E-B1/ 19
D1
12
LC
07
LC
06
F1
8
F1
E-B1/ 1
UNISEX
TOILET/SHOWER
LCP-B1/13
F1
2
J2
12
B1
E-B1/ 3
F1
2
R1
F1
8
F1
3
021
F1
8
CIRCUIT TO
N-B1 UNO
F1
1
R
F1
1
F1
1
C.3
BUILDING
SUPPORT
F1
3
F1
3
50358
07/24/15
STUDENT HEALTH AND
ACADEMIC RENOVATION
018
F1
2
F1
2
LC
05
OS
LCP-B1/2
B1
6
F1
3
LC
05
James A. LeClaire
F1
1
F1
E-B1/ 1 2
R
EM
ND-B1
NR-B2
C
N-B2
E3
E-B1/ 2
LCP-B1/2
B1
6
LCP-B1/13
B1
E-B1/ 3
COS1
B.8
STAIR B
S002
B.2
B
F1
3
COS1
COS1
033
F1
3
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
LC
04
H1
E-B1/ 7
E1
E-B1/ 2
COS1
Signature
D
C.9
EM
LC
06
CUSTODIAN
SHOWER/
RESTROOM
F1
3
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Project For
F1
E-B1/ 1
EM
D1
E-B1/ 19
DATA ROOM
F1
8
2
R
LCP-B1/2
COS1 B1
6
F1
1
LC
06
SW
R
EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL
OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE
CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS
INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO
SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU-200
EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL.
032
2 R EM
014
D1
E-B1/ 19
J2
LC
12
07
D1
12
J2
12
013
F1
1
3
MSB
ELECTRICAL
ROOM
LCP-B1/2
B1
6
S
001
R
OS
E2
E-B1/ 2
LC
LCP-B1/2
B1
04
6
COS1
2
Registration Number
MECHANICAL
ROOM
016
CORRIDOR
LCP-B1/2
B1
6
B1
E-B1/ 3
2
2
S
F1
14
COS1
LCP-B1/13
D1
5
E1
OS
MECHANICAL
ROOM
F1
2
EM
SHOWER/
RESTROOM
D1
1
LC
07
LCP-B1/1
PASSENGER
ELEVATOR
CIRCUIT FIXTURE IN ELEVATOR PIT TO SAME 120V CIRCUIT AS
RECEPTACLE(S) WITHIN PIT. DO NOT CONNECT LIGHT TO LOAD SIDE OF
GFI RECEPTACLE. COORDINATE LOCATION OF LIGHT FIXTURE WITH
ELEVATOR CONTRACTOR.
Date
052
S
LC
06
PASS./SERV.
ELEV. EQUIP.
ROOM
R
D1
12
COS1
F1
1
RESISTANCE
TRAINING
D1
E-B1/ 19
051
A3
1
S
F1
14
D1
1
A3
E-B1/ 19
LCP-B1/1
B1
5
005
R
050
2
E
D.9
F1
1
F1
1
LC
07
J2
1
RESTROOM
WOMANS
LOCKER ROOM
S
J2
2 2
F1
1
035
OS SHOWER/
D1
1
F1
1
S8
4
A1
3
D1
LC
07
055
SHOWER
OS
RESTROOM
F1
1
CVS1
R1
R
F1
E-B1/ 1
LC
02
COS1
2 R EM
CORRIDOR
D1
A1
3
A1
3
D1
1
LCP-B1/1
B1
5
A3
2 LC
07
D
D1
LC
02
RC0-1
R R3
A3
2
R1
D
A1
3
S
006
R
LCP-B1/1
B1
5
B1
5
LC
04
OS
F1
7
010
CVS1
003
D1
10
EXAM/ CONSULT
011
S
EM
D1
10
R
S8
4
EXAM/ CONSULT
COS1
S
2
S8
4
COS1
B1
E-B1/ 3
WAITING
LC
07
LC
03
S8
4
LCP-B1/13
B1
5
F1
7
J2
10
1
009
LCP-B1/1
007
S8
4
EXERCISE/TRAINING
E2
SHOWER/
RESTROOM
F1
7
COS1
LCP-B1/1
KEY NOTES:
F1
E-B1/ 1
S
1
03A
B1
5
S8
4
S
SERVICE
ELEVATOR
S8
4
S
COS1 LCP-B1/1
B1
5
CORRIDOR
B1
4
OS
S
S
J1
2
E1
E-B1/ 2
LCP-B1/13
B1
E-B1/ 3
LC
05
S
E1
E-B1/ 2
F1
E-B1/ 1
2
R
EM
F1
3
F1
3
MECHANICAL
ROOM
F1
3
019
CIRCUIT TO
N-B2 UNO
F1
3
LC
06
F1
E-B1/ 1
A
Project No.
2263.001.00
Drawn By
MMK
Checked By
JL
Date
AA
0
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
LOWER LEVEL LIGHTING PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
LOWER LEVEL
LIGHTING PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:01:18 PM
E100
GENERAL LIGHTING NOTES:
144"
LCP-B1/24
W2
E1 E-B1/ 27
E-B1/ 5
A1
1
c
A1
1
R
c
R3
c
CVS1
d
S
R
CVS1
C4
3
R3 D5
D
A1
5
d
COS1
P1
A1
5
d
A1
5
A4
5
d
d
A1
5
f
f
C1
2
LCP-11/2
D1
3
LC
07
LCP-11/3
LCP-11/5 LCP-11/5
D1
D1
7
7
PASS
ELEVATOR
A4
5
115
C4
2 a
R3
C4
D D5 2 a
R
LCP-11/5
D1
7
COS1
OS
1 R
D1
E-B1/ 25
C6
3
COS1
S
S
LCP-11/28
C3
E2 E-B1/ 4
E-B1/ 5
LCP-11/9
LCP-11/9
C3
7
1
LC
07
EM
B1
E-B1/ 4
d
P1
A1
6
S
CVS1
D D1
R1
A1
R
6
CVS1
A1
8
COS1
LCP-11/28
EM C2
D1 1
E-B1/ 25
COS2
R
D1
1
LC
07
LC
02
LC
04
107
126
0
1
2
LCP-B1/14
W1 72"
E-B1/ 10
3
PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH
BOXES.
H.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
I.
VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT
FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
D1
E-B1/ 25
B1
21
COS1
C4
7
R
R1
A1
8
D D1
CVS1
A1
8
PC
P1
R
C4 LCP-11/9
7
E1
E-B1/ 6
RESEARCH
DIRECTOR
125
LC
01
LC
04
H1
E-B1/ 7
LCP-11/8
D1
7
CVS1
R1
A1
8
A1
8
PC
P1
R
Consultants
UCHOOSE & RC
121
LC
01
R1
A1
8
A1
8
PC
P1
UCHOOSE & RC
120
EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL
OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE
CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS
INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO
SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU200 EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
07/24/15
STUDENT HEALTH AND
ACADEMIC RENOVATION
LC
01
STAIR A
B
A1
6
R3
A1
6
b
a
c
B1
6
A1
6
P1
HEALTH ED &
PROMOTION
COORD
LC
01
c
A1
6
A1
6
b
a
PC
LCP-11/28
P2
RECOVERY
C4
E-B1/ 4
C4
7
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
B.2
D D1
E1
E-B1/ 6
PC
COMMUNITY
RESOURCE
AREA
A1
6
LCP-11/29
P2
SOUTH ENTRY
E-B1/ 8
c
A1
6
134
b
A1
6
144"
LCP-B1/8
W2
O-B1A/ 21
Project No.
A
a
LC
04
LCP-B1/14
72"
W1
E-B1/ 10
4.8 5
CL
5.55.6
66.2
6.7 7
LCP-B1/14
72"
W1
E-B1/ 10
8
MMK
Checked By
CVS1
Date
109
LCP-B1/14
72" W1
E-B1/ 10
2263.001.00
Drawn By
JL
2/19/16
NORTH ENTRY
4.5
50358
H1
E-B1/ 7
LCP-11/8
D1
7
LCP-11/8LCP-11/8LCP-11/8
D1
D1
D1
7
7
7
COS1
LCP-11/29
P2 PC
E-B1/ 8
4.2
James A. LeClaire
S102
R
D D1 CVS1
C
B.8
E1
E-B1/ 6
C3
7
LCP-11/9
LCP-11/9
LC
01
F1
3
LCP-B1/8
W2
O-B1A/ 21
144"
COS1
LCP-11/28 LCP-11/9
C3
C5
E-B1/ 4
N-11/ 7
C3
N-11/ 7
F1
3
L6
LCP-11/4
11
LCP-11/5
D1
7
LCP-11/5
D1
7
LCP-11/9
D D1 CVS1
C.3
RADIOLOGY
(COMMUNITY
PARTNER)
119
4
612.677.7100
612.677.7499 fax
www.rsparch.com
D
C.9
LC
06
110
LC
02
F1
3
LCP-11/6
112
RESEARCH
DATA
G.
RSP Architects
Registration Number
118
C1
1
MENS
RESTROOM
INFO/KIOSK
122
E1
E-B1/ 5
CVS1
WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL,
ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER
DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER
PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM
RATING.
108
GRAD ASSIST
R
N-12
F1
3
C2
1
A1
8
CVS1
D D1
R1
A1
8
PC
LCP-11/9
C4
E-B1/ 4
S
A1
6
LC
01
S
127
D1
D
PC
RESEARCH
COORDINATOR
A1
6
S
A1
6
R1
F.
Date
B1
21
S
R
R
A1
6
COS1
LC
04
R1
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE
PLACEMENT IN GYP BOARD AND ACT CEILING.
LCP-11/6
D1
2
CVS1
LCP-11/5
D1
7
S
R1
S
R
LCP-11/7 LCP-11/7 LCP-11/7
D1
D1
D1
7
7
7
E.
Project For
CVS1
S
A1
6
LC
01
R1 D D1
136
A1
8
S
144"
LCP-B1/8
W2
O-B1A/ 21
R
D1
D
INFO/KIOSK
A1
8
R1 D D1
A1
8
F1
3
C4
2
S
128
R
C4
7
S
P1
LCP-11/9
COS1
REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL
REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM.
COS1
S
PC
LCP-11/9
C3
7
S
S
A1
6
LC
02 A1
6
124
F1
3
3
S
A1
6
RESEARCHER
129
E
D.9
CIRCULATION
C1
1
LCP-11/9
C3
N-11/ 7
C3
7
LCP-B1/8
W2
O-B1A/ 21
144"
LC
06
F1
LCP-11/27
ASST.
CVS1
NR-12B
NR-12A
C4
2
P1
2 b
UNISEX TOILET
LCP-11/9
C3
7
F1
3
SHELL SPACE
L6
9
LCP-11/9
COS1
LC
04
P1
2 b
D2
2 c
LCP-11/1
D1
N-11/ 3
COS1
LCP-11/3
a
L5
LCP-11/10
10
LCP-11/5
LCP-11/5
LCP-11/5
D1
D1
D1
7
7
7
LC
COS1
04
LCP-11/12
R
C3
7
D.
1
LCP-11/6
B1
21
C4
2
a
CVS1
132
111
D D5
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
KEY NOTES:
LCP-11/6
R3
LC
02
C5
3
C5
E-B1/ 4
DIRECTORY
COS1
C4 a
2
R
C5
3
R
B1
21
117
LCP-11/26LCP-11/26
EM
D1
E-B1/ 23
COS1
C5
3
COS1
E2
E-B1/ 5
C4
E-B1/ 4
B1
21
UCHOOSE
STUDENT STAFF
WORK
C5
LCP-11/3 LCP-11/3 3
1
C2
2
LCP-11/7
D1
R R1
LC 7
106
LCP-11/7
LCP-11/7
04
CIRCULATION
D1
D1
COS1
D
105
7
7
P1 F3
D1
PC
H1
7
LC E-B1/ 7
STAIR A
04
S101
LC CVS1
RESEARCH
01
R5
LACTATION
ROOM
LCP-11/3 LCP-11/3
C4
3
C4
3
COS1
104
E1
E-B1/ 5
L5
10
LCP-11/10
C4
3
C1
2
D1
2
103
S
f
CVS1
A1
5
C1
2
WOMENS
RESTROOM
D1
E-B1/ 23
STORAGE
S
A1
5
C5
3
C2
2
LC
05
e
LCP-11/3 LCP-11/3 LCP-11/3
A4
5
A1
5
d
A1
5
C5
3
COS1
C4
3
S
A1
5
LCP-11/26 LCP-11/3 LCP-11/3
123
CVS1
d
PC
d
SHHS
INTERDISCIPLINARY
A1
5
e
R
d
LC
02
A1
5
A1
5
C4
E-B1/ 4
B1
E-B1/ 4
e
L5
10
LCP-11/10
LC
04
S
e
A1
5
S
A1
5
C4
3
LCP-11/3 LCP-11/3
C4
3
D
D5
R4
A1
5
LCP-11/3
LCP-11/2
D1
3
S
b
OS
LCP-11/26LCP-11/26
C4
C5
E-B1/ 4
E-B1/ 4
133
102
C.
F
3
LCP-11/27
P1
f
P1
P1 P1
P1
P1 2 e 2 e 2 e 2 e
2
CVS1
C4 a
a
2
PEER ED/
VENDING
STORAGE
c
A1
1
LC
05
A1
1
PC
C5
2
S
c
LC
06
F1
4
VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING
HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES.
S
A1
1
L5
3
COS1
LCP-11/11
LCP-11/2
D1
3
S
b
A1
1
A1
1
116
A1
1
LC
06
114
C5
3
f
S
HEALTH ED
INTERDISCIPLINARY
LC
09
A1
1
F1
NR-11B 4
131
C4
3
E1
E-B1/ 6
LCP-11/6
S
c
SERVICE
ELEVATOR
S
c
S
b
A1
1
DATA
LCP-11/3 LCP-11/3
S
A1
1
F1
4
NR-11A
LCP-11
P2
LCP-11/2
D1
3
F1
4
P1
A1
1
PC
LCP-11/1
E1
LCP-11/30
PC
E-B1/ 5
P1
P2
E-B1/ 11
S
N-11
PC
B1
E-B1/ 4
130
a
COS1
CVS1
C5
2
135
S
D5 D
a
ELECTRICAL
VESTIBULE
S
a
A1
1
B1
COS1 3
LCP-B1/24
144" W2
E-B1/ 27
E1
COS1
E-B1/ 6
144" LCP-B1/24
W2
E-B1/ 27
S
A1
1
LCP-11/2
D1
3
LCP-11/25
144" LCP-B1/24
W2
E1
E-B1/ 27
E-B1/ 5
S
S
A1
1
B1
3
LCP-11/1
144" LCP-B1/24
W2
L5 E-B1/ 27
LCP-11/10
10
S
E1
E-B1/ 5
E1
E-B1/ 5
R5
H1
E-B1/ 21
S
R
113
B.
Dunham Job #: 415134
S
CVS1
H1
E-B1/ 21
S
S100
CIRCULATION
WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES
SHALL ALWAYS BE “ON”.
CIRCUIT TO
N-12 UNO
S
STAIR D
CIRCUIT TO
N-11 UNO
S
UP
LCP-B1/8
W2
144"
O-B1A/ 21
LCP-B1/8
W2 144"
O-B1A/ 21
S
144" LCP-B1/8
W2
O-B1A/ 21
A.
AA
CIRCUIT TO
N-12 UNO
CIRCUIT TO
N-11 UNO
9
10
11
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
FIRST LEVEL LIGHTING PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
FIRST LEVEL LIGHTING
PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:01:32 PM
E101
GENERAL LIGHTING NOTES:
A.
WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES
SHALL ALWAYS BE “ON”.
B.
VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING
HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES.
C.
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
D.
REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL
REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM.
E.
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE
PLACEMENT IN GYP BOARD AND ACT CEILING.
F.
WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL,
ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER
DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER
PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM
RATING.
G.
PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH
BOXES.
H.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
I.
VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT
FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION.
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
H1
E-21/ 31
CIRCUIT TO
N-21 UNO
S200
O-21A
R3
WOMENS
RESTROOM
A1
2
A1
2
A1
2
L2
COS1
E-21/ 16
D1
E-21/ 32
D1
12
U2
5
WAITING
CIRCULATION
COS1
C1
12
CVS1
U2
5
LC
02
260
A1
2
LCP-21/14
CVS1
L1
E-21/ 16
L1
E-21/ 16
E2
E-21/ 1
LCP-21/14
D3
6
LCP-11/5
B1
6
P1 PC
A2
6
R
A2
6
PHARMACY
A2
6
A2
6
A2
6
A2
6
CVS1
CVS1
R1
A1
9
D
D1
S
A2
6
LC
01
242
R2
A2
6
PC
A2
6
R
R1
R
A1
9
PC
A1
9
LCP-21/6
HALLWAY
266
A2
O-21A/ 5
256
A2
O-21A/ 5
B1
O-21A/ 6
R
R1
D
D1
PC
CVS1
A1
9
P1
R
PC
LCP-21/15
R1
D1
D
A1
O-21A/ 6
P1
P1
LCP-21/6
A1
9
CIRCUIT TO
N-22 UNO
CASHIER
STUDENT
INSURANCE
ADVOCATE
REFERRAL
COORDINATOR
OFFICE
SUB
WAITING
244
245
247
248
249
LC
01
LC
01
LC
01
LC
01
B1
O-21A/ 6
R
LCP-21/6
S
1
2
3
A2
O-21A/ 5
4
4.2
4.5
4.8 5
OS
CL
5.55.6
LC
04
COS1 B1
E-21/ 3
230
P1
R
R1
R
R1
227
A1
7
PC
R1
LC
02
Project For
LC
02
A1
7
270
A1
7
PC
NP OFFICE
P1
C.3
NURSING
MANAGER
228
CVS1
A1
7
REF.
N-22
A1
7
LC
02
C
B.8
CLEAN SUPPLY
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
234
B.2
B
CVS1
R2
A2
O-21A/ 3
A2
O-21A/ 3
D D1
R
CVS1
A2
O-21A/ 3
A2
O-21A/ 3
LABORATORY
A2
O-21A/ 3
LC
01
A2
O-21A/ 3
251
A2
O-21A/ 3
PC
P1
A2
O-21A/ 3
A2
O-21A/ 3
Project No.
A
CVS1
LAB TOILET PHLEBOTOMY
6.7 7
STUDENT HEALTH AND
ACADEMIC RENOVATION
LC
02
2263.001.00
Drawn By
MMK
Checked By
250
LC
07
66.2
07/24/15
H1
E-21/ 8
S202
LC
01
268
50358
D
C.9
A1
7
P1 PC
D1
D
B1
O-21A/ 6
LCP-21/15
NR-22A
OS
LC
NR-22B
05
LC
04
MED/ NOURISH
ROOM
D
D5
JL
Date
A2
O-21A/ 3
0
CVS1
James A. LeClaire
R1
A1
7
CVS1
Signature
Date
MD OFFICE
NP OFFICE
D1
D
D D1
A2
O-21A/ 3
BUSINESS
MANAGER
R
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Registration Number
PC
R1
LCP-21/6
A2
O-21A/ 5
A1
7
P1
LCP-21/15
255
A2
O-21A/ 5
H1
E-21/ 8
PC
C2
O-21A/ 3
A1
7
224
STAFF TOILET
LC
05
E
D.9
CVS1
R
LC
02
A1
7
CVS1
D1
D
E2
D1
E-21/
2
E-21/ 10
C1
E-21/ 10
223
C1
E-21/ 11
COS1
OS
D1
O-21A/ 3
R1
A1
7
P1PC
EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL
OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE
CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS
INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO
SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU200 EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL.
STAIR B
LC
07
OS
D1
C1
E-21/ 11
E-21/ 11
LCP-21/6
LC
05
B1
O-21A/ 6
LC
04
LC
02
A1
7
R
OS
PROCESS ROOM
A2
O-21A/ 5
E1
B1
E-21/ 2
O-21A/ 6
B1
E-21/ 3
B1
A1
O-21A/ 6
E-21/ 3
CVS1
LCP-21/6
B1
E-21/ 3
LCP-21/6
A1
9
A1
9
LCP-21/6
PATIENT TOILET
267
271
LC
07
A2
O-21A/ 5
O-21A /9
A2
O-21A/ 5 J
B1
O-21A/ 1
B1
OS
O-21A/ 1
3
CVS2
R2
CVS1
A1
9
D
D1
P1
LC
04
STORAGE
A1
9
D3 NURSE STATION
O-21A/ 1
231
E2
E-21/ 2
LCP-21/15
B1
O-21A/ 6
B1
O-21A/ 1
D3
O-21A/ 1
EXAM ROOM
225
B1
232
O-21A/ 1
BP
5
A2
6
CIRCUIT TO
N-21 UNO
A2
6
CVS1
P1
241
A2
6
CVS1
A1
9
CVS2
S
D1
A2
6
A1
9
B1
6
A1
9
PRESCRIPTION
PICK-UP/DROP-OFF
D
R
LCP-11/5
S
S
CVS1
LCP-11/5
COS1
B1
6
LCP-21/6
LC
04
269
LC
02
TREATMENT
ROOM
EXAM ROOM
B1
O-21A/ 6
COS1
D D1
3
D3
O-21A/ 1
A2
O-21A/ 4
LC
04
LCP-21/6
R
U2
3
229
R
D D1
LC
03
246
S
LC
01
P1 PC
R1
D1
D
S
A1
6
S
239
R
A1
6
243
R1
D D1
COS1
B1
O-21A/ 6
A2
O-21A/ 4
R1
D1 D
B1
O-21A/ 6
D3
O-21A/ 1
LCP-21/6
F2
15
LC
03
RECEPTION
240
U2
5
CVS1
D3
6
WORK
OTC SALES
CONSULTATION
AREA
D3
6
U2
5
EXAM ROOM
S
H1
E-21/ 8
S
H1
E-21/ 8
COS1
LCP-21/14
COS1
S
S201
A2
O-21A/ 4
LCP-21/15
COS1
B1
E-21/ 3
226
S
STAIR A
R
EXAM ROOM
CVS1
238
LC
02
D3
O-21A/ 1
B1
O-21A/ 6
LC
02
A2
O-21A/ 4
R1
D1 D
A2
O-21A/ 4
LC
04
CVS1
R
D1 D
E1
E-21/ 1
U2
5
LC
02
A2
O-21A/ 4
PASS ELEVATOR
207
LC
04
LC
U2 02
5
CVS1 S
203
C1
12
A1
2
LC
02
265
R3
CVS1
S
R
A2
O-21A/ 4
HALLWAY
INJECTION
ROOM
S
S
P1
219
D1 D
R1
LC
A2 02
O-21A/ 4
R
R1
R
S
S
205
R1
A2
O-21A/ 4
D1 D
A2
O-21A/ 4
S
CONFERENCE
PC
D1 D
R
EXAM ROOM
C1
12
A2
O-21A/ 4
D1
A2
R1 D
O-21A/ 7
R
CVS1
A2
O-21A/ 7
LC R
R1
02
A2
D D1 O-21A/ 7
REF.
A2
O-21A/ 4
S
LC
01
D1
D R R1 A2
O-21A/ 7
LCP-21/6
217
U2
3
A2
O-21A/ 7
OBSERVATION
(IVS) - EKG
EXAM ROOM
U2
3
B1
O-21A/ 6
HALLWAY
D1
D
259
1
S
LCP-21/14
D1
D
EXAM ROOM
S
EM
D1
E-21/ 32
LC
07
R
D1
D
A2
O-21A/ 2
CVS1
LC
02
A2
O-21A/ 7
LC
02
LCP-21/6
233A
D1
216
A2
A2
A2 D
HALLWAY
O-21A/ 2
O-21A/ 2
O-21A/ 2
258
LCP-21/15
LCP-21/15
LCP-21/6
EXAM
ROOM
EXAM ROOM LC
COS1
221
220
B1
B1
B1
04
HALLWAY
E2
E-21/
3
E-21/ 3
O-21A/ 6
264
E-21/ 2
S
1
A1
2
A2
O-21A/ 2
U2
3
CVS1
CVS1
222
MD OFFICE
CVS1
U2
3
MEDICAL
DIRECTOR
OFFICE
P1
R1
R
S
A2
O-21A/ 2
S
A1
2
R1 U2
4
U2
3
CVS1
S
LCP-21/1
R
S
B1
8
R1
LCP-21/6
A2
O-21A/ 7
S
B1 COS1
E-21/ 4
LCP-21/13
HALLWAY
R1 U2
4
LC
02
R
CVS1
EXAM ROOM
E2
E-21/ 1
R
U2
4
LC
02
S
C1
12
R1
PC
COS1
A2
O-21A/ 7
S
S
A1
2
LC
02
LC
02
R
KEY NOTES:
REF.
A1
7
D D1
S
C1
12
C2
12
A1
2
R1
U2
4
LC
02
CVS1
L1
E-21/ 16
D1 D
CVS1
R
218
B1
8
261
LC
02
R1 D
D1
S
S
COS1
LC
04
B1
8
LCP-21/1
COS1
LC
07
201
LCP-21/1
S
S
A1
2
B1
8
LCP-21/1
S
S
P1
LC
01
MENS
RESTROOM
R1
S
C2
12
R
R
LC
02
A2
O-21A/ 7
LC
02
B1
O-21A/ 6
LC
04
B1
O-21A/ 6
R
S
D1
OS
12
COS1
1 R EM
A1
D1
10 E-21/ 32 OS
LC
07
OS
1
S
CUSTODIAN
U2
4
U2
4
C2
12
EM
D1
E-21/ 32
S
PC
210
F1
10
CVS1
214
S
202
B1
8
R1
A1 D1
2 D
UNISEX
RESTROOM
CVS1
S
LC
05
LCP-21/1
CVS1
LC R
02
R1
A2
O-21A/ 7
A2
O-21A/ 7
LCP-21/6
D
D1
CVS1
S
A1
10
EXAM ROOM
COS1
A2
O-21A/ 2
S
COS1
R
SHS ASST
DIRECTOR
E-21
212
A1
2
CVS1
254
R1 D
R
D1
S
209
DATA
A2
O-21A/ 7
236
S
211
206
237
E2
E-21/ 2
215
A2
O-21A/ 2
A2
O-21A/ 2
257
LCP-21/15
B1 CONSULT ROOM
(CAPS)
O-21A/ 6
B1
235
E-21/ 3
S
262
F1
10
P1
213
SERVICE
ELEVATOR
F1
10
TRIAGE ROOM
S
HALLWAY
P1
F1
10
O-21B
LARGE CENTRAL
SUPPLY
PC
A2
O-21A/ 2
A2
D1 D
O-21A/ 2 ISOLATION
EXAM
HALLWAY
LCP-21/6
CONSULT ROOM
(E-EXAM)
B1
O-21A/ 6
S
R1
A1 D1
2 D
NR-21A
LCP-21 LC
NR-21B F1
10
06
LC
05
LCP-21/13
A3
B1
10
E-21/ 4
PC
SHS DIRECTORS
A3
10
LCP-21/14
F1
10
N-21
B1
O-21A/ 6
A2
D1 D O-21A/ 2
D1 D
EXAM ROOM
LCP-21/6
S
LC
04
R
LC
01
OS
COS1
B1
E-21/ 3
S
B1
8
R1
R
253
COS1
B1
LCP-21/15
E-21/ 3
LCP-21/6
LC
PC
P1 04
S
A1
2
LC
06
B1
8
LCP-21/1
LCP-21/15
S
D1
D
208
ELECTRICAL
E1
E-21/ 1
L1
E-21/ 16
S
P1
B1
8
S
PC
252
263
S
A1
2
LC
01
UCHOOSE
ADMINISTRATOR
E1
E-21/ 1
LCP-21/1
LC
LCP-21/13
04
B1
COS1
E-21/ 4
HALLWAY
LCP-21/1
SOILED HOLD
Dunham Job #: 415134
F
E2
E-21/ 1
S
S
CVS1
CIRCUIT TO
N-22 UNO
S
STAIR D
S
H1
E-21/ 31
S
UP
UP
8
A2
O-21A/ 3
A2
O-21A/ 3
9
AA
A2
O-21A/ 3
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
SECOND LEVEL LIGHTING PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
SECOND LEVEL
LIGHTING PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:01:48 PM
E102
GENERAL LIGHTING NOTES:
STAIR D
CIRCUIT TO
N-31 UNO
S300
CVS1 D D1
A1 A1 R R1
5 5
LC
02
S
STORAGE
302
H1
E-21/ 8
L3
E-21/ 17
L3
COS1 E-21/ 17
E2
E-21/ 7
F2
5
A1
4
D1
11
LC
01
CVS1
422
P1
11
CVS1
419
B1
11
A1
11
D1
11
?
A1
4
FILE & ARCHIVE
321
385
LC
01
A1
9
A1
E-21/ 5
A1
4
A1
4
D
D5
CONFERENCE
/GROUP ROOM
LCP-31/4
AOD
COUNSELOR
PC
R
A1
2
374
COS1
LC
01
NR-32A
NR-32B
A1
7
C.3
P1
LCP-31/15
B1
E-21/ 5
A1
4
G.
PROVIDE NEUTRAL CONDUCTOR DOWN TO ALL LINE VOLTAGE SWITCH
BOXES.
Consultants
H.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
I.
VERIFY MOUNTING HEIGHTS OF ALL DECORATIVE AND SUSPENDED LIGHT
FIXTURES WITH ARCHITECT PRIOR TO INSTALLATION.
R
612.677.7100
612.677.7499 fax
www.rsparch.com
5.55.6
66.2
6.7 7
KEY NOTES:
EMERGENCY SHUNT RELAY SHALL BE WIRED IN PARALLEL WITH MANUAL
OR AUTOMATIC DIMMING CONTROLS. LOCATE ABOVE ACCESSIBLE
CEILING SPACE AN CONNECT TO NORMAL AND EMERGENCY CIRCUITS
INDICATED IN ROOM. RELAY TO ALLOW EMERGENCY FIXTURE(S) TO
SWITCH/DIM WITH NORMAL FIXTURES IN SPACE, WATTSTOPPER #ELCU200 EMERGENCY LIGHTING CONTROL UNIT OR APPROVED EQUAL.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
THERAPIST
OFFICE
CVS1
50358
07/24/15
STUDENT HEALTH AND
ACADEMIC RENOVATION
C
R1
375
B.8
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
B
CVS1
LCP-31/4
B1
11
LC
04
B1
11
CVS1
A1
4
388
D
D1
P1
PC
A1
4
R
R1
D D1
R1
A1
4
A1
4
P1
A1
4
A
PC
CL
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
A1
2
LC
01
CASE MANAGER
OFFICE
R1
D1 D
CIRCUIT TO
N-32 UNO
4.8 5
RSP Architects
PC
A1
2
B1
E-21/ 5
376
387
R
S
4.5
WHERE LIGHTING CONTROL DEVICES (OCCUPANCY SENSOR, PHOTOCELL,
ETC) ARE SHOWN ON PLANS, LOCATE DEVICES IN EACH SPACE PER
DEVICE TYPE AND MANUFACTURER RECOMMENDATIONS. INSTALL POWER
PACK AND/OR RELAYS IN NEMA 1 ENCLOSURE TO ACHIEVE PLENUM
RATING.
D
C.9
CASE MANAGER
INTERN
LC
02
LC
01
-1
4.2
F.
H1
E-21/ 8
V SN
4
REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR FIXTURE
PLACEMENT IN GYP BOARD AND ACT CEILING.
LC
01
LC
04
N-1
VS
3
E.
B.2
N-1
VS
2
REFER TO LIGHTING CONTROL SCHEDULES FOR ADDITONAL
REQUIREMENTS FOR THE LIGHTING CONTROL SYSTEM.
Project For
CAPS DIRECTOR
OFFICE
8
389
9
Project No.
2263.001.00
Drawn By
MMK
Checked By
JL
Date
AA
1
D.
P1
R1
CVS1
0
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
Date
COS1
R
CIRCUIT TO
N-31 UNO
B1
2
B1
2
CVS1
LC
A1
04
2
P1PC
D1
R R1
LCP-31/4
D
B1 THERAPIST
OFFICE
11
THERAPIST
OFFICE
H1
E-21/ 8
320
A1
11
R1
D1
D
E1
E-21/ 6
WORK ROOM
359
E
D.9
R1
LC
01
LCP-31/15 D1
D
LC
02
LC
02
A1
7
A1
4
VS
D1
11
A1
7
E2
E-21/ 6
A1
9
ADMIN
SUPPORT/
RECEPTION
R
CVS1
LCP-31/4
B1
11
A1
4
R1
CVS1
LCP-31/4
B1
B1
E-21/ 5
11
LCP-31/15
LC
05
D1
7
A1
7
378
HALLWAY
A1
9
A1
4
A1
4
A1
11
D
D5
LC
04
COS1
A1
4
PRIVATE
WAITING AREA
KITCHEN
P1
11
A1
11
D1 D
A1
11
B1
11
S
A1
11
D1
11
S
A1
11
D1
11
A1
11
D1
11
P1
11
1
E1
E-21/ 6
323
A1
E-21/ 7
STAFF BREAK
ROOM
324
CVS1
B1
4
CAPS ENTRY
D
D1
LC
01
B1
E-21/ 5
R
D
D1
B1
11
A1
5
OS
A1
7
R1
R
360
381
D5
D
COS1 LCP-31/14
LCP-31/14
E1
E-21/ 7
A1
11
F2
5
LC
05
D1
D
LC
04
LCP-31/4
R1
STORAGE/AV
S
S301
A1
11
THERAPIST R
PREDOCTORAL
379
S
STAIR A
D1
5
A1
5
VS
S
H1
E-21/ 8
LC
02
D1
5
B1
11
R
LC
02
361
C1
7
377
D
D1
R
B1
11D1
B1
E-21/ 5
STAFF TOILET
AOD
COUNSELOR
VS
N-1
S
LC
04
A1
5
LC
02
A1
5
D1
5
A1
5
380
COS1
VS
CVS1
LCP-31/4
B1
11
COS1
A1
7
LC
02
A1
2
P1PC
D
COS1
THERAPIST
E2
OFFICE
E-21/ 6
373
LCP-31/15
CVS1
LCP-31/4
S
363
THERAPIST
PREDOCTORAL
CVS1
S
PASS ELEVATOR
C.
Registration Number
A1
3
D D1
LCP-31/4 LC
B1 04
11
CVS1
S
D1
5
E2
E-21/ 6
B1
E-21/ 5
COS1
S
382
A1
2
GROUP
THERAPY ROOM
LCP-31/15
LC
01
372
LCP-31/4
S
RELAXATION
ROOM
VERIFY ALL CEILING TYPES, RECESSED CONDITIONS, AND MOUNTING
HARDWARE REQUIRED PRIOR TO PURCHASING ANY LIGHT FIXTURES.
1
A1
2
THERAPIST
OFFICE
A1
3
R1
CVS1
A1
2
D
D1
S
COS1
R1
A1
3
S
384
C1
4
LC
05
A1
8
397
HALLWAY
S
S
S
SHHS FACULTY
COMMAND
CENTER
C1
4
B1
5
R
303
D1 R R1
D
S
A1
2
LC
02
D1
4
D1
E-21/ 7
CVS1
A1
5
B1
11
S
S
COS1
CVS1
A1
A1
2
LCP-31/13 D R
2
R1
D1
A1
D
B1
2
R1 D1
E-21/ 7
COS1
CVS1
D D1
D D5
D1
R2
D1
5
5
A1
A1
5
5
CVS1
S
396
LCP-31/14
355
LC
02
S
SHHS FACULTY
COMMAND
CENTER
LC
02
R1
A1
5
LC
04
WOMENS
RESTROOM
D1
E-21/ 7
S
LC
07
C1
4
A1
5
E1
E-21/ 6
R
A1
3
S
S
R
C2
4
383
LCP-31/15
A1
3
LC
02
R1
B1
E-21/ 5
LCP-31/4
A1
3
R
S
340
LCP-31/4
B1
LC
11
04
B1
E-21/ 5
RELAXATION
ROOM
D1 D
A1
3
LC
02
B1
11
A1
1
R
370
S
LCP-31/1
E1
E-21/ 6
COS1
352
E2
E-21/ 7
R1
CVS1
398
S
S
R
B2
6
D1 D
R
LCP-31/15
OPEN STUDY
S
LC
01
C1
4
B2
COS1
E-21/ 7
A1
2
CVS1
A1
1
367
A1
3
CAPS INTERN
OFFICE
LC
01
A1
2
B1
D
R R1
E-21/ 5
THERAPIST
D1
OFFICE PC
LCP-31/15 371 P1
COS1
S
394
A1
1
CVS1
D1 D R R1
L4
E-21/ 17
A1
B1 2
6 D
D1
LCP-31/1
368
A1
3
PRACTICUM
INTERN OFFICE
COS1
LCP-31/4
PRACTICUM
THERAPY
LC
02
A1
3
A1
3
LC
04
A1
1
CVS1
CVS1
S
SHHS CLINICAL
P1 ROOM
A1
2
S
A1
2
CVS1
LCP-31/14
HALLWAY
D1
D
369
COS1
PRACTICUM
THERAPY
LC
02
S
A1
2
P1 PC
C1
4
LCP-31/13
B1
E-21/ 7
COS1
PRACTICUM
THERAPY
B1
11
A1
1
LC
02
A1
1
S
R1
393
PC
LC
04
D1
E-21/ 7
A1
1
R1
366
A1
1
S
SHHS CLINICAL
R
ROOM
301
L4
E-21/ 17
COS1
LC
07
B1
6
D1
E-21/ 7
LCP-31/1
LCP-31/13
B1
6
E1
E-21/ 7
B1
2
LC
01
LCP-31/1
OS
UNISEX
RESTROOM
365
D D1
A1
3
R
COS1
N-32
S
B1
2
S
D
D1
R1
R
S
LC
01
CVS1
R1
D1
D
A1
1 PRACTICUM LC
THERAPY
02
B1
11
COS1
LC
04
S
S
392
R
354
D1
E-21/ 7
S
PC
B1
2
MENS
RESTROOM
LC
07
A1
10
395
R
A1
1
S
B1
2 P1
SHHS GROUP
THERAPY ROOM
A1
COS1
10
F2
10
C1
4
D1 D
R
CVS1
R1
A1
1 PRACTICUM LC
THERAPY
LCP-31/4
02
R1
C2
4
341
LC
02
D1 D
CVS1
B2
E-21/ 5
S
A1
10
R
COS1
S
CVS1
F1
12
CLOSET
A1
10
L7
13
399
R1
CVS1
A1 PRACTICUM
1 THERAPY LC
02
364
362
DATA ROOM
D1 D
356
B1
11
LCP-31/4
S
F1
12
A1
2 LCP-31/1
B1
6
CVS1
SHHS CLINICAL
ROOM
LC
06
LCP-21
NR-31A
F1
12
NR-31B
B1
E-21/ 5
LCP-31/15
CIRCULATION
S
LC
05
LCP-31/14
SERVICE
ELEVATOR
F1
12
E1
E-21/ 6
S
A1
2
F1
12
L3
E-21/ 17
COS1
S
PC
R1
D1
D
LC
06 F1
12
N-31
LCP-31/4
LC
04
S
P1
R
B1
E-21/ 7
LC
04
COS1
LCP-31/15
COS1
B1
LCP-31/4
11
S
391
LC
01
S
SHHS CLINICAL
ROOM
LCP-31/13
B1
6
E2
E-21/ 7
300
D
R1
R
B1 LCP-31/1
6
B1
E-21/ 7
ELECTRICAL
ROOM
S
S
D1
PC
353
E1
E-21/ 7
LCP-31/1
LC
04
S
LC
01
LCP-31/13
B1
LCP-31/1
6
COS1
CUSTODIAN
S
A1
2
P1
E1
E-21/ 7
F
S
CVS1
A1
2
390
B.
Dunham Job #: 415134
S
SHHS CLINICAL
ROOM
H1
E-21/ 31
WIRE EXIT LIGHT FIXTURES WITH A CONTINUOUS HOT CIRCUIT; FIXTURES
SHALL ALWAYS BE “ON”.
CIRCUIT TO
N-32 UNO
S
DN
H1
E-21/ 31
A.
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
THIRD LEVEL LIGHTING PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
THIRD LEVEL
LIGHTING PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:02:04 PM
E103
GENERAL POWER NOTES:
A.
VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH
ARCHITECTURAL ELEVATIONS.
B.
ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR
UNLESS NOTED OTHERWISE.
C.
MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE
COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6”
ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL
ELEVATIONS FOR COUNTER HEIGHTS.
D.
REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL
CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT.
E.
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
F.
REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION
RELATED TO ELECTRICAL SYSTEMS.
G.
COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES
SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE
SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING
STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING.
H.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
I.
PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS
REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO
LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET.
J.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
RSP Architects
1
UP
STAIR D
CIRCUIT TO
NR-B1A UNO
S001
CIRCUIT TO
NR-B2 UNO
F
1
TO EXTERIOR
ENCLOSED
CIRCUIT BREAKER
ENCLOSURE
16
15
17
4
18
12
CORRIDOR
PROPOSED
CONDUIT ROUTE (6)
3-1/2"C, 4#400KCMIL
+ #250 GND
(2 ROWS OF 3)
2
009
E2
13
60"
3
13
AHUR
03
AHUS
03
3
E
D.9
O-B1A /17
13
11
J
19
AC
5
20
10
12
WAITING
007
8
60" 12 19
AC
003
EXAM/ CONSULT
056
10
8
N-B1 /26,28
J
8
8
SHOWER
RESTROOM
14
RD-B1 /15
11
12
12
J J
J
13
RD-B1 /13
RD-B1 /17
PASS./SERV.
ELEV. EQUIP.
ROOM
11
6
J
TF
01
3
36"
1 2
3
AC
N-B1 /19,21
J
013
032
8
8
J
7
SHOWER/
RESTROOM
CUSTODIAN
014
018
M001
6
PULLBOX
2
21
O-B1B /1
G
ATS-E
22
24
ATS-R
ATS-O
LCP-B1
O-B1B
O-B1A
B.8
STAIR B
B.2
NR-B1A /4
5
B
SCP
01
1
BUILDING
SUPPORT
DATA ROOM
021
O-B1B /9 O-B1A /5 J
NR-B1A
5
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
9
HWP
01
UH
001
O-B1B /5
GFS
01
23
O-B1B /11
HWP
02
Registration Number
Date
07/24/15
Project For
9
120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING
HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER.
10
WIREWAY OF ENCLOSED CIRCUIT BREAKERS FOR GENERATOR
DISTRIBUTION AND SYSTEM SEPARATION TO TRANSFER SWITCHES,
REFER TO RISER DIAGRAM FOR ADDITIONAL INFORMATION.
11
120V, 30A LOCKABLE FUSED DISCONNECT FOR ELEVATOR CAB
EQUIPMENT. CIRCUIT SHALL BE FUSED AT 15A.
12
120V POWER CONNECTION FOR ELEVATOR CONTROLLER. COORDINATE
FINAL LOCATION IN FIELD.
13
BUSSMAN POWER MODULE SWITCH ELEVATOR DISCONNECT RATED AT
100A. FUSE PER ELEVATOR MANUFACTURER RECOMMENDATIONS.1-1/4"C,
3#3 & 1#6G.
14
120V POWER FOR SHUNT TRIP POWER ON PANEL.
15
BUSSMAN POWER MODULE SWITCH ELEVATOR DISCONNECT RATED AT
200A. FUSE PER ELEVATOR MANUFACTURER RECOMMENDATIONS.1-1/2"C,
3#1/0 & 1#6G.
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
MECHANICAL
ROOM
1
DWP
01
CIRCUIT TO
NR-B2 UNO
UH
002
Project No.
A
Drawn By
MMK
JL
1
Date
AA
2
2263.001.00
Checked By
1
1
50358
SWH
01
019
CIRCUIT TO
NR-B1A UNO
0
James A. LeClaire
5
033
O-B1B /3
RD-B1
NR-B1B
INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL CONTRACTOR)
AT SHOWN LOCATION, 208V CONNECTION TO HAND DRYER. REFER TO
ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHT. REFER TO
PANELBOARD SCHEDULE FOR ADDITIONAL INFORMATION REGARDING
CIRCUIT BREAKER SIZE AND TYPE.
NR-B1A /4
O-B1B /13
O-B1B /7
6
8
S002
25
NRD-B1
N-B1
5
O-B1A /9 J
3
2
C
O-B1B /15
10
6
ND-B1
2
E-B1 /14
E-B1
120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS
(TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/
WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS.
PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING
FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22. TRANSFORMERS
LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH DIV. 22
CONTRACTOR.
C.3
3
022
G
MECHANICAL
ROOM
7
AHUR
01
J N-B1 /22,24
AC 7
ELECTRICAL
ROOM 6
ELECTRICAL CONNECTION TO EMS PANEL. VERIFY LOCATION IN THE
FIELD.
ELECTRICAL CONNECTION TO SMOKE GUARD.
UH
003
4
6
AHUS
01
2
001
MSB
120V CONNECTION FOR LIGHTS AND RECEPTACLES PROVIDED WITH AIR
HANDLING UNIT. PROVIDE CONDUIT AND WIRING BETWEEN DEVICES.
COORDINATE LOCATIONS WITH MANUFACTURES EQUIPMENT.
6
D
C.9
4
8
016
CORRIDOR
3
RECEPTACLE FOR ELECTRIC WATER COOLER. PROVIDE GFCI BREAKER
AT INDICATED CIRCUIT. COORDINATE RECEPTACLE MOUNTING HEIGHT
WITH EQUIPMENT ACCESS IN THE FIELD.
3
AC
7
8
AHUR
02
2
MECHANICAL
ROOM
UNISEX
TOILET/SHOWER
E1
GENERATOR
ANNUNCIATOR
PANEL
3
5
J N-B2 /6
N-B1 /23,25
AC
8
E-B1 /13
PASSENGER
ELEVATOR
004
J N-B2 /8
AHUS
02
SHOWER/
RESTROOM
J
J
J RD-B1 /1,3,5
J RD-B1 /9
J RD-B1 /11
14
8 J AC
9
N-B1
/14,16
10
9
J RD-B1 /7
050
WOMANS
LOCKER ROOM
J O-B1A /3
051
AC
GFI PIT RECEPTACLE. CONNECT TO PIT LIGHTING CIRCUIT. VERIFY
LOCATION WITH ELEVATOR CONTRACTOR.
4
035
AC
7
SHOWER/
RESTROOM
055
7
2
J O-B1A /3
MENS LOCKER
ROOM
005
LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD.
4
8
7
1
052
CORRIDOR
15
3
AC
20
008
RD-B1 /2,4,6
13
MECHANICAL
ROOM
9
8 J
N-B1 /15,17
RESISTANCE
TRAINING
20
010
19
J N-B1 /18,20
006
AC
19 20
011
SHOWER/
RESTROOM
SUMP ROOM
EXAM/ CONSULT
N-B2
12
SHOWER/
RESTROOM
NR-B2
SP
01
COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH
ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
KEY NOTES:
EXERCISE/TRAINING
11
Dunham Job #: 415134
13
SERVICE
ELEVATOR
2
Consultants
J N-B2 /10
03A
36"
612.677.7100
612.677.7499 fax
www.rsparch.com
054
6
J E-B1 /15
14
STORAGE
12
K.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
LOWER LEVEL POWER PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
LOWER LEVEL POWER
PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:02:25 PM
E200
GENERAL POWER NOTES:
UP
CUH
103
MAIN
CIRCUIT
BREAKER
ENCLOSURE
A.
VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH
ARCHITECTURAL ELEVATIONS.
B.
ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR
UNLESS NOTED OTHERWISE.
C.
MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE
COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6”
ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL
ELEVATIONS FOR COUNTER HEIGHTS.
D.
REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL
CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT.
E.
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
RSP Architects
F.
REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION
RELATED TO ELECTRICAL SYSTEMS.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
G.
COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES
SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE
SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING
STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING.
H.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
I.
PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS
REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO
LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET.
J.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
CIRCUIT TO
NR-12A UNO
DN
F
K.
REFRIG
1
XFMR
12
CIRCULATION
113
10
4
2
18
AC
MICRO
CUH
104
FCU
102
7
19
19
ELECTRICAL
130
7
6
3
DATA
SERVICE
ELEVATOR
131
114
J
5
7
6
3
3
102
FSD
1
124
13
12
13
VENDING
13
133
PEER ED/
UCHOOSE
STUDENT STAFF
WORK
6
3
60"
14
N-12 /4
J
N-12 /4 J
1
1
LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD.
2
120V CONNECTION TO AUTOMATIC DOOR OPENER. VERIFY LOCATIONS
AND MOUNTING HEIGHT WITH ARCHITECTURAL PLANS.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
3
MOUNT DEVICES HORIZONTALLY UNDERNEATH PERIMETER FIN TUBE
RADIATION.
Signature
4
120V CONNECTION TO ELECTRIC FIREPLACE.
5
120V CONNECTION TO ALL SHOWN FIRE/SMOKE DAMPERS IN THIS AREA.
CIRCUIT ALL FIRE/SMOKE DAMPERS ON THIS PLAN TO THE INDICATED
CIRCUIT. COORDINATE WITH MECHANICAL CONTRACTOR FOR LOCATIONS.
REFER TO FIRE ALARM DETAILS SHEET FOR ADDITIONAL INFORMATION.
14
117
K
11
E
D.9
5
12
5
GEN
KEY NOTES:
8
2
SHELL SPACE
12
2
N-11 /16 J
STORAGE
1
1
4
N-11 /14
116
FVAV
101
AC
16
16
15 AC
15 AC
16
15 AC
HEALTH ED
INTERDISCIPLINARY
J
8
AC
14 14
14
14
6
120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS
(TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/
WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS.
PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING
FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22.
TRANSFORMERS LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH
DIV. 22 CONTRACTOR.
9
3
6
7
INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL CONTRACTOR)
AT SHOWN LOCATION, 208V CONNECTION TO HAND DRYER. REFER TO
ARCHITECTURAL ELEVATIONS FOR MOUNTING HEIGHT. REFER TO
PANELBOARD SCHEDULE FOR ADDITIONAL INFORMATION REGARDING
CIRCUIT BREAKER SIZE AND TYPE.
6
J O-B1A /1
103
J O-B1A /1
9
11
3
STORAGE
11
AC
104
9
7
3
J N-11 /13,15
8
8
3
108
C.3
AC
4
14
AC
4
2
C
E-B1 /16
PASS
ELEVATOR
8
N-12 /5,7
132
14
J
RADIOLOGY
(COMMUNITY
PARTNER)
107
UNISEX TOILET
J N-11 /17,19
10
1
J
J N-12 /9,11
14
MENS
RESTROOM
N-12 /12,14
J 7
7
8
D
C.9
2
J O-B1A /1
WOMENS
RESTROOM
SHHS
INTERDISCIPLINARY
1
CIRCULATION
118
14
123
1
DIRECTORY
115
2
111
3
B.8
15
LACTATION
ROOM
15
CIRCULATION
106
3
Date
50358
07/24/15
8
STUB THREE (3) 3/4" CONDUITS UP TO ACCESSIBLE CEILING SPACE IN
CORRIDOR FOR FUTURE USE.
9
120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING
HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER.
STUDENT HEALTH AND
ACADEMIC RENOVATION
10 ELECTRICAL CONNECTION TO SMOKE GUARD.
11 POWER FOR MOTORIZED PARTITION. KEYED SWITCHES AND PUSH
BUTTON PROVIDED BY OTHERS. ELECTRICAL CONTRACTOR SHALL
PROVIDE REQUIRED SINGLE GANG BACK BOXES, CONDUIT AND CABLING
BETWEEN CONTROL BOX AND ASSOCIATED KEYED SWITCHES AND PUSH
BUTTON.
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
STAIR A
3
3
S102
STAIR A
S101
9
15
9
21
15
16
17
GRAD ASSIST
136
122
10
INFO/KIOSK
9
20
8
6
7
11
5
RESEARCH
7
6
UCHOOSE & RC
121
18
20
RESEARCH
DIRECTOR
8
N-11 /25
J 2
18
RESEARCH
COORDINATOR
120
7
137
5
UCHOOSE & RC
6
119
134
3
HEALTH ED &
PROMOTION
COORD
11
5
125
N-12 /19
J 2
A
19
127
CUH
101
RESEARCH
DATA
18
126
19
NORTH ENTRY
112
2
19
J
N-11 /26
SOUTH ENTRY
CIRCUIT TO
NR-11A UNO
CIRCUIT TO
NR-12A UNO
109
J
J
N-11 /23
N-12 /17
2
J
2
13
12
12
2
3
4
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
Date
J
N-12 /15
8
MMK
JL
60"
AA
2
J
N-12 /13
4.2
2263.001.00
Checked By
1
N-11 /27
Project No.
Drawn By
CUH
102
1
1
RECOVERY
COMMUNITY
RESOURCE
AREA
11
AC
60"
8
17
B
11
11
10
17
20
3
16
128
AC
20
110
16
129
RESEARCHER
B.2
21
AC
INFO/KIOSK
RESEARCH
ASST.
XFMR
0
Registration Number
12 120V CONNECTION TO FIRE ALARM NAC PANEL.
105
PMH
SWITCH
James A. LeClaire
Project For
N-11 /18,20,22
K
9
3
COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH
ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
19
FSD
6
3
NR-11A /10
WP
FCU
101
J E-B1 /17
17
135
Dunham Job #: 415134
N-12
2
E201
NR-12B
1
3
NR-12A
5
VESTIBULE
FSD
3
Consultants
1
CIRCUIT TO
NR-11A UNO
STAIR D
S100
5
612.677.7100
612.677.7499 fax
www.rsparch.com
9
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
FIRST LEVEL POWER PLAN
1/8" = 1'-0"
Revisions
No.
NR-11A /4
O-B1B /6
G
N-11
9
Description
NR-11A /21
O-B1B /10
J
O-B1A /6
ELECTRICAL
130
NR-11A /24
NR-11A
12
NR-11B
Date
E-B1 /12
J
O-B1B /2
NR-11A /22
O-B1B /8
O-B1B /4
DATA
J
131
E-B1 /9
2
2
FIRST FLOOR ELECTRICAL AND DATA ROOMS
1/4" = 1'-0"
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:02:38 PM
3
FIRST LEVEL POWER
PLAN
E201
GENERAL POWER NOTES:
A.
VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH
ARCHITECTURAL ELEVATIONS.
B.
ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR
UNLESS NOTED OTHERWISE.
C.
MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE
COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6”
ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL
ELEVATIONS FOR COUNTER HEIGHTS.
D.
REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL
CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT.
E.
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
F.
REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION
RELATED TO ELECTRICAL SYSTEMS.
G.
COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES
SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE
SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING
STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING.
H.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
I.
PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS
REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO
LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET.
J.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
RSP Architects
1
UP
UP
STAIR D
S200
CIRCUIT TO
NR-21A UNO
CIRCUIT TO
NR-22A UNO
NR-22B /10
12
27
J
27
E-21 /19
NR-21B /7
3
SOILED HOLD
ELECTRICAL
DATA
252
253
254
206
SHS DIRECTORS
J
N-21 /11,13
212
J
7
LARGE CENTRAL
SUPPLY
3
NR-21B /2,4
5
7
UNISEX
RESTROOM
202
201
N-21 /7,9
8
5
210
EXAM ROOM
EXAM ROOM
218
AC
13
20
48"
16
48"
16
48"
15
4
48"
48"
31
29
WOMENS
RESTROOM
15
3
258
N-21 /15,17 AC
8 J
11
WAITING
CIRCULATION
EXAM ROOM
EXAM ROOM
6
219
AC
O-21B /25
220
O-21B /25
2
AC
31
AC
260
8
48"
12
48"
12
EXAM ROOM
10
221
AC
O-21B /26
6
AC
AC
18
14
J
N-21 /16,18
J
14
12
O-21B /27
O-21B /27
18
39
EXAM ROOM
48"
EXAM ROOM
225
269
48"
226
16
PASS ELEVATOR
EXAM ROOM
20
AC
15
13
31
16
48"
AC
26
O-21B /13
48"
24
48"
20
HALLWAY
NP OFFICE
259
227
27
AC
D
C.9
29
8
31
N-21 /14
J
10
17
STAIR A
13
S201
15
O-21B /23
13 O-21B /2313
N-22 /4,6
31
30
J
AC
O-21B /15
-1
V SN
VSN-1
5
25
1
NR-21B /1
PRESCRIPTION
PICK-UP/DROP-OFF
7
245
BUSINESS
MANAGER
PHARMACY
P
244
23
241
1
3
5
STUDENT
INSURANCE
ADVOCATE
247
J
SUB
WAITING
5
PROCESS ROOM
O-21A /11
30
35
7
NURSING
MANAGER
228
NR-22B
9
N-22
33
33
3REF.
NR-31B /2
3
NR-22B /20
AC
2
NR-22B /2
PHLEBOTOMY
NR-22B /18
250
AC
AC
NR-22B /18 NR-22B /6
NR-22B /18
LABORATORY
251
NR-22B /4
48"
21
21
NR-21B /1
42
1
42
CIRCUIT TO
NR-21A UNO
CIRCUIT TO
NR-22A UNO
1
NR-22B /26 J 5
42
B.8
42
19 2119 21
NR-22B /22
NR-22B /24
NR-22B /22
NR-22B /24
NR-22B /22
NR-22B /24
NR-22B /22
NR-22B /24
NR-22B /22
NR-22B /24
NR-22B /22
A
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
11
120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING
HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER.
12
ELECTRICAL CONNECTION TO SMOKE GUARD.
13
120V CONNECTION TO AUTOMATIC DOOR OPENER. VERIFY LOCATIONS
AND MOUNTING HEIGHT WITH ARCHITECTURAL PLANS.
14
120V CONNECTION TO FIRE ALARM NAC PANEL.
07/24/15
Project For
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
8
9
Project No.
2263.001.00
Drawn By
MMK
Checked By
JL
Date
10
2
ALL RECEPTACLES SHOWN WITHIN DASHED LINE SHALL BE HOSPITAL
GRADE DEVICE, REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
Date
B
AA
1
10
C
19 21
0
STUB THREE (3) 3/4" CONDUITS UP TO ACCESSIBLE CEILING SPACE IN
CORRIDOR FOR FUTURE USE.
50358
3
NR-21B /1
23
9
1
AC
NR-22B /8
J
268
17
INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL
CONTRACTOR) AT SHOWN LOCATION, 208V CONNECTION TO HAND
DRYER. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING
HEIGHT. REFER TO PANELBOARD SCHEDULE FOR ADDITIONAL
INFORMATION REGARDING CIRCUIT BREAKER SIZE AND TYPE.
3
NR-22A
9
B.2
N-22 /11,13 NR-22B /18
7
17
8
C.3
33
S202
NR-22B /8
AC
LAB TOILET
249
120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS
(TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/
WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS.
PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING
FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22.
TRANSFORMERS LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH
DIV. 22 CONTRACTOR.
Registration Number
J O-B1A /19
O-B1A /2
8
248
CASHIER
17
17
REFERRAL
COORDINATOR
OFFICE
3
1
242
7
17
7
STAIR B
60"
11
120V CONNECTION TO ALL SHOWN FIRE/SMOKE DAMPERS IN THIS AREA.
CIRCUIT ALL FIRE/SMOKE DAMPERS ON THIS PLAN TO THE INDICATED
CIRCUIT. COORDINATE WITH MECHANICAL CONTRACTOR FOR
LOCATIONS. REFER TO FIRE ALARM DETAILS SHEET FOR ADDITIONAL
INFORMATION.
James A. LeClaire
Signature
NR-22B /20
NR-22B /2
O-21B /21
3
AC
243
25
O-21B /19
17
17
6
31
AC
40
N-22 /8,10
256
246
19
239
19
9
RECEPTION
240
VSN-1
O-21B /23
J
PATIENT TOILET
267
11
AC
11
AC
120V CONNECTION TO FUME HOOD.
NP OFFICE
O-21B /17
WORK
OTC SALES
CONSULTATION
AREA
40
STORAGE
5
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
40
8
NR-22B /28
19
7
O-B1A /2 J
266
MOUNT DEVICES HORIZONTALLY UNDERNEATH PERIMETER FIN TUBE
RADIATION.
J
37
J
17
4
29
N-21 /1 13
HALLWAY
POWER CONNECTION AND SWITCH FOR LAB TOILET WATER SHUTT OFF.
SWITCH SHALL HAVE AN INDICATOR LIGHT AND BE LABELED AS "LIGHT
ON VALVE ON" AND "LIGHT OFF VALVE OFF"
29
7
AC
229
36
NR-22B /16 AC
36
32 O-21B /10
MED/ NOURISH
38
ROOM
AC
AC
O-21B
/12
230
O-21B /16
28
CLEAN SUPPLY
38
234
O-21B /14
32 AC
AC
32
32
O-21B /13
207
13
231
O-21B /11
NR-22B /14
AC
26
48"
24
3
270
26
NR-32B /5
NR-32B /5
22
AC
RECEPTACLE FOR ELECTRIC WATER COOLER. PROVIDE GFCI BREAKER
AT INDICATED CIRCUIT. COORDINATE RECEPTACLE MOUNTING HEIGHT
WITH EQUIPMENT ACCESS IN THE FIELD.
224
AC
STAFF TOILET
34
232
NURSE STATION
AC
O-21B /31
O-21B /26
TREATMENT
ROOM
O-21B /11
41
2
AC
22
O-21B /15
MD OFFICE
35
48"
255
AC
10
27
48"
35
28
2
27
271
37
AC
26
E
D.9
25
O-B1A /7 J
LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD.
223
25
AC
EXAM ROOM
33
35
265
MD OFFICE
35
1
25
O-21B /29
AC
38
48"
38
NR-21A /40
O-21B /11
10
AC
AC
AC
E-21 /18
3
13
48"
8
AC
29
15
205
HALLWAY
264
AC
33
AC
HALLWAY
29 60"
203
15
238
24
48"
8
48"
4
2
13
AC
38 38
48"
48"
40
48"
NR-21B /5
HALLWAY
35
29
15
40
24
48"
20
48"
J O-B1A /2
13
1
OBSERVATION
(IVS) - EKG
KEY NOTES:
23
235
O-21B /29
36
AC
O-21B /30
233A
216
36
AC
236
INJECTION
ROOM
E-21 /9
6
EXAM ROOM
217
7
CONFERENCE
22
AC
222
CONSULT ROOM
(CAPS)
O-21B /28
30
AC
O-21B /30
MEDICAL
DIRECTOR
OFFICE
23
34
48"
CONSULT ROOM
(E-EXAM)
O-21B /28
26
AC
NR-21B /3 N-22 /2
N-22 /2 J
J
34
30
AC
237
COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH
ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
3
48"
27
261
AC
26
AC
215
18 O-21B /22
AC
HALLWAY
5
TRIAGE ROOM
AC
22
O-21B /24
48"
Dunham Job #: 415134
23
48"
32 32
28
28
48"
EXAM ROOM
O-21B /22
10
AC
AC
18
48"
N-22 /2 J
N-22 /2
O-21B /20
6
AC
O-21B /24
31
J O-B1A /2
7
J O-B1A /2
J
SHS ASST
DIRECTOR
14
AC
10
AC
214
AC
AC
14
31
MENS
RESTROOM
AC
9
31
FSD
8
211
6
O-21B /20
2
AC
9
AC
8
J
EXAM ROOM
213
STAIR C
S203
N-21 /3
N-21 /3 J
CUSTODIAN
209
2
AC
6
262
48"
ISOLATION EXAM
HALLWAY
3
27
48"
12
12
48"
8
8
K.
Consultants
Mini
Fridge
NR-21B /3
REF.
27
FSD
1
SERVICE
ELEVATOR
48"
4
4
48"
J
F
612.677.7100
612.677.7499 fax
www.rsparch.com
3
REF.
Low for microwave
257
NR-21B /3
48"
1
23
HALLWAY
6
N-21 /19
13 J
FSD
3
263
FSD
FVAV
201
1
208
2
E202
FSD
1
AC
HALLWAY
1
FSD
UCHOOSE
ADMINISTRATOR
1
NR-22B /12
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
SECOND LEVEL POWER PLAN
1/8" = 1'-0"
Revisions
No.
NR-21B /7
Date
Description
G
NR-21B /9
N-21
O-21B /3
E-21 /13
J
14
NR-21A
O-21B /5
J
O-21B
O-21A /8
O-21B /1
11
J
E-21
NR-11A /23 O-21B /7
O-21B /9
FSD
O-21A
NR-21B /11
NR-21B /15
253
NR-21B
DATA
254
ELECTRICALE-21 /12
3
SECOND FLOOR ELECTRICAL AND DATA ROOMS
2
1/4" = 1'-0"
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:02:58 PM
SECOND LEVEL
POWER PLAN
E202
GENERAL POWER NOTES:
A.
VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH
ARCHITECTURAL ELEVATIONS.
B.
ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR
UNLESS NOTED OTHERWISE.
C.
MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE
COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6”
ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL
ELEVATIONS FOR COUNTER HEIGHTS.
D.
REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL
CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT.
E.
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
F.
REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION
RELATED TO ELECTRICAL SYSTEMS.
G.
COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES
SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE
SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING
STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING.
H.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
I.
PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS
REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO
LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET.
J.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
1
CUH
303
J
1
1
SHHS CLINICAL
ROOM
1
21
10
J
1
1
CUSTODIAN
300
353
2
362
399
34
4
PRACTICUM
THERAPY
364
3
2
NR-31B /3
21
3
SHHS CLINICAL
ROOM
4
CLOSET
11
391
11
J
SHHS GROUP
THERAPY ROOM
5
11
11
SHHS CLINICAL
ROOM
11
PRACTICUM
THERAPY
369
4
6
12
14
14
AC
USB
8
10
8
PRACTICUM
THERAPY
PRACTICUM
THERAPY
368
367
10
12
20
20
AC
USB
AC
USB
AC
USB
8
26
28
7
34
AC
USB
372
32
NR-31B /7
340
393
396
13
7
NR-32A /12
NR-32A /12
WOMENS
RESTROOM
NR-31B /7
21
9
303
12
GROUP
THERAPY ROOM
14
37
9
J
1
N-31 /20,22
J
10
397
RELAXATION
ROOM
PASS ELEVATOR
382
30
37
30
THERAPIST
OFFICE
15
381
375
376
11
THERAPIST
PREDOCTORAL
8
25
1
C
11
11
J
15
N-31 /24
STAIR A
J N-31 /5
25
S301
15
23
23
ADMIN
SUPPORT/
RECEPTION
23
323
23
25
33
2
385
35
27
AC
CASE MANAGER
INTERN
10
35
AC
31
AC
2
4
388
29
29
2
4
35
4
10
31
33
VS
N-1
N-1
VS
CIRCUIT TO
NR-31A UNO
A
CIRCUIT TO
NR-32A UNO
CAPS DIRECTOR
OFFICE
-1
33
2
389
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
31
2
2263.001.00
Drawn By
Date
AA
9
Project No.
MMK
Checked By
V SN
N-1
VS
23
1
2
120V CONNECTION TO AUTOMATIC DOOR OPENER. VERIFY LOCATIONS
AND MOUNTING HEIGHT WITH ARCHITECTURAL PLANS.
320
2
1
11
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
29
1
0
ELECTRICAL CONNECTION TO SMOKE GUARD.
WORK ROOM
31
2
10
27
27
2
23
120V CONNECTION TO ACCESS CONTROL PANEL, VERIFY MOUNTING
HEIGHT AND LOCATION WITH ACCESS CONTROL SYSTEM INSTALLER.
STUDENT HEALTH AND
ACADEMIC RENOVATION
35
29
31
23
9
Project For
CASE MANAGER
OFFICE
419
AC
ALL RECEPTACLES SHOWN WITHIN DASHED LINE SHALL BE HOSPITAL
GRADE DEVICE, REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
07/24/15
AC
6
422
KITCHEN
33
8
Date
50358
B
27
FILE & ARCHIVE
321
6
PRIVATE
WAITING AREA
4
35
359
STAFF BREAK
ROOM
324
CONFERENCE
/GROUP ROOM
35
STUB THREE (3) 3/4" CONDUITS UP TO ACCESSIBLE CEILING SPACE IN
CORRIDOR FOR FUTURE USE.
Registration Number
B.2
387
AC
7
James A. LeClaire
S302
360
CAPS ENTRY
INSTALL AND WIRE HAND DRYER (PROVIDED BY GENERAL
CONTRACTOR) AT SHOWN LOCATION, 208V CONNECTION TO HAND
DRYER. REFER TO ARCHITECTURAL ELEVATIONS FOR MOUNTING
HEIGHT. REFER TO PANELBOARD SCHEDULE FOR ADDITIONAL
INFORMATION REGARDING CIRCUIT BREAKER SIZE AND TYPE.
Signature
HALLWAY
AC
35
4
23
35
18
4
6
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
STAIR B
10
AC
6
35
35 60" 35
120V CONNECTION TO SINK/FLUSH VALVE TRANSFORMERS
(TRANSFORMERS PROVIDED BY DIV. 22) FOR AUTOMATIC LAVATORY/
WATER CLOSET / URINAL FOR MEN'S AND WOMEN'S RESTROOMS.
PROVIDE 120V WIRING TO EACH TRANSFORMER. LOW VOLTAGE WIRING
FROM TRANSFORMER TO SENSOR PROVIDED BY DIV. 22.
TRANSFORMERS LOCATED IN ACCESSIBLE SPACE, COORDINATE WITH
DIV. 22 CONTRACTOR.
379
8
8
5
15
B.8
11
120V CONNECTION TO ALL SHOWN FIRE/SMOKE DAMPERS IN THIS
AREA. CIRCUIT ALL FIRE/SMOKE DAMPERS ON THIS PLAN TO THE
INDICATED CIRCUIT. COORDINATE WITH MECHANICAL CONTRACTOR FOR
LOCATIONS. REFER TO FIRE ALARM DETAILS SHEET FOR ADDITIONAL
INFORMATION.
C.3
25
378
STORAGE/AV
1
THERAPIST
OFFICE
AOD
COUNSELOR
7
1
12
363
9
7
60" 3
4
23
15 NR-31A /26
11
3
3
120V CONNECTION TO FIRE ALARM NAC PANEL.
THERAPIST
OFFICE
23
15
9
7
1
E-21 /20
STORAGE
302
5
384
SHHS FACULTY
COMMAND
CENTER
14
SHHS CLINICAL
ROOM
N-31 /19,21
AC
6 J
NR-31B /1
3
374
10
HALLWAY
9
J
5
380
6
J
AC
13
377
9
MOUNT DEVICES HORIZONTALLY UNDERNEATH PERIMETER FIN TUBE
RADIATION.
D
C.9
23
N-32 /8,10
O-B1A /4
AOD
COUNSELOR
1
15
355
13
5
6
361
1
383
2
21
5
3
LIGHTNING PROTECTION CONDUIT AND CONDUCTOR DOWNLEAD,
OFFSET FROM ROOF PENETRATION INTO FURRED OUT WALL.
21
21
THERAPIST
PREDOCTORAL
1
373
26
3
RELAXATION
ROOM
SHHS FACULTY
COMMAND
CENTER
HALLWAY
7
19
STAFF TOILET
1
E
D.9
THERAPIST
OFFICE
32
NR-31B /9
NR-31B /9
28
19
THERAPIST
OFFICE
20
20
AC
USB
COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH
ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
KEY NOTES:
USB
16
16
Dunham Job #: 415134
1
19
CAPS INTERN
OFFICE
370
Consultants
371
22
22
32
32
612.677.7100
612.677.7499 fax
www.rsparch.com
THERAPIST
OFFICE
17
AC
USB
24
32
26
J
O-B1A /4 21
1
AC
USB
22
22
7
24
20
20AC
398
AC
USB
OPEN STUDY
5
21
394
PRACTICUM
INTERN OFFICE
16
16
8
24
24
K.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
17
17
18
18 AC
USB
18
18
AC
USB
AC
USB
6
26
352
5
SHHS CLINICAL
ROOM
14
14
NR-31B /3
O-B1A /4 J 5
O-B1A /4 J
AC
17
366
10
354
6
365
12
MENS
RESTROOM
J
301
5
392
J
PRACTICUM
THERAPY
NR-31B /3
J N-31 /7
N-31 /15,17
UNISEX
RESTROOM
395
AC
C
PRACTICUM
THERAPY
2
N-31 /7 N-31 /16,18 FSD
N-31 /23,25
FVAV
301
3
J
6
6
4
17
FSD
341
26
26
SERVICE
ELEVATOR
DATA ROOM
F
N-32 /6
FSD
E-21 /21
NR-31B /3
ELECTRICAL
ROOM
J
356
42
390
4
N-32 /6
FSD
CIRCULATION
21
2
E203
4
CIRCUIT TO
NR-32A UNO
NR-32A
DN
CIRCUIT TO
NR-31A UNO
N-32
S300
NR-32B
STAIR D
RSP Architects
10
11
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
THIRD LEVEL ELECTRICAL PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
NR-31A /38
NR-31A /42
G
J O-21A /10
N-31
O-21B /4
9
ELECTRICAL
ROOM
NR-31A
O-21B /6
300
E-21 /14
NR-31A /19
J
3
NR-31B
NR-31A /36
E-21 /15
DATA ROOM
399
O-21B /2
J
O-21B /8
NR-21B /13
NR-31A /40
2
2
THIRD FLOOR ELECTRICAL AND DATA ROOMS
1/4" = 1'-0"
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:03:16 PM
3
THIRD LEVEL POWER
PLAN
E203
GENERAL POWER NOTES:
A.
VERIFY MOUNTING HEIGHTS AND LOCATIONS OF WALL OUTLETS WITH
ARCHITECTURAL ELEVATIONS.
B.
ALL DEVICES AND RECEPTACLES MOUNTED AT 18” ABOVE FINISHED FLOOR
UNLESS NOTED OTHERWISE.
C.
MOUNT DEVICES NOTED AS ABOVE COUNTER (AC) 6” ON CENTER ABOVE
COUNTERTOP HEIGHT. MOUNT DEVICES NOTED AS UNDERCOUNTER (UC) 6”
ON CENTER BELOW COUNTERTOP HEIGHT. REFER TO ARCHITECTURAL
ELEVATIONS FOR COUNTER HEIGHTS.
D.
REFER TO MECHANICAL ELECTRICAL SCHEDULES FOR ELECTRICAL
CONNECTION REQUIREMENTS OF MECHANICAL EQUIPMENT.
E.
ALL BRANCH CIRCUITS SHALL HAVE DEDICATED NEUTRALS.
F.
REFER TO ELECTRICAL DETAILS AND RISERS FOR ADDITIONAL INFORMATION
RELATED TO ELECTRICAL SYSTEMS.
G.
COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION DEVICES
SUCH THAT DEVICES SHALL BE MOUNTED NEXT TO EACH OTHER AT THE
SAME HEIGHTS AND WITHIN 12” OF EACH OTHER. PROVIDE MOUNTING
STRAPS BETWEEN STUDS TO ACCOMMODATE ADJACENT MOUNTING.
H.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
I.
PROVIDE MINIMUM #10 AWG CONDUCTOR SIZE (INCREASING IN SIZE AS
REQUIRED) FOR A MAXIMUM OF 3 PERCENT VOLTAGE DROP FROM PANEL TO
LOAD FOR 120V/20A CIRCUITS LONGER THAN 75 FEET.
J.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
K.
COORDINATE ELECTRICAL DEVICE AND COVERPLATE COLOR WITH
ARCHITECTURAL FINISH PLAN, SEE SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
KEY NOTES:
F
1
FREE STANDING STEEL CHANNEL RACK TO MOUNT DISCONNECTS
AND/OR RECEPTACLES.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
EF
02
WP
36"
NR-32B /1
Signature
James A. LeClaire
Registration Number
1
E
D.9
Date
50358
07/24/15
Project For
EF
01
36" NR-31B /5
WP
1
D
C.9
C.3
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
C
B.8
B.2
B
EF
03
WP
NR-32B /3
36"
Project No.
2263.001.00
Drawn By
1
MMK
Checked By
Date
A
AA
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
0
1
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
Date
Description
11
ROOF POWER PLAN
1/8" = 1'-0"
ROOF POWER PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:06:31 PM
E204
GENERAL SIGNAL NOTES:
A.
DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR
COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY
SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY
REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY
PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT,
BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS
NOTED OTHERWISE.
B.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
C.
ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES.
D.
ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS.
RSP Architects
E.
REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION REGARDING FIRE ALARM SYSTEM.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
F.
MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS.
G.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
KEY NOTES:
UP
F
SMOKE DETECTOR FOR ELEVATOR RECALL.
2
EZ PATH 44 SERIES.
3
FIRE ALARM HORN/STROBE ABOVE SIAMESE CONNECTION. VERIFY
LOCATION WITH PLUMBING PLANS.
4
FLOW AND TAMPER SWITCHES LOCATED AT WATER AND FIRE
ENTRANCES. COORDINATE EXACT LOCATIONS WITH MECHANICAL.
5
FIRE ALARM CONNECTION TO SMOKE GUARD.
F
1
5
1
F P
F CM
S
STORAGE
S F
Dunham Job #: 415134
054
CORRIDOR
03A
SERVICE
ELEVATOR
EXERCISE/TRAINING
009
E2
F
F
S
S
P
P
F
S F
F
P
F
FS
E
D.9
S F
FS
S F
WAITING
SHOWER/
RESTROOM
EXAM/ CONSULT
EXAM/ CONSULT
RESISTANCE
TRAINING
011
010
035
003
Signature
James A. LeClaire
Registration Number
50358
Date
007
MECHANICAL
ROOM
07/24/15
Project For
052
SHOWER/
RESTROOM
SHOWER/
RESTROOM
050
006
FS
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
MENS LOCKER
ROOM
FS
D
C.9
008
F
F
CORRIDOR
S
055
WOMANS
LOCKER ROOM
S
FS
051
P
SHOWER/
RESTROOM
F
SHOWER
RESTROOM
F
005
S F
FS
MECHANICAL
ROOM
013
S
FS
P
P
P
F
F
F
032
C.3
STUDENT HEALTH AND
ACADEMIC RENOVATION
PASS./SERV.
ELEV. EQUIP.
ROOM
5
004
P
F
P
E1
1
FS
F
SHOWER/
RESTROOM
CUSTODIAN
001
P
S
018
014
CORRIDOR
C
R
FS
016
PASSENGER
ELEVATOR
F
UNISEX
TOILET/SHOWER
F CM
P
S F F
S F
F
S
F
F
FS
P
S F
S F
F
B.8
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
S F
STAIR B
2
S002
F
S F
S F
B.2
FS
FACP
B
DATA ROOM
021
P
P
F
F
F
BUILDING
SUPPORT
P
P
F
F
P
033
S
F
F P
ELECTRICAL
ROOM
022
MECHANICAL
ROOM
019
F
TS
TS
TS
P
F F FS
F F FS F TS
F F FS F TS
TS F F FS 4
3
F
A
Project No.
2263.001.00
Drawn By
MMK
Checked By
JL
Date
AA
0
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
LOWER LEVEL SYSTEMS PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
LOWER LEVEL
SYSTEMS PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:03:27 PM
E300
GENERAL SIGNAL NOTES:
A.
DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR
COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY
SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY
REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY
PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT,
BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS
NOTED OTHERWISE.
B.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
C.
ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES.
D.
ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS.
E.
REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION REGARDING FIRE ALARM SYSTEM.
F.
MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS.
G.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
UP
KEY NOTES:
STAIR D
S100
DN
Dunham Job #: 415134
CIRCULATION
VESTIBULE
S F
113
S
F
4
2
S F
P
CM
F
F
135
REF.
F
P
2
EZ PATH 44 SERIES.
3
FIRE ALARM CONNECTION TO SHOWN FIRE/SMOKE DAMPERS NEAR THIS
LOCATIONS. COORDINATE WITH MECHANICAL CONTRACTOR FOR
LOCATIONS. REFER TO FIRE ALARM DETAIL SHEET REGARDING FIRE
ALARM INTERFACE. REFER TO POWER PLANS FOR 120VAC CONNECTION.
4
FIRE ALARM CONNECTION TO SMOKE GUARD.
5
ROUGH-IN FOR FUTURE CARD READER AND ELECTRONIC LOCK SET AT
INDICATED DOOR.
F
S F
P
F
SMOKE DETECTOR FOR FIRE ALARM RECALL.
P
S F
1
1
5
F
ELECTRICAL
DATA
130
131
P
F
F
NAC
114
2
3
F SD
VENDING
CM F FSD 133
102
124
E
D.9
117
P
F
S F
CM
F F SD
3
S F
S
CM F F SD
F
Signature
James A. LeClaire
50358
FS
P
F
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Registration Number
FSD
STORAGE
SHELL SPACE
PEER ED/
UCHOOSE
STUDENT STAFF
WORK
116
FSD
HEALTH ED
INTERDISCIPLINARY
SERVICE
ELEVATOR
P
S F
S F
Date
5
07/24/15
Project For
F
S
P
5
F
FS
CIRCULATION
D
C.9
118
P
F
MENS
RESTROOM
S F
RADIOLOGY
(COMMUNITY
PARTNER)
107
SHHS
INTERDISCIPLINARY
UNISEX TOILET
FS
123
S F
132
WOMENS
RESTROOM
108
C.3
S F
FS
103
STUDENT HEALTH AND
ACADEMIC RENOVATION
P
F
STORAGE
S
104
4
F
CM
F
DIRECTORY
111
C
PASS
ELEVATOR
F P
1
115
LACTATION
ROOM
CIRCULATION
P
F
S F
P
105
F
106
B.8
S F
S F
S F
FS
S F
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
STAIR A
S102
STAIR A
S101
B.2
S F
B
GRAD ASSIST
122
INFO/KIOSK
RESEARCH
ASST.
INFO/KIOSK
129
136
S F
S F
110
RECOVERY
COMMUNITY
RESOURCE
AREA
RESEARCHER
P
128
P
F
S F F
F
S F
P
RESEARCH
DIRECTOR
UCHOOSE & RC
UCHOOSE & RC
HEALTH ED &
PROMOTION
COORD
125
121
120
119
134
S F
FS
RESEARCH
COORDINATOR
A
127
126
NORTH ENTRY
SOUTH ENTRY
112
109
Date
AA
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
MMK
Checked By
FAAP
1
2263.001.00
Drawn By
RESEARCH
DATA
0
Project No.
8
9
10
11
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
FIRST LEVEL SYSTEMS PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
FIRST LEVEL SYSTEMS
PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:03:37 PM
E301
GENERAL SIGNAL NOTES:
STAIR D
S200
F
F
263
4
2
208
S
F CM
F
S
F
S
S
F
ELECTRICAL
FP
253
HALLWAY
SOILED HOLD
262
252
P
NAC
F
SERVICE
ELEVATOR
DATA
206
254
SHS DIRECTORS
CUSTODIAN
209
212
LARGE CENTRAL
SUPPLY
F
Low for microwave
S
TRIAGE ROOM
CONSULT ROOM
(E-EXAM)
CONSULT ROOM
(CAPS)
213
214
215
237
236
235
F SD
SD
3 F
CM F
FSD
P
CM F F SD
S
F
202
MENS
RESTROOM
S F
201
EXAM ROOM
EXAM ROOM
EXAM ROOM
218
217
216
F
F
F
S
OBSERVATION
(IVS) - EKG
INJECTION
ROOM
EXAM ROOM
233A
238
271
MD OFFICE
223
E
D.9
224
P
P
261
P
F
F
F
HALLWAY
S
F
F
F
F
S
264
S
P
HALLWAY
S
F
265
EXAM ROOM
EXAM ROOM
EXAM ROOM
REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION REGARDING FIRE ALARM SYSTEM.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
F.
MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS.
G.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
1
SMOKE DETECTOR FOR ELEVATOR RECALL.
2
EZ PATH 44 SERIES.
3
FIRE ALARM CONNECTION TO SHOWN FIRE/SMOKE DAMPERS NEAR THIS
LOCATIONS. COORDINATE WITH MECHANICAL CONTRACTOR FOR
LOCATIONS. REFER TO FIRE ALARM DETAIL SHEET REGARDING FIRE
ALARM INTERFACE. REFER TO POWER PLANS FOR 120VAC CONNECTION.
4
FIRE ALARM CONNECTION TO SMOKE GUARD.
Dunham Job #: 415134
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
Bryan Schmidt
26566
07/24/15
HALLWAY
S
259
NP OFFICE
D
C.9
219
220
221
S
STAFF TOILET
TREATMENT
ROOM
F
NP OFFICE
255
270
232
S
WOMENS
RESTROOM
F
203
S
F
F
S F
260
F
E.
Project For
258
WAITING
CIRCULATION
205
RSP Architects
Date
HALLWAY
F
F
ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS.
227
P
CONFERENCE
D.
Registration Number
S
HALLWAY
ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES.
MD OFFICE
S
SHS ASST
DIRECTOR
S
C.
222
F
F
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
Mini
Fridge
MEDICAL
DIRECTOR
OFFICE
S
210
B.
REF.
SD
CM F F 3
UNISEX
RESTROOM
211
F
F
S
EXAM ROOM
FSD
CM F
257
EXAM ROOM
FSD
F
S
P
F
F P
ISOLATION EXAM
2
P
HALLWAY
SD
CM F F 3
P
CM F F SD
F
P
F
F
FSD
S
UCHOOSE
ADMINISTRATOR
P
F
FSD
F
F P
F P
FSD
1
DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR
COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY
SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY
REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY
PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT,
BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS
NOTED OTHERWISE.
KEY NOTES:
UP
UP
HALLWAY
A.
S
S F
F
NURSE STATION
S
231
PROCESS ROOM
F P
C.3
229
STUDENT HEALTH AND
ACADEMIC RENOVATION
S
F
S
4
EXAM ROOM
EXAM ROOM
226
225
269
230
F P
1
PASS ELEVATOR
207
NURSING
MANAGER
MED/ NOURISH
ROOM
228
C
REF.
CLEAN SUPPLY
REF.
F CM
EXAM ROOM
234
P
B.8
F
P
P
F
S F
STAIR A
F
F
S
F
F
HALLWAY
S
266
P
F
F
S
S
FS
S201
F
STORAGE
P
240
F
F
RECEPTION
WORK
F
243
246
S
S
239
S
B.2
S F
F
VSN-1
-1
V SN
S202
256
B
OTC SALES
VSN-1
STAIR B
PATIENT TOILET
267
CONSULTATION
AREA
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
S F
PRESCRIPTION
PICK-UP/DROP-OFF
242
CASHIER
244
245
REFERRAL
COORDINATOR
OFFICE
247
248
P
F
F
SUB
WAITING
S
S F
P
PHLEBOTOMY
LAB TOILET
249
S F
PHARMACY
F
BUSINESS
MANAGER
STUDENT
INSURANCE
ADVOCATE
F
250
268
241
LABORATORY
S
251
Project No.
A
S F
2263.001.00
Drawn By
MMK
Checked By
JL
Date
AA
0
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
SECOND LEVEL SYSTEMS PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
SECOND LEVEL
SYSTEMS PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:03:51 PM
E302
GENERAL SIGNAL NOTES:
A.
DIVISION 26 CONTRACTOR SHALL PROVIDE COMPLETE ROUGH-IN FOR
COMMUNICATION SYSTEMS AND ELECTRONIC SAFETY AND SECURITY
SYSTEMS. COMMUNICATION AND ELECTRONIC SAFETY AND SECURITY
REQUIREMENTS AND DEVICE LAYOUTS ARE INDICATED ON THE TECHNOLOGY
PLANS. DIVISION 26 CONTRACTOR SHALL PROVIDE ALL CONDUIT,
BACKBOXES, JUNCTION BOXES, FLOOR BOXES, AND IN-WALL BOXES UNLESS
NOTED OTHERWISE.
B.
DEVICES SHALL NOT BE INSTALLED BACK TO BACK TO PREVENT NOISE
TRAVEL UNLESS NOTED OTHERWISE, REFER TO SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
C.
ALL CABLES SHALL BE CONCEALED IN FINISHED SPACES.
D.
ALL CONDUIT ENDS SHALL HAVE NYLON BUSHING AND PULL STRINGS.
RSP Architects
E.
REFER TO FIRE ALARM MATRIX AND SPECIFICATIONS FOR ADDITIONAL
INFORMATION REGARDING FIRE ALARM SYSTEM.
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
F.
MOUNT SMOKE DETECTORS 3’ MINIMUM FROM SUPPLY DIFFUSERS.
G.
PROVIDE CUTTING AND PATCHING FOR ELECTRICAL WORK.
S300
Dunham Job #: 415134
DN
3
P
S
F
SHHS CLINICAL
ROOM
4
S
CM
F
F
F 1
S
F
P
SHHS CLINICAL
ROOM
NAC
353
PRACTICUM
THERAPY
PRACTICUM
THERAPY
PRACTICUM
THERAPY
364
365
366
S F
S F
S F
F
S
S
THERAPIST
OFFICE
FSD
CLOSET
F CM
F CM
341
3
SD F
SD FFSD
FS
F
MENS
RESTROOM
FS
PRACTICUM
THERAPY
PRACTICUM
THERAPY
PRACTICUM
THERAPY
369
368
367
S F
S F
S F
PRACTICUM
INTERN OFFICE
CAPS INTERN
OFFICE
398
370
F
S
373
P
P
P
F
352
P
F
F
F
F
S
S
S
F
F
F
S F
340
P
GROUP
THERAPY ROOM
Project For
S
S
384
397
377
THERAPIST
OFFICE
S
STAFF TOILET
374
361
P
F
P
F
P
HALLWAY
394
303
F
F
FS
SHHS FACULTY
COMMAND
CENTER
AOD
COUNSELOR
F
S
SHHS CLINICAL
ROOM
THERAPIST
PREDOCTORAL
380
355
S F
F
07/24/15
D
C.9
383
WOMENS
RESTROOM
396
F
50358
F
F
S
S
RELAXATION
ROOM
SHHS FACULTY
COMMAND
CENTER
HALLWAY
James A. LeClaire
P
SHHS CLINICAL
ROOM
393
Signature
Date
OPEN STUDY
F
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
THERAPIST
OFFICE
301
392
FIRE ALARM CONNECTION TO SMOKE GUARD.
Registration Number
S
354
S F
SHHS CLINICAL
ROOM
4
F
UNISEX
RESTROOM
395
E
D.9
372
F
SHHS GROUP
THERAPY ROOM
FIRE ALARM CONNECTION TO SHOWN FIRE/SMOKE DAMPERS NEAR THIS
LOCATIONS. COORDINATE WITH MECHANICAL CONTRACTOR FOR
LOCATIONS. REFER TO FIRE ALARM DETAIL SHEET REGARDING FIRE
ALARM INTERFACE. REFER TO POWER PLANS FOR 120VAC CONNECTION.
P
F
F
P
391
S
3
F
F
S
EZ PATH 44 SERIES.
371
399
S F
2
S
DATA ROOM
F
SMOKE DETECTOR FOR ELEVATOR RECALL.
S
362
F
CUSTODIAN
S
F F
SERVICE
ELEVATOR
P
F
P
F P
F
1
THERAPIST
OFFICE
S
P
SD F FSD
FSD F SD
356
S
F
F CM
F
ELECTRICAL
ROOM
300
3
F CM
P
390
S F
CIRCULATION
P F
P
F
F
Consultants
KEY NOTES:
STAIR D
F
612.677.7100
612.677.7499 fax
www.rsparch.com
F
S
F
C.3
F
S
STUDENT HEALTH AND
ACADEMIC RENOVATION
S
THERAPIST
OFFICE
S F
CM
F
4
STORAGE
PASS ELEVATOR
302
RELAXATION
ROOM
P
F
363
THERAPIST
PREDOCTORAL
AOD
COUNSELOR
379
378
376
THERAPIST
OFFICE
F
375
S
C
382
1
STORAGE/AV
HALLWAY
381
360
B.8
P
F
F
S F
P
STAIR A
F
S301
F
F
S
S
S
P
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
F
FS
F
S
B
ADMIN
SUPPORT/
RECEPTION
F
S
F
CAPS ENTRY
S
323
B.2
P
F
321
CASE MANAGER
INTERN
387
STAFF BREAK
ROOM
324
F
PRIVATE
WAITING AREA
S
422
KITCHEN
CONFERENCE
/GROUP ROOM
419
359
FILE & ARCHIVE
P
F
CASE MANAGER
OFFICE
385
F
388
S
F
P
S
F
WORK ROOM
320
F
S
CAPS DIRECTOR
OFFICE
VS
N-1
S
389
N-1
VS
F
A
Project No.
2263.001.00
Drawn By
MMK
V SN
-1
N-1
VS
Checked By
JL
Date
AA
0
1
2
3
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
1
THIRD LEVEL SYSTEMS PLAN
1/8" = 1'-0"
Revisions
No.
Date
Description
THIRD LEVEL
SYSTEMS PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:04 PM
E303
GENERAL NOTES:
1/E405
4/E405
4/E405
4/E405
4/E405
A.
REFER TO NFPA-780 INSTALLATION OF LIGHTNING PROTECTION SYSTEMS,
FOR FURTHER INFORMATION.
B.
THE TIP OF AN AIR TERMINAL SHALL BE NOT LESS THAN 10 INCHES ABOVE
THE OBJECT OR AREA IT IS TO PROTECT.
C.
THE DISTANCE BETWEEN STRIKE TERMINATION DEVICES AND EDGES OR
OUTSIDE CORNERS OF ROOF, SHALL NOT EXCEED 2 FEET.
D.
STRIKE TERMINATION DEVICES SHALL BE PLAED AROUND THE PERIMETER
OF ROOFS. AT INTERVALS NOT EXCEEDING 20 FEET.
E.
THE MAIN ROOF CONDUCTOR SHALL BE RUN ADJACENT TO THE VERTICAL
ROOF MEMBERS SO THAT THE SINGLE CABLE FROM THE STRIKE
TERMINATION DEVICE IS AS SHORT AS POSSIBLE AND IN NO CASE LONGER
THAN 16 FEET.
F.
EACH DOWN CONDUCTOR SHALL TERMINATE AT A GROUNDING
ELECTRODE DEDICATED TO THE LIGHTNING PROTECTION SYSTEM.
2/E405
1/E405
4/E405
1
4/E405
4/E405
4/E405
4/E405
4/E405
4/E405
4/E405
4/E405
4/E405
2/E405
2/E405
1/E405
4/E405
2/E405
2/E405
1
1
2/E405
6/E405
6/E405
F
1/E405
1
7/E4045
4/E405
4/E405
4/E405
4/E405
7/E405
3
E
D.9
G.
GROUNDING ELECTRODES SHALL BE INSTALLED BELOW THE FROST LINE
WHERE POSSIBLE.
H.
GROUND RODS SHALL BE NOT LESS THAN 3/4" IN DIAMETER AND 8' LONG.
I.
THE GROUND RODS SHALL EXTEND VERTICALLY NOT LESS THAN 10 FEET
INTO THE EARTH.
J.
WHERE MULTIPLE GROUND RODS ARE USED. THE SEPERATION BETWEEN
ANY TWO GROUND RODS SHALL BE AT LEAST THE SUM OF THEIR DRIVEN
DEPTHS, WHERE PRACTIBLE.
K.
ALL GROUNDING MEDIA AND BURIED METALLIC CONDUCTORS THAT CAN
ASSIST IN PROVIDING A PATH FOR LIGHTNING CURRENTS IN OR ON A
STRUCTURE SHALL BE INTERCONNECTED TO PROVIDE A COMMON
GROUND POTENTIAL. THIS INTERCONNECTION SHALL INCLUDE LIGHTNING
PROTECTON, ELECTRIC SERVICE, COMMUNICATIONS, AND ANTENNA
SYSTEM GROUNDS, AS WELL AS UNDERGROUND METALLIC PIPING
SYSTEMS.
3
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
4
4/E405
4
4/E405
4
4
6/E405
4/E405
4/E405
D
C.9
KEY NOTES:
4/E405
4/E405
2/E405
C.3
1/E405
4/E405
4/E405
2/E405
C
2/E405
1
1/E405
1
6/E405
4/E405
4/E405
4/E405
4/E405
B.8
1
DOWNLEAD CONDUCTOR FROM ROOF DOWN THROUGH NEW ROOF
PENETRATION, AND THEN THROUGH NEW INTERIOR STUD WALLS TO
GROUND ROD LOCATION. SEE SHEETS E200, E201, E202, E203 FOR
CONTINUATION OF DOWNLEAD CONDUCTORS.
2
BOND TO ROOF HATCH.
3
BOND TO LADDER
4
BOND TO ROOF DRAIN.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
6/E404
B.2
4/E405
4
4/E405
4/E405
B
4
2
4
4
STUDENT HEALTH AND
ACADEMIC RENOVATION
7/E405
4/E405
4/E405
2/E405
2/E405
4/E405
4/E405
4/E405
4/E405
4/E405
4/E405
4/E405
A
6/E405
1
1
4/E405
4/E405
4/E405
1
2
3
AA
4/E405
4/E405
1/E405
1/E405
1
6/E405
2/E405
2/E405
0
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
4
4.2
4.5
4.8 5
CL
5.55.6
66.2
6.7 7
8
9
10
11
LIGHTNING PROTECTION PLAN
1/8" = 1'-0"
Project No.
2263.001.00
Drawn By
DM
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
LIGHTNING
PROTECTION PLAN
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:05:33 PM
E404
28str x 14Ga BARE Cu CONDUCTOR
SOLID Alum BLUNT TIP
AIR TERMINAL
1" PVC CONDUIT BY ELECTRICAL CONTRACTOR
SEE AIR TERMINAL DETAIL
NOTES:
1. DEPTH OF GROUNDING PER CONTRACT
ST
UB
REQUIREMENTS OR CODE.
BE C
LO ON
W DU
GR IT
AD OU
EO TA
R P PP
ER ROX
CO IMA
NT TE
RA LY
CT 6"
RE - 12
QU "
IR
EM
EN
TS
BARE CONDUCTOR
BARE Alum CONDUCTOR
CABLE FROM HIGH ROOF
DOWN TO LOW ROOF
RSP Architects
SEE ROOF PENETRATION DETAIL
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
SEE AIR TERMINAL DETAIL
STUB OUT ABOVE LOW
ROOF COUNTER-FLASHING
SINCE CAP IS EITHER
GALVANIZED OR ALUMINUM, ALL
LIGHTNING PROTECTION SYSTEM
MATERIALS MUST BE OF ALUMINUM
CONSTRUCTION FOR CODE
COMPLIANCE AND ELECTROLYTIC
COMPATIBILITY.
1" PVC CONDUIT - BY
ELECTRICAL CONTRACTOR
GRADE
6" - 1'-0" MAX.
3/4" GROUND ROD CLAMP
2' MIN.
SEE GROUND
ROD DETAIL
CROSS RUN CABLE CLAMP
0"
MI
N.
3/4" x 10' COPPER-CLAD
GROUND ROD
1
GROUND ROD - CONDUIT TO CROSS RUN CLAMP DETAIL
NO SCALE
2
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
CABLE FROM ROOF
DOWN TO GROUND
2'
-
Alum ADHESIVE FLAT
MOUNT POINT BASE
ADHESIVE CABLE HOLDER @ 3'-0" O/C
DOWNLEAD ROUTING IN CONDUIT - TWO LEVEL WITH PARAPET DETAIL
NO SCALE
REFER TO INSPEC ROOFING
DETAILS FOR ROOF
PENETRATION REQUIREMENTS
3
ROOF PENETRATION DETAIL
NO SCALE
4
SINCE MECHANICAL EQUIPMENT IS
EITHER GALVANIZED OR ALUMINUM,
ALL LIGHTNING PROTECTION
SYSTEM MATERIALS MUST BE OF
ALUMINUM CONSTRUCTION FOR
CODE COMPLIANCE AND
ELECTROLYTIC COMPATIBILITY.
SINCE MECHANICAL EQUIPMENT IS
EITHER GALVANIZED OR ALUMINUM,
ALL LIGHTNING PROTECTION
SYSTEM MATERIALS MUST BE OF
ALUMINUM CONSTRUCTION FOR
CODE COMPLIANCE AND
ELECTROLYTIC COMPATIBILITY.
Dunham Job #: 415134
AIR TERMINAL - PARAPET TOP MOUNT DETAIL
NO SCALE
TYPICAL BONDING AND SPLICING
M
S
= MAIN, FULL SIZE CABLE
= SECONDARY SIZE CABLE
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
Alum BLUNT TIP
AIR TERMINAL
James A. LeClaire
Registration Number
50358
SOLID Alum BLUNT TIP AIR TERMINAL
Date
MECHANICAL EQUIPMENT
POINT BASE - Alum
SOLID Alum BLUNT TIP AIR TERMINAL
FLAT MOUNT POINT BASE - Alum
Project For
M
No. 800: BONDING
STRAP
M
No. 240 or 240X: BONDING
CLAMP
SWIVEL POINT ADAPTER
BARE Alum CONDUCTOR
ADHESIVE CABLE
HOLDER @ 3'-0" O/C
M
ADHESIVE FLAT MOUNT
POINT BASE
No. 142X: SECONDARY
SIZE BONDING CLAMP
No. 702: BONDING
PLATE
S
BOND PLATE
No. 423B: PARALLEL
CABLE SPLICER
BARE Alum CONDUCTOR
M
BARE Alum CONDUCTOR
No. 551: BONDING LUG
ALUM PARALLEL
CABLE SPLICER
07/24/15
STUDENT HEALTH AND
ACADEMIC RENOVATION
M
Alum PARALLEL
CABLE SPLICER
No. 561: BONDING LUG
M
S
No. 143: CABLE SPLICER
M
M
No. 142HD: FLAT
METAL BONDING
CLAMP
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
S
AIR TERMINAL - SWIVEL POINT ADAPTER DETAIL
5
NO SCALE
AIR TERMINAL - MECHANICAL VENT - PARALLEL CABLE DETAIL
6
NO SCALE
AIR TERMINAL - MECHANICAL EQUIPMENT - PARALLEL CABLE DETAIL
7
NO SCALE
8
TYPICAL BONDING & SPLICING DETAILS
NO SCALE
Project No.
Drawn By
Checked By
Date
2263.001.00
Author
Checker
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
LIGHTNING
PROTECTION DETAILS
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:07:00 PM
E405
NAME: MSB
ELECTRICAL PANEL NOMENCLATURE
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
EQUIPMENT OPTIONS: FR, SPD, M, 200% NEUTRAL
MAIN OCPDTYPE: MLO
MAIN OCPD OPTIONS: NOT APPLICABLE
MINIMUM BUS SIZE: 1600 A
MAIN SIZE:
MAIN SETTING:
LHD - B1
PANEL NUMBER
N - NORMAL BRANCH
E - EMERGENCY BRANCH
R - LEGALLY REQUIRED
O - OPTIONAL STANDBY
42,654A
CALCULATED
A.F.C.
R - RECEPTACLE
CKT
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
B - BASEMENT
1 - 1ST FLOOR
2 - 2ND FLOOR
3 - 3RD FLOOR
PM
D - DISTRIBUTION
91.5
TRANSFER SWITCH SCHEDULE
ATS NAME
ATS-E
ATS-O
ATS-R
VOLTAGE
208 V
208 V
208 V
SIZE
100 A
200 A
400 A
SWITCH TYPE
AUTOMATIC
AUTOMATIC
AUTOMATIC
TRANSFER POLES
4-POLE
4-POLE
4-POLE
TRANSITION
OPEN
OPEN
OPEN
MOUNTING
WALL
WALL
WALL
ACCESS
FRONT
FRONT
FRONT
OPTIONS
ECM, SCM
ECM, SCM, LSR
ECM, SCM, ECC, ESR
NOTES
24.00
BI - BYPASS ISOLATION
DO - DRAW OUT
ECC - ELEVATOR CONTROL CONTACTS
ECM - ETHERNET COMMUNICATIONS MODULE
ON - OVERSIZED NEUTRAL
PM - POWER MANAGER
RA - REMOTE ANNUNCIATOR
SCM - SERIAL COMMUNICATION MODULE
SMDR - SEQUENTIAL MOTOR DISCONNECT RELAY
ESR - ELEVATOR/ESCALATOR PRE-TRANSFER
IPM - IN-PHASE MONITOR
LSR - LOAD SHED RELAY
MDR - MOTOR DISCONNECT RELAY
1.5
42.00
42.00
36.00
GENERAL NOTES
A.
SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. TRANSFER SWITCH SHALL HAVE HIGHER SHORT-CIRCUIT
CURRENT RATING THAN CALCULATED VALUE SHOWN ON RISER DIAGRAM.
36.00
78.00
ELECTRICAL NOTES:
2
MSB ELEVATION AND FLOOR PLAN
NO SCALE
OCPD
FRAME...
TRIP
RATING
A
B
C
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
225 A
225 A
1200 A
100 A
400 A
225 A
1000 A
225 A
400 A
225 A
225 A
100 A
100 A
100 A
225 A
225 A
225 A
225 A
1000 A
100 A
300 A
225 A
1000 A
225 A
400 A
225 A
225 A
100 A
100 A
100 A
225 A
225 A
4213 VA
4855 VA
38423 VA
3680 VA
25182 VA
18757 VA
54768 VA
10559 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
3634 VA
4108 VA
38423 VA
3788 VA
25686 VA
18158 VA
46800 VA
9354 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
3554 VA
3376 VA
38423 VA
2155 VA
24990 VA
17177 VA
45320 VA
9054 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
TOTAL CONN. LOAD: 160436 VA
TOTAL AMPS:
1345 A
DEMAND FACTOR
LOAD DEMAND (VA)
125%
40383 VA
10 KVA @ 100%, REMAINING @...
80030 VA
100%
100%
100%
227704 VA
100%
125%
227704 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, REMAINING @...
100%
40200 VA
100%
149950 VA
1257 A
144048 VA
1200 A
N-22
N-B2
NRD-B1
ATS-E
ATS-R
ATS-O
NRD-B1
N-B1
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
FUTURE COMMUNITY PARTNER
FUTURE COMMUNITY PARTNER
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
LARGEST MOTOR - PROJECT (DA_LPM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
TRANSFER SWITCH OPTIONS:
# OF
POLES
CIRCUIT DESCRIPTION
CONNECTED LOAD (VA)
32306 VA
150060 VA
227704 VA
227704 VA
40200 VA
OCPD TYPE OCPD OPTIONS NOTES
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
MCCB
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
ET, AIT, TM
TOTAL CONN. LOAD: 454435 VA
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT: 1261 A
TOTAL EST. DEMAND... 1089 A
NOTES:
1. PROVIDE ARC ENERGY REDUCTION MAINTENANCE SWITCH WITH LOCAL INDICATOR LIGHT AND BEACON LIGHT AT THE MAIN ENTRY TO THE ROOM.
2. PROVIDE DIGITAL METERING AND ASSOCIATED CT'S FOR METERING.
3.
4.
MCCB
TM - THERMAL MAGNETIC BREAKER
ET - ELECTRONIC TRIP
CL - CURRENT LIMITING
IF - INTERNALLY FUSED
GFEP - GROUND FAULT EQUIPMENT
GFCI - GROUND FAULT CIRCUIT INTERRUPTION
AIT - ADJUSTABLE INSTANTANEOUS TRIP
ICCB
FB - FIXED BREAKER
(5) 4"C, 3#400KCMIL + 2#400KCMIL N + #4/0 G
2
1-1/4"C, 3#3 + #3/0 N + #8 G
3
(4) 3"C, 3#250KCMIL + 2#250KCMIL N + #2/0 G
4
(2) 3-1/2"C, 3#350KCMIL + 2#350KCMIL N + #1 G
5
(2) 3"C, 3#3/0 + #600KCMIL N + #3 G
6
3"C, 3#4/0 + #700KCMIL N + #6 G
7
3-1/2"C, 3#350KCMIL + 2#350KCMIL N + #4 G
DOB - DRAW OUT BREAKER
SWITCH
BPS - BOLTED PRESSURE SWITCH
EQUIPMENT OPTIONS
SE - SERVICE ENTRANCE RATED
LS - LOAD SHEDDING
KEY NOTES:
1
LSI MOLDED CASE CIRCUIT BREAKER WITH ARC FLASH MAINTENANCE
(AMS) SWITCH.
2
100A/3P ENCLOSED THERMAL MAGNETIC CIRCUIT BREAKER WITH
ELECTRONIC TRIP AND ADJUSTABLE INSTANTEOUS TRIP.
3
400A/3P ENCLOSED THERMAL MAGNETIC CIRCUIT BREAKER WITH
ELECTRONIC TRIP AND ADJUSTABLE INSTANTEOUS TRIP.
4
225A/3P ENCLOSED THERMAL MAGNETIC CIRCUIT BREAKER WITH
ELECTRONIC TRIP AND ADJUSTABLE INSTANTEOUS TRIP.
2
2
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
50358
Date
07/24/15
OCPD TYPE OPTIONS:
OCPD TYPES:
1
RSP Architects
TOTALS
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. EQUIPMENT SHALL HAVE STANDARD SHORT-CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED
VALUE SHOWN ON RISER DIAGRAM.
FEEDER SCHEDULE
1, 2
FS - FUSED SWITCH
M - METER
SR - SERIES RATED
GFP - GROUND FAULT PROTECTION
CC - COMMUNICATIONS CAPABILITIES
UT - UNDERVOLTAGE TRIP
KI - KIRK KEY INTERLOCK
ZI - ZONE SELECTIVE INTERLOCKING
ST - SHUNT TRIP
AU - AUXILARY CONTACTS
BL - BREAKER LOCK
ZI - ZONE SELECTIVE INTERLOCKING
KI - KIRK KEY INTERLOCK
RT - REMOTE TRIP
CC - COMMUNICATIONS CAPABILITIES
BL - BREAKER LOCK
GFP - GROUND FAULT PROTECTION
SRVR - SERVICE RATED
BL - BREAKER LOCK
H - STRIP HEATERS
FR - FULLY RATED
EO - EMERGENCY OFF REQUIREMENTS
SPD - SURGE PROTECTION DEVICE
C - COMPARTMENTALIZED
Project For
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
ROOF
3RD FLOOR
NORTHEAST
ELECTRICAL
ROOM
SECOND FLOOR
N-31
NR-31A
NR-31B
8724A
11764A
11608A
GENERATOR
600A FRAME
540A TRIP
ET, AIT, MCCB
C3
C2
FIRST FLOOR
C4
2ND FLOOR
SOUTHWEST
6
5
NR-32B
5457A
7792A
7722A
6
5
6
Project No.
N-21
EXTERIOR PAD MOUNTED
OIL FILLED TRANSFORMER
RATED AT 500KVA 12.47KV PRIMARY,
208/120V SECONDARY
NR-21A
NR-21B
O-21B
O-21A
E-21
N-22
NR-22A
NR-22B
2263.001.00
Drawn By
MMK
Checked By
9367A
12675A
6
5
12494A
1ST FLOOR
NORTHEAST
ELECTRICAL
ROOM
ENCLOSED
CIRCUIT BREAKER
- SERVICE
ENTRANCE
RATED (NEMA 3R)
1600A
NR-32A
5
2ND FLOOR
NORTHEAST
ELECTRICAL
ROOM
150KW DIESEL GAS GENERATOR
WITH WEATHER PROOF SOUND
ATTENUATED ENCLOSURE
N-32
M
6
EXISTING PMH SWITCH UTILIZE SPARE FEEDER
COMPARTMENT (C4)
5
METERING FOR B3
PLUG LOADS
THIRD FLOOR
UNDERGROUND
PRIMARY TAP FEEDERS
- 3-1/0 AWG COPPER,
15KV CABLE AND 1-1/0
AWG COPPER
NEUTRAL, FEEDERS
SHALL BE CONCRETE
ENCASED
3RD FLOOR
SOUTHWEST
5
8678A
8817A
6
3346A
7423A
1ST FLOOR
SOUTHEAST
8
6
6908A
6822A
5
6
6
N-11
NR-11A
NR-11B
N-12
NR-12A
NR-12B
10109A
10943A
10733A
5628A
9163A
9067A
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
TRANSFORMER
1
C1
BUILDING METER
Revisions
6
1
© Copyright RSP Architects 2015. All rights reserved.
EXTERIOR
6
EXISTING PRIMARY TAP
FEEDERS - 3-1/0 AWG
COPPER, 15KV CABLE AND 11/0 AWG COPPER NEUTRAL
BASEMENT
MECHANICAL
ROOM
BASEMENT
NORTHWEST GEN
DISTRIBUTION
ELECTRICAL
ROOM
BASEMENT
NORTHWEST
MAIN ELECTRICAL
ROOM
No.
Date
Description
5
TO RIVERVIEW
6
1
EXISTING PRIMARY LOOP
FEEDERS - 3-4/0 AWG
COPPER, 15KV CABLE AND 14/0 AWG COPPER NEUTRAL
METERING FOR B3
PLUG LOADS
6
7
2
M
6
3
2
6
BASEMENT
N-B1
ELECTRICAL RISER DIAGRAM
NO SCALE
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:15 PM
NRD-B1
NR-B1A
6
NR-B1B
25533A
24477A
21814A
21100A
RD-B1
E-B1
DIST
22191A
2
6
2
MSB - SWITCHBOARD 208/120V, 3PH, 4W, 1600A
1
6
6
M
INCOMING
MAIN LUG
AND DIST
SECTION
7
4
ATS-E
13410A
2
11854A
ATS-R
20147A
7
19269A
ATS-O
20311A
O-B1A
O-B1B
18677A
18120A
3
4
NR-B2
N-B2
ND-B1
7760A
8162A
19660A
6
INCOMING
M
6
M
GEN DIST
ELECTRICAL RISER
DIAGRAM
METERING FOR B3
PLUG LOADS
E500
LUMINAIRE SCHEDULE
FIXTURE
LETTER
FIXTURE TYPE
VOLTAGE
MOUNTING
LAMPS
CONTROL MEDIA
(LENS, LOUVER, ETC.)
MANUFACTURER'S
SERIES NUMBERS
LUMINAIRE SCHEDULE
LUMINAIRE DESCRIPTION
NOTES
A1
2X4 RECESSED LED
TROFFER
120V
RECESSED
LAY-IN GRID
INVERTED TEE
LED
4000
LUMENS
MIN 35W
3500K
FROSTED ACRYLIC
LENS
METALUX #24CZ SERIES
COLUMBIA #LCAT24 SERIES
STEEL HOUSING. 0-10V DIMMING DRIVER.
WHITE ENAMEL FINISH. STEEL HATCHES.
SAFETY-LOCK HINGES.
2
A2
2X4 RECESSED LED
TROFFER
120V
RECESSED
LAY-IN GRID
INVERTED TEE
LED
7500
LUMENS
MIN 75W
3500K
FROSTED ACRYLIC
LENS
METALUX #24CZ SERIES
COLUMBIA #LCAT24 SERIES
STEEL HOUSING. 0-10V DIMMING DRIVER.
WHITE ENAMEL FINISH. STEEL HATCHES.
SAFETY-LOCK HINGES.
-
A3
2X4 RECESSED LED
TROFFER
120V
RECESSED
GYP BOARD
LED
4000
LUMENS
MIN 35W
3500K
FROSTED ACRYLIC
LENS
METALUX #24CZ SERIES
COLUMBIA #LCAT24 SERIES
STEEL HOUSING. 0-10V DIMMING DRIVER.
WHITE ENAMEL FINISH. STEEL HATCHES.
SAFETY-LOCK HINGES.
2
A4
B1
B2
C1
C2
C3
C4
C5
2X4 LENSED TROFFER
2X2 RECESSED
TROFFER
2X2 RECESSED
TROFFER
4' RECESSED LINEAR
6' RECESSED LINEAR
8' RECESSED LINEAR
6' RECESSED LINEAR
4' RECESSED LINEAR
120V
120V
120V
120V
120V
120V
120V
120V
RECESSED
LAY-IN GRID
INVERTED TEE
2-F32 T8
4100K
.125" MINIMUM
ACRYLIC LENS
RECESSED
LAY-IN GRID
INVERTED TEE
LED
2400
LUMENS
MIN 23W
3500K
FROSTED ACRYLIC
LENS
RECESSED
GYP BOARD
LED
2400
LUMENS
MIN 23W
3500K
FROSTED ACRYLIC
LENS
LED
3500K
440
LMNS/FT
7W/FT
SATIN LENS
LED
3500K
440
LMNS/FT
7W/FT
SATIN LENS
LED
3500K
515
LMNS/FT
MIN
9W/FT
MAX
SATIN LENS
LED
3500K
515
LMNS/FT
MIN
9W/FT
MAX
SATIN LENS
LED
3500K
515
LMNS/FT
MIN
9W/FT
MAX
SATIN LENS
RECESSED SHEET ROCK
FLANGED
RECESSED SHEET ROCK
FLANGED
RECESSED
RECESSED
RECESSED
COLUMBIA #ST824 SERIES
LITHONIA #2SP8 SERIES
METALUX #2GC8 SERIES
DAY-BRITE #2DPG SERIES
LIGHTOLIER #SPS2 SERIES
WILLIAMS #50G-S24 SERIES
SPRING LATCHES. POST PAINTED STEEL
HOUSING. FLUSH WHITE ALUM. MITERED
CORNERED DOOR FRAME, GASKETED
AND/OR WITH METAL LIGHT BAFFLES. DOOR
CAN BE LATCHED FROM EITHER SIDE OF
HOUSING. ONE ELECTRONIC BALLASTS.
-
METALUX #22CZ SERIES
COLUMBIA #LCAT22 SERIES
STEEL HOUSING. 0-10V DIMMING DRIVER.
WHITE ENAMEL FINISH. STEEL HATCHES.
SAFETY-LOCK HINGES.
-
STEEL HOUSING. 0-10V DIMMING DRIVER.
WHITE ENAMEL FINISH. STEEL HATCHES.
SAFETY-LOCK HINGES.
-
METALUX #22CZ SERIES
COLUMBIA #LCAT22 SERIES
NEORAY #22DR SERIES
AXIS #BRLED SERIES
NEORAY #22DR SERIES
AXIS #BRLED SERIES
EXTRUDED ALUMINUM HOUSING. WHITE
POWDER COAT FINISH. 0-10V DIMMING.
EXTRUDED ALUMINUM HOUSING. WHITE
POWDER COAT FINISH. 0-10V DIMMING.
EXTRUDED ALUMINUM HOUSING. WHITE
POWDER COAT FINISH. 0-10V DIMMING.
NEORAY #23DR SERIES
AXIS #BMRLED SERIES
EXTRUDED ALUMINUM HOUSING. WHITE
POWDER COAT FINISH. 0-10V DIMMING.
EXTRUDED ALUMINUM HOUSING. WHITE
POWDER COAT FINISH. 0-10V DIMMING.
LED
3000K
900
LUMEN
20W
L1
3FT DECORATIVE
RING
120V
SURFACE
L2
4FT DECORATIVE
RING
120V
SURFACE
3FT DECORATIVE
RING PENDANT
120V
4FT DECORATIVE
RING PENDANT
120V
PENDANT
PENDANT
CONTROL MEDIA
(LENS, LOUVER, ETC.)
ACRYLIC LENS
MANUFACTURER'S
SERIES NUMBERS
LUMINAIRE DESCRIPTION
NOTES
TECH LIGHTING #700BCMET
SERIES
SATIN NICKEL FINISH.
-
LED
3500K
8600
LUMENS
MIN
108W
MAX
ADVENT #AIP11847 SERIES
5IN. HEIGHT. 0-10V DIMMING. INTEGRAL
POWER SUPPLY. MATTE OPAL ACRYLIC
FINISH.
-
LED
3500K
12000
LUMENS
MIN
150W
MAX
ADVENT #AIP11848 SERIES
5IN. HEIGHT. 0-10V DIMMING. INTEGRAL
POWER SUPPLY. MATTE OPAL ACRYLIC
FINISH.
-
LED
3500K
8600
LUMENS
MIN
108W
MAX
ADVENT #AIP11847 SERIES
LED
3500K
12000
LUMENS
MIN
150W
MAX
ADVENT #AIP11848 SERIES
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
5IN. HEIGHT. 0-10V DIMMING. INTEGRAL
POWER SUPPLY. MATTE OPAL ACRYLIC
FINISH.
-
5IN. HEIGHT. 0-10V DIMMING. INTEGRAL
POWER SUPPLY. MATTE OPAL ACRYLIC
FINISH.
-
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
L5
LED TAPE LIGHT
120V
SURFACE/COVE
LED
3500K
207
LMNS/FT
3W/FT
WAC LIGHTING #LED-T24
SERIES
ACCLAIM #FLEX2I SERIES
L6
COLORED LINEAR
FIXTURE
120V
RECESSED
LED
ACCLAIM #FTA SERIES
-
FLEXIBLE SILICONE CASED. DIMMING.
-
-
-
WALL GRAZE
120V
RECESSED
-
DECORATIVE
PENDANT
120V
PENDANT
-
LED
3500K
657
LMNS/FT
12.5W/FT
10° X 60° BEAM
ANGLE,
POLYCARBONATE
LENS
LED
3000K
370
LUMENS
4W
PRESSED GLASS
DIFFUSER
PHILIPS #EW FUSE
POWERCORE SERIES
ARDRON LED #ECO COVE
INTEGRAL SERIES
ECOSENSE #TROV L50 SERIES
END-TO-END LOCKING POWER
CONNECTORS. DIE-CAST ALUMINUM
HOUSING. WHITE POWDER COAT FINISH.
EUREKA LIGHTING #4005-CLC
SERIES
0-10V DIMMING.
-
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
-
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
P2
DECORATIVE
PENDANT
120V
PENDANT
LED
3000K
840
LUMENS
10W
S8
LINEAR PENDANT
120V
SUSPENDED
LED
3500K
5000
LUMENS
46W
ACRYLIC LENS
ACRYLIC LENS
EUREKA LIGHTING #4404B
SERIES
0-10V DIMMING.
-
CORELITE MB SERIES
EXTRUDED ALUMINUM HOUSING. 0-10V
DIMMING. WHITE POWDER COAT FINISH.
PROVIDE CONTINUOUS ROW AS INDICATED
ON PLANS.
-
-
120V
RECESSED
LED
3500K
515
LMNS/FT
MIN
9W/FT
MAX
SATIN LENS
NEORAY #23DR SERIES
AXIS #BMRLED SERIES
EXTRUDED ALUMINUM HOUSING. WHITE
POWDER COAT FINISH. 0-10V DIMMING.
-
D1
RECESSED LED
DOWNLIGHT
120V
RECESSED
LED
3500K
1500
LUMENS
23W
SPECULAR CLEAR
PORTFOLIO #LD6A SERIES
PRESCOLITE #LC6LED SERIES
0-10V DIMMING. ALUMINUN HOUSING.
EXTRUDED ALUMINUM HEAT SINK.
ALUMINUM REFLECTORS. SELF-FLANGED.
-
D2
RECESSED LED
DOWNLIGHT - WALL
WASH
120V
RECESSED
LED
3500K
1500
LUMENS
23W
SPECULAR CLEAR
PORTFOLIO #LD6A SERIES
0-10V DIMMING. ALUMINUN HOUSING.
EXTRUDED ALUMINUM HEAT SINK.
ALUMINUM REFLECTORS. SELF-FLANGED.
SINGLE WALL WASH REFLECTOR.
-
D3
RECESSED LED
DOWNLIGHT
120V
RECESSED
LED
3500K
1500
LUMENS
25W
CYLINDRICAL
GLASS, POLISHED FROSTED
SHAPER #340-6 LED DL SERIES
WITH PORTFOLIO #LD615
SERIES
SPECTRUM #SGE6LEDOS
SERIES
0-10V DIMMING. ALUMINUN HOUSING.
EXTRUDED ALUMINUM HEAT SINK.
-
D4
LACTATION ROOM
120V
SURFACE
0-10V DIMMING.
-
E1
EXIT SIGN SINGLE
FACE EDGE LIT LED
DIE CAST HOUSING
120V
RECESSED
CLEAR FACE WITH MIRROR BACKGROUND,
CONFIRM ARROW ORIENTATION WITH
FLOOR PLANS, BRUSHED ALUMINUM
COVERPLATE, FULLY RECESSED HOUSING,
AC ONLY.
-
SURE-LITES #EUX6 SERIES
LAMPS
WALL
L4
3' RECESSED LINEAR
RED LETERS
STENCIL FACE
MOUNTING
120V
P1
NEORAY #23DR SERIES
AXIS #BMRLED SERIES
VOLTAGE
2' LINEAR SCONCE
L7
NEORAY #23DR SERIES
AXIS #BMRLED SERIES
FIXTURE TYPE
J2
L3
C6
LED
FIXTURE
LETTER
U2
2' UNDERCABINET
LIGHT
120V
SURFACE
LED
3500K
800
LUMENS
9W
W1
EXTERIOR WALL
SCONCE
120V
WALL
LED
W2
EXTERIOR WALL
SCONCE
120V
WALL
LED
4000K
55W
MAX
3800
LUMENS
TYPE 4
DISTRIBUTION
FAIL-SAFE #UCL SERIES
GARDCO #101L SERIES
NO SUBSTITUTIONS
STEEL HOUSING. WHITE POWDER COAT
FINISH. INTEGRAL ROCKER SWITCH.
-
CUSTOM FIXTURE TO MATCH EXISTING.
-
TRAPEZOID LED FIXTURE. WET LOCATION.
VERIFY FINISH WITH ARCHITECT.
1
GENERAL NOTES:
KEY NOTES:
A. SEE SPECIFICATION FOR ADDITIONAL LIGHT FIXTURE REQUIREMENTS
B. MINIMUM LUMENS LISTED FOR SOLID STATE LIGHT FIXTURES ARE DELIVERED LUMENS BASED ON PHOTOMETRIC
TESTING COMPLETED IN ACCORDANCE WITH IES LM-79 STANDARD.
1. OWNER'S CAMPUS STANDARD EXTERIOR LIGHT FIXTURE
MANUFACTURER, NO SUBSTITUTIONS.
2. VERIFY CEILING TYPE PRIOR TO ORDERING AND INSTALLING
FIXTURES.
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
Project No.
2263.001.00
Drawn By
MMK
Checked By
E2
E3
EXIT SIGN DOUBLE
FACE EDGE LIT LED
DIE CAST HOUSING
EXIT SIGN SINGLE
FACE LED DIE CAST
HOUSING
120V
120V
RECESSED
UNIVERSAL
LED
LED
RED LETERS
STENCIL FACE
RED LETERS
STENCIL FACE
SURE-LITES #EUX6 SERIES
DUAL-LITE #SE SERIES
SURE-LITES #CX SERIES
LIGHTALARMS #XLD SERIES
CLEAR FACE WITH MIRROR BACKGROUND,
CONFIRM ARROW ORIENTATION WITH
FLOOR PLANS, BRUSHED ALUMINUM
COVERPLATE, FULLY RECESSED HOUSING,
AC ONLY.
-
DIFFUSING OVERLAY, BLACK DIE CAST
ALUMINUM HOUSING, BRUSHED ALUMINUM
FACEFLATE, UNIVERSAL ARROWS, AC ONLY.
-
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:07:09 PM
E4
BATTERY PACK
120V
UNIVERSAL
LED
SURE-LITES #LEM SERIES
WHITE FINISH. PLASTIC HOUSING.
-
F1
4' INDUSTRIAL
120V
SURFACE/CHAIN 2-F32 T8
HUNG
4100K
COLUMBIA #KL SERIES
METALUX #DMF SERIES
WILLIAMS #82 SERIES
STEEL CHANNEL, WHITE POWDER COAT
WIRE GAURD, ONE ELECTRONIC BALLAST.
-
F2
2' WRAPAROUND
120V
SURFACE
LED
3500K
2000
LUMEN
23W
METALUX #SLWP SERIES
STEEL CHANNEL, WHITE POWDER COAT
WIRE GAURD, ONE ELECTRONIC BALLAST.
-
F3
4' WRAPAROUND
120V
SURFACE
LED
3500K
3900
LUMENS
40W
METALUX #SLWP SERIES
STEEL CHANNEL, WHITE POWDER COAT
WIRE GAURD, ONE ELECTRONIC BALLAST.
-
H1
STAIR LIGHT
120V
SURFACE
LED
3500K
4000
LUMENS
41W
FROSTED LENS
METALUX #SWLED SERIES
COLUMBIA #LBIL SERIES
INTEGRAL OCCUPANCY SENSOR. STEEL
HOUSING. POST PAINTED FINISH. ONE
DRIVER.
-
J1
4' WALL BRACKET
120V
SURFACE
2-F32 T8
4100K
#12 ARCYLIC
PRISMATIC
DIFFUSER
COLUMBIA #W SERIES
METALUX #BC SERIES
WILLIAMS #20 SERIES
POST PAINTED STEEL HOUSING. WHITE
INJECTED MOLDED END CAPS. HEAT SINK
EMBOSSMENTS IN BODY FOR BALLAST
COOLING. FIXTURE PAINTED WHITE. 1 - 2
LAMP ELECTRONIC BALLAST.
-
APERATURED
REFLECTOR WITH
20% UP LIGHT
No.
Date
Description
ELECTRICAL
SCHEDULES
E600
LIGHTING CONTROL PANEL SCHEDULE
LIGHTING CONTROL DEVICE SCHEDULE
SWITCH TYPE
COS1
COS2
CVS1
CVS2
D1
D5
EM
OS
P1
P2
R1
R2
R3
R4
R5
SW
VS
DEVICE DESCRIPTION
CEILING MOUNT DLM DIGITAL ULTRASONIC OCCUPANCY SENSOR
CEILING MOUNT STAND-ALONE LINE VOLTAGE DUAL TECHNOLOGY OCCUPANCY SENSOR
CEILING CORNER MOUNT DLM DIGITAL DUAL TECHNOLOGY VACANCY SENSOR
CEILING MOUNT DLM DIGITAL DUAL TECHNOLOGY VACANCY SENSOR
SINGLE BUTTON DLM DIGITAL DIMMING SWITCH
FIVE BUTTON DLM DIGITAL SCENE SELECTOR SWITCH WITH MANUAL RAISE/LOWER SWITCH
EMERGENCY LIGHTING CONTROL UNIT
WALL MOUNT OCCUPANCY SENSOR SWITCH
DIGITAL DLM DIMMING SINGLE ZONE PHOTOSENSOR
DIGITAL DLM DIMMING MULI-ZONE PHOTOSENSOR
DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROL - 1 RELAY
DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROL - 2 RELAY
DIGITAL ON/OFF/0-10V DIMMING ROOM CONTROL - 3 RELAY
DIGITAL PARTITION INTERFACE - INDICATES TO LIGHTING CONTROLS WHEN ROOM PARTITION IS
OPEN/CLOSED
SERIAL DATA INTERFACE - RS-232 INTERFACE TO CONNECT LIGHTING CONTROL SYSTEM TO 3RD PARTY AV
CONTROL SYSTEM
DIGITAL WALL SWITCH
WALL MOUNT VACANCY SENSOR SWITCH
MANUFACTURER SERIES
NUMBER
LMUC-100-2
DT-355
LMDX-100
LMDC-100
LMDM-101
LMSW-105
ELCU-200
DW-100
LMLS-400
LMLS-500
LMRC-211
LMRC-212
LMRC-213
LMIO-102
NOTES
3
1
1
1
LMDI-100
LMSW-100
DW-100
3
GENERAL NOTES:
A. SYSTEM IS DESIGNED AROUND A WATTSTOPPER DLM SERIES SYSTEM. DOCUMENTS INDICATE CONTROL DEVICES, SEQUENCE OF OPERATION, AND OVERRIDE CONTROL LOCATIONS. CONTRACTOR SHALL
PROVIDE ALL REQUIRED POWER PACKS, DIMMING POWER PACKS, BRIDGES, GATEWAYS, AND PROGRAMMING AS REQUIRED TO ACCOMPLISH THE CONTROL SEQUENCES INDICATED. NOT ALL PARTS AND PIECES
ARE SHOWN ON PLAN. CONTRACTOR SHALL PROVIDE ADDITIONAL COMPONENTS FOR A COMPLETE SYSTEM.
ELECTRICAL NOTES:
1. MOUNT ROOM CONTROLLER IN ACCESSIBLE CEILING SPACE ABOVE ENTRY DOOR (TYPICAL FOR SMALLER ENCLOSED SPACES).
2. MOUNT PLUG LOAD CONTROLLER NEXT TO ASSOCIATED ROOM CONTROLLER IN ACCESSIBLE CEILING.
3. TURN OFF 'AUTO SET' FUNCTION PRIOR TO INSTALLATION.
LIGHTING CONTROL SEQUENCE SCHEDULE
LC
#
LIGHTING CONTROL SEQUENCE SYMBOL FOUND ON LIGHTING PLAN(S).
LIGHTING
NETWORK
CONTROL
CONTROL
EMS/BAS
SEQUENCE CAPABILITIES SYSTEM
LC 01
NO
NO
LC 02
NO
NO
LC 03
YES
YES
LC 04
YES
YES
LC 05
NO
NO
LC 06
NO
NO
LC 07
NO
NO
LC 08
YES
YES
LC 09
NO
NO
TIME
CLOCK
NO
NO
YES
YES
NO
NO
NO
YES
NO
AUTO OFF
TIME
VACANCY OCCUPANCY
(MINUTES)
SENSOR
SENSOR
YES
NO
15
YES
NO
15
NO
YES
30
NO
YES
30
YES
NO
5
NO
NO
NA
NO
YES
20
NO
NO
NA
YES
NO
15
DIMMING
TYPE
0-10V
0-10V
0-10V
0-10V
NA
NA
NA
NA
0-10V
DIMMING
LEVEL
10%
10%
10%
10%
NA
NA
NA
NA
10%
SIDELIGHT
DAYLIGHT
HARVEST
(AUTOMATIC/ AFTERHOURS OVERRIDE
SWITCHED)
OVERRIDE DURATION
AUTOMATIC
NA
NA
NA
NA
NA
NA
YES
2 HOURS
AUTOMATIC
YES
2 HOURS
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NO
NA
AUTOMATIC
NA
NA
LIGHTING
CONTROL PANEL
RELAY
NUMBER
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-11
LCP-21
LCP-21
LCP-21
LCP-21
LCP-21
LCP-21
LCP-21
LCP-31
LCP-31
LCP-31
LCP-31
LCP-31
LCP-31
LCP-31
LCP-31
LCP-B1
LCP-B1
LCP-B1
LCP-B1
LCP-B1
LCP-B1
RELAY DESCRIPTION
CONTROL DESCRIPTION
PANEL
CIRCUIT
NUMBER
1
2
3
4
5
6
7
8
9
10
11
12
25
26
27
28
29
30
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING - EMERGENCY
CORRIDOR LIGHTING - EMERGENCY
CORRIDOR LIGHTING - EMERGENCY
CORRIDOR LIGHTING - EMERGENCY
ENTRY VESTIBULE - EMERGENCY.
ENTRY VESTIBULE - EMERGENCY.
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
N-11
N-11
N-11
N-11
3
3
3
11
N-12
N-11
N-11
N-11
N-11
N-11
N-11
E-B1
E-B1
E-B1
E-B1
E-B1
E-B1
21
7
7
7
10
3
9
4
4
4
4
8
11
1
2
6
13
14
15
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING - OPTIONAL
CORRIDOR LIGHTING - EMERGENCY
CORRIDOR LIGHTING - EMERGENCY
CORRIDOR LIGHTING - EMERGENCY
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
N-21
N-21
O-21A
E-21
E-21
E-21
8
5
6
4
16
3
1
2
3
4
13
14
15
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING
CORRIDOR LIGHTING - EMERGENCY
CORRIDOR LIGHTING - EMERGENCY
CORRIDOR LIGHTING - EMERGENCY
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
N-31
N-31
N-31
N-31
E-21
E-21
6
9
13
11
7
17
1
2
8
9
10
CORRIDOR LIGHTING
CORRIDOR LIGHTING
EXTERIOR WALL PACKS
FRONT ENTRY LIGHTING POLES
EXTERIOR POLES BETWEEN
EASTMAN AND RIVERVIEW
EXTERIOR POLE IN NE PARKING LOT
EXTERIOR POLE IN SOUTH PARKING
LOT
CORRIDOR LIGHTING - EMERGENCY
EXTERIOR WALL PACKS EMERGENCY
EXTERIOR WALL PACKS EMERGENCY
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
ENERGY MANAGEMENT SYSTEM
ENERGY MANAGEMENT SYSTEM
ENERGY MANAGEMENT SYSTEM
N-B1
N-B1
O-B1A
N-B1
N-B1
5
6
21
9
13
ENERGY MANAGEMENT SYSTEM
ENERGY MANAGEMENT SYSTEM
N-B1
N-B1
13
11
TIME OF DAY, OCCUPANCY SENSOR OVERRIDE, DIMMING
ENERGY MANAGEMENT SYSTEM
E-B1
E-B1
3
10
ENERGY MANAGEMENT SYSTEM
E-B1
27
LCP-B1
LCP-B1
11
12
LCP-B1
LCP-B1
13
14
LCP-B1
24
NOTES
1
1
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
1
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
Date
NOTES
1
1
GENERAL NOTES:
A.
BASIS OF DESIGN MANUFACTURER - DOUGLAS LIGHTING CONTROLS #LITEPAK. EQUAL BY LC&D, WATTSTOPPER, OR LEVITON WITH ENGINEER PRIOR
APPROVAL.
B.
PANEL TO HAVE DIGITAL ASTRO TIME CLOCK AND COMPARTMENTS FOR SEPARATION OF DUAL VOLTAGE/SERVICE BRANCHES.
C.
ALL LIGHTING CONTROL PANELS SHALL BE NETWORKED TOGETHER FOR SINGLE STATION MONITORING.
D.
ALL TIME OF DAY SETTING, PUSH BUTTON FUNCTIONS, LIGHT LEVEL SETTINGS, AND OCCUPANCY SENSOR OVERRIDES SHALL BE COORDINATED AND
REVIEWED WITH OWNER, CAMPUS FACILITY STAFF, AND ELECTRICAL ENGINEER IN A PRE-INSTALLATION/PRE-PROGRAMMING MEETING WITH A FACTORY
REPRESENTATIVE PRESENT FROM LIGHTING CONTROL SYSTEM MANUFACTURER. DIV. 26 CONTRACTOR RESPONSIBLE FOR COORDINATING AND
FACILITATING MEETING.
E.
EMERGENCY RELAY SHALL MEET NEC (NFPA 70) UL 924 REQUIREMENTS FOR EMERGENCY LIGHTING CONTROL. UPON LOSS OF NORMAL POWER,
EMERGENCY LIGHTING SHALL TURN ON TO FULL BRIGHTNESS.
50358
07/24/15
Project For
ELECTRICAL NOTES:
1. EMERGENCY RELAY REQUIRED.
1
STUDENT HEALTH AND
ACADEMIC RENOVATION
GENERAL NOTES:
A. PROVIDE ALL COMPONENTS, WIRING AND PROGRAMMING NECESSARY TO MAKE A FUNCTIONAL LIGHTING CONTROL SYSTEM WITH CONTROLS AS NOTED ABOVE.
B. CONTROLS MANUFACTURER OR REPRESENTATIVE SHALL PROVIDE COMPLETE WIRING DIAGRAM IN SHOP DRAWING SUBMITTAL.
C. IF DIMMING IS CALLED FOR IN SCHEDULE, IT IS THE CONTRACTOR'S RESPONSIBILITY TO VERIFY AND PROVIDE ALL NECESSARY PARTS, BALLASTS, DRIVERS, ETC. TO PROVIDE THE DIMMING
FUNCTION.
D. CONTRACTOR TO PROVIDE ALL WIRING NECESSARY INCLUDING ANY 0-10V CONTROL WIRING AS REQUIRED.
E. CONTRACTOR SHALL REVIEW ALL COMPONENTS AND REQUIRED WIRING METHODS WITH CONTROLS MANUFACTURER OR REPRESENTATIVE PRIOR TO BID.
F. ALL TIME OF DAY SETTING, PUSH BUTTON FUNCTIONS, LIGHT LEVEL SETTINGS, AND OCCUPANCY SENSOR OVERRIDES SHALL BE COORDINATED AND REVIEWED WITH OWNER, CAMPUS
FACILITY STAFF, AND ELECTRICAL ENGINEER IN A PRE-INSTALLATION/PRE-PROGRAMMING MEETING WITH A FACTORY REPRESENTATIVE PRESENT FROM LIGHTING CONTROL SYSTEM
MANUFACTURER. DIV. 26 CONTRACTOR RESPONSIBLE FOR COORDINATING AND FACILITATING MEETING.
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
ELECTRICAL NOTES:
1.
2.
LOCAL DIMMER SWITCH SHALL OVERRIDE AUTOMATIC DAYLIGHTING CONTROLS WITHIN ROOM. DAYLIGHTING PHOTOSENSOR SHALL TAKE CONTROL AFTER NEXT OCCUPANCY SENSOR TIME
OUT.
ROOMS SHALL FUNCTION AS TWO SEPERATE SPACES WHEN THE PARTITION IS CLOSED, AND SHALL FUNCTION AS ONE SPACE WHEN PARTITION IS OPEN. CONTROL SWITCHES AT ENTRY
POINTS SHALL AUTOMATICLLY ADJUST SCENE CONTROL BASE ON PARTITION INTERFACE DEVICE. LIGHTING SHALL INTERFACE WITH 3RD PARTY AV SYSTEM. REFER TO FLOOR PLANS FOR
ADDITIONAL INFORMATION RELATED TO CONTROL DEVICES.
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
ELECTRICAL
SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:23 PM
E601
NAME: NRD-B1
NAME: NR-B1A
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
MIN. BUS RATING: 1000 A
MAIN SIZE: 1000 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
NR-B1A
--NR-11A
--NR-21A
--Spare
--Spare
--Spare
--Spare
1
--1
--1
---------
39 --
--
41 --
--
225 A
--225 A
--400 A
--400 A
--400 A
--200 A
--100 A
3
--3
--3
--3
--3
--3
--3
--
--
A
B
C
MOUNTING: SURFACE
POLES TRIP NOTES
5528... 1260...
3420... 720 VA
3420...
0 VA
4320... 10840...
3240... 12240...
4140... 1008...
1926... 13560...
16740... 10440...
16020... 1166...
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
--TOTAL LOAD:
54768 VA
46800 VA
TOTAL AMPS:
458 A
392 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LIGHTING LOAD (DA_L)
128 VA
125%
RECEPTACLE LOAD (DA_R)
129600 VA
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
MOTOR LOAD TOTALS
0 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
17160 VA
100%
SPARE CAPACITY (DA_SP)
100%
0 VA
0 VA
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
NR-B2
--NR-22A
--NR-12A
--Spare
--Spare
--Spare
--Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
225 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3
244 VA 244 VA
--
--
3
--3
--3
--3
--3
--3
--3
225 A
--400 A
--225 A
--200 A
--100 A
--100 A
--200 A
1
--1
--1
---
--
--
--
--
40
39 --
--
--
--
--
--
42
41 --
--
45320 VA
378 A
LOAD DEMAND (VA)
160 VA
69800 VA
-------
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
146888 VA
87120 VA
408 A
242 A
0 VA
0 VA
17160 VA
ELEV PIT RECEPT & LIGHT
DA_R ELEVATOR EQUIPMENT ROOM 004
DA_R BUILDING SUPPORT 033
DA_R UNISEX TOILET 016
MENS LOCKER ROOM 015
ELECTRIC WATER COOLERS
EXERCISE/TRAINING 009
TREADMILL
TREADMILL
DA_R EXAM/ CONSULT 011
DATA ROOM 021
DATA ROOM 021
DATA ROOM 021
Spare
Spare
Spare
Spare
Spare
NR-B1B
B
C
MOUNTING: SURFACE
POLES TRIP NOTES
CIRCUIT DESCRIPTION
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
ELEV PIT RECEPT & LIGHT
DA_R MECHANICAL ROOM 019
DA_R ELECTRICAL ROOM 022
WOMANS LOCKER ROOM 051
DA_R SHOWER/RESTROOM 007
DA_R CORRIDOR 008
TREADMILL
TREADMILL
TREADMILL
DA_R EXAM/CONSULT 010
DATA ROOM 021
DATA ROOM 021
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
20 A
Spare
40
--0 VA
0 VA
1
20 A
TOTAL LOAD:
5528 VA
3420 VA
3420 VA
TOTAL AMPS:
46 A
29 A
29 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
128 VA
125%
160 VA
RECEPTACLE LOAD (DA_R)
12240 VA
10 KVA @ 100%, Remaining @ 50%
11120 VA
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
0 VA
0 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
100%
SPARE CAPACITY (DA_SP)
100%
Spare
42
1
720 VA 540 VA
540 VA 900 VA
720 VA 900 VA
540 VA 540 VA
360 VA 900 VA
900 VA 180 VA
180 VA 180 VA
180 VA 180 VA
900 VA 900 VA
180 VA 180 VA
180 VA 180 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
360 VA
0 VA
0 VA
360 VA
0 VA
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
12368 VA
11280 VA
34 A
31 A
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1. PROVIDE THERMAL MAGNETIC MOLDED CASE CIRCUIT BREAKER WITH ELECTRONIC TRIP WITH ADJUSTABLE INSTANTANEOUS SETTING.
2.
3.
4.
NOTES:
1. PROVIDE GFCI BREAKER.
2.
3.
4.
CIRCUIT DESCRIPTION
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
POLE MOUNTED RECEPTACLES
POLE MOUNTED RECEPTACLES
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
39 Spare
41 Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
1
A
360 VA
B
C
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
720 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
POLES TRIP NOTES
0 VA
360 VA
0 VA
MOUNTING: SURFACE
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
360 VA
360 VA
3A
3A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
0 VA
0 VA
720 VA
NOTES TRIP POLES
A
L - WOMEN'S LOCKER ROOM AND...
LIGHTING - EXAM/CONSULT 011 AND 010
LIGHTING - CORRIDOR 001
LIGHTING - SUMP ROOM 056
FRONT SITE LIGHTING
PARKING LOT LIGHTING
SIDE SITE LIGHTING
HAND DRYER - SHOWER/ RESTROOM 006
-HAND DRYER - UNISEX TOILET/SHOWER...
-HAND DRYER - SHOWER/ RESTROOM 013
-Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
-20 A
-20 A
-20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
2
-2
-2
-1
1
1
1
1
1
232 VA 208 VA
20 A
1
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
1
20 A
Spare
40
39 Spare
1
20 A
Spare
42
41 Spare
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
720 VA
720 VA
2A
2A
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
CIRCUIT DESCRIPTION
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
0 VA
0A
LOAD DEMAND (VA)
Date
CKT
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
B
C
CIRCUIT DESCRIPTION
CKT
L - MENS LOCKER ROOM AND...
LIGHTING - EXERCISE/TRAINING 009
LIGHTING - CORRIDOR 034
LIGHTING - ELECTRICAL AND DATA...
LIGHTING - SHOWER/ RESTROOM 006
LIGHTING - UNISEX TOILET/SHOWER 016
HAND DRYER - SHOWER RESTROOM 005
-HAND DRYER - SHOWER/ RESTROOM 007
-HAND DRYER - SHOWER/ RESTROOM 014
-HAND DRYER - SHOWER/ RESTROOM 050
-Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
20 A
20 A
20 A
20 A
20 A
20 A
20 A
-20 A
-20 A
-20 A
-20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
20 A
1
0 VA
0 VA
1
20 A
TOTAL LOAD:
10559 VA
9354 VA
9054 VA
TOTAL AMPS:
88 A
78 A
75 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
13009 VA
125%
16261 VA
RECEPTACLE LOAD (DA_R)
720 VA
10 KVA @ 100%, Remaining @ 50%
720 VA
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
3216 VA
100%
3216 VA
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
3216 VA
3216 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
9180 VA
100%
9180 VA
SPARE CAPACITY (DA_SP)
100%
Spare
42
----
172 VA 140 VA
192 VA 448 VA
400 VA 224 VA
440 VA 288 VA
300 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
0 VA
0 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
-----
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
28967 VA
32219 VA
80 A
89 A
Project No.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
Drawn By
NOTES:
1.
2.
3.
4.
NOTES:
1.
2.
3.
4.
Date
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
1
3
5
7
9
11
13
15
17
CIRCUIT DESCRIPTION
PASSENGER ELEVATOR E1
--PASSENGER ELEVATOR CONTROLLER
PASSENGER ELEVATOR SHUNT TRIP
PASSENGER ELEVATOR CAB
SERVICE ELEVATOR CONTROLLER
SERVICE ELEVATOR SHUNT TRIP
SERVICE ELEVATOR CAB
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
A
B
C
MMK
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
MOUNTING: SURFACE
© Copyright RSP Architects 2015. All rights reserved.
Revisions
POLES TRIP NOTES
110 A
3
9391... 14411...
3
175 A
---9391... 14411...
-----9391... 1441...
--20 A
1
180 VA 828 VA
3
20 A
20 A
1
180 VA 828 VA
--20 A
1
180 VA 828 VA
--20 A
1
180 VA 192 VA
1
20 A
20 A
1
180 VA 696 VA
1
20 A
20 A
1
180 VA 0 VA
1
20 A
TOTAL LOAD:
25182 VA
25686 VA
24990 VA
TOTAL AMPS:
210 A
214 A
208 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
192 VA
125%
240 VA
RECEPTACLE LOAD (DA_R)
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
74585 VA
100%
74585 VA
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
74585 VA
74585 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
1080 VA
100%
1080 VA
SPARE CAPACITY (DA_SP)
100%
-----
CIRCUIT DESCRIPTION
CKT
SERVICE ELEVATOR E2
--SP 01
--LIGHTING - ELEVATOR EQUIPMENT ROO...
TF 01
Spare
2
4
6
8
10
12
14
16
18
No.
Date
Description
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
75857 VA
75905 VA
211 A
211 A
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
2263.001.00
Checked By
NAME: RD-B1
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:29 PM
07/24/15
Project For
POLES TRIP NOTES
160 VA 916 VA
50358
MOUNTING: SURFACE
1
1
1
1
1
1
2
-2
-2
-2
-1
1
1
1
1
CKT
James A. LeClaire
Registration Number
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Signature
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
Dunham Job #: 415134
NAME: N-B1
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
RSP Architects
TOTALS
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
CKT
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
NAME: NR-B1B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, 200% NEUTRAL
PANEL SCHEDULES
E602
NAME: O-B1A
NAME: O-B1B
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
CIRCUIT DESCRIPTION
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
NOTES TRIP POLES
A
B
C
MOUNTIN... SURFACE
POLES TRIP NOTES
DA_MI MENS RESTROOM 107
DA_MI CORRIDOR 002
DA_MI DATA ROOM 021
PUPLIC LAV/URINAL SENSOR
EMS PANEL
HWP-01
--DA_MI MECHANICAL ROOM 052
LAB TOILET WATER SHUT OFF
DA_L
Spare
Spare
Spare
Spare
20 A
1
540 VA 900 VA
1
20 A
20 A
1
360 VA 720 VA
1
20 A
1
20 A
1
180 VA 180 VA
1
20 A
20 A
1
180 VA 180 VA
1
20 A
20 A
1
180 VA 3036...
3
50 A
50 A
3
3036... 3036...
-----3036... 3036...
-----3036... 1320...
3
25 A
20 A
1
180 VA 1320...
--20 A
1
180 VA 1320...
--20 A
1
700 VA 0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
TOTAL LOAD:
18757 VA
18158 VA
17177 VA
TOTAL AMPS:
158 A
153 A
143 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
4852 VA
125%
6065 VA
RECEPTACLE LOAD (DA_R)
19560 VA
10 KVA @ 100%, Remaining @ 50%
14780 VA
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
24771 VA
100%
24771 VA
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
24771 VA
24771 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
4860 VA
100%
4860 VA
SPARE CAPACITY (DA_SP)
100%
1
-----
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
DA_MI HALLWAY 266
DA_MI
ACCESS CONTROL POWER SUPPLY
BLUE LIGHT CALL STATION
HWP-02
--SCP 01
--Spare
Spare
Spare
Spare
Spare
CKT
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
CIRCUIT DESCRIPTION
RACK - DATA ROOM 021
RACK - DATA ROOM 021
RACK - DATA ROOM 021
DATA ROOM 021
DATA ROOM 021
DATA ROOM 021
DATA ROOM 021
DATA ROOM 021
DA_MI
Spare
Spare
Spare
Spare
Spare
Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
54092 VA
50525 VA
150 A
140 A
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
NOTES TRIP POLES
1
1
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
A
B
C
360 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
0 VA
180 VA
0 VA
0 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
0 VA
0 VA
1080 VA
9A
LOAD DEMAND (VA)
CIRCUIT DESCRIPTION
RACK - DATA 131
RACK - DATA 131
DATA 131
DATA 131
DATA 131
BLUE LIGHT CALL STATION
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
3240 VA
3600 VA
3600 VA
10 A
10 A
Dunham Job #: 415134
0 VA
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
360 VA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
360 VA 360 VA
1260 VA
1260 VA
11 A
11 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
3240 VA
POLES TRIP NOTES
360 VA 360 VA
180 VA
MOUNTIN... SURFACE
360 VA
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER.
2.
3.
4.
NOTES:
1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER.
2.
3.
4.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
NAME: E-B1
NAME: ND-B1
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
MIN. BUS RATING: 100 A
MAIN SIZE: 100 A
MAIN OPTIONS: MLO, FEED THRU LUGS, 200% NEUTRAL
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
BACK OF HOUSE EMERGENCY
CORRIDOR EMERGENCY
FIRST FLOOR EXIT LIGHTS
STAIR LIGHTING
FIRST FLOOR NAC PANEL - ELECTRICAL...
VESTIBULE 135
SMOKE GUARD
SMOKE GUARD
SMOKE GUARD
LIGHTING - WOMANS LOCKER ROOM 051
LIGHTING - STAIR D S001
LIGHTING - WOMENS RESTROOM 103
LIGHTING - UNISEX TOILET 132
DA_L
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
640 VA 35 VA
20 A
1
C
MOUNTING: SURFACE
POLES TRIP NOTES
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
EXIT LIGHTS
DA_L OPEN/GATHERING 101
FIRST FLOOR EXIT LIGHTS
NORTH ENTRY 112
EXTERIOR WALL SCONCE
FIRST FLOOR NAC PANEL - ELECTRICAL...
FACP
SMOKE GUARD
LIGHTING - SHOWER/ RESTROOM 007
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
60 A
--60 A
--175 A
--100 A
--100 A
--100 A
--60 A
3
--3
--3
--3
--3
--3
--3
3864... 7452...
--
--
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
39 --
--
20 A
1
0 VA
0 VA
1
20 A
TOTAL LOAD:
3680 VA
3788 VA
2155 VA
TOTAL AMPS:
33 A
34 A
18 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
6155 VA
125%
7694 VA
RECEPTACLE LOAD (DA_R)
180 VA
10 KVA @ 100%, Remaining @ 50%
180 VA
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
0 VA
0 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
2700 VA
100%
2700 VA
SPARE CAPACITY (DA_SP)
100%
Spare
42
41 --
--
39 Spare
1
41 Spare
120 VA 501 VA
60 VA
25 VA
256 VA 64 VA
180 VA 400 VA
32 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 136 VA
168 VA
0 VA
192 VA
0 VA
64 VA
96 VA
500 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
1
1
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
9623 VA
11162 VA
27 A
31 A
AHUS 01
--AHUR 01
--AHUS 03
--Spare
--Spare
--Spare
--Spare
MIN. BUS RATING: 1200 A
MAIN SIZE: 1200 A
MAIN OPTIONS: MCB, 200% NEUTRAL
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
-------------
B
C
3864... 7452...
3864... 3036...
3864... 3036...
3864... 3036...
1441... 5796...
14411... 5796...
14411... 5796...
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
--TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
115268 VA
POLES TRIP NOTES
3864... 7452...
0 VA
38423 VA
38423 VA
320 A
320 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
115268 VA
0 VA
MOUNTING: SURFACE
0 VA
3
--3
--3
--3
--3
--3
--3
100 A
--50 A
--90 A
--100 A
--200 A
--30 A
--60 A
--
--
--
--
38423 VA
320 A
LOAD DEMAND (VA)
115268 VA
0 VA
115268 VA
CIRCUIT DESCRIPTION
CKT
AHUS 02
--AHUR 02
--AHUR 03
--Spare
--Spare
--Spare
--Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
--
--
40
--
--
42
-------------
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
115268 VA
115268 VA
320 A
320 A
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER.
2.
3.
4.
NOTES:
1.
2.
3.
4.
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
PANEL SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:36 PM
E603
NAME: NR-B2
NAME: NR-12A
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, 200% NEUTRAL
NOTES TRIP POLES
A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
360 VA 900 VA
20 A
1
DA_R MECHANICAL ROOM 019
DA_R BLDG MECHANICAL 052
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
39 Spare
41 Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
B
720 VA
C
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
0 VA
1260 VA
720 VA
11 A
7A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
1980 VA
POLES TRIP NOTES
0 VA
0 VA
0 VA
MOUNTING: SURFACE
0 VA
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
DA_R PHYSICAL THERAPY (COMMUNITY...
DA_R
DA_R HEALTH ED & PROMOTION COORD...
DA_R UCHOOSE & RC 121
GRAD ASSIST 122
DA_R RECOVERY COMMUNITY RESOUR...
COFFEE MAKER
DA_R PEER ED/ UCHOOSE STUDENT...
REFRIGERATOR
DA_MI PEER ED/ UCHOOSE STUDENT...
DA_R GRAD ASSIST 122
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
540 VA 900 VA
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
DA_R STAIR S002
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
1
20 A
Spare
40
39 Spare
1
20 A
Spare
42
41 Spare
0 VA
0A
LOAD DEMAND (VA)
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
1980 VA
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
1980 VA
1980 VA
5A
5A
0 VA
0 VA
0 VA
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
B
C
720 VA 720 VA
720 VA 720 VA
540 VA 540 VA
1080... 540 VA
1800... 900 VA
1080... 540 VA
360 VA 1400...
1760... 360 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
0 VA
13560 VA
10440 VA
115 A
87 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
29700 VA
0 VA
CIRCUIT DESCRIPTION
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
DA_R CIRCULATION 118
DA_R UNISEX TOILET 132
DA_R UCHOOSE & RC 120
DA_R RESEARCH DIRECTOR 125
DA_R
DA_R RECOVERY COMMUNITY RESOUR...
DA_R PEER ED/ UCHOOSE STUDENT...
DA_R PEER ED/ UCHOOSE STUDENT...
MICROWAVE
DA_R RECOVERY COMMUNITY RESOUR...
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
20 A
Spare
40
1
20 A
Spare
42
11660 VA
99 A
LOAD DEMAND (VA)
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
19850 VA
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
35660 VA
25810 VA
99 A
72 A
0 VA
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
5960 VA
POLES TRIP NOTES
1080... 360 VA
360 VA
MOUNTING: RECESSED
5960 VA
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
NOTES:
1.
2.
3.
4.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
NAME: N-B2
NAME: N-12
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
BLDG MECHANICAL 052
MECHANICAL ROOM 019 & BUILDING...
SWH 01
DWP 01
-UH 002
UH 003
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
NOTES TRIP POLES
A
B
20 A
20 A
20 A
20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
2
-1
1
1
1
1
1
1
1
1
1
1
1
1
1
704 VA 320 VA
20 A
1
C
MOUNTING: SURFACE
POLES TRIP NOTES
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
MENS RESTROOM
COMMUNITY PARTNERS
HAND DRYER - MENS RESTROOM 107
-HAND DRYER - UNISEX TOILET 132
-AUTO DOOR OPENER
AUTO DOOR OPENER - SOUTH ENTRY 109
AUTO DOOR OPENER - SOUTH ENTRY 109
AUTO DOOR OPENER
LIGHTING - CIRCULATION 118
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
-20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
2
-2
-1
1
1
1
1
1
1
1
1
1
1
1
1
228 VA 747 VA
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
25 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
BLDG JANITOR 018 & MECH ROOM 32
UH 001
AHU LIGHTS AND RECEPTACLES
AHU LIGHTS AND RECEPTACLES
AHU LIGHTS AND RECEPTACLES
GFS 01
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
1
20 A
Spare
40
39 Spare
20 A
1
0 VA
0 VA
1
20 A
TOTAL LOAD:
4855 VA
4108 VA
3376 VA
TOTAL AMPS:
41 A
35 A
28 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
2954 VA
125%
3693 VA
RECEPTACLE LOAD (DA_R)
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
6048 VA
100%
6048 VA
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
6048 VA
6048 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
2700 VA
100%
2700 VA
SPARE CAPACITY (DA_SP)
100%
Spare
42
41 Spare
39 Spare
41 Spare
--
704 VA 300 VA
180 VA 180 VA
960 VA 180 VA
960 VA 180 VA
300 VA 1656...
300 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
12339 VA
13078 VA
34 A
36 A
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, 200% NEUTRAL
B
C
MOUNTING: RECESSED
POLES TRIP NOTES
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
20 A
Spare
40
20 A
1
0 VA
0 VA
1
20 A
TOTAL LOAD:
2391 VA
1964 VA
1060 VA
TOTAL AMPS:
21 A
18 A
9A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
1226 VA
125%
1533 VA
RECEPTACLE LOAD (DA_R)
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
1392 VA
100%
1392 VA
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
1392 VA
1392 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
2160 VA
100%
2160 VA
SPARE CAPACITY (DA_SP)
100%
Spare
42
---
180 VA 340 VA
180 VA 696 VA
180 VA 696 VA
180 VA 180 VA
180 VA 180 VA
180 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
180 VA
0 VA
100 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
20 A
20 A
20 A
20 A
20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
CKT
PEER ED/ UCHOOSE STUDENT STAFF...
FIRE/SMOKE DAMPERS
RECOVERY COMMUNITY RESOURCE...
CUH-102
CUH-104
HAND DRYER - MENS RESTROOM 107
-Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
448 VA 360 VA
1
1
1
1
1
2
-1
1
1
1
1
1
1
1
1
1
1
1
CIRCUIT DESCRIPTION
--
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
5415 VA
5722 VA
15 A
16 A
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
NOTES:
1.
2.
3.
4.
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
PANEL SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:42 PM
E604
NAME: NR-12B
NAME: N-11
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
39 Spare
20 A
1
41 Spare
20 A
1
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
A
0 VA
B
C
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
5860 VA
5940 VA
49 A
50 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
HEALTH ED INTERDISCIPLINARY 116 &...
CIRCULATION 113 & VESTIBULE
SHHS INTERDISCIPLINARY 123 &...
CIRCULATION
COLORED STRIP
COLORED STRIP
HAND DRYER - WOMENS RESTROOM 103
-HAND DRYER - WOMENS RESTROOM 103
-CUH-101
AUTO DOOR OPENER - NORTH ENTRY 112
AUTO DOOR OPENER
AUTO DOOR OPENER
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
-20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
2
-2
-1
1
1
1
1
1
1
1
1
600 VA 277 VA
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
1
20 A
Spare
40
39 Spare
20 A
1
1
20 A
Spare
42
41 Spare
20 A
1
---
B
C
720 VA 400 VA
1317... 480 VA
49 VA 196 VA
49 VA 600 VA
180 VA 180 VA
180 VA 180 VA
180 VA
180 VA
18640 VA
14820 VA
52 A
41 A
0 VA
0 VA
1000 VA
0 VA
0 VA
696 VA
0 VA
180 VA 696 VA
180 VA 180 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
MOUNTING: SURFACE
POLES TRIP NOTES
1065... 256 VA
0 VA
TOTAL LOAD:
8279 VA
6754 VA
TOTAL AMPS:
70 A
56 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LIGHTING LOAD (DA_L)
8889 VA
125%
RECEPTACLE LOAD (DA_R)
720 VA
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
3216 VA
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
MOTOR LOAD TOTALS
3216 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
6660 VA
100%
SPARE CAPACITY (DA_SP)
100%
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
13820 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
6840 VA
57 A
LOAD DEMAND (VA)
0 VA
1000 VA
POLES TRIP NOTES
0 VA
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
17640 VA
MOUNTING: RECESSED
CIRCUIT DESCRIPTION
CKT
WOMENS RESTROOM 103
ELECTRICAL AND DATA ROOMS
RESEARCH AREA
OFFICES AND GRAD ASSISTANTS
COVE - OPEN/GATHERING 101
FCU 01 & FCU 02
FIREPLACE
FIRE/SMOKE DAMPER
MOTORIZED PARTITION
--CUH-103
AUTO DOOR OPENER - NORTH ENTRY 112
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
1
1
1
1
1
1
1
3
--1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
15 A
20 A
20 A
20 A
--20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
1
20 A
Spare
42
7294 VA
61 A
LOAD DEMAND (VA)
11111 VA
720 VA
3216 VA
0 VA
3216 VA
---
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
22327 VA
24549 VA
62 A
68 A
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
6660 VA
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
NOTES:
1.
2.
3.
4.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
NAME: NR-11B
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
VENDING MACHINE
VENDING MACHINE
DA_R HEALTH ED INTERDISCIPLINARY 116
DA_R HEALTH ED INTERDISCIPLINARY 116
DA_R SHHS INTERDISCIPLINARY 123
DA_R WOMENS RESTROOM 103
DA_R
DA_R LACTATION ROOM 106
DA_R RESEARCHER 128
DA_R RESEARCH DATA 126
DATA 131
DATA 131
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
180 VA 180 VA
39 Spare
20 A
1
41 Spare
20 A
1
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
Dunham Job #: 415134
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NAME: NR-11A
RSP Architects
B
C
540 VA 720 VA
540 VA 900 VA
720 VA 180 VA
360 VA 720 VA
540 VA 1080...
720 VA 720 VA
720 VA 720 VA
540 VA 360 VA
180 VA 180 VA
180 VA 180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
11700 VA
POLES TRIP NOTES
180 VA 360 VA
0 VA
4320 VA
3240 VA
37 A
27 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
MOUNTING: SURFACE
0 VA
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
CIRCUIT DESCRIPTION
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, 200% NEUTRAL
NOTES TRIP POLES
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
VENDING MACHINE
DA_R CIRCULATION 113
DA_R HEALTH ED INTERDISCIPLINARY 116
DA_R SHHS INTERDISCIPLINARY 123
EXTERIOR RECEPTACLE
DA_R
DA_R
DA_R RESEARCH ASST. 129
DA_R RESEARCH COORDINATOR 127
DA_R
DATA 131
DATA 131
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
Spare
40
39 Spare
20 A
1
1
20 A
Spare
42
41 Spare
20 A
1
4140 VA
36 A
LOAD DEMAND (VA)
10850 VA
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
11700 VA
10850 VA
32 A
30 A
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
A
0 VA
B
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
POLES TRIP NOTES
0 VA
0 VA
0 VA
C
MOUNTING: SURFACE
0 VA
0 VA
0 VA
0 VA
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
0 VA
0 VA
0A
0A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
CIRCUIT DESCRIPTION
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
20 A
Spare
40
1
20 A
Spare
42
0 VA
0A
LOAD DEMAND (VA)
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
0 VA
0 VA
0A
0A
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
NOTES:
1.
2.
3.
4.
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
PANEL SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:49 PM
E605
NAME: NR-22A
NAME: N-22
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
NOTES TRIP POLES
A
B
C
EXAM ROOMS 237, 234, 235, 271, 238, 233
EXAM ROOMS 221, 220, 219, 226, 225, 269
OFFICES 222, 223, 224, 227, 270, 228
243, 244, 245, 246, 248, 247 RECEPTION...
HAND DRYER - LAB TOILET 268
-HALLWAY 266
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
2
-1
1
1
1
1
1
1
1
1
1
1
1
39 Spare
20 A
1
41 Spare
20 A
1
--
102 VA 180 VA
102 VA 180 VA
520 VA 180 VA
480 VA 180 VA
180 VA
180 VA
0 VA
0 VA
20 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
TOTAL LOAD:
4213 VA
3634 VA
TOTAL AMPS:
35 A
30 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LIGHTING LOAD (DA_L)
5016 VA
125%
RECEPTACLE LOAD (DA_R)
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
3816 VA
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
MOTOR LOAD TOTALS
3816 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
2520 VA
100%
SPARE CAPACITY (DA_SP)
100%
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
FIRE/SMOKE DAMPERS
HAND DRYER - STAFF TOILET 255
-HAND DRYER - PATIENT TOILET 256
-Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
BUSINESS MANAGER 244
CASHIER 245
STUDENT INSURANCE ADVOCATE 247
REFERRAL COORDINATOR OFFICE 248
COPIER/PRINTER - WORK 246
GENERAL RECEPTACLES Room 246, 266,...
RECEPTION 243
RECEPTION 243
GENERAL RECEPTACLES SUB WAITING...
WIREMOLD - LABORATORY 251
WIREMOLD - LABORATORY 251
MEDICAL DIRECTOR OFFICE 222
MD OFFICE 223
MD OFFICE 224
NP OFFICE 227
NP OFFICE 270
NURSING MANAGER 228
CORRIDOR 259 & 265
DA_R TREATMAN ROOM 232
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
720 VA 360 VA
0 VA
CIRCUIT DESCRIPTION
1
2
-2
-1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
-20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
39 ICE MAKER - HALLWAY 258
1
20 A
Spare
42
41 ELECTRIC WATER COOLER - HALLWAY 258
---
3554 VA
30 A
LOAD DEMAND (VA)
6270 VA
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
3816 VA
0 VA
3816 VA
11401 VA
12655 VA
32 A
35 A
2520 VA
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
1
20 A
1
B
C
720 VA 360 VA
720 VA 360 VA
1000... 360 VA
540 VA 360 VA
360 VA 360 VA
180 VA 360 VA
1260... 360 VA
540 VA 360 VA
540 VA 360 VA
900 VA 360 VA
720 VA 720 VA
720 VA 360 VA
720 VA 360 VA
720 VA 720 VA
720 VA 180 VA
720 VA 360 VA
360 VA 360 VA
1560... 540 VA
180 VA 720 VA
10840 VA
12240 VA
91 A
103 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
25920 VA
CIRCUIT DESCRIPTION
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
EXAM ROOM 219
EXAM ROOM 219
EXAM ROOM 220
EXAM ROOM 220
EXAM ROOM 221
EXAM ROOM 221
EXAM ROOM 226
EXAM ROOM 226
EXAM ROOM 225
EXAM ROOM 225
EXAM ROOM 269
EXAM ROOM 269
NURSE STATION 231
NURSE STATION 231
DA_R TREATMAN ROOM 232
MED/ NOURISH ROOM 230
STAFF TOILET 255
PROCESSING ROOM 229
CLEAN SUPPLY 236
1
20 A
HALLWAY 258 & 266 & STAIR S202
40
1
20 A
REFRIGERATOR - LABORATORY 251
42
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
17960 VA
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, 200% NEUTRAL
NOTES TRIP POLES
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
39 Spare
20 A
1
41 Spare
20 A
1
A
0 VA
B
C
0 VA
1400...
0 VA
1440...
0 VA
1080...
0 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
900 VA
1200...
0 VA
0 VA
720 VA
360 VA
0 VA
0 VA
360 VA
1000...
0 VA
0 VA
180 VA
540 VA
0 VA
0 VA
POLES TRIP NOTES
180 VA
0 VA
0 VA
MOUNTING: RECESSED
360 VA
0 VA
0 VA
0 VA
0 VA
0 VA
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
3460 VA
4280 VA
31 A
37 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
3960 VA
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
7240 VA
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
NAME: N-21
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
5940 VA
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
0 VA
0 VA
NOTES:
1. PROVIDE GFCI BREAKER.
2.
3.
4.
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
RSP Architects
33160 VA
25200 VA
92 A
70 A
NOTES:
1.
2.
3.
4.
CIRCUIT DESCRIPTION
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
TOTALS
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
CKT
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
10080 VA
84 A
LOAD DEMAND (VA)
0 VA
7240 VA
POLES TRIP NOTES
720 VA 360 VA
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
MOUNTING: RECESSED
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NAME: NR-22B
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
CKT
POLES TRIP NOTES
720 VA
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
MOUNTING: RECESSED
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
0 VA
CIRCUIT DESCRIPTION
CKT
CKT
ELECTRIC WATER COOLERS
DA_R LABORATORY 251
DA_R LABORATORY 251
DA_R LABORATORY 251
MICROWAVE - MEDICAL DIRECTOR...
MINI FRIDGE - MEDICAL DIRECTOR OFFI...
PRINTER - NURSE STATION 231
AUTOCLAVE - PROCESSING ROOM 229
PHLEBOTOMY 250 REC
LAB TOILET 268 REC
DA_R LABORATORY 251
DA_R LABORATORY 251
FUME HOOD - LABORATORY 251
SCALE - HALLWAY 266
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
20 A
20 A
20 A
20 A
-20 A
-20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
2
-2
-2
-1
1
1
1
1
1
1
1
1
1
180 VA 600 VA
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
39 Spare
20 A
1
1
20 A
Spare
42
41 Spare
20 A
1
5940 VA
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
9900 VA
9900 VA
27 A
27 A
0 VA
0 VA
3960 VA
AUTO DOOR OPENER - HALLWAY 266
FIRE/SMOKE DAMPERS
DA_L WAITING CIRCULATION 260
HAND DRYER - UNISEX RESTROOM 202
-HAND DRYER - MENS RESTROOM 201
-HAND DRYER - WOMENS RESTROOM 203
-AUTO DOOR OPENER - WAITING...
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2160 VA
18 A
LOAD DEMAND (VA)
1
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
----
B
C
POLES TRIP NOTES
360 VA 102 VA
673 VA 1016...
180 VA 160 VA
180 VA 544 VA
180 VA 456 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
TOTAL LOAD:
4705 VA
3952 VA
TOTAL AMPS:
40 A
33 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LIGHTING LOAD (DA_L)
5489 VA
125%
RECEPTACLE LOAD (DA_R)
720 VA
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
1224 VA
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
MOTOR LOAD TOTALS
1224 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
4860 VA
100%
SPARE CAPACITY (DA_SP)
100%
MOUNTING: SURFACE
1
1
1
1
1
1
1
2
-1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
CIRCUIT DESCRIPTION
CKT
208, 209, 210, 205
EXAM ROOMS 214, 215, 213, 218, 217, 216
PHARMACY AREA
WAITING CIRCULATION 260
STORAGE, JANITOR, ELECTRICAL AND...
RESTROOMS
AUTO DOOR OPENER - WAITING...
HAND DRYER - WOMENS RESTROOM 203
-Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
20 A
Spare
40
20 A
Spare
42
4469 VA
38 A
LOAD DEMAND (VA)
6861 VA
720 VA
1224 VA
0 VA
1224 VA
STUDENT HEALTH AND
ACADEMIC RENOVATION
--
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
13126 VA
14498 VA
36 A
40 A
Project No.
Drawn By
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1. PROVIDE GFCI BREAKER.
2.
3.
4.
NOTES:
1.
2.
3.
4.
MMK
Checked By
Date
4860 VA
2263.001.00
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
PANEL SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:04:56 PM
E606
NAME: NR-21A
NAME: NR-21B
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
UCHOOSE ADMINISTRATOR 208
SHS DIRECTORS 209
SHS ASST DIRECTOR 210
Room 211, 212
Room 201, 202
WOMENS RESTROOM 203
CONFERENCE 205
CONFERENCE 205
Room 260, S201
CONSULTATION AREA 239
PHARMACY 241
PHARMACY 241, 240
OTC SALES 240
GENERAL RECEPTACLES Room 260, 262,...
WAITING CIRCULATION 260
WAITING CIRCULATION 260
EXAM ROOM 271
EXAM ROOM 271
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
720 VA 360 VA
20 A
1
39 Spare
41 Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
B
720 VA 360 VA
540 VA 360 VA
360 VA 360 VA
180 VA 360 VA
1080... 360 VA
1080... 360 VA
360 VA 360 VA
720 VA 360 VA
540 VA 360 VA
540 VA 360 VA
720 VA 360 VA
900 VA 360 VA
720 VA 360 VA
1080... 360 VA
360 VA 360 VA
360 VA 360 VA
0 VA
720 VA
0 VA
720 VA
0 VA
19260 VA
16740 VA
161 A
140 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
540 VA
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
ISOLATION EXAM 213
ISOLATION EXAM 213
EXAM ROOM 214
EXAM ROOM 214
EXAM ROOM 215
EXAM ROOM 215
EXAM ROOM 218
EXAM ROOM 218
EXAM ROOM 217
EXAM ROOM 217
Room 216
EXAM ROOM 216
TRIAGE ROOM 237
TRIAGE ROOM 237
CONSULT ROOM (E-EXAM) 234
CONSULT ROOM (E-EXAM) 234
CONSULT ROOM (CAPS) 235
CONSULT ROOM (CAPS) 235
INJECTION ROOM 238
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
1
20 A
OBSERVATION (IVS) - EKG 233
40
39 Spare
1
20 A
DA_R PHARMACY 241
42
41 Spare
29030 VA
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
52020 VA
32990 VA
144 A
92 A
3960 VA
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
540 VA 180 VA
20 A
1
DA_R PHARMACY 241
HALLWAY 257 & 258
SCALE - HALLWAY 258
ELECTRICAL 253 & JANITOR 252
DATA 254
DATA 254
DATA 254
DATA 254
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
CIRCUIT DESCRIPTION
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
16020 VA
134 A
LOAD DEMAND (VA)
0 VA
3960 VA
POLES TRIP NOTES
720 VA 360 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
48060 VA
C
MOUNTING: SURFACE
B
C
360 VA
180 VA
0 VA
0 VA
0 VA
180 VA
0 VA
0 VA
0 VA
180 VA
180 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
11520 VA
9900 VA
97 A
83 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
2
-1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
CIRCUIT DESCRIPTION
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
20 A
Spare
40
20 A
Spare
42
18950 VA
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
3960 VA
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
SECOND FLOOR EXIT LIGHTS
DA_L HALLWAY 257
DA_L
THIRD FLOOR EXIT LIGHTS
CRASH CART - HALLWAY 258
PATIENT TOILET 256 - LIGHTING
SECOND FLOOR NAC PANEL -...
THIRD FLOOR NAC PANEL - ELECTRICAL...
DA_L OPEN STUDY 352
SMOKE GUARD
SMOKE GUARD
Spare
Spare
Spare
Spare
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
NAME: O-21A
MIN. BUS RATING: 100 A
MAIN SIZE: 100 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
Consultants
0 VA
0 VA
NOTES:
1.
2.
3.
4.
CIRCUIT DESCRIPTION
612.677.7100
612.677.7499 fax
www.rsparch.com
31860 VA
22910 VA
88 A
64 A
NOTES:
1.
2.
3.
4.
CKT
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
TOTALS
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
RSP Architects
Dunham Job #: 415134
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NAME: E-21
CKT
DA_MI MENS RESTROOM 201
-Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
--
10440 VA
88 A
LOAD DEMAND (VA)
0 VA
3960 VA
POLES TRIP NOTES
540 VA 180 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
27900 VA
MOUNTING: SURFACE
A
B
C
MOUNTING: SURFACE
POLES TRIP NOTES
20 A
1
45 VA 50 VA
1
20 A
20 A
1
220 VA 60 VA
1
20 A
20 A
1
260 VA 55 VA
1
20 A
20 A
1
350 VA 512 VA
1
20 A
20 A
1
180 VA 81 VA
1
20 A
20 A
1
130 VA 180 VA
1
20 A
1
20 A
1
180 VA 180 VA
1
20 A
1
20 A
1
180 VA 634 VA
1
20 A
20 A
1
673 VA 180 VA
1
20 A
20 A
1
180 VA 180 VA
1
20 A
20 A
1
180 VA 0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
TOTAL LOAD:
2061 VA
1535 VA
1478 VA
TOTAL AMPS:
17 A
13 A
12 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
3307 VA
125%
4134 VA
RECEPTACLE LOAD (DA_R)
180 VA
10 KVA @ 100%, Remaining @ 50%
180 VA
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
0 VA
0 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
1440 VA
100%
1440 VA
SPARE CAPACITY (DA_SP)
100%
1
1
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
CIRCUIT DESCRIPTION
SECOND FLOOR EXIT LIGHTS
DA_L WAITING CIRCULATION 260
THIRD FLOOR EXIT LIGHTS
DA_L STAIR S202
STAFF TOILET - LIGHTING
SECOND FLOOR NAC PANEL -...
THIRD FLOOR NAC PANEL - ELECTRICAL...
DA_L WAITING CIRCULATION 260
SMOKE GUARD
SMOKE GUARD
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
LIGHTING - NURSE STATION
LIGHTING - PHLEBOTOMY 250
LIGHTING - TREATMENT, MED/NOURISH,...
LIGHTING - INJECTION ROOM 238
OVERHEAD SURGICAL LIGHT - TREATMA...
EXAM TABLE - TREATMAN ROOM 232
FVAV-101
FVAV-301
Spare
Spare
Spare
Spare
Spare
Spare
Spare
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
5074 VA
5901 VA
14 A
16 A
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
NOTES TRIP POLES
A
B
C
MOUNTIN... SURFACE
POLES TRIP NOTES
20 A
1
240 VA 720 VA
1
20 A
20 A
1
921 VA 720 VA
1
20 A
20 A
1
480 VA 400 VA
1
20 A
20 A
1
720 VA 180 VA
1
20 A
20 A
1
180 VA 180 VA
1
20 A
20 A
1
180 VA 865 VA
1
20 A
20 A
1
865 VA 0 VA
1
20 A
20 A
1
865 VA 0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
20 A
1
0 VA
0 VA
1
20 A
TOTAL LOAD:
8125 VA
7546 VA
8165 VA
TOTAL AMPS:
68 A
63 A
69 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LOAD DEMAND (VA)
LIGHTING LOAD (DA_L)
4152 VA
125%
5190 VA
RECEPTACLE LOAD (DA_R)
16320 VA
10 KVA @ 100%, Remaining @ 50%
13160 VA
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
2595 VA
100%
2595 VA
LARGEST MOTOR - BRANCH (DA_LBM)
125%
0 VA
MOTOR LOAD TOTALS
2595 VA
2595 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
720 VA
100%
720 VA
SPARE CAPACITY (DA_SP)
100%
1
1
CIRCUIT DESCRIPTION
DA_L ISOLATION EXAM 213
DA_L EXAM ROOM 219
CORRIDOR
ACCESS CONTROL POWER SUPPLY
ACCESS CONTROL POWER SUPPLY
FVAV-201
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
CKT
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
23836 VA
21714 VA
66 A
60 A
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER.
2.
3.
4.
NOTES:
1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER.
2.
3.
4.
Project No.
Drawn By
Checked By
Date
2263.001.00
Author
Checker
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
PANEL SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:06:40 PM
E607
NAME: O-21B
NAME: NR-32A
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
RACK - DATA 254
DATA 254
DATA 254
DATA 254
DATA 254
DA_R NURSE STATION 231
DA_R NURSE STATION 231
DA_R TREATMAN ROOM 232
DA_R TREATMAN ROOM 232
PHARMACY REFRIGERATOR
PHARMACY REFRIGERATOR
RECEPTION 243
DA_R EXAM ROOM 219
DA_R EXAM ROOM 225
DA_R CONSULT ROOM (CAPS) 235
DA_R HALLWAY 258
Spare
Spare
Spare
1
39 Spare
41 Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
1
A
B
C
POLES TRIP NOTES
360 VA 360 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 720 VA
1080... 1560...
720 VA 360 VA
360 VA 180 VA
180 VA 360 VA
720 VA 720 VA
720 VA 720 VA
540 VA 720 VA
720 VA 720 VA
720 VA 720 VA
720 VA 720 VA
360 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
0 VA
5400 VA
4680 VA
46 A
39 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
16320 VA
MOUNTING: SURFACE
0 VA
1
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
RACK - DATA ROOM 399
DATA ROOM 399
DATA ROOM 399
DATA ROOM 399
REFRIGERATOR - MED/NOURISH ROOM...
ICE MAKER MED/NOURSIH ROOM 230
UC REFRIG - MED/NOURISH ROOM 230
DA_R CLEAN SUPPLY 236
DA_R ADMIN SUPPORT/ RECEPTION 321
DA_R ISOLATION EXAM 213
DA_R EXAM ROOM 215
DA_R EXAM ROOM 218
DA_R EXAM ROOM 221
DA_R TRIAGE ROOM 237
DA_R INJECTION ROOM 238
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
39 Spare
1
20 A
Spare
42
41 Spare
6240 VA
53 A
LOAD DEMAND (VA)
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
13160 VA
16320 VA
13160 VA
45 A
37 A
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
NOTES TRIP POLES
A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1260... 1000...
20 A
1
Room 383, 382
GROUP THERAPY ROOM 380
THERAPIST PREDOCTORAL 303
THERAPIST PREDOCTORAL 379
AOD COUNSELOR 377
AOD COUNSELOR 378
STAFF TOILET 361
THERAPIST OFFICE 376
THERAPIST OFFICE 371
THERAPIST OFFICE 372
THERAPIST OFFICE 373
THERAPIST OFFICE 374
THERAPIST OFFICE 375
CASE MANAGER INTERN 387
CASE MANAGER OFFICE 388
CAPS DIRECTOR OFFICE 389
CAPS DIRECTOR OFFICE 389
FILE & ARCHIVE 385
Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
0 VA
0 VA
0 VA
CIRCUIT DESCRIPTION
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
B
C
720 VA 900 VA
720 VA 360 VA
720 VA 720 VA
720 VA 720 VA
0 VA
720 VA
720 VA
720 VA
0 VA
720 VA
0 VA
900 VA
0 VA
0 VA
0 VA
0 VA
360 VA
0 VA
0 VA
0 VA
720 VA
720 VA
720 VA
0 VA
720 VA
720 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
0 VA
5860 VA
5940 VA
49 A
50 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
17640 VA
0 VA
CIRCUIT DESCRIPTION
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
COPIER/PRINTER
DA_R
DA_R
DA_R
DA_R
DA_R OPEN STUDY 352
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
20 A
Spare
40
1
20 A
Spare
42
Consultants
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
1000 VA
NOTES:
1. PROVIDE BREAKER LOCK ON INDICATED CIRCUIT BREAKER.
2.
3.
4.
NOTES:
1.
2.
3.
4.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
NAME: N-31
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, 200% NEUTRAL
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
Room 364, 365, 366, 367, 368, 369 THERAP...
Room 398, 370 INTERN OFFICES
Room379, 303, 380, 383, 382 RELAXATION...
Room 376, 378, 377, 361 COUNSELOR,...
DA_L
Room 359, 360, 134
EF 02
--Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
--20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
3
--1
1
1
1
1
1
1
1
1
1
480 VA 360 VA
20 A
1
41 Spare
612.677.7100
612.677.7499 fax
www.rsparch.com
18640 VA
14820 VA
52 A
41 A
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
39 Spare
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
13820 VA
RSP Architects
Dunham Job #: 415134
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NAME: N-32
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
6840 VA
57 A
LOAD DEMAND (VA)
0 VA
1000 VA
POLES TRIP NOTES
900 VA 900 VA
180 VA
MOUNTING: RECESSED
---
B
C
POLES TRIP NOTES
480 VA 620 VA
732 VA 360 VA
321 VA 180 VA
120 VA 180 VA
728 VA 828 VA
444 VA 828 VA
444 VA 828 VA
444 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
MOUNTING: RECESSED
0 VA
CIRCUIT DESCRIPTION
CKT
CKT
Room 371, 372, 373, 374, 375 OFFICES
Room 389, 388, 387
FIRE/SMOKE DAMPERS
HAND DRYER - STAFF TOILET 361
-EF 03
--Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
A
20 A
15 A
20 A
20 A
20 A
20 A
20 A
20 A
-20 A
-20 A
--
1
1
1
1
1
1
1
2
-2
-2
--
696 VA 640 VA
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
20 A
1
20 A
20 A
20 A
20 A
-20 A
--20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
39 Spare
1
20 A
Spare
42
41 Spare
0 VA
3092 VA
26 A
LOAD DEMAND (VA)
4740 VA
3816 VA
0 VA
3816 VA
----
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
8377 VA
9325 VA
23 A
26 A
720 VA
MIN. BUS RATING: 225 A
MAIN SIZE: 225 A
MAIN OPTIONS: MCB, 200% NEUTRAL
NOTES TRIP POLES
1
1
1
2
-3
--1
1
1
1
1
1
1
1
1
1
1
0 VA
20 A
1
TOTAL LOAD:
2613 VA
2672 VA
TOTAL AMPS:
22 A
22 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LIGHTING LOAD (DA_L)
3792 VA
125%
RECEPTACLE LOAD (DA_R)
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
3816 VA
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
MOTOR LOAD TOTALS
3816 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
720 VA
100%
SPARE CAPACITY (DA_SP)
100%
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CUH-303
EF-01
AUTO DOOR OPENER - CAPS ENTRY 323
FIRE/SMOKE DAMPERS
OPEN STUDY - LTG
PRIVATE WAITING - LTG
Lighting
HAND DRYER - UNISEX RESTROOM 301
-HAND DRYER - WOMENS RESTROOM 355
-HAND DRYER - MENS RESTROOM 354
--
----
B
C
POLES TRIP NOTES
528 VA 424 VA
180 VA 160 VA
360 VA 40 VA
554 VA 180 VA
340 VA 384 VA
49 VA 720 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA 180 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
3045 VA
2406 VA
TOTAL AMPS:
26 A
21 A
LOAD CLASSIFICATION
CONNECTED LOAD (VA)
DEMAND FACTOR
LIGHTING LOAD (DA_L)
2330 VA
125%
RECEPTACLE LOAD (DA_R)
720 VA
10 KVA @ 100%, Remaining @ 50%
MOTOR LOAD - HEATING (DA_HM)
100%
MOTOR LOAD - COOLING (DA_CM)
100%
MOTOR LOAD - GENERAL (DA_M)
1224 VA
100%
LARGEST MOTOR - BRANCH (DA_LBM)
125%
MOTOR LOAD TOTALS
1224 VA
KITCHEN LOAD (DA_K)
DEMAND PER NEC
ELECTRONIC LOAD (DA_EL)
100%
ELECTRIC HEATING (DA_E)
100%
DWELLING UNIT - GENERAL LOAD (DA_D)
10 KVA @ 100%, Remaining @ 40%
MISCELLANEOUS LOAD (DA_MI)
2520 VA
100%
SPARE CAPACITY (DA_SP)
100%
0 VA
MOUNTING: SURFACE
0 VA
CIRCUIT DESCRIPTION
CKT
Room 390, 391, 392, 393, 394, 396, 397
Restrooms
DA_L OPEN STUDY 352
DA_L
DA_L SHHS GROUP THERAPY ROOM 395
DA_L DATA ROOM 399
DA_R SHHS FACULTY COMMAND CENTE...
HAND DRYER - MENS RESTROOM 354
-HAND DRYER - WOMENS RESTROOM 355
-AUTO DOOR OPENER - OPEN STUDY 352
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
1
1
1
1
1
1
2
-2
-1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
-20 A
-20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
20 A
Spare
40
1
20 A
Spare
42
1784 VA
15 A
LOAD DEMAND (VA)
2913 VA
720 VA
1224 VA
0 VA
1224 VA
---
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
7235 VA
7818 VA
20 A
22 A
Project No.
Drawn By
Checked By
Date
2520 VA
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
NOTES:
1.
2.
3.
4.
2263.001.00
Author
Checker
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
PANEL SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:06:46 PM
E608
NAME: NR-32B
NAME: NR-31A
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CKT
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
CIRCUIT DESCRIPTION
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MLO, 200% NEUTRAL
NOTES TRIP POLES
ROOF RECEPTACLE
ROOF RECEPTACLE
DA_R HALLWAY 258
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
39 Spare
41 Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
1
A
180 VA
B
C
0 VA
720 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
1080 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
POLES TRIP NOTES
0 VA
180 VA
0 VA
MOUNTING: RECESSED
180 VA
180 VA
2A
2A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
0 VA
0 VA
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
CIRCUIT DESCRIPTION
CKT
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
SHHS CLINICAL ROOM 390
SHHS CLINICAL ROOM 391
SHHS CLINICAL ROOM 392
SHHS CLINICAL ROOM 393
SHHS CLINICAL ROOM 394
SHHS GROUP THERAPY ROOM 395
SHHS FACULTY COMMAND CENTER 396
GENERAL REC Room 352, 302, S301
UNISEX RESTROOM 301 REC
DATA ROOM 399
GENERAL REC Room 352, 340
STAFF BREAK ROOM 360
REFRIGERATO,R KITCHEN 134
REFRIGERATOR, KITCHEN 134
COFFEE MAKER, KITCHEN 134
KITCHEN 134
KITCHEN 134
CONFERENCE /GROUP ROOM 359
DA_R SHHS FACULTY COMMAND CENTE...
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
540 VA 540 VA
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
1
20 A
Spare
40
39 Spare
1
20 A
Spare
42
41 Spare
720 VA
6A
LOAD DEMAND (VA)
1080 VA
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
1080 VA
1080 VA
3A
3A
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MCB, FEED THRU LUGS, 200% NEUTRAL
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
B
C
540 VA 540 VA
540 VA 540 VA
540 VA 540 VA
900 VA 540 VA
720 VA 720 VA
720 VA 720 VA
360 VA 720 VA
180 VA 1080...
1080... 720 VA
1440... 720 VA
720 VA 1260...
720 VA 720 VA
1800... 720 VA
360 VA 900 VA
360 VA 360 VA
1080... 180 VA
720 VA 180 VA
180 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
0 VA
10260 VA
8820 VA
87 A
74 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
25560 VA
360 VA
CIRCUIT DESCRIPTION
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
PRACTICUM THERAPY 364
PRACTICUM THERAPY 365
PRACTICUM THERAPY 366
PRACTICUM THERAPY 367
PRACTICUM THERAPY 368
PRACTICUM THERAPY 369
PRACTICUM INTERN OFFICE 398
PRACTICUM INTERN OFFICE 398
PRACTICUM INTERN OFFICE 398
PRACTICUM INTERN OFFICE 398
CAPS INTERN OFFICE 370
CAPS INTERN OFFICE 370
GENERAL RECEPTACLES CIRCULATION...
DA_R SHHS FACULTY COMMAND CENTE...
DA_R SHHS FACULTY COMMAND CENTE...
DA_R CAPS INTERN OFFICE 370
DA_R PRACTICUM INTERN OFFICE 398
DATA ROOM 399
DATA ROOM 399
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
20 A
DATA ROOM 399
40
1
20 A
DA_R JANITOR 353
42
10080 VA
86 A
LOAD DEMAND (VA)
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
17780 VA
29160 VA
21380 VA
81 A
59 A
0 VA
0 VA
0 VA
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
3600 VA
POLES TRIP NOTES
540 VA 540 VA
0 VA
MOUNTING: SURFACE
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
3600 VA
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
NOTES:
1.
2.
3.
4.
Signature
James A. LeClaire
Registration Number
Date
50358
07/24/15
Project For
NAME: NR-31B
VOLTAGE: 120/208
PHASE: 3
WIRE: 4
MIN. BUS RATING: 400 A
MAIN SIZE: 400 A
MAIN OPTIONS: MLO, 200% NEUTRAL
CKT
CIRCUIT DESCRIPTION
NOTES TRIP POLES
A
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
37
WOMENS RESTROOM 355 REC
DA_R OPEN STUDY 352
ROOF RECEPTACLE
DA_R SHHS FACULTY COMMAND CENTE...
DA_R OPEN STUDY 352
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
180 VA 360 VA
20 A
1
39 Spare
41 Spare
LOAD CLASSIFICATION
LIGHTING LOAD (DA_L)
RECEPTACLE LOAD (DA_R)
MOTOR LOAD - HEATING (DA_HM)
MOTOR LOAD - COOLING (DA_CM)
MOTOR LOAD - GENERAL (DA_M)
LARGEST MOTOR - BRANCH (DA_LBM)
MOTOR LOAD TOTALS
KITCHEN LOAD (DA_K)
ELECTRONIC LOAD (DA_EL)
ELECTRIC HEATING (DA_E)
DWELLING UNIT - GENERAL LOAD (DA_D)
MISCELLANEOUS LOAD (DA_MI)
SPARE CAPACITY (DA_SP)
B
720 VA
720 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
1260 VA
1080 VA
12 A
10 A
DEMAND FACTOR
125%
10 KVA @ 100%, Remaining @ 50%
100%
100%
100%
125%
0 VA
360 VA
0 VA
0 VA
20 A
1
TOTAL LOAD:
TOTAL AMPS:
CONNECTED LOAD (VA)
2160 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
180 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
0 VA
POLES TRIP NOTES
0 VA
360 VA
0 VA
C
MOUNTING: SURFACE
DEMAND PER NEC
100%
100%
10 KVA @ 100%, Remaining @ 40%
100%
100%
0 VA
0 VA
CIRCUIT DESCRIPTION
CKT
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
20 A
UC REFRIGERATOR - NURSING MANAGE...
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
Spare
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
1
20 A
Spare
40
1
20 A
Spare
42
180 VA
2A
LOAD DEMAND (VA)
2160 VA
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
TOTALS
TOTAL CONN. LOAD:
TOTAL EST. DEMAND:
TOTAL CONN. CURRENT:
TOTAL EST. DEMAND...
2520 VA
2520 VA
7A
7A
0 VA
0 VA
Project No.
Drawn By
Checked By
Date
360 VA
GENERAL NOTES:
A. SEE RISER DIAGRAM FOR CALCULATED AVAILABLE FAULT CURRENT. PANELBOARD AND ASSOCIATED DEVICES WITHIN PANELBOARD ASSEMBLY SHALL HAVE A SHORT CIRCUIT
CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN ON RISER DIAGRAM.
NOTES:
1.
2.
3.
4.
STUDENT HEALTH AND
ACADEMIC RENOVATION
2263.001.00
Author
Checker
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
PANEL SCHEDULES
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:06:53 PM
E609
THERMOSTAT
BY TEMP.
CONTROL
CONTRACTOR
1 1/2" TYP.
DETAIL NOTES
DIMMER SWITCH
(WHERE INDICATED
ON PLANS)
1
#12 WIRE TO FIXTURE(S) OR AS INDICATED.
PROVIDE IN-LINE FUSE AND FUSE HOLDER WITH
BREAKAWAY CAPABILITY, FERRAZ SHAMUT FEY,
COOPER HEB SERIES, (4)(20)(XX) AMPERE
BUSSMAN TYPE KTK OR PRE-APPROVED EQUAL.
2
PROVIDED BUSHED RIGID CONDUITS. CONDUIT
STUBBED UP ADJACENT TO HANDHOLE; NUMBER
AND SIZE AS REQUIRED. CAP SPARE CONDUITS.
3
COPPER EQUIPMENT GROUNDING CONDUCTOR ATTACH TO INTERNAL LUG WELDED TO
INTERIOR OF POLE. CONDUCTOR TO BE SAME
SIZE AND TYPE AS SUPPLY PHASE CONDUCTOR.
6
1
3
8
2
7
6
1
4
INSULATED COPPER GROUNDING CONDUCTOR
ATTACHED TO INTERNAL LUG WELDED TO
INTERIOR OF POLE. SIZE PER NFPA 70.
EXOTHERMIC WELD TO DRIVEN GROUND ROD.
5
3/4"x10' COPPER GROUND ROD (MIN 6" BELOW
GRADE).
6
FIXTURE POLE - REFER TO SITE LIGHTING
FIXTURE SCHEDULE AND LIGHTING STANDARD
DETAILS.
7
SET TOP OF CONCRETE FOUNDATION ABOVE
GRADE AS INDICATED ON SITE LIGHTING
FIXTURE SCHEDULE.
8
PROVIDE DOUBLE ANCHOR BOLT NUTS ABOVE
AND BELOW POLE BASE. ADJUST TO PLUMB
POLE. ANCHOR BOLT ASSEMBLY SHALL BE
PROVIDED BY POLE MFG. INSTALL ACCORDING
TO MFG TEMPLATE. USE SHRINK PROOF GROUT
ON BASE. FURNISH BASE COVER FOR POLES.
9
REINFORCED ROUND CONCRETE FOUNDATION
BASE. CONCRETE 5-7% AIR ENTRAINED 4000 PSI
MINIMUM. 3 INCH MINIMUM CONCRETE COVER
ON BARS AND TIES. FINISH CONCRETE ABOVE
GRADE LEVEL AND BEVEL EDGE 45 DEGREES.
FOOTING SHALL BE FORMED WHERE SOIL
CONDITIONS REQUIRE. CHAMFER ALL EDGES
OF CONCRETE BASE 1/2". TREAT EXPOSED
CONCRETE WITH PROSOCO SALT-GUARD
WATER-BASED OR PRE-APPROVED EQUAL.
3
8
4
10
10
36" MIN
36" MIN
5
9
5
9
11
11
12
~ ~
~
~ ~
~
THERMOSTAT
BY TEMP.
CONTROL
CONTRACTOR
12
15
MOTORIZED SHADE SWITCH BY
OTHERS
(WHERE INDICATED ON PLANS)
15
13
13
14 "Y"
14 "Y"
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
SIDE CLOSEST TO DOOR
Consultants
10
FULLY COMPACTED BACKFILL.
11
CIRCUIT CONDUCTORS AND CONDUIT TO
POWER SOURCE OR NEXT POLE.
12
#4 BARS VERTICAL AT 6" EACH FACE (UNLESS
NOTED OTHERWISE ON SITE LIGHTING FIXTURE
SCHEDULE).
Dunham Job #: 415134
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
"X"
4'-0" A.F.F.
STD. MULTI - GANG
BRUSHED STAINLESS
STEEL SWITCH PLATE
BASE HEIGHT NOTES
BASE HEIGHT SCHEDULE
1.
POLE HEIGHT "Y" DEPTH (FEET) "X" WIDTH (INCHES)
2.
NOTES:
ALL DEVICES AND COVER PLATES SHALL HAVE THE SAME COLOR.
SWITCH PLATE COVER DETAIL
NO SCALE
DETAIL B
13
#3 BARS AT 12" ON CENTER HORIZONTALLY
(UNLESS NOTED OTHERWISE ON SITE LIGHTING
FIXTURE SCHEDULE).
14
REFER TO SITE LIGHTING FIXTURE SCHEDULE
FOR DEPTH "Y" AND WIDTH "X" DIMENSIONS.
15
PROVIDE A MINIMUM ONE INCH RACEWAY FOR
SECURITY DEVICES (AND CCTV CAMERAS).
RACEWAY SHALL EXTEND TO SECURITY SYSTEM
HEADEND UNLESS NOTED OTHERWISE.
LIGHT SWITCHES
MACHINE ENGRAVED
BLACK FILLED LETTERS
1
14
DETAIL A
SHADES
1.
"X"
14
DIMMER SWITCH
(WHERE INDICATED
ON PLANS)
3.
2
BASE HEIGHT IS TYPICAL FOR SEDIMENTARY AND
FOLIATED ROCK SOIL, ROUND TAPERED, POLES EXPOSED
TO WINDS OF 70MPH, WITH ONE LIGHT FIXTURE.
CONFIRM WITH STRUCTURAL ENGINEER FOR BASE WIDTH
AND DEPTH REQUIREMENTS IF ENVIRONMENTAL
VARIABLES DIFFER FROM ABOVE. [REFER TO POLE DEPTH
CALCULATION FOR ADDITIONAL INFORMATION].
DESIGNER SHALL CHOOSE THE MOST APPLICABLE
DETAIL, A OR B, FOR THE PROJECT. THE PRIMARY
DIFFERENCE IS HEIGHT OF FOUNDATION ABOVE GROUND.
EXTERIOR POLE BASE DETAIL WITH GROUNDING
NO SCALE
612.677.7100
612.677.7499 fax
www.rsparch.com
7
2
4
OR
RSP Architects
REBAR
<14'
5
16
(4)#5 REBAR
<14'
4.5
24
(4)#5 REBAR
15'-29'
6
24
(6)#5 REBAR
30'-40'
8
24
(8)#5 REBAR
30'-40'
6
30
(8)#5 REBAR
James A. LeClaire
Registration Number
50358
Date
07/24/15
Project For
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
LIGHTING DETAILS
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:05:02 PM
E700
DETAIL NOTES:
1.
TYPICAL, CONNECTIONS TO
OTHER SYSTEMS, PIPING,
BUILDING STEEL, LIGHTNING
PROTECTION, AND OTHER
SYSTEMS.
WALL
2" MIN
GROUND LUG
TWO HOLE COMPRESSION
TYPICAL, SEE NOTE 5
GROUND
BUSBAR
SEE NOTE 4
REFER TO TYPICAL SERVICE GROUNDING DETAIL AND
GROUNDING RISER DIAGRAM FOR ADDITIONAL
INFORMATION.
MAXIMUM O.D.
OF CONDUIT
MAXIMUM
OPENING SIZE
MINIMUM PUTTY
THICKNESS
FIRE RATING OF
ASSEMBLY
5"
6 1/4 INCH
1/2 INCH
2 HOUR
10"
12 1/4 INCH
1 INCH
3 HOUR
O.D. OF CONDUIT
2.
BUS BAR SHALL BE INSTALLED IN AN ACCESSIBLE
LOCATION.
3.
PROVIDE ELECTRO-TIN PLATED, CU BUSBAR WITH HOLES
FOR USE WITH CORRECTLY MATCHED LISTED LUGS AND
HARDWARE.
4.
BUSBAR SHALL BE A MINIMUM OF 0.25" THICK BY 2 INCHES
WIDE AND 24 INCHES IN LENGTH FOR ELECTRICAL
GROUNDING BUSBARS.
5.
MAKE CONNECTIONS WITH UL LISTED COMPRESSION OR
MECHANICAL CONNECTORS.
6.
GROUNDING ELECTRODE CONDUCTORS, BONDING
CONDUCTORS AND JUMPERS, TYPICAL.
PUTTY THICKNESS
SEE TABLE ABOVE
ANNULAR SPACE
3/4" MAX.
FIRE RATED
CONCRETE
FLOOR
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
METAL CONDUIT
SEE NOTE 6
24" AFF
PHENOLIC
STANDOFF
INSULATOR
Consultants
NOTES:
TO NEUTRAL BUS IN
SERVICE ENTRANCE
EQUIPMENT OR
SEPARATELY DERIVED
SYSTEMS EQUIPMENT
OPENING SIZE
SEE TABLE
ABOVE
FINISHED FLOOR
SIDE VIEW
SECTION
1
2
GROUNDING EQUALIZER
(IF REQUIRED)
SEE NOTE 5, NOTE 9
3M RECOMMENDATIONS ARE BASED ON U.L. FIRESTOP SYSTEM 202.
3.
3M FIRE BARRIER MP MOLDABLE PUTTY INSTALLED FLUSH TO BOTH
SURFACES OF THE WALL.
PENETRATION FIRESTOP FOR CONDUIT THROUGH CONCRETE FLOOR (2,3 HOUR) DETAIL
NO SCALE
1.
REFER TO TYPICAL SERVICE GROUNDING DETAIL AND
GROUNDING RISER DIAGRAM FOR ADDITIONAL
INFORMATION.
2.
BUS BAR SHALL BE INSTALLED IN AN ACCESSIBLE
LOCATION.
3.
PROVIDE ELECTRO-TIN PLATED, CU BUSBAR WITH HOLES
FOR USE WITH CORRECTLY MATCHED LISTED LUGS AND
HARDWARE. BUSBAR SHALL BE A MINIMUM OF 0.25" THICK
BY 2 INCHES WIDE AND 18 INCHES IN LENGTH.
O.D. OF CONDUIT
BONDING CONDUCTOR SIZE VS
LENGTH (TABLE 1)
LINEAR LENGTH
(FEET)
PHENOLIC
STANDOFF
INSULATOR
GROUND LUG
TWO HOLE COMPRESSION
TYPICAL, SEE NOTE 4
7'-0" AFF
5.
6.
SEE NOTE 3
7.
SEE NOTE 7
FINISHED FLOOR
14-20
MAXIMUM
OPENING SIZE
MINIMUM PUTTY
THICKNESS
FIRE RATING OF
ASSEMBLY
5"
6 1/4 INCH
1/2 INCH
2 HOUR
10"
12 1/4 INCH
1 INCH
3 HOUR
SIZE (AWG)
PUTTY THICKNESS
SEE TABLE ABOVE
6
Signature
Registration Number
8.
9.
MAKE CONNECTIONS WITH UL LISTED, IRREVERSIBLE,
COMPRESSION OR MECHANICAL CONNECTORS.
21-26
3
SIZE BONDING CONDUCTORS PER ANSI-607-B. REFER TO
TABLE 1, THIS DETAIL.
27-33
2
34-41
1
42-52
1/0
TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
SHALL BE A MINIMUM OF #6AWG CU.
James A. LeClaire
4
4.
WALL
NEAREST ELECTRICAL
GROUND BUS OR
TELECOMMUNICATIONS
BONDING BACKBONE (IF
APPLICABLE)
SEE NOTE 5
LESS THAN 13
MAXIMUM O.D.
OF CONDUIT
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
METAL CONDUIT
Date
PROVIDE CONNECTION TO STRUCTURAL STEEL WITH A #
6AWG CU CONDUCTOR, MINIMUM.
53-66
2/0
ALL CONDUCTORS SHALL BE GREEN OR MARKED WITH A
DISTINCTIVE GREEN COLOR.
67-84
3/0
50358
07/24/15
Project For
ANNULAR SPACE 3/4" MAX.
FIRE RATED CONCRETE
OR CONCRETE BLOCK
WALL
NOTES:
OPENING SIZE
SEE TABLE
ABOVE
GROUNDING EQUALIZERS CONNECT MULTIPLE TMGB AND
TGB ON THE SAME FLOOR.
SIDE VIEW
CROSS-SECTION VIEW
1.
MAXIMUM ANNULAR SPACE BETWEEN CONDUIT AND OPENING SHALL
NOT EXCEED 3/4 INCH.
2.
3M RECOMMENDATIONS ARE BASED ON U.L. FIRESTOP SYSTEM 202.
3.
3M FIRE BARRIER MP MOLDABLE PUTTY INSTALLED FLUSH TO BOTH
SURFACES OF THE WALL.
STUDENT HEALTH AND
ACADEMIC RENOVATION
ELEVATION
SECTION
TELECOMMUNICATIONS GROUND BAR DETAIL (TGB)
NO SCALE
4
GROUNDING EQUALIZER
(IF REQUIRED)
SEE NOTE 5, NOTE 9
4" MIN (TMGB)
TYPICAL, SEE NOTE 6
GROUND LUG
TWO HOLE COMPRESSION
TYPICAL, SEE NOTE 4
PHENOLIC
STANDOFF
INSULATOR
PENETRATION FIRESTOP FOR CONDUIT THROUGH CONCRETE WALL (2,3 HOUR) DETAIL
NO SCALE
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
DETAIL NOTES:
1.
GROUND
BUSBAR
REFER TO TYPICAL SERVICE GROUNDING DETAIL AND
GROUNDING RISER DIAGRAM FOR ADDITIONAL
INFORMATION.
2.
BUS BAR SHALL BE INSTALLED IN AN ACCESSIBLE
LOCATION.
3.
PROVIDE ELECTRO-TIN PLATED, CU BUSBAR WITH HOLES
FOR USE WITH CORRECTLY MATCHED LISTED LUGS AND
HARDWARE. BUSBAR SHALL BE A MINIMUM OF 0.25" THICK BY
4 INCHES WIDE AND 18 INCHES IN LENGTH.
BONDING CONDUCTOR SIZE VS
LENGTH (TABLE 1)
1 HOUR RATED GYPSUM WALL
LINEAR LENGTH
(FEET)
SIZE (AWG)
LESS THAN 13
6
14-20
4
MAKE CONNECTIONS WITH UL LISTED, IRREVERSIBLE,
COMPRESSION OR MECHANICAL CONNECTORS.
21-26
3
SIZE BONDING CONDUCTORS PER ANSI-607-B. REFER TO
TABLE 1, THIS DETAIL.
27-33
2
34-41
1
42-52
1/0
PROVIDE CONNECTION TO STRUCTURAL STEEL WITH A #
6AWG CU CONDUCTOR, MINIMUM.
53-66
2/0
ALL CONDUCTORS SHALL BE GREEN OR MARKED WITH A
DISTINCTIVE GREEN COLOR.
67-84
3/0
4.
WALL
7'-0" AFF
5.
6.
SEE NOTE 3
7.
TO NEAREST ELECTRICAL
GROUND BUS
SEE NOTE 5
SEE NOTE 7
8.
9.
TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
SHALL BE A MINIMUM OF #6AWG CU.
1/4" MINIMUM DIAMETER BEAD OF 3M
FIRE BARRIER CP25N/S CAULK (TYPICAL)
NOTES:
METAL CONDUIT
GROUNDING EQUALIZERS CONNECT MULTIPLE TMGB AND
TGB ON THE SAME FLOOR.
THE CAULK SHALL BE FORCED INTO THE ANNULAR SPACE TO THE MAXIMUM EXTENT
POSSIBLE, FLUSH WITH THE EXTERIOR OF PENETRATION SURFACE.
2.
FINISH CAULKING WITH 1/4" MINIMUM BEAD OF CP25N/S CAULK APPLIED TO THE
PERIMETER OF THE CONDUIT AT ITS EGRESS FROM THE WALL.
3.
THE MAXIMUM ANNULAR SPACE SHALL NOT EXCEED 3/16" INSTALL 3M FIRESTOP ON BOTH
SIDES OF THE WALL.
3M RECOMMENDATION ARE BASED ON ASTM E-814 (UL 1479) FIRE TEST AND U.L.
THROUGH -PENETRATION FIRESTOP SYSTEM #147.
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
ELEVATION
TELECOMMUNICATIONS GROUND BAR DETAIL (TMGB)
NO SCALE
1.
4.
FINISHED FLOOR
5
2.
CROSS-SECTION VIEW
DETAIL NOTES:
SEE NOTE 6
SECTION
MAXIMUM ANNULAR SPACE BETWEEN CONDUIT AND OPENING SHALL
NOT EXCEED 3/4 INCH.
Dunham Job #: 415134
ELECTRICAL GROUND BAR DETAIL (SGB/EGB)
NO SCALE
GROUND
BUSBAR
3
1.
ELEVATION
2" MIN
612.677.7100
612.677.7499 fax
www.rsparch.com
6
PENETRATION FIRESTOP FOR CONDUIT THROUGH GYPSUM WALL (1 HOUR) DETAIL
NO SCALE
© Copyright RSP Architects 2015. All rights reserved.
Revisions
No.
Date
Description
ELECTRICAL DETAILS
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:05:09 PM
E701
DETAIL KEY NOTES:
TO ADDITIONAL
EQUIPMENT
XFMR
TO OTHER SYSTEMS
TGB
XFMR
GEC
TO OTHER SYSTEMS
TO OTHER MAIN SERVICE
DISCONNECTING MEANS
TO OTHER SEPARATELY
DERIVED SYSTEMS
TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR
(TMGB)
G
2
TELDATA
ROOM
B. ALL BONDING BACKBONE CABLING WORK BY DIVISION 26.
C. DIVISION 26 TO PROVIDE PULL STRING IN ALL CONDUIT RUNS.
D. REFER TO GROUNDING DETAILS FOR ADDITIONAL DIRECTION.
TO METAL GAS PIPING
THIRD FLOOR
THIRD FLOOR
DATA 254
1/A
GROUND ROD GROUNDING ELECTRODE; PROVIDE GROUND ROD
GROUNDING ELECTRODES WHERE CODE COMPLIANT WATER PIPE, METAL
FRAME STRUCTURE, AND CONCRETE ENCASED GROUNDING ELECTRODES
DO NOT EXIST. PROVIDE DRIVEN GROUND RODS IN ACCORDANCE WITH
NEC 250.52(A)(5), 250.53(A), 250.53(B), AND 250.53(G).
KEY NOTES:
1
MOUNT DEVICE AT 7'-0" AFF.
RSP Architects
COMMON GROUNDING ELECTRODE CONDUCTOR; PROVIDE #3/0 CU,
MINIMUM, IN ACCORDANCE WITH NEC 250.30(A). CONDUCTOR SHALL BE
CONTINUOUS. CONNECTIONS SHALL BE MADE AT A EQUIPMENT
GROUNDING BUSBAR.
TGB
G
2
MULTIPLE SERVICE DISCONNECTS; PROVIDE COMMON GROUNDING
ELECTRODE IN ACCORDANCE WITH NEC 250.58, SIZE GROUNDING
ELECTRODE CONDUCTOR, FOR MULTIPLE SERVICES, IN ACCORDANCE
WITH NEC 250.64(D).
G
1
MAIN SERVICE EQUIPMENT
TO OTHER SYSTEMS
DATA 131
NEUTRAL BUSBAR
METER
GEC
MAIN BONDING JUMPER AND SYSTEM BONDING JUMPERS; PROVIDE
JUMPER IN ACCORDANCE WITH NEC 250.28(A) THROUGH 250.28(C). SIZE
JUMPER ACCORDANCE WITH NEC 250.28(D)(1) THROUGH 250.28(D)(3), AND
NO SMALLER THAN THOSE SPECIFIED IN TABLE 250.102(C)(1). PROVIDE
GROUNDING AND BONDING FOR SEPARATELY DERIVED (GROUNDED)
SYSTEMS IN ACCORDANCE WITH NEC 250.30.(A).
SERVICE EQUIPMENT BONDING; PROVIDE BONDING JUMPER IN
ACCORDANCE WITH NEC 250.92 AND SIZED IN ACCORDANCE WITH NEC
250.102(C).
TGB
TO SERVICE
TRANSFORMER
BOND METAL WATER PIPES IN ACCORDANCE WITH NEC 250.104(A). SIZE
BONDING JUMPERS IN ACCORDANCE WITH NEC 250.66.
GEC
GEC
GEC
METAL WATER
SERVICE
PIPES BURIED
TO 10'-0"MIN
ELECTRICAL ROOM 022
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB).
PROVIDED AND INSTALLED BY DIVISION 26. SEE DETAILS FOR
ADDITIONAL DIRECTION.
G
2
TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) PROVIDED AND
INSTALLED BY DIVISION 26. SEE DETAILS FOR ADDITIONAL
DIRECTION.
G
3
ELECTRICAL ROOM GROUNDING BUS BAR (EGB)
PROVIDED AND INSTALLED BY DIVISION 26. SEE DETAILS FOR
ADDITIONAL DIRECTION.
G
4
SERVICE GROUNDING BUS BAR (SGB) PROVIDED AND INSTALLED BY
DIVISION 26. SEE DETAILS FOR ADDITIONAL DIRECTION.
DATA ROOM 021
1.
THE DETAIL REPRESENTS A TYPICAL GROUNDING AND BONDING INSTALLATION. ALL NECESSARY ACCESSORIES AND
REQUIREMENTS ARE NOT SHOWN. NOT ALL COMPONENTS AND EQUIPMENT SHOWN MAY BE UTILIZED IN THE PROJECT.
2.
ALL CONDUCTOR SIZES SHOWN ARE BASED ON CU. REVISE CONDUCTOR SIZES PER NEC IF ALUMINUM CONDUCTORS
ARE PROVIDED.
3.
INSTALL EQUIPMENT GROUNDING CONDUCTORS, GROUNDING ELECTRODE CONDUCTORS (GEC), AND BONDING
JUMPERS IN ACCORDANCE WITH NEC 250.8.
4.
INSTALL GROUNDING ELECTRODE CONDUCTORS (GEC) IN ACCORDANCE WITH NEC 250.64. INSTALL GROUNDING
ELECTRODE CONDUCTORS AT BUSBAR LOCATIONS IN ACCORDANCE WITH NEC 250.64(B) AND 250.64(C).
5.
MAKE SPLICES OF WIRE TYPE GEC WITH LISTED IRREVERSIBLE COMPRESSION OR MECHANICAL-TYPE CONNECTORS
OR BY EXOTHERMIC WELD.
6.
MAKE GROUNDING ELECTRODE CONDUCTOR (GEC) AND BONDING JUMPER CONNECTIONS IN ACCORDANCE WITH NEC
250.68 AND 250.70.
7.
SIZE GROUNDING ELECTRODE CONDUCTORS (GEC) AND TAPS IN ACCORDANCE WITH NEC 250.66, UNLESS INDICATED
OTHERWISE.
8.
GROUND AND BOND ALL METALLIC UNDERGROUND PIPING.
Dunham Job #: 415134
CABLE TYPE CALLOUT
CABLE QUANTITIES
BOND UNGROUNDED STRUCTURAL METAL IN ACCORDANCE WITH NEC
250.104(C). SIZE JUMPERS CONDUCTORS IN ACCORDANCE WITH NEC
250.66.
#/A
1/A
BOND LIGHTNING PROTECTION SYSTEMS (IF AVAILABLE) IN ACCORDANCE
WITH NEC 250.106 AND NFPA 780.
DETAIL NOTES
#/A
1/A
SGB
ELEC ROOM
BOND OTHER SYSTEMS (CATV, ANTENNA, FIBER OPTIC,
TELECOMMUNICATIONS SYSTEMS) TO THE ELECTRICAL GROUND SYSTEM
WITH A #6AWG CU CONDUCTOR, MINIMUM, IN ACCORDANCE WITH NEC
250.94, UNLESS INDICATED OTHERWISE.
INDIVIDUAL DEVICE CALLOUT
CABLE TYPE:
FIRST FLOOR
FIRST FLOOR
BOND OTHER METAL PIPING IN ACCORDANCE WITH NEC 250.104(B). SIZE
BONDING JUMPERS IN ACCORDANCE WITH NEC 250.122.
Consultants
DEVICE TYPE CALLOUT
G
1
G
2
TELDATA
ROOM
SIZE BONDING JUMPER PER NEC 250.122, WHERE GROUNDING ELECTRODE
CONDUCTOR IS CONNECTED SUPPLY SIDE OF WATER METER.
612.677.7100
612.677.7499 fax
www.rsparch.com
SECOND FLOOR
SECOND FLOOR
SERVICE NEUTRAL CONDUCTOR; DO NOT PROVIDE EQUIPMENT
GROUNDING CONDUCTOR IN CONDUITS FROM SERVICE EQUIPMENT
(TRANSFORMERS).
1/A
TO LIGHTNING
PROTECTION SYSTEM
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
EQUIPMENT:
TELDATA
ROOM
TO METAL WATER PIPING
ELECTRICAL
GROUND BUSBAR
1
A. ALL CABLING SHALL BE INDEPENDENTLY SUPPORTED FROM
STRUCTURE.
GROUND RING TYPE GROUNDING ELECTRODE; ELECTRODE SHALL BE
COMPLIANT WITH NEC 250.52(A)(4) AND 250.53(F). GROUND ELECTRODE
CONDUCTOR SHALL BE THE SAME SIZE CONDUCTOR AS RING CONDUCTOR
IN ACCORDANCE WITH NEC 250.66(C), A MINIMUM OF #2/0AWG CU.
ELECTRICAL
GROUNDING
BUSBAR (EGB)
GENERAL NOTES:
DATA 399
CONCRETE ENCASED GROUNDING ELECTRODE; ELECTRODE SHALL BE
COMPLIANT WITH NEC 250.52(A)(3).
TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR
(TGB)
GROUNDED METAL BUILDING FRAME
UNDERGROUND METAL WATER PIPE GROUNDING ELECTRODE; PIPE MUST
BE BURIED A MINIMUM OF 10'-0" IN ACCORDANCE WITH NEC 250.52(A)(1)
AND INSTALLED PER NEC 250.53(D).
METAL FRAME OF BUILDING OR STRUCTURE USED AS GROUNDING
ELECTRODE; ELECTRODE SHALL BE COMPLIANT WITH NEC 250.52(A)(2).
GEC
UNGROUNDED METAL BUILDING FRAME
ROOF LEVEL
G
4
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
#3/0 AWG CABLE [TELECOMMUNICATION BONDING].
G
1
TMGB
IT ROOM
Signature
James A. LeClaire
Registration Number
50358
LOWER LEVEL
Date
REFER TO ELECTRICAL GROUNDING BUSBAR (EGB) DETAIL FOR
ADDITIONAL INFORMATION.
07/24/15
Project For
REFER TO TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB)
DETAIL FOR ADDITIONAL INFORMATION.
2
GROUNDING RISER DIAGRAM
NO SCALE
REFER TO TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) DETAIL FOR
ADDITIONAL INFORMATION.
NOTES:
1.
ROOFING CONTRACTOR TO FLASH AND SEAL ROOF PENETRATIONS
PER ARCHITECTURAL SPECIFICATIONS AND APPLICABLE CODES.
LOCATE UL LABEL ADJACENT
TO EZ-PATH ASSEMBLY (TYP)
TYPICAL SERVICE GROUNDING DETAIL - (BASED ON 2014 NEC)
NO SCALE
MOUNT DUPLEX OUTLET
TO UNISTRUT
UL
LABEL
EZ-PATH SERIES "44"
PATHWAY MODULE
UNISTRUT - MIN. 26" ABOVE
FINISHED ROOF TO TOP
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
SERIES "44" MODULAR
GRID SYSTEM
WP IN-USE COVER
STUDENT HEALTH AND
ACADEMIC RENOVATION
WELD UNISTRUT TO
STEEL PLATE SOLID
1" HOLE FOR CONDUIT
3
NOTES:
6"X6"X1/4" STEEL PLATE.
BOLT TO ROOF DECK IN
4 PLACES
ROOFTOP RECEPTACLE DETAIL - UNISTRUT MOUNTED
NO SCALE
4
1.
INSTALL PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2.
PART NUMBERS LISTED FOR REFERENCE AND MAY NOT REPRESENT ALL REQUIRED
COMPONENTS FOR A COMPLETE INSTALLATION. SEE SPECIFICATIONS.
FIRE STOP DETAIL - CORRIDOR PENETRATION
NO SCALE
Project No.
2263.001.00
Drawn By
MMK
Checked By
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
SPD
Revisions
No.
Date
Description
PM
91.50
35.50
1.5
24.00
36.00
24.00
36.00
60.00
5
2000A ENCLOSED CIRCUIT BREAKER ELEVATION AND FLOOR PLAN
NO SCALE
ELECTRICAL DETAILS
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:05:16 PM
E702
ROOF
GENERAL NOTES
ACCESS CTRL RELEASE
TAMPER FLOW
SWITCH SWITCH
F
F
#/C
#/E
TYP
F
F
F
sF
F
F SB
#/C #/C
F
MM
S ES S ML
CM F
#/C
F P FH
F
F
F
MC
FR
F
TYP
F RL F
B.
THE SYSTEM DIAGRAM IS BASED ON A DIGITAL, ADDRESSABLE FIRE ALARM
SYSTEM.
C.
3
sF
THE WIRING DIAGRAM IS CONCEPTUAL ONLY AND DOES NOT INDICATE ALL
DEVICES, DEVICE TYPES OR QUANTITY OF LOOPS. REFER TO FLOOR
PLANS FOR DEVICE QUANTITIES AND LOCATIONS.
F P FH
F P FH
F MC
F
F
MM MM
A.
S EL
#/C
D.
DIGITAL VOICE
EVAC/PAGING
AMPLIFIER
4
C
NAC
DH
F
TO ADDITIONAL
DOOR HOLDERS
DH
F
#/B
(DATA ROOM)
4
C
TO ADDITIONAL
SMOKE,
FIRE/SMOKE
DAMPERS
D
D
5
#/C #/C
#/C
#/E
TYP
F
F
F
F
MM
sF
F
F SB
F
F
F
MC
FR
F
TYP
F I/O
F I/O
R
G
KEY NOTES
DIGITAL VOICE
EVAC/PAGING
AMPLIFIER
4
C
NAC
DH
F
TO ADDITIONAL
DOOR HOLDERS
DH
F
TO ADDITIONAL
SMOKE,
FIRE/SMOKE
DAMPERS
#/B
(DATA ROOM)
D
1
RELOCATED FIRE ALARM CONTROL PANEL.
2
DIGITAL VOICE EVACUATION AND PAGING SYSTEM INTERFACE WITH
TELEPHONE SYSTEM.
3
EMS CONNECTION, COORDINATE WITH CONTROLS CONTRACTOR FOR
FINAL CONNECTION REQUIREMENTS
4
LIFE SAFETY BRANCH CIRCUIT (REFER TO POWER PLAN DWGS).
5
FIRE/SMOKE AND SMOKE DAMPER MOTORS ARE SHOWN ON
MECHANICAL PLANS. VERIFY QUANTITIES AND LOCATIONS. PROVIDE
FIRE ALARM CONNECTIONS TO RELAY SO THAT THE FIRE/SMOKE AND
SMOKE DAMPERS CLOSE UPON LOSS OF POWER. (DIVISION 26 SHALL
PROVIDE RELAY AND CIRCUITING. SEE POWER PLANS FOR 120V
CIRCUITING, RELAY LOCATIONS, ETC.) PROVIDE ONE (1) FIRE ALARM
CONTROL MODULE PER FIRE/SMOKE DAMPER GROUP ON EACH FLOOR
OF EAST AND WEST BUILDINGS.
4
C
D
5
SECOND FLOOR
ACCESS CTRL RELEASE
TAMPER FLOW
SWITCH SWITCH
F
F
#/E
TYP
F
WP
FIRE DEPARTMENT +10' AFG CM
F F
CONNECTOIN (FDC)
F
F
F
MM
sF
F
F SB
#/C #/C
#/C
S ES S ML
CM F
#/C
F P FH
F
F P FH
F P FH
F MC
F
F
MM MM
S EL
F
F
MC
FR
F
TYP
6
F RL F
AHU
sF
AHU
4
C
NAC
DH
F
TO ADDITIONAL
DOOR HOLDERS
DH
F
TO ADDITIONAL
SMOKE,
FIRE/SMOKE
DAMPERS
#/B
(DATA ROOM)
4
C
D
ID TAG NOTATION
#/A
5
CABLE TYPE
BRANCH CIRCUIT
#/C
CONTROL CIRCUIT
#/D
FIBER OPTIC CONNECTION
#/E
SIGNAL LINE CIRCUIT
#/F
TWO-HOUR RATED PRIMARY BACKBONE (CLASS A)
#/G
TWO-HOUR RATED REDUNDANT BACKBONE (CLASS A)
#/H
FUTURE FIRE FIGHTERS TELEPHONE HOMERUN
#/ J
AUDIO INPUT
REMOTE INDICATOR/TEST
STATION, FURNISHED BY
FIRE/SMOKE DAMPER
MANUFACTURE IN
ACCORDANCE WITH
DIVISION 23, INSTALLED AND
WIRED BY DIVISION 26.
SHALL HAVE RED LED FOR
CLOSED, GREEN FOR OPEN,
AND KEYED TEST SWITCH.
REFER TO FIRE/SMOKE
DAMPER SCHEDULE AND
PLANS FOR LOCATION
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
VFD
FIRE ALARM OUTPUT
MODULE (1 FOR EACH
AHU). PROVIDED BY
DIVISION 26.
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
James A. LeClaire
Registration Number
BMS
FACP
BUILDING
MANAGEMENT
SYSTEM (BMS)
FACP
#/B
K
BMS DATA LINK
BMS
INITIATING LINE CIRCUIT
G
FIRE ALARM CONTROL
PANEL (FACP). REFER
TO FIRE ALARM
CONTROL MATRIX
FOR PROGRAMMING
OF FA SYSTEM.
CABLE TYPE CALLOUT
#/A
K
FIRE ALARM DATA LINK
FIRE ALARM DATA LINK
CABLE QUANTITIES
FIRST FLOOR
R
RELAY WIRING,
PROVIDED BY DIVISION
23
FIRE ALARM OUTPUT
MODULE (1 FOR EACH
AHU). PROVIDED BY
DIVISION 26.
BUILDING MANAGEMENT
SYSTEM (BMS)
D
FSD
BMS INPUT MODULE,
PROVIDED BY DIVISION
23 (1 PER AHU)
BMS DATA LINK
DIGITAL VOICE
EVAC/PAGING
AMPLIFIER
F I/O
F CM
RELAY WIRING,
PROVIDED BY
DIVISION 23
#/C
FIRE ALARM
ADDRESSABLE I/O RELAY
MODULE WITH EOL FOR
DUCT DETECTOR
"SUPERVISORY" SIGNAL
AND DUCT DETECTOR
RESET
FIRE/SMOKE DAMPER,
AS SPECIFIED; WITH
120V MOTOR,
FURNISHED AND
INSTALLED IN
ACCORDANCE WITH
DIVISION 23, WIRED
BY DIVISION 26
VFD
BMS INPUT MODULE,
PROVIDED BY DIVISION
23 (1 PER AHU)
3
F I/O
F
R
F CM
PHONE CONNECTION TO PHONE SWITCH.
MR
G
REMOTE INDICATOR/
RESET STATION,
FURNISHED BY FIRE/
SMOKE DAMPER
MANUFACTURE IN
ACCORDANCE WITH
DIVISION 23, INSTALLED
AND WIRED BY DIVISION
26. SHALL HAVE RED LED
FOR TROUBLE, GREEN
FOR NORMAL, AND A
RESET SWITCH. REFER TO
FIRE/ SMOKE DAMPER
SCHEDULE AND PLANS
FOR LOCATION.
#/C
FIRE ALARM
ADDRESSABLE I/O RELAY
MODULE WITH EOL FOR
DUCT DETECTOR
"TROUBLE" SIGNAL AND
DUCT DETECTOR RESET
J
PHOTOELECTRIC DUCT
SMOKE DETECTOR
FURNISHED AND
FACTORY INSTALLED
WITH FIRE/SMOKE
DAMPER IN
ACCORDANCE WITH
DIVISION 23.
FIRE ALARM
ADDRESSABLE I/O
RELAY MODULE WITH
EOL FOR DUCT
DETECTOR
"SUPERVISORY"
SIGNAL AND DUCT
DETECTOR RESET.
F RL F
3
sF
F
PHOTOELECTRIC DUCT
SMOKE DETECTOR
FURNISHED AND FACTORY
INSTALLED WITH FIRE/SMOKE
DAMPER IN ACCORDANCE
WITH DIVISION 23.
REFER TO FIRE ALARM CONTROL MATRIX FOR ALL CONTROL
REQUIREMENTS.
H.
F P FH
F P FH
F MC
F
F
MM MM
S EL
#/C
F P FH
FIRE ALARM
ADDRESSABLE I/O
RELAY MODULE WITH
EOL FOR DUCT
DETECTOR "TROUBLE"
SIGNAL AND DUCT
DETECTOR RESET.
120V POWER WIRING, BY
DIVISION 26. REFER TO PLANS
FOR CIRCUITING
INFORMATION
ALL SPRINKLER HEADS, LOCATED IN ELEVATOR SHAFTS AND ELEVATOR
EQUIPMENT ROOMS, ARE TO HAVE A HEAT DETECTOR MOUNTED WITHIN
TWO (2) FEET OF HEAD FOR ACTIVATION OF SHUNT TRIP POWER DEVICE.
VERIFY QUANTITY ON SITE.
G.
S ES S ML
CM F
PROVIDE MOTOR RATED
TOGGLE SWITCH FOR
EACH DAMPER MOTOR
PROVIDE ALL CONTROL WIRING FROM FIRE ALARM CONTROLLER AND/OR
DEVICES TO HVAC CONTROLLERS.
F.
ACCESS CTRL RELEASE
TAMPER FLOW
SWITCH SWITCH
F
F
THE INSTALLATION SHALL BE FROM DRAWINGS THAT HAVE BEEN
SUBMITTED, REVIEWED AND APPROVED BY THE AUTHORITIES HAVING
JURISDICTION.
EACH SIGNALLING CIRCUIT SHALL ALLOW 15% SPARE CAPACITY TO ADD
ADDITIONAL AUDIO, VISUAL OR COMBINATION AUDIO/VISUAL SIGNALING
DEVICES TO ANY OF THESE CIRCUITS.
E.
THIRD FLOOR
ALL WIRING AND CABLING SHALL BE IN CONDUIT (MINIMUM 3/4" C.) EMT
CONDUIT USED FOR FIRE ALARM WIRING SHALL INCLUDE FACTORYAPPLIED RED TOPCOAT UL-LISTED FOR FIRE ALARM USE.
120V POWER WIRING,
BY DIVISION 26. REFER
TO PLANS FOR
CIRCUITING
INFORMATION
FIRE ALARM CONTROL
PANEL (FACP). REFER
TO FIRE ALARM
CONTROL MATRIX FOR
PROGRAMMING OF FA
SYSTEM
Date
50358
07/24/15
Project For
STUDENT HEALTH AND
ACADEMIC RENOVATION
ACCESS CTRL RELEASE
#/E
TYP
F
F
F
F
ELEV
CONTROLLER
F
TAMPER FLOW
SWITCH SWITCH
F
F
#/C
sF
sF
#/C
F
MM
#/C
#/C
F
F
MM MM
3
S EL
#/C
F P FH
F
F P FH
F P FH
F MC
F
CM
ELEV
RECALL
S ES S ML
CM F
F
F
MC
2
FR
F
TYP
F RL F
DUCT DETECTOR DETAIL
NO SCALE
3
#/C
LOUVER
DIGITAL VOICE
EVAC/PAGING
AMPLIFIER
1
RELOCATED
FACP
4
C
DH
F
TO ADDITIONAL
DOOR HOLDERS
DH
F
#/B
(MAIN ELECTRICAL ROOM)
#/B
OWNER LAN CONNECTION
#/D
BACNET IP GATEWAY
COMMUNICATION CONNECTIONS TO
ENERGY MANAGMENT SYSTEM AND
LIGHTING CONTROL SYSTEM
#/H
#/A
4
#/ J
6
4
C
TO ADDITIONAL
SMOKE,
FIRE/SMOKE
DAMPERS
D
F
D
F P
TOP OF SHAFT
DACT IP DIGITAL ALARM
COMMUNICATION
TRANSMITTER
F
3RD FLOOR LOBBY
F P
SUPERVISED MANUAL SHUT-OFF VALVE
IN SPRINKLER LINE BY DIV 21. IF
INSTALLED, DIV 26 TO CONNECT TO FA
SYSTEM FOR SUPERVISED STATUS.
BASEMENT
135
HEAT DETECTOR, FIXED RATE, SET AT 135°
SPRINKLER HEAD SET AT 212°
212°
SUPERVISED FLOW SWITCH BY DIV 21.
DIV 26 TO CONNECT TO FA SYSTEM
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
F P SMOKE DETECTOR
J
F 135
F
5
2
#/B
FIRE/SMOKE DAMPER - DUCT DETECTOR DIAGRAM
NO SCALE
2ND FLOOR LOBBY
F P
1ST FLOOR LOBBY
F P
K
FIRE ALARM CABLING RISER DIAGRAM
NO SCALE
1
FIRE ALARM CONTROL MATRIX
ACTION
SEND ALARM SIGNAL TO FACP
1
SEND SUPERVISORY SIGNAL TO FACP
1
SEND TROUBLE SIGNAL TO FACP
1
MANUAL
PULL
STATION
XX
PATIENT
AREA
ROOM
HEAT
SMOKE
SMOKE
DETECTOR
DETECTOR
DETECTOR
XX
XX
ACTIVATE NOTIFICATION DEVICES ON FLOOR OF ACTIVATION, FLOOR
ABOVE, AND FLOOR BELOW
RELEASE DOOR HOLDS, POWERED FIRE DOORS, AND POWERED
SECURITY DOORS THROUGHOUT BUILDING
RELEASE DOOR HOLDS, POWERED FIRE DOORS, AND POWERED
SECURITY DOORS IN SMOKE COMPARTMENT OF INITIATION ONLY
RECALL CORRESPONDING ELEVATOR/ELEVATOR BANK TO
PRIMARY LEVEL
RECALL CORRESPONDING ELEVATOR/ELEVATOR BANK TO ALTERNATE
LEVEL(S)
ACTIVATE CORRESPONDING ELEVATOR/ELEVATOR BANK
SHUNT TRIP
5
ELEVATOR LOBBY
SMOKE DETECTOR
HEAT
PRIMARY ALTERNATE SMOKE
LEVEL
LEVEL
DETECTOR DETECTOR
XX
XX
ELEVATOR EQUIPMENT ROOM AND
ELEVATOR SHAFT
XX
XX
XX
FLOW
SWITCH
XX
ZONE
WATER
FLOW
SWITCH
XX
MAIN
WATER
FLOW
SWITCH
POST
SPRINKLER
INDICATOR
SYSTEM
VALVE
TAMPER
TAMPER
SWITCH
FA
PHONE
LINE
LOSS
XX
XX
XX
XX
SPEAKER
PRIMARY &
FIRE ALARM
AMP OR
SECONDARY
PANEL/
GENERATOR
TONE
POWER
CIRCUIT
MONITOR
GENERATOR
MONITOR
TROUBLE
TROUBLE
F
F
F P
MACHINE ROOM
PHASE ONE RECALL TO MAIN
FLOOR OR ALTERNATE IF
OVER 25 FT OF TRAVEL AS PER
ANSI A17.1 SECTION 211.3
XX
XX
XX
XX
XX
XX
XX
3 PHASE FEED
XX
POWER SHUT
DOWN SHUNT
TRIP DEVICE
MMK
Checked By
F 135
212°
2263.001.00
Drawn By
212°
XX
XX
5
XX
XX
SHUT DOWN ENTIRE SMOKE COMPARTMENT SUPPLY, RETURN, AND
EXHAUST FANS; & CLOSE ASSOCIATED SMOKE DAMPERS
ACTIVATE NOTIFICATION DEVICES ON ALL FLOORS
DEDICATED
F/S
DOOR
AHU
DAMPER
HOLD
DUCT
DUCT
SMOKE
DETECTOR
DETECTOR
DETECTOR
Project No.
F P
PIT
FIRE ALARM DEVICE
NOTES
NOTES:
F 135
3 PHASE
ELEVATOR
CONTROLLER
Date
JL
2/19/16
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
XX
XX
Revisions
XX
4
ELEVATOR FIRE ALARM CONTROL RISER DIGRAM
NO SCALE
No.
Date
Description
XX
XX
XX
XX
XX
XX
XX
10
XX
XX
10
2,4
4,15
7
4
4
12
12
12
XX
XX
9,12
11,12
6
17
3
14
8,16
GENERAL NOTES:
A. REFER TO DIVISION 28 SPECIFICATIONS FOR ADDITIONAL FIRE ALARM SYSTEM REQUIREMENTS.
B. ALL ACTIONS SHALL INDICATE A SPECIFIC DEVICE AND LOCATION TO THE CONTROL PANEL(S), ANNUNCIATOR PANEL(S), DACT, AND SYSTEM PRINTER.
C. NOT ALL DEVICES MAY BE REQUIRED. REFER TO PLANS FOR ACTUAL DEVICES.
SPECIFIC NOTES:
1. SEND SIGNAL TO REMOTE ALARM RECEIVING STATION.
2. IN SOME ROOMS, AREA SMOKE DETECTORS SHALL BE PROGRAMMED SO THAT UPON ACTIVATION OF THE FIRST SMOKE DETECTOR, A SUPERVISORY SIGNAL IS SENT. UPON ACTIVATION OF A SECOND SMOKE DETECTOR AN ALARM SIGNAL WILL BE SENT. REFER TO PLANS FOR DUAL SMOKE DETECTOR LOCATIONS AND ZONING.
3. FACP SHALL SWITCH TO SECOND PHONE LINE AND SEND TROUBLE SIGNAL TO REMOTE ALARM RECEIVING STATION.
4. FOR SMOKE TYPE DETECTORS FOR SMOKE DAMPER CONTROL, FACP SHALL SEND SIGNAL TO BUILDING MANAGEMENT SYSTEM TO SHUT DOWN ONLY SUPPLY, RETURN, AND EXHAUST FANS FOR ENTIRE AFFECTED SMOKE COMPARTMENT (10) SECONDS PRIOR TO CLOSING ASSOCIATED FIRE/SMOKE DAMPERS. REFER TO AHU ZONING PLANS.
5. ACTIVATE ALL EXTERIOR NOTIFICATION DEVICES.
6. ACTIVATE STAND-ALONE EXTERIOR NOTIFICATION DEVICE LOCATED ABOVE SIAMESE CONNECTION.
7. RELEASE DOOR HOLD FOR ASSOCIATED DOOR ONLY. REFER TO PLANS FOR DEDICATED DOOR HOLD SMOKE DETECTOR LOCATIONS.
8. FOR OVERHEAD COILING DOORS, PROVIDE TIME DELAY OF AT LEAST 15 SECONDS AFTER LOSS OF POWER BEFORE DOOR HOLDS ARE RELEASED.
9. LOCATE DEVICE WITHIN 2' OF EACH SPRINKLER HEAD. HEAT DETECTORS SHALL HAVE A LOWER RESPONSE TIME INDEX (RTI) THAN THE SPRINKLER HEAD IN THAT AREA.
10. ELEVATOR RECALL SHALL NOT RECALL ELEVATOR/ELEVATOR BANK TO SAME FLOOR AS FLOOR WITH ACTIVATED INITIATING DEVICE.
11. DEVICE(S) SHALL ACTIVATE SHUNT TRIP IMMEDIATELY UPON OR PRIOR TO DISCHARGE OF WATER.
12. ACTION SHALL BE MANUALLY RESET ONLY. ELEVATOR SMOKE DETECTORS ARE NOT ALLOWED TO PERFORM ALARM VERIFICATION.
13. MONITOR FOR PUMP RUNNING, PHASE REVERSAL, AND FAILURE.
14. GENERATOR FAILED START SHALL SEND TROUBLE SIGNAL. UPON GENERATOR START, FACP AND REMOTE FAAP'S SHALL INDICATE GENERATOR IN "RUN" MODE.
15. SMOKE DETECTOR SHALL HAVE AUXILIARY CONTACTS FOR CONNECTION TO PATIENT ROOM NURSE CALL LIGHT, WIRING BY OTHERS.
16. DACT PRIMARY POWER TROUBLE SIGNAL SHALL BE SENT WHEN BATTERY CAPACITY IS BETWEEN 25 & 50%.
17. SEND SIGNAL ON BOTH OFF-NORMAL POSITION AND RETURN TO NORMAL POSITION.
18. UPON ACTIVATION OF MAIN WATER FLOW SWITCH, FA SHALL SEND SIGNAL TO CONTROL MODULE AT MATER SERVICE EMERGENCY CONTROL VALVE TO CLOSE DOMESTIC WATER SUPPLY TO THE REST OF THE BUILDING. COORDINATE WITH MECHANICAL CONTRACTOR.
5
FIRE ALARM CONTROL MATRIX
NO SCALE
C:\Revit Projects\SCSU Health Services - Electrical 2016_MadelineK.rvt
2/18/2016 4:05:24 PM
FIRE ALARM DETAILS
E703
PLUMBING FIXTURE SCHEDULE
FIXTURE TAG
P-1
FIXTURE
DESCRIPTION
WATER CLOSET
MOUNTING
WALL
ADA
NO
P-1A
WATER CLOSET
WALL
YES
P-2
URINAL
WALL
NO
P-2A
URINAL
WALL
YES
P-3
LAVATORY
SEMI-COUNTER
TOP
YES
P-3A
LAVATORY
COUNTER DROP IN
NO
P-3B
LAVATORY
WALL
YES
P-4
ICE MAKER
CONNECTION BOX
WALL
NA
P-5
SERVICE SINK
FLOOR
NA
P-5A
SERVICE SINK
WALL
NA
P-6
DOUBLE BOWL SINK
COUNTER DROP IN
NO
P-7
SHOWER
P-8
WALL
WALL HYDRANT
FIXTURE
AMERICAN STANDARD AFWALL
3351.101, ELONGATED BOWL, WALL
MOUNTED WITH TOP SPUD, WHITE,
EVERCLEAN SURFACE.
AMERICAN STANDARD AFWALL
3351.101, ELONGATED BOWL, WALL
MOUNTED WITH TOP SPUD, WHITE,
EVERCLEAN SURFACE.
AMERICAN STANDARD WASHBROOK
6590.001, ELONGATED 14" RIM, WALL
MOUNTED WITH TOP SPUD, WASHOUT
FLUSH, STRAINER, WHITE.
AMERICAN STANDARD WASHBROOK
6590.001, ELONGATED 14" RIM, WALL
MOUNTED WITH TOP SPUD, WASHOUT
FLUSH, STRAINER, WHITE.
AMERICAN STANDARD MEZZO
SEMI-COUNTERTOP, SINGLE HOLE
WALL
VENT
(IN)
2
CW
(IN)
1 1/2
HW
(IN)
NA
RO
(IN)
NA
FLOOR SET VERTICALLY ADJUSTABLE
WITH AUXILIARY SUPPORT ASSEMBLY
(4 FEET SUPPORTS).
4
NA
2
1 1/2
NA
NA
PROVIDE OPEN FRONT WHITE SEAT EQUAL TO OLSONITE 95SSCT. FLUSH VALVE HANDLE TO
BE ON THE APPROACH SIDE OF WATER CLOSET.
FLOOR MOUNTED, HANGER PLATE,
ADJUSTABLE SUPPORTING RODS,
STRUCTURAL UPRIGHTS AND WELDED
FEET.
FLOOR MOUNTED, HANGER PLATE,
ADJUSTABLE SUPPORTING RODS,
STRUCTURAL UPRIGHTS AND WELDED
FEET.
NA
2
NA
1-1/2
3/4
NA
NA
ALL URINALS TO BE INSTALLED WITH MANUFACTURERS STAINLESS STEEL
NON-REMOVEABLE DRAIN STRAINER
2
NA
1-1/2
3/4
NA
NA
ALL URINALS TO BE INSTALLED WITH MANUFACTURERS STAINLESS STEEL
NON-REMOVEABLE DRAIN STRAINER
1-1/2
1-1/4
1-1/2
1/2
1/2
NA
PROVIDE CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8
FITTINGS)
TRAP
INTEGRAL
CARRIER
FLOOR SET VERTICALLY ADJUSTABLE
WITH AUXILIARY SUPPORT ASSEMBLY
(4 FEET SUPPORTS).
SLOAN MANUAL FLUSHOMETER MODEL ROYAL 111-1.28,
1-1/2" SPUD
INTEGRAL ANGLE STOP ON FLUSH
VALVE.
INTEGRAL
SLOAN FLUSHOMETER MODEL ROYAL OPTIMA SMOOTH
186-1.0-HW, HARDWIRED SIDE MOUNT SENSOR
OPERATED, 1.0 GPF LOW CONSUMPTION, ANGLE STOP,
3/4" IPS, TOP SPUD, POLISHED CHROME.
SLOAN FLUSHOMETER MODEL ROYAL OPTIMA SMOOTH
186-1.0-HW, HARDWIRED SIDE MOUNT SENSOR
OPERATED, 1.0 GPF LOW CONSUMPTION, ANGLE STOP,
3/4" IPS, TOP SPUD, POLISHED CHROME.
CHICAGO FAUCETS 116.706.AB.1, HARDWIRED SENSOR
OPERATED, DECK MOUNTED, SINGLE HOLE, 0.5 GPM,
POLISHED CHROME.
INTEGRAL ANGLE STOP ON FLUSH
VALVE.
INTEGRAL
INTEGRAL ANGLE STOP ON FLUSH
VALVE.
INTEGRAL
CHICAGO 1025-ABCP QUARTER TURN
POLISHED C.P. CAST BRASS ANGLE
VALVE KITS, LOOSE KEY, FLEXIBLE
RISERS, ESCUTCHEON
CHICAGO 1025-ABCP QUARTER TURN
POLISHED C.P. CAST BRASS ANGLE
VALVE KITS, LOOSE KEY, FLEXIBLE
RISERS, ESCUTCHEON
CHICAGO 1025-ABCP QUARTER TURN
POLISHED C.P. CAST BRASS ANGLE
VALVE KITS, LOOSE KEY, FLEXIBLE
RISERS, ESCUTCHEON
1-1/4" PVC TRAP, EXT TO WALL, W/
ESCUTCHEON W/ GRID STRAINER
CHICAGO FAUCETS 540-LD897SWXFXKCP, WALL
CRANE/FIAT MSB 2424 MOP SERVICE
BASIN, 24" X 24" X 10" DEEP, MOLDED MOUNTED, 5-3/4" VACUUM BREAKER SPOUT WITH HOSE
STONE, STAINLESS STEEL DRAIN WITH THREAD, PAIL HOOK & WALL BRACE, LEVER HANDLES,
CERAMIC CARTRIDGE, POLISHED CHROME.
COMBINATION DOME STRAINER & LINT
BASKET.
CHICAGO FAUCETS 305-VBXKCP, WALL MOUNTED, 2-3/8"
AMERICAN STANDARD LAKEWELL
7692.008, DRILLED BACK 2 HOLES ON 8" VACUUM BREAKER SPOUT WITH HOSE THREAD & PAIL
CENTERS, WALL HANGER, RIM GUARD, HOOK, ADJUSTABLE ARMS, LEVER HANDLES, CERAMIC
CARTRIDGE, POLISHED CHROME.
ENAMELED CAST IRON, WHITE.
ELKAY LR1919, 18 GAUGE, TYPE 304
CHICAGO FAUCETS 786-E29XKABCP, DECK MOUNTED,
STAINLESS STEEL, 19-1/2" X 19" X 7-1/2" 5-1/4" RIGID/SWING GOOSENECK SPOUT, 8" CENTERS,
DEEP, 3 HOLE, UNDERCOATED.
WRISTBLADE HANDLES, CERAMIC CARTRIDGE, 2.2 GPM
LAMINAR FLOW OUTLET, POLISHED CHROME.
CHICAGO FAUCETS 1905-VOCCP PRESSURE BALANCING
AQUATIC 1363BFSC 36X36X75"
SHOWER VALVE,
ACCESSIBLE SHOWER WITH VERTICAL
AND HORIZONTAL GRAB BARS, AND
FOLD UP SEAT, AND HAND-HELD
SHOWER ASSEMBLY WITH SLIDE BAR
ZURN ECOLOTROL CERAMIC DISK WALL
HYDRANT, ENCASED, NON-FREEZE,
ANTI-SIPHON, AUTOMATIC DRAINING
MECHANICAL NOTES
PROVIDE OPEN FRONT WHITE SEAT EQUAL TO OLSONITE 95SSCT.
1-1/2" PVC TRAP, EXT TO WALL, W/
ESCUTCHEON W/ GRID STRAINER
NA
1-1/2
1-1/4
1-1/2
1/2
1/2
NA
PROVIDE CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8
FITTINGS)
1-1/4" PVC TRAP, EXT TO WALL, W/
ESCUTCHEON W/ GRID STRAINER
FLOOR MOUNTED, CONCEALED ARMS,
LEVELING AND SECURING SCREWS,
STRUCTURAL UPRIGHTS AND WELDED
FEET.
1-1/2
1-1/4
1-1/2
1/2
1/2
NA
PROVIDE AMERICAN STANDARD 0059.020EC SHROUD/KNEE CONTACT GUARD, EVERCLEAN
SURFACE. PROVIDE McGUIRE CAST BRASS CHROME PLATED TAILPIECE & OPEN GRID
STRAINER, ALL METAL PARTS TREATED INSIDE & OUTSIDE WITH SANIGUARD, PROVIDE
CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8 FITTINGS)
NA
NA
NA
NA
NA
NA
1/2
NA
NA
COORDINATE LOCATION & MOUNTING HEIGHT OF WALL BOX WITH CASEWORK & EQUIPMENT
REQUIREMENTS.
ACCESSIBLE CHECK VALVES &
SHUTOFFS ON HOT & COLD SUPPLIES.
3" 'P' TRAP
NA
3
3
1-1/2
3/4
3/4
NA
PROVIDE CRANE/FIAT 832-AA HOSE & HOSE BRACKET, 889-CC MOP HANGER, (2) E-88-AA
STAINLESS STEEL BUMPERGUARD, (2) MSG2424 STAINLESS STEEL WALL GUARD. SEE DETAIL
FOR ALL PIPING REQUIREMENTS.
CHICAGO FAUCETS 786-E29XKABCP, DECK MOUNTED,
5-1/4" RIGID/SWING GOOSENECK SPOUT, 8" CENTERS,
WRISTBLADE HANDLES, CERAMIC CARTRIDGE, 2.2 GPM
LAMINAR FLOW OUTLET, POLISHED CHROME.
CHICAGO FAUCETS 786-E29XKABCP, DECK MOUNTED,
AMERICAN STANDARD MURRO
5-1/4" RIGID/SWING GOOSENECK SPOUT, 8" CENTERS,
0958.908EC, WALL HUNG FOR
WRISTBLADE HANDLES, CERAMIC CARTRIDGE, 2.2 GPM
CONCEALED ARMS SUPPORT, 8"
LAMINAR FLOW OUTLET, POLISHED CHROME.
CENTERS, LESS OVERFLOW, VITREOUS
CHINA, WHITE, EVERCLEAN SURFACE.
NA
GUY GRAY MIB1AB, RECESSED, WHITE
POWDER COATED STEEL ICE MAKER
OUTLET BOX, WITH BRASS PLATED,
QUARTER TURN, LEAD-FREE
COMPLIANT BALL VALVE.
NA
TRAP
(IN)
NA
STOP
INTEGRAL ANGLE STOP ON FLUSH
VALVE.
ELKAY LR1919, 18 GAUGE, TYPE 304
STAINLESS STEEL, 19-1/2" X 19" X 7-1/2"
DEEP, 3 HOLE, UNDERCOATED.
YES
WASTE
(IN)
4
TRIM
SLOAN MANUAL FLUSHOMETER MODEL ROYAL 113-1.28,
1-1/2" SPUD
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
Dunham Job #: 415134
Certification
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
ACCESSIBLE CHECK VALVES &
SHUTOFFS ON HOT & COLD SUPPLIES.
AMERICAN STANDARD 7798.030, 3" CAST
IRON 'P' TRAP STANDARD TO WALL &
STRAINER FOR 3" IRON PIPE.
WALL HANGER SUPPLIED WITH
FIXTURE.
3
3
1-1/2
3/4
3/4
NA
PROVIDE CHICAGO FAUCET #952 AND BACKFLOW PREVENTOR.
CHICAGO 1025-ABCP QUARTER TURN
POLISHED C.P. CAST BRASS ANGLE
VALVE KITS, LOOSE KEY, FLEXIBLE
RISERS, ESCUTCHEON
CHICAGO 1771-ABCP QUARTER TURN
POLISHED
1-1/2" 'P' TRAP
NA
2
2
1-1/2
1/2
1/2
NA
PROVIDE CHICAGO FAUCETS 122-ABNF THERMOSTATIC MIXING VALVE, TMV-2, (FOR UP TO 8
FITTINGS)
ENCASED, KEY-OPERATED
RSP Architects
Signature
Bryan Schmidt
Registration Number
NA
INTEGRAL
NA
NA
2
NA
2
NA
NA
NA
1/2
NA
1/2
3/4
NA
NA
INCLUDE SHOWER CURTAIN AND ROD, ADD VERTICAL GRAB BAR, ADD FLEXIBLE DAM
NA
Date
26566
07/24/15
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
ALL FROST PROOF HYDRANTS SHALL BE INSTALLED IN A SLEEVE
Signature
James A. LeClaire
Registration Number
THERMOSTATIC MIXING VALVE SCHEDULE
EQUIPMENT
TAG
TMV-1
TMV-2
MINIMUM
FLOW
(GPM)
1.5
0.5
MAXIMUM FLOW
(GPM)
10.5
20
COLD WATER BYPASS
(GPM)
2.3
0
Date
EMERGENCY PLUMBING FIXTURE SCHEDULE
PRESSURE DROP AT MAXIMUM
FLOW (PSI)
60
125
OUTLET TEMPERATURE
(F)
INLET TEMPERATURE (F)
140
85
140
110
CW INLET
(IN)
1/2"
1/2"
HW INLET
(IN)
1/2"
1/2"
OUTLET
(IN)
1/2"
1/2"
MANUFACTURER
BRADLEY
CHICAGO
FAUCETS
MODEL
NUMBER
S-19-2000
122-ABNF
EQUIPMENT
TAG
EP-1
MECHANICAL NOTES
1,2
-
EP-2
FIXTURE DESCRIPTION
EMERGENCY EYE / FACEWASH
MOUNTING
WALL
ADA
YES
EMERGENCY EYEWASH / FAUCET
COMBINATION
COUNTER
NO
MECHANICAL NOTES:
1. SEE DETAIL FOR ADDITIONAL PIPING REQUIREMENTS
2. PROVIDE INLET CHECK VALVES ON MIXING VALVE.
FIXTURE
SPEAKMAN SE-1000, YELLOW PLASTIC BOWL,
WITH TAIL PIECE STAINLESS STEEL PUSH
HANDLE, UNIVERSAL EMERGENCY SIGN
SPEAKMAN SEF-1800-CA, EYESAVER
LABORATORY WIDESPREAD FAUCET WITH
INTEGRATED EYEWASH
STOP
BALL VALVE
TRAP
1-1/4
WASTE
(IN)
1-1/2
TRAP
(IN)
1-1/4
VENT
(IN)
1-1/2
CW
(IN)
NA
HW
(IN)
NA
TW
(IN)
1/2
MECHANICAL
NOTES
1
BALL VALVE
NA
NA
NA
NA
1/2
1/2
1/2
1
50358
07/24/15
Project For
MECHANICAL NOTES:
1. INSTALL TMV-1 WITH EMERGENCY EQUIPMENT.
FLOOR SINK SCHEDULE
EQUIPMENT
TAG
FS-1
SIZE
(IN)
3"
MANUFACTURER
JOSAM
STUDENT HEALTH AND
ACADEMIC RENOVATION
STEAM WATER HEATER SCHEDULE - SEMI-INSTANTANEOUS
MODEL
NUMBER
49503-LF-NB
MECHANICAL
NOTES
-
MECHANICAL (223500)
WATER
EQUIPMENT
TAG
SWH 01
MECHANICAL NOTES:
APPLICATION
LOWER LEVEL
STORAGE CAPACITY
(GAL)
215
RECOVERY RATE (GPH)
600
TEMPERATURE RISE (F)
80
PRESSURE BEFORE CONTROL VALVE
(PSIG)
8-10
STEAM
CONTROL VALVE PRESSURE DROP
(PSIG)
5
STEAM PRESSURE AT BUNDLE
(PSIG)
3-5
STEAM CAPACITY
(LBS/HR)
410
DOUBLE WALL
HEAT EXCHANGER
(YES/NO)
YES
MANUFACTURER
PVI INDUSTRIES
MODEL NUMBER
600 L 215A-QSD
MECHANICAL NOTES
1
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
MECHANICAL NOTES:
1. SET LEAVING WATER TEMPERATURE TO 140F
ELECTRICAL
FLOOR DRAIN SCHEDULE
EQUIPMENT
TAG
FD-1
FD-2
SIZE (IN)
SEE FLOOR PLAN
SEE FLOOR PLAN
MANUFACTURER
JOSAM
JOSAM
MODEL
NUMBER
30000-A
30000-A
EQUIPMENT
TAG
SWH 01
MECHANICAL NOTES
1
1,2
MECHANICAL NOTES:
1. ROUND NIKALOY FINISH TOP, LESS BACKWATER VALVE
2. DRY PAN DRAIN
HP/LOAD
20A CKT
VOLTAGE PHASE
120 V
1
TYPE
CP
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 22/DIV. 22
INTEGRAL
CTRL WIRE BY
DIV. 22
AMPS/TYPE
MRS
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
1
DIV. 26/DIV. 26
LOCATION
AT UNIT
PANEL
N-B2
CIRCUIT
NUMBER
5
CONDUIT/FEEDER SIZE
3/4" C, 2#12, 1#12G
ELECTRICAL NOTES
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE
INFORMATION.
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
ELECTRICAL NOTES:
ELECTRIC WATER COOLER SCHEDULE
EQUIPMENT
TAG
EWC-1
FIXTURE DESCRIPTION
DUAL ELECTRIC WATER
COOLER
MOUNTING
WALL
ADA
YES
SUMP PUMP SCHEDULE
FIXTURE
EZH20 BOTTLE FILLING STATION, BI-LEVEL, MODELS
EZSTL8WS & EZSTLDDWS
STOP
INTEGRAL
TRAP
SEE PLAN FOR
SIZE
WASTE
(IN)
1-1/2"
TRAP
(IN)
1-1/4"
VENT
(IN)
1-1/2"
CW
(IN)
1/2"
MECHANICAL
NOTES
1
MECHANICAL NOTES:
MECHANICAL (221429)
EQUIPMENT
TAG
SP 01
APPLICATION
ELEVATOR SUMP
Project No.
TYPE
SUBMERSIBLE
GPM
100
DISCHARGE
HEAD (FT)
22
NUMBER OF
PUMPS
1
BASIN
DIAMETER
DEPTH
(IN)
(IN)
30
114
MOTOR RPM
(EACH)
1750
Drawn By
MANUFACTURER
WEIL
MODEL NUMBER
2445 - 1.5HP
MECHANICAL NOTES
PROVIDE WITH CONTROL PANEL 8153
Checked By
1. REFER TO ELECTRICAL PLANS FOR RECEPTACLE LOCATION.
Date
EQUIPMENT
TAG
SP 01
AREA DRAIN SCHEDULE
MECHANICAL (221319)
EQUIPMENT
TAG
AD-1
SIZE
(IN)
3
MECHANICAL NOTES:
MANUFACTURER
JOSAM
MODEL
NUMBER
22083
MECHANICAL
NOTES
-
HP/LOAD
1.5 HP
VOLTAGE PHASE
208 V
3
TYPE
MAGS
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 26/DIV. 26
SEE PLANS
DISCONNECT AT MOTOR
CTRL WIRE BY
DIV. 23
AMPS/TYPE
SEE STARTER
SCHEDULE
FUSE SIZE (AMPS)
SEE STARTER
SCHEDULE
NEMA TYPE
SEE STARTER
SCHEDULE
FURNISHED BY/
INSTALLED BY
SEE STARTER
SCHEDULE
LOCATION
AT UNIT
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE
INFORMATION.
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
PANEL
RD-B1
CIRCUIT
NUMBER
8,10,12
CONDUIT/FEEDER SIZE
3/4" C, 3#12, 1#12G
ELECTRICAL
NOTES
Nick U
Nic I
2/19/2016
MECHANICAL NOTES:
ELECTRICAL
2263.001.00
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
Revisions
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
No.
Date
Description
ELECTRICAL NOTES:
DOMESTIC WATER PUMP SCHEDULE
MECHANICAL (221123)
EQUIPMENT
TAG
DWP 1
APPLICATION
HOT WATER RECIRCULATION
TYPE
HORIZONTAL
GPM
17
DISCHARGE NPSHR
HEAD (FT)
(FT)
22
2
RPM
2100
BHP
1.0
SUCTION
SIZE (IN)
1-1/2
DISCHARGE
SIZE (IN)
1-1/2
VFD
(YES/NO)
YES
MANUFACTURER
BELL AND GOSSET
MODEL
NUMBER
ECOCIRC XL
B 65-130
MECHANICAL NOTES
1
MECHANICAL NOTES:
1. PUMP SIZED FOR 17GPM WHICH INCLUDES FUTURE SHELL SPACE PIPING.
ELECTRICAL
EQUIPMENT
TAG
DWP 01
HP/LOAD
1 HP
TYPE
CP
CTRL WIRE BY
DIV. 22
AMPS/TYPE
MRS
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
1
DIV. 26/DIV. 26
LOCATION
AT UNIT
PANEL
N-B2
CIRCUIT
NUMBER
7,9
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
ELECTRICAL NOTES:
C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt
2/18/2016 3:49:51 PM
VOLTAGE PHASE
208 V
1
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 22/DIV. 22
INTEGRAL
CONDUIT/FEEDER SIZE
3/4" C, 2#12, 1#12G
ELECTRICAL NOTES
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
PLUMBING
ELECTRICAL
SCHEDULES
M901
AIR HANDLING UNIT SCHEDULE
MECHANICAL (237313, 237316, 237333, 237339)
EQUIPMENT
TAG
AHU 01
AHU 02
AHU 03
APPLICATION
HEATING/COOLING
HEATING/COOLING
HEATING/COOLING
FACE & BYPASS
DAMPERS (YES/NO)
YES (HX)
NO
NO
MIXING BOX
(YES/NO)
NO
NO
NO
MINIMUM OUTDOOR
AIR CFM
7400
2000
6500
COOLING
COIL
AHUCC 01
AHUCC 02
AHUCC 03
HEATING
COIL
AHUHC 01
AHUHC 02
AHUHC 03
HEAT
RECOVERY
COIL
HX 01
NO
NO
AIR
FILTER
AHUAF 01
AHUAF 02
AHUAF 03
AIR
PRE-FILTER
AHUPF 01
AHUPF 02
AHUPF 03
AIR
FINAL-FILTER
AHUFF 01
AHUFF 02
AHUFF 03
HUMIDIFIER
NO
NO
NO
AIR BLENDER
NO
AHUAB 02
AHUAB 03
SUPPLY
FAN
AHUS 01
AHUS 02
AHUS 03
PREHEAT COIL
AHUPHC-01
NO
NO
RETURN
FAN
AHUR 01
AHUR 02
AHUR 03
MANUFACTURER
DAIKIN-MCQUAY
DAIKIN-MCQUAY
DAIKIN-MCQUAY
MODEL NUMBER
VISION
VISION
VISION
MECHANICAL NOTES
MECHANICAL NOTES:
ELECTRICAL
EQUIPMENT
TAG
HP/LOAD
VOLTAGE PHASE
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
TYPE
CTRL WIRE BY
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
AMPS/TYPE
LOCATION
CIRCUIT
NUMBER
PANEL
CONDUIT/FEEDER SIZE
ELECTRICAL NOTES
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
ELECTRICAL NOTES:
AIR HANDLING UNIT - SUPPLY FAN SCHEDULE
Dunham Job #: 415134
MECHANICAL (233416)
EQUIPMENT
TAG
AHUS 01
AHUS 02
AHUS 03
NUMBER OF
FANS
1
1
1
AHU SERVED
AHU 01
AHU 02
AHU 03
TYPE
CENTRIFUGAL-PLENUM
CENTRIFUGAL-PLENUM
CENTRIFUGAL-PLENUM
CLASS
2
2
2
CFM PER FAN
7400
13000
26000
TOTAL CFM
7400
13000
26000
ESP (IN W.C.)
2.5
3.0
3.0
TOTAL SP
(IN W.C.)
4.33
4.64
4.59
Certification
WHEEL
DIAMETER
(IN)
20.0
24.5
44.5
VFD
(YES/NO)
YES
YES
YES
FAN
RPM
2337
2014
903
BHP
5.34
14.23
27.28
DRIVE TYPE
(BELT/DIRECT)
BELT
BELT
BELT
MODEL
NUMBER
NA
NA
NA
MANUFACTURER
DAIKIN-MCQUAY
DAIKIN-MCQUAY
DAIKIN-MCQUAY
MECHANICAL NOTES
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
Signature
Bryan Schmidt
MECHANICAL NOTES:
Registration Number
Date
ELECTRICAL
EQUIPMENT
TAG
AHUS 01
AHUS 02
AHUS 03
AIR HANDLING UNIT - AIR BLENDER SCHEDULE
EQUIPMENT
TAG
AHUAB 02
AHUAB 03
AHU
SERVED
AHU 02
AHU 03
MINIMUM
CFM
6500
13000
DESIGN
CFM
13000
26000
DESIGN APD
(IN W.C.)
0.14
0.15
DESIGN
VELOCITY
(FPM)
977
1036
HP/LOAD
10 HP
20 HP
40 HP
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 23/DIV. 26
SEE PLANS
DIV. 23/DIV. 26
SEE PLANS
DIV. 23/DIV. 26
SEE PLANS
TYPE
VFD
VFD
VFD
VOLTAGE PHASE
208 V
3
208 V
3
208 V
3
CTRL WIRE BY
DIV. 23
DIV. 23
DIV. 23
AMPS/TYPE
60A/FUSED
100A/FUSED
200A/FUSED
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
PER MANUF.
1
DIV. 23/DIV. 26
PER MANUF.
1
DIV. 23/DIV. 26
PER MANUF.
1
DIV. 23/DIV. 26
LOCATION
SEE PLANS
SEE PLANS
SEE PLANS
CIRCUIT
NUMBER
1,3,5
2,4,6
13,15,17
PANEL
ND-B1
ND-B1
ND-B1
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
CONDUIT/FEEDER SIZE
3/4" C, 3#8, 1#10G
1 1/4" C, 3#4, 1#6G
1 1/2" C, 3#1/0, 1#6G
ELECTRICAL
NOTES
1,2
1,2
1,2
07/24/15
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
James A. LeClaire
Signature
Registration Number
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
50358
Date
07/24/15
ELECTRICAL NOTES:
MECHANICAL (237313 & 237316)
MINIMUM
VELOCITY
(FPM)
488
518
26566
Project For
1. DISCONNECT IS INTERGRAL TO VFD WITH OVERCURRENT PROTECTION.
2. PROVIDE 120V POWER FOR LIGHTS AND RECEPTACLES WITHIN ENCLOSURE.
MANUFACTURER
BLENDER PRODUCTS
BLENDER PRODUCTS
MODEL
NUMBER
IV
IV
MECHANICAL NOTES
AIR HANDLING UNIT - RETURN FAN SCHEDULE
MECHANICAL NOTES:
MECHANICAL (233416)
EQUIPMENT
TAG
AHUR 01
AHUR 02
AHUR 03
NUMBER OF
FANS
1
1
1
AHU SERVED
AHU 01
AHU 02
AHU 03
TYPE
CENTRIFUGAL-PLENUM
CENTRIFUGAL-PLENUM
CENTRIFUGAL-PLENUM
CLASS
2
2
2
CFM PER FAN
9000
11000
20000
TOTAL CFM
9000
11000
20000
TOTAL SP
(IN W.C.)
3.54
1.67
1.66
ESP (IN W.C.)
2.5
1.50
1.50
WHEEL
DIAMETER
(IN)
22.25
24.5
33.0
VFD
(YES/NO)
YES
YES
YES
FAN
RPM
1988
1525
1113
BHP
8.09
5.53
9.79
DRIVE TYPE
(BELT/DIRECT)
BELT
BELT
BELT
MANUFACTURER
DAIKIN-MCQUAY
DAIKIN-MCQUAY
DAIKIN-MCQUAY
MODEL
NUMBER
NA
NA
NA
MECHANICAL NOTES
MECHANICAL NOTES:
AIR HANDLING UNIT - PREFILTER SCHEDULE
MECHANICAL (234100)
EQUIPMENT
TAG
AHUPF 01
AHUPF 02
AHUPF 03
AHU
SERVED
AHU 01
AHU 02
AHU 03
TYPE
PLEATED
PLEATED
PLEATED
CFM
7400
13000
26000
NUMBER OF
MODULES
6
3/6
12/6/5
SIZE PER MODULE (H"xL"xD")
20"x24"x2"
24"x24"x2"/20"x24"x2"
24"x20"x2"/20"x20"x2"/12"x24"x2"
STUDENT HEALTH AND
ACADEMIC RENOVATION
MERV
RATING
7
7
7
APD CLEAN
(IN W.C.)
0.27
0.31
0.29
APD AT 50%
LOADING (IN W.C.)
0.63
0.66
0.65
MANUFACTURER
NA
NA
NA
MODEL
NUMBER
NA
NA
NA
MECHANICAL
NOTES
ELECTRICAL
EQUIPMENT
TAG
AHUR 01
AHUR 02
AHUR 03
MECHANICAL NOTES:
HP/LOAD
10 HP
7.5 HP
15 HP
VOLTAGE PHASE
208 V
3
208 V
3
208 V
3
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 23/DIV. 26
SEE PLANS
DIV. 23/DIV. 26
SEE PLANS
DIV. 23/DIV. 26
SEE PLANS
TYPE
VFD
VFD
VFD
CTRL WIRE BY
DIV. 23
DIV. 23
DIV. 23
AMPS/TYPE
60A/FUSED
60A/FUSED
100A/FUSED
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
PER MANUF.
1
DIV. 23/DIV. 26
PER MANUF.
1
DIV. 23/DIV. 26
PER MANUF.
1
DIV. 23/DIV. 26
LOCATION
SEE PLANS
SEE PLANS
SEE PLANS
CIRCUIT
NUMBER
7,9,11
8,10,12
14,16,18
PANEL
ND-B1
ND-B1
ND-B1
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
CONDUIT/FEEDER SIZE
3/4" C, 3#8, 1#10G
3/4" C, 3#8, 1#10G
1" C, 3#6, 1#8G
ELECTRICAL
NOTES
1,2
1,2
1,2
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
ELECTRICAL NOTES:
1. DISCONNECT IS INTERGRAL TO VFD WITH OVERCURRENT PROTECTION.
2. PROVIDE 120V POWER FOR LIGHTS AND RECEPTACLES WITHIN ENCLOSURE.
AIR HANDLING UNIT - AIR FILTER SCHEDULE
MECHANICAL (234100)
EQUIPMENT
TAG
AHUAF 01
AHUAF 02
AHUAF 03
AHU
SERVED
AHU 01
AHU 02
AHU 03
TYPE
CARTRIDGE
CARTRIDGE
CARTRIDGE
CFM
7400
13000
26000
NUMBER OF
MODULES
6
3/6
12/6/5
SIZE PER MODULE (H"xL"xD")
20"x24"x4"
24"x24"x4"/20"x24"x4"
24"x20"x4"/20"x20"x4"/12"x24"x4"
MERV
RATING
13
13
13
APDP CLEAN
(IN W.C.)
0.34
0.40
0.37
APD AT 50%
LOADING (IN W.C.)
0.92
0.95
0.94
MANUFACTURER
VARICEL
VARICEL
VARICEL
MODEL
NUMBER
II MH
II MH
II MH
MECHANICAL
NOTES
AIR HANDLING UNIT - COOLING COIL SCHEDULE - CHILLED WATER
MECHANICAL (238216)
COIL
EQUIPMENT
TAG
AHUCC 01
AHUCC 02
AHUCC 03
MECHANICAL NOTES:
AHU
SERVED
AHU 01
AHU 02
AHU 03
CFM
7400
13000
26000
NUMBER EACH COIL SIZE
OF COILS
(W"xH")
1
36"x67"
2
30"x67"
2
36"X106"
AIR
ROWS
8
8
8
FINS
PER
INCH
10
10
10
EAT
DB
WB
(F)
(F)
80.1 73.1
79.5 68.0
79.5 68.0
LAT
DB
WB
(F)
(F)
52.6 52.4
51.0 50.8
51.0 50.8
WATER
FACE
VELOCITY
(FPM)
442
466
477
EWT
(F)
42
42
42
APD (IN W.C.)
0.42
0.46
0.48
LWT
(F)
54
54
54
GPM
84
113
226
GLYCOL TYPE
NONE
NONE
NONE
GLYCOL
%
0
0
0
WPD
(FT)
14.0
13.9
18.6
SENSIBLE
CAPACITY
(MBH)
222.317
405.510
811.363
TOTAL
CAPACITY
(MBH)
500.773
678.125
1357.423
MANUFACTURER
DAIKIN-MCQUAY
DAIKIN-MCQUAY
DAIKIN-MCQUAY
MODEL
NUMBER
5WS1008A
5WS1008A
5WM1008A
MECHANICAL
NOTES
Project No.
2263.001.00
Drawn By
Bryan S
Checked By
Nic I
Date
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
AIR HANDLING UNIT - HEATING COIL SCHEDULE - HEATING WATER
MECHANICAL (238216)
COIL
EQUIPMENT
TAG
AHUHC 01
AHUHC 02
AHUHC 03
AHU
SERVED
AHU 01
AHU 02
AHU 03
HEATING CFM
7400
13000
26000
NUMBER
OF COILS
1
2
2
EACH COIL SIZE
(W"xH")
36"x64"
30"x64"
36"x106"
ROWS
1
1
1
FINS
PER
INCH
6
6
6
EAT
(F)
51.2
40.0
40.0
LAT
(F)
64.8
52
52
AIR
FACE
VELOCITY
(FPM)
463
488
491
2/19/2016
WATER
© Copyright RSP Architects 2015. All rights reserved.
MAX. APD (IN
W.C.)
0.1
0.1
0.1
EWT
(F)
180.0
180.0
180.0
LWT
(F)
160
160
160
GPM
12.0
18.3
36.6
GLYCOL TYPE
PROPYLENE
PROPYLENE
PROPYLENE
GLYCOL
%
35
35
35
WPD
(FT)
0.40
0.60
1.80
CAPACITY
(MBH)
110,242
168,000
336,000
MANUFACTURER
DAIKIN-MCQUAY
DAIKIN-MCQUAY
DAIKIN-MCQUAY
MODEL
NUMBER
5WB0601B
5WB0601C
5WB0601C
MECHANICAL
NOTES
Revisions
No.
Date
Description
AIR HANDLING UNIT - PREHEAT COIL SCHEDULE - HEATING WATER
MECHANICAL (238216)
COIL
EQUIPMENT
TAG
AHUPHC 01
DESCRIPTION
PREHEAT COIL
CFM
7400
NUMBER
OF COILS
1
EACH COIL SIZE
(W"xH")
64" X 36"
ROWS
1
FINS
PER
INCH
7
EAT
(F)
-20
LAT
(F)
10
AIR
FACE
VELOCITY
(FPM)
463
WATER
APD (IN W.C.)
0.07
EWT
(F)
180
LWT
(F)
160
GPM
25
GLYCOL TYPE
PROPYLENE
GLYCOL
%
30
WPD
(FT)
5
CAPACITY
(MBH)
250
MANUFACTURER
DAIKIN
MODEL
NUMBER
5WB0701B
MECHANICAL
NOTES
FIXED-PLATE AIR-TO-AIR HEAT EXCHANGER SCHEDULE
MECHANICAL (237200)
EQUIPMENT
TAG
HX 001
UNIT
SERVED
AHU-01
RETURN AIR ENTERING
DB
RH
(F)
(%)
CFM
75.0
54
9000
MECHANICAL NOTES:
WINTER PERFORMANCE
OUTDOOR AIR ENTERING OUTDOOR/SUPPLY AIR LEAVING
DB
RH
DB
RH
(F)
(%)
(F)
(%)
CFM
CFM
-20.0
0
7400
51.2 32
7400
ENERGY
RECOVERED
(MBH)
569.326
RETURN AIR ENTERING
DB
RH
(F)
(%)
CFM
75
54
9000
SUMMER PERFORMANCE
OUTDOOR AIR ENTERING OUTDOOR/SUPPLY AIR LEAVING
DB
RH
DB
RH
(F)
(%)
(F)
(%)
CFM
CFM
91.0
54
7400
80.1
74
7400
ENERGY
RECOVERED
(MBH)
89.581
APD (IN W.C.)
1.04
MANUFACTURER
DAIKIN-MCQUAY
MODEL
NUMBER
XLT-H
50(24)-60
MECHANICAL
NOTES
1
MECHANICAL
ELECTRICAL
SCHEDULES
1. PROVIDE SUPPLY AIR FACE AND BYPASS DAMPER
C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt
2/18/2016 3:50:35 PM
M902
FAN POWERED VARIABLE AIR VOLUME BOX SCHEDULE - HEATING WATER
MECHANICAL (233600)
EQUIPMENT
TAG
FVAV 101
FVAV 201
FVAV 301
PRIMARY AIR
MAXIMUM
MINIMUM
CFM
CFM
800
0
800
0
800
0
INLET
SIZE
(IN)
14x8
14x8
14x8
TYPE
PARALLEL
PARALLEL
PARALLEL
FAN
CFM
800
800
800
HEATING COIL
ESP (IN W.C.)
0.2
0.2
0.2
HEATING
CFM
0
0
0
EAT
(F)
LAT
(F)
CAPACITY
(MBH)
EWT
(F)
LWT
(F)
GPM
GLYCOL TYPE
MAXIMUM
WPD (FT)
GLYCOL %
MAXIMUM
COIL RADIATED
NC
ROWS
40
40
40
MODEL
NUMBER
DFLP
DFLP
DFLP
MANUFACTURER
TITUS
TITUS
TITUS
MECHANICAL NOTES
MECHANICAL NOTES:
ELECTRICAL
EQUIPMENT
TAG
FVAV 101
FVAV 201
FVAV 301
HP/LOAD
1/3 HP
1/3 HP
1/3 HP
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 26/DIV. 26
AT UNIT
DIV. 26/DIV. 26
AT UNIT
DIV. 26/DIV. 26
AT UNIT
TYPE
MRS
MRS
MRS
VOLTAGE PHASE
120 V
1
120 V
1
120 V
1
CTRL WIRE BY
DIV. 23
DIV. 23
DIV. 23
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
1
DIV. 26/DIV. 26
1
DIV. 26/DIV. 26
1
DIV. 26/DIV. 26
AMPS/TYPE
MRS
MRS
MRS
LOCATION
AT UNIT
AT UNIT
AT UNIT
PANEL
O-21A
O-21A
O-21A
CIRCUIT
NUMBER
13
12
15
CONDUIT/FEEDER SIZE
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
ELECTRICAL NOTES
RSP Architects
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
ELECTRICAL NOTES:
Dunham Job #: 415134
UNIT HEATER SCHEDULE - HEATING WATER
Certification
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
MECHANICAL (238239)
FAN
EQUIPMENT
TAG
CUH 101
CUH 102
CUH 103
CUH 104
CUH 303
UH 001
UH 002
UH 003
APPLICATION
HEATING
HEATING
HEATING
HEATING
HEATING
HEATING
HEATING
HEATING
TYPE
WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE
WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE
WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE
WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE
WALL SURFACE, TOP FRONT INTAKE, BOTTOM DISCHARGE
HORIZONTAL
HORIZONTAL
HORIZONTAL
CFM
620
620
620
620
620
1120
1120
1120
COIL
MOTOR HP
1/10
1/10
1/10
1/10
1/10
1/10
1/10
1/10
EAT
(F)
60
60
60
60
60
60
60
60
COIL
ROWS
2
2
2
2
2
1
1
1
EWT
(F)
180
180
180
180
180
180
180
180
LWT
(F)
160
160
160
160
160
160
160
160
GPM
7.3
7.3
7.3
7.3
7.3
4.7
4.7
4.7
GLYCOL TYPE
PROPYLENE
PROPYLENE
PROPYLENE
PROPYLENE
PROPYLENE
PROPYLENE
PROPYLENE
PROPYLENE
GLYCOL
%
35
35
35
35
35
35
35
35
MAX.
WPD
(FT)
5
5
5
5
5
5
5
5
CAPACITY
(MBH)
60
60
60
60
60
40
40
40
MANUFACTURER
RITTLING
RITTLING
RITTLING
RITTLING
RITTLING
RITTLING
RITTLING
RITTLING
MODEL
NUMBER
RWI-300-06
RWI-300-06
RWI-300-06
RWI-300-06
RWI-300-06
RH-63
RH-63
RH-63
MECHANICAL NOTES
Signature
Bryan Schmidt
Registration Number
26566
Date
07/24/15
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
MECHANICAL NOTES:
James A. LeClaire
Signature
ELECTRICAL
EQUIPMENT
TAG
CUH 101
CUH 102
CUH 103
CUH 104
CUH 303
UH 001
UH 002
UH 003
Registration Number
HP/LOAD
1/4 HP
1/4 HP
1/4 HP
1/4 HP
1/4 HP
1/10 HP
1/10 HP
1/10 HP
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 23/DIV. 23
INTEGRAL
DIV. 23/DIV. 23
INTEGRAL
DIV. 23/DIV. 23
INTEGRAL
DIV. 23/DIV. 23
INTEGRAL
DIV. 23/DIV. 23
INTEGRAL
DIV. 26/DIV. 26
AT UNIT
DIV. 26/DIV. 26
AT UNIT
DIV. 26/DIV. 26
AT UNIT
TYPE
MRS
MRS
MRS
MRS
MRS
MRS
MRS
MRS
VOLTAGE PHASE
120 V
1
120 V
1
120 V
1
120 V
1
120 V
1
120 V
1
120 V
1
120 V
1
CTRL WIRE BY
DIV. 23
DIV. 23
DIV. 23
DIV. 23
DIV. 23
DIV. 23
DIV. 23
DIV. 23
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
1
DIV. 23/DIV. 23
1
DIV. 23/DIV. 23
1
DIV. 23/DIV. 23
1
DIV. 23/DIV. 23
1
DIV. 23/DIV. 23
1
DIV. 26/DIV. 26
1
DIV. 26/DIV. 26
1
DIV. 26/DIV. 26
AMPS/TYPE
MRS
MRS
MRS
MRS
MRS
MRS
MRS
MRS
LOCATION
INTEGRAL
INTEGRAL
INTEGRAL
INTEGRAL
INTEGRAL
AT UNIT
AT UNIT
AT UNIT
CIRCUIT
NUMBER
21
8
24
10
1
4
11
13
PANEL
N-11
N-12
N-11
N-12
N-31
N-B2
N-B2
N-B2
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE
INFORMATION.
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
CONDUIT/FEEDER SIZE
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
ELECTRICAL
NOTES
1,2
1,2
1,2
1,2
1,2
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
ELECTRICAL NOTES:
1. ROUTE TO SINGLE POINT CONNECTION AT FACTORY MOUNTED DISCONNECT.
2. MRS LISTED UNDER CONTROLLER AND DISCONNECT ARE THE SAME SWITCH.
50358
Date
07/24/15
Project For
STUDENT HEALTH AND
ACADEMIC RENOVATION
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
FAN COIL UNIT SCHEDULE - CHILLED AND HEATING WATER
MECHANICAL (238219)
FAN
COOLING COIL
WATER
EQUIPMENT
TAG
FCU 101
FCU 102
APPLICATION
HEATING
HEATING
TYPE
HIDE AWAY
HIDE AWAY
NUMBER
OF FANS
2
2
MOTOR HP RPM
TOTAL
(EACH)
(EACH) CFM
1/10
1155
550
1/10
1155
550
ESP (IN W.C.)
0.3
0.3
EWT
(F)
LWT
(F)
GPM
GLYCOL TYPE
GLYCOL WPD
%
(FT)
EAT
DB
(F)
EAT
WB
(F)
HEATING COIL
AIR
LAT LAT
DB
WB
(F)
(F)
FILTER
WATER
FACE
VELOCITY
(FPM)
SENSIBLE
TOTAL
CAPACITY CAPACITY
(MBH)
(MBH)
EWT
(F)
180
180
LWT
(F)
160
160
GPM
4.5
4.5
AIR
GLYCOL TYPE
PROPYLENE
PROPYLENE
GLYCOL WPD
%
(FT)
35
5
35
5
EAT
(F)
65
65
LAT
(F)
135
135
CAPACITY
(MBH)
41
41
TYPE
THROWAWAY
THROWAWAY
MERV
RATING
4
4
MANUFACTURER
DAIKIN
DAIKIN
MODEL
MECHANICAL
NUMBER
NOTES
THINLINE S04
THINLINE S04
MECHANICAL NOTES:
ELECTRICAL
EQUIPMENT
TAG
FCU 101
FCU 102
HP/LOAD
1/10 HP
1/10 HP
VOLTAGE PHASE
120 V
1
120 V
1
TYPE
CP
CP
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 23/DIV. 23
INTEGRAL
DIV. 23/DIV. 23
INTEGRAL
CTRL WIRE BY
DIV. 23
DIV. 23
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
1
DIV. 26/DIV. 26
1
DIV. 26/DIV. 26
AMPS/TYPE
MRS
MRS
LOCATION
AT UNIT
AT UNIT
PANEL
N-11
N-11
CIRCUIT
NUMBER
12
12
CONDUIT/FEEDER SIZE
3/4" C, 2#12, 1#12G
3/4" C, 2#12, 1#12G
ELECTRICAL NOTES
Project No.
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE
INFORMATION.
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
2263.001.00
Drawn By
Bryan S
Checked By
ELECTRICAL NOTES:
Nic I
Date
2/19/2016
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
© Copyright RSP Architects 2015. All rights reserved.
FAN SCHEDULE
Revisions
MECHANICAL (233413, 233416, 233423)
EQUIPMENT
TAG
EF 01
EF 02
EF 03
TF 01
APPLICATION
EXHAUST
EXHAUST
EXHAUST
TRANSFER
TYPE
CENTRIFUGAL
CENTRIFUGAL
CENTRIFUGAL
CENTRIFUGAL
CFM
160
500
1500
1,000
ESP (IN W.C.)
0.5
0.75
0.75
0.25
BHP
.04
0.45
1.3
0.11
FAN
RPM
1466
2341
3372
1357
DRIVE
TYPE
DIRECT
BELT
BELT
DIRECT
SOUND
7.2 SONES
65 DB
76 DB
7.9 SONES
VFD
(YES/NO)
NO
NO
NO
NO
MANUFACTURER
GREENHECK
GREENHECK
GREENHECK
GREENHECK
No.
MODEL
NUMBER
G-080-VG
VK-H-10-5
VK-H-10-9
SQ-100-VG
Date
Description
MECHANICAL NOTES
ECM MOTOR
1
2
ECM MOTOR
MECHANICAL NOTES:
1. FAN SHALL HAVE 5" DISCHARGE NOZZE WITH MIN. 3,000 FT/MIN OUTLET VELOCITY AND A MINIMUM PLUME HEIGHT OF 15' @ 10 MPH WIND
2. FAN SHALL HAVE 9" DISCHARGE NOZZE WITH MIN. 3,000 FT/MIN OUTLET VELOCITY AND A MINIMUM PLUME HEIGHT OF 15' @ 10 MPH WIND,
ELECTRICAL
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 26/DIV. 26
AT UNIT
DIV. 26/DIV. 26
SEE PLANS
EQUIPMENT
TAG
EF 01
EF 02
HP/LOAD
1/6 HP
3/4 HP
EF 03
1.5 HP
208 V
3
MAGS
DIV. 26/DIV. 26
SEE PLANS
TF 01
1/4 HP
120 V
1
CP
DIV. 23/DIV. 23
INTEGRAL
VOLTAGE PHASE
120 V
1
208 V
3
TYPE
MRS
MAGS
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
CTRL WIRE BY AMPS/TYPE
DIV. 23
MRS
1
DIV. 26/DIV. 26
DIV. 23
SEE STARTER SEE STARTER SEE STARTER SEE STARTER
SCHEDULE
SCHEDULE
SCHEDULE
SCHEDULE
DIV. 23
SEE STARTER SEE STARTER SEE STARTER SEE STARTER
SCHEDULE
SCHEDULE
SCHEDULE
SCHEDULE
DIV. 23
MRS
1
DIV. 26/DIV. 26
LOCATION
AT UNIT
SEE PLANS
PANEL
N-31
N-32
CIRCUIT
NUMBER
3
13,15,17
CONDUIT/FEEDER SIZE
3/4" C, 2#12, 1#12G
3/4" C, 3#12, 1#12G
SEE PLANS
N-32
12,14,16
3/4" C, 3#12, 1#12G
AT UNIT
RD-B1
16
3/4" C, 2#12, 1#12G
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
ELECTRICAL
NOTES
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
ELECTRICAL NOTES:
MECHANICAL
ELECTRICAL
SCHEDULES
C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt
2/18/2016 3:50:04 PM
M903
HYDRONIC PUMP SCHEDULE
MECHANICAL (232123)
EQUIPMENT
TAG
HWP 01
HWP 02
APPLICATION
HEATING WATER
HEATING WATER
TYPE
BASE MOUNTED
BASE MOUNTED
GPM
200
200
DISCHARGE
GLYCOL
HEAD (FT) GLYCOL TYPE
%
70
PROPYLENE
30
70
PROPYLENE
30
NPSHR
(FT)
3
3
RPM
1760
1760
SUCTION
SIZE (IN)
3
3
BHP
5.1
5.1
DISCHARGE
SIZE (IN)
2.5
2.5
VFD
(YES/NO)
YES
YES
MANUFACTURER
TACO
TACO
MODEL
NUMBER
FI2509C
FI2509C
MECHANICAL
NOTES
MECHANICAL NOTES:
ELECTRICAL
EQUIPMENT
TAG
HWP 01
HP/LOAD
7.5 HP
HWP 02
7.5 HP
TYPE
MAGS
VOLTAGE PHASE
208 V
3
208 V
3
MAGS
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 26/DIV. 26
SEE PLANS
DIV. 26/DIV. 26
SEE PLANS
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
CTRL WIRE BY AMPS/TYPE
DIV. 23
SEE STARTER SEE STARTER SEE STARTER SEE STARTER
SCHEDULE
SCHEDULE
SCHEDULE
SCHEDULE
DIV. 23
SEE STARTER SEE STARTER SEE STARTER SEE STARTER
SCHEDULE
SCHEDULE
SCHEDULE
SCHEDULE
LOCATION
SEE PLANS
PANEL
O-B1A
CIRCUIT
NUMBER
11,13,15
SEE PLANS
O-B1A
10,12,14
RSP Architects
CONDUIT/FEEDER SIZE
3/4" C, 3#8, 1#10G
3/4" C, 3#8, 1#10G
ELECTRICAL NOTES
1220 Marshall Street NE
Minneapolis
Minnesota 55413-1036
612.677.7100
612.677.7499 fax
www.rsparch.com
Consultants
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
ELECTRICAL NOTES:
Dunham Job #: 415134
Certification
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
STEAM CONDENSATE PUMP SCHEDULE
MECHANICAL (232223)
PUMP
EQUIPMENT
TAG
SCP 01
APPLICATION
STEAM CONDENSATE
TYPE
DUPLEX
NUMBER OF
PUMPS
2
MOTOR HP
(EACH)
1.5
RPM
3500
DISCHARGE PRESSURE
(PSIG)
50
GPM
12
Signature
TANK
CAPACITY
(GAL)
14
MANUFACTURER
DOMESTIC
MODEL
NUMBER
MECHANICAL NOTES
Registration Number
07/24/15
I hereby certify that this plan, specification or report was
prepared by me or under my direct supervision and that I am
a duly licensed Professional Engineer under the laws of the
State of Minnesota.
ELECTRICAL
HP/LOAD
(2) 1.5 HP
26566
Date
MECHANICAL NOTES:
EQUIPMENT
TAG
SCP 01
Bryan Schmidt
VOLTAGE PHASE
208 V
3
TYPE
CP
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 23/DIV. 23
INTEGRAL
CTRL WIRE BY
DIV. 23
AMPS/TYPE
30A/FUSED
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
PER MANUF.
1
DIV. 26/DIV. 26
LOCATION
AT UNIT
PANEL
O-B1A
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE
INFORMATION.
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
CIRCUIT
NUMBER
16,18,20
CONDUIT/FEEDER SIZE
3/4" C, 3#12, 1#12G
ELECTRICAL
NOTES
1
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
James A. LeClaire
Signature
Registration Number
50358
Date
07/24/15
Project For
ELECTRICAL NOTES:
1. SINGLE POINT ELECTRICAL CONNECTION.
STUDENT HEALTH AND
ACADEMIC RENOVATION
GLYCOL FILL STATION SCHEDULE
MECHANICAl (232113)
EQUIPMENT
TAG
GFS 01
APPLICATION
HEATING WATER
NUMBER OF
PUMPS
1
GPM
(EACH)
5
DISCHARGE
HEAD (FT)
140
PUMP
MOTOR HP
(EACH)
3/4
RPM
(EACH)
3600
VOLTAGE/PHASE
(EACH)
120/1
TANK
CAPACITY
(GAL)
55 GAL
MANUFACTURER
BELL & GOSSETT
MODEL
NUMBER
GMU-60
MECHANICAL NOTES
DESIGN
DEVELOPMENT
ISSUE DATE 2/19/2016
MECHANICAL NOTES:
ELECTRICAL
EQUIPMENT
TAG
GFS 01
HP/LOAD
3/4 HP
VOLTAGE PHASE
120 V
1
TYPE
CP
CONTROLLER
FURNISHED BY/
INSTALLED BY
LOCATION
DIV. 23/DIV. 23
INTEGRAL
CTRL WIRE BY
DIV. 23
DISCONNECT AT MOTOR
FURNISHED BY/
FUSE SIZE
INSTALLED BY
(AMPS)
NEMA TYPE
1
DIV. 26/DIV. 26
AMPS/TYPE
MRS
LOCATION
AT UNIT
PANEL
N-B2
GENERAL ELECTRICAL NOTES:
CONTROLLER TYPES:
A. WHEN THE CONTROLLER TYPE IS A MAGNETIC STARTER, REFER TO THE MAGNETIC STARTER SCHEDULE FOR MORE
INFORMATION.
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
CIRCUIT
NUMBER
12
CONDUIT/FEEDER SIZE
3/4" C, 2#10, 1#10G
ELECTRICAL
NOTES
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
ELECTRICAL NOTES:
Project No.
VARIABLE FREQUENCY MOTOR CONTROLLER SCHEDULE
Drawn By
MECHANICAL/ELECTRICAL (230923)
EQUIPMENT
TAG
VOLTAGE PHASE
AHUR 01
208 V
3
AHUR 02
208 V
3
AHUR 03
208 V
3
AHUS 01
208 V
3
AHUS 02
208 V
3
AHUS 03
208 V
3
ENCLOSURE
PLENUM
RATED
CALCULATED ENCLOSURE TYPE
(YES/NO)
AFC
(NEMA 1/4X/12)
5303A
1
NO
4037A
1
NO
3720A
1
NO
3850A
1
NO
6653A
1
NO
9160A
1
NO
HARMONIC CONTROL
SEISMIC
BRACING
(YES/NO)
NO
NO
NO
NO
NO
NO
2263.001.00
VARIABLE TORQUE/ INPUT AC LINE OUTPUT AC
(YES/NO)
LINE (YES/NO)
CONSTANT TORQUE
VARIABLE
NO
NO
VARIABLE
NO
NO
VARIABLE
NO
NO
VARIABLE
NO
NO
VARIABLE
NO
NO
VARIABLE
NO
NO
BYPASS
(YES/NO)
NO
NO
NO
NO
NO
NO
VFD BYPASS
BYPASS TYPE BYPASS CONTROL
MOTOR STARTING IN
(CONTACTOR/
TYPE (MANUAL/
BYPASS MODE
VFD)
AUTOMATIC)
(FULL/REDUCED VOLTAGE)
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
MULTIPLE
MOTOR
CONTROL
(YES/NO)
NO
NO
NO
NO
NO
NO
ESSENTIAL
DAMPER
CONTROL SERVICE/ FIRE
LEED
CIRCUIT FIGHTER MODE REQUIREMENTS
(YES/NO)
(YES/NO)
(YES/NO)
NOTES
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
Bryan S
Checked By
Nic I
Date
2/19/2016
NOTICE: The designs shown and described herein
including all technical drawings, graphics, and models
thereof, are proprietary and cannot be copied, duplicated
or commercially exploited, in whole or in part, without
express written permission of RSP Architects. These are
available for limited review and evaluation by clients,
consultants, contractors, government agencies, vendors
and office personnel only in accordance with this Notice.
GENERAL NOTES:
© Copyright RSP Architects 2015. All rights reserved.
A. FOR VFD'S WITH BYPASS PROVISIONS, SEPARATE MOTOR OVERLOAD PROTECTION REQUIRED FOR EACH MOTOR, WHEN IN THE BYPASS POSITION.
B. VFD EQUIPMENT SHALL HAVE STANDARD SHORT-CIRCUIT CURRENT RATING HIGHER THAN THE CALCUALTED VALUE SHOWN IN THE SCHEDULE.
C. ALL VFDS SHALL HAVE INTEGRAL DISCONNECT WITH OVERCURRENT PROTECTION UNLESS NOTED OTHERWISE.
Revisions
No.
Date
Description
NOTES:
MAGNETIC STARTER SCHEDULE
STARTER
EQUIPMENT
TAG
VOLTAGE PHASE
EF 02
208 V
3
EF 03
208 V
3
HWP 01
208 V
3
HWP 02
208 V
3
SP 01
208 V
3
TYPE
FVNR
FVNR
FVNR
FVNR
FVNR
SIZE
00
00
1
1
00
CONTROL
VOLTAGE
24V
24V
24V
24V
24V
AMPS/TYPE
30A/FUSED
30A/FUSED
60A/FUSED
60A/FUSED
30A/FUSED
FUSE SIZE
(AMPS)
PER MANUF
PER MANUF
PER MANUF
PER MANUF
PER MANUF
FURNISHED BY/
INSTALLED BY
DIV. 26/DIV. 26
DIV. 26/DIV. 26
DIV. 26/DIV. 26
DIV. 26/DIV. 26
DIV. 26/DIV. 26
NOTES
GENERAL NOTES:
STARTER TYPES:
A. REFER TO ENCLOSED CONTROLLER SPECIFICATION FOR ACCESSORIES/MODIFIERS.
B. REFER TO MOTOR SCHEDULE FOR DISCONNECT REQUIRED AT MOTOR WHEN STARTER/DISCONNECT COMBINATION
DOES NOT SATISFY THE REQUIREMENT.
FVNR - FULL VOLTAGE NON-REVERSING
FVR - FULL VOLTAGE REVERSING
RVS - REDUCED VOLTAGE STARTER
MULTI - MULTIPLE SPEED MAGNETIC STARTER
NOTES:
C:\Revit Projects\SCSU Health Services - Mechanical 2016_MadelineK.rvt
2/18/2016 3:50:17 PM
ENCLOSURE
(NEMA TYPE)
3R
3R
1
1
1
DISCONNECT AT STARTER
DISCONNECT
(COMBINATION/
EXTERNAL)
COMBINATION
COMBINATION
COMBINATION
COMBINATION
COMBINATION
MECHANICAL
ELECTRICAL
SCHEDULES
M904