Sensor Technologies
Passive Infrared (PIR) Technology
•
•
Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF.
PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.
Using this paper versus standard paper
produced the following environmental benefits.
Based on Environmental Defense Fund Paper Calculator
Ultrasonic (US) Technology
•
•
•
Ultrasonic sensors use the Doppler principle. These sensors produce low intensity, inaudible sound and detect changes in sound waves caused by motion.
They are volumetric in nature and therefore not line-of-sight dependant.
They are much more sensitive to smaller motions.
Dual Technology
•
•
•
Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today.
This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use.
Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.
Number of Trees Saved
12
Total Energy Saved—Million BTU’s
7.9
Greenhouse Gas Reduction—lbs of CO2
4391
Gallons of Water Saved
4129
Solid Waste Reduction— lbs of Waste
683
Kilo-watt (kwh) Hours Saved
1702
MicroSet Self-Adjusting Technology
•
•
Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time.
By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.
North America Headquarters
203 Cooper Circle
Peachtree City, GA 30269
P: 800-553-3879
F: 800-954-7016
About Energy Codes
www.coopercontrol.com
ControlsSales@cooperindustries.com
Cooper Controls Ltd
Usk House, Lakeside,
Llantarnam Park,
Cwmbran, NP44 3HD. UK
P: +44 (0)1923 495495
F: +44 (0)1923 867880
Canada
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-507-4000
F: 905-568-7049
www.coopercontrol.com
enquiries@coopercontrols.co.uk
Energy costs and consumption continue to rise. Today, many energy codes and energy policies either require or incentivize the use of
energy efficient lighting controls on commercial projects.
ASHRAE 99.1-1999, 2001, 2004, 2007, 2010
In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off.
• Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the
ASHRAE standard.
• In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee
cafeterias and break rooms.
As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum.
LEED Green Building Rating System
Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a
prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009.
• Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.
Version
3.0
California Title 24
Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied:
•
•
•
•
Offices 250 sq. ft. or smaller
Multipurpose rooms of less than 1000 sq. ft.
Classrooms of any size
Conference rooms of any size
Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices.
Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.
IECC
• ASHRAE and Title 24 requirements must be met.
• IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.
Cooper US, Inc.
600 Travis, Suite 5600
Houston, TX 77002
P: 713-209-8400
F: 713-209-8995
www.cooperindustries.com
ACC120033
Cooper Controls, Greengate, Novitas, PCI Lighting Control Systems, VisionTouch,
VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, IntelliRelay, NeoSwitch,
TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the
U.S. and other countries. You are not permitted to use Cooper Trademarks without
the prior written consent of Cooper Industries.
Printed in USA
Greengate Occupancy
Sensor Guide
Occupancy Sensor Application Guide
Commercial Wall Switch Sensors
Commercial Line
Voltage
Fixture Mount
Commercial Line Voltage Ceiling Sensor
Commercial Low Voltage
Wall/Corner Mount
OAWC-DT-120W
OAWC-P-009L-H
OAWC-P-120W
OEF-P-2MH0-MV-S
OAC-P-1500-DMV
OAC-P-1500-MV
OAC-P-0500-DMV
OAC-P-0500-MV
OXC-P-2MH0-R
OXC-P-1500-R
OAC-DT-2000
OAC-DT-1000
OAC-DT-0501
OAC-U-2000
OAC-U-1000
OAC-U-0501
OAC-P-1500
OAC-P-0500
VNLW-P-1001-MV-N-*
ONW-P-1001-RR7-*
ONW-P-1001-SP-*
ONW-P-1001-D347-*
ONW-P-1001-347-*
ONW-P-1001-DMV-*
ONW-P-1001-MV-*
ONW-D-1001-RR7-*
ONW-D-1001-SP-*
ONW-D-1001-DMV-N*
ONW-D-1001-MV-N-*
ONW-D-1001-MV-*
ONW-D-1001-DMV-*
Specification Grade
OSW-U-0721-MV-*
OSW-P-0451-DMV-*
OSW-P-0451-MV-*
OSW-P-1001-MV-*
Commercial Grade
Commercial Low Voltage Ceiling Sensors
Specifications
Specifications
Passive Infrared
Technology
Ultrasonic
Dual Technology
Mounting
Coverage (sq. ft.)
1000
450
1000
1500
Manual
Self-Adjust
360°
500
1000
2000
500
1000
2000
120 or 277V
120 or 277V
120 or 277V
Not Required
15 sec to 2 hr
10-30 VDC
24 VAC
Required
RR7 Relay
Required
Not Included
120 or 277V
347V
360°
1500
2MHO
360°
up to 25’
Dual Technology Technology
Wall/Corner Mount
Mounting
1200
90 Linear
1200
120°
180°
8 to 12’
120°
120 to 277V
10 to 30 VDC
Required
RR7 Relay
Required
Not Required
Required
Not Required
Included
Not Included
Included
Not Included
Included
Not Included
SP, True
3-Way,
No Neutral
Required
W, V, A
SP, 3-Way*,
No Neutral Required
Dual Relay,
3-Way*, No
Neutral
Required
OAC-P0500-R
OAC-P-1500-R
OAC-U0501-R
OAC-U1000-R
OAC-U2000-R
OAC-DT0501-R
OAC-DT2000-R
SP, 3-Way*,
Light Icon No
Neutral
Dual Relay,
3-Way*, Light
Icon, Fan
Mode, No
Neutral
Required
SP, 3-Way*,
Light Icon,
EcoMeter
Dual Relay,
3-Way*, Light
Icon, Fan
Mode, EcoMeter
SP, Light Icon, EcoMeter
SP, 3-Way*,
No Neutral
Required,
Light Icon,
EcoMeter
Dual Relay,
3-Way*, No
SP, 3-Way*, No
Neutral Neutral, Light
Required, Light
Icon, EcoMeter
Icon, EcoMeter
Dual Relay,
3-Way*, No
Neutral Required,
Light Icon, EcoMeter
SP, Light Icon, EcoMeter
SP, 3-Way*,
Light Icon,
EcoMeter
Night Light
GOOD
BETTER
BEST
BEST
BEST
BEST
BETTER
BETTER
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
Copy/File/Storage
Room
BEST
BEST
BEST
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
Commercial Line Voltage Ceiling Sensors
BEST
GOOD
BEST
BEST
BETTER
BETTER
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
GOOD
GOOD
Hallway
GOOD
GOOD
BETTER
BEST
BEST
BEST
BEST
Office Home
Office Private
Open Office
w/Cubicles
Parking Garage
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
GOOD
GOOD
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER
BETTER
GOOD
GOOD
GOOD
BEST
BEST
BEST
Restroom Partitioned
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BETTER
BETTER
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BETTER
BEST
BETTER
BEST
BETTER
BEST
GOOD
BEST
BEST
BEST
BEST
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
Cafeteria
Classroom
BETTER
BEST
Computer Room
GOOD
BETTER
BEST
Conference Room
BEST
BEST
GOOD
BETTER
Copy/File/Storage
Room
BETTER
Hallway
BEST
Loading Dock
BETTER
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
BEST
GOOD
GOOD
BETTER
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BEST
Office Executive
BEST
BEST
Office Home
Office Private
Open Office
w/Cubicles
Parking Garage
BEST
BEST
Refrigerated Storage
BEST
GOOD
Applications
Cafeteria High Ceiling
GOOD
GOOD
Feature
Closet/Utility
BEST
Residential Room
GOOD
BETTER
BEST
BEST
BEST
BEST
GOOD
BEST
GOOD
Restroom Non-Partitioned
BEST
Restroom Partitioned
BEST
Restroom Residential
GOOD
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
GOOD
BEST
BEST
Warehouse Aisles
BETTER
BETTER
Warehouse Open
BETTER
BETTER
3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out.
SP: Single Pole
Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black
Other specialty sensors available at www.coopercontrols.com
Commercial Low Voltage Wall/Corner Mount
GOOD
BEST
BEST
Fixture Mount
GOOD
BETTER
Stairwell
Environmental Operating
Temperature/Humidity
Up to 5 sensors can be used per Switchpack
GOOD
BEST
Refrigerated Storage
BETTER
OAWC-DT-120W- Photocell
R
BAS/HVAC Relay
BEST
BEST
GOOD
GOOD
BEST
Loading Dock
Office Executive
OAWC-P-009LH-R
BEST
BEST
Computer Room
Conference Room
No Switchpack Required
BEST
BETTER
BEST
OAWC-P-120W-R
Available Colors
Commercial Low Voltage Ceiling Sensors
BEST
Switchpack/Power
Pack
32°F to 104°F (0°C to 40°C) / 20% to 90%, non-condensing
Up to 5 sensors can be used per Switchpack
Classroom
BEST
Not Included
Voltage
Required
W
BEST
BEST
Included
Included
W, V, LA
Commercial Wall Switch Sensors
BEST
Not Included
NEMA WD 7
Standard Tested
Pattern
Mounting Height (ft.)
Time Delay
10 to 30 VDC
Not Required
OAC-DT1000-R
Coverage (sq. ft.)
Adjustment
120 to 277V
-40°F to 125°F (-40°C to 52°C) /
less than 95%, non-condensing
W, V, LA, G, & B
SP 3-Way*,
No Neutral Required
up to 40’
Self-Adjust or Manual
120 to 347V
32°F - 104°F (0°C - 40°C) / 20 to 90%, non-condensing
W, V, LA, G, B
8 to 12’
Self-Adjust
15 sec to 30 min
24 VAC
Cafeteria High Ceiling
Vending Room
500
180°
10-30 VDC
GOOD
Restroom Residential
2MHO
0 sec to 30 min
Cafeteria
Restroom Non-Partitioned
1500
Self-Adjust
15 sec to 30 min
Included
180°
Self-Adjust or Manual
Applications
Residential Room
Passive Infrared
Fixture
8 to 12’
Manual
Environmental Operating
Temperature/Humidity
Closet/Utility
Passive Infrared
Yes
BAS/HVAC Relay
Feature
500
180°
4’
Voltage
Available Colors
Dual Technology
Ceiling
720
Time Delay
Switchpack/Power
Pack
Photocell
Ultrasonic
Wall Switch
NEMA WD 7
Standard Tested
Pattern
Mounting Height (ft.)
Adjustment
Passive Infrared
GOOD
Stairwell
BEST
Vending Room
GOOD
Warehouse Aisle
Warehouse Open
Occupancy Sensor Application Guide
Commercial Wall Switch Sensors
Commercial Line
Voltage
Fixture Mount
Commercial Line Voltage Ceiling Sensor
Commercial Low Voltage
Wall/Corner Mount
OAWC-DT-120W
OAWC-P-009L-H
OAWC-P-120W
OEF-P-2MH0-MV-S
OAC-P-1500-DMV
OAC-P-1500-MV
OAC-P-0500-DMV
OAC-P-0500-MV
OXC-P-2MH0-R
OXC-P-1500-R
OAC-DT-2000
OAC-DT-1000
OAC-DT-0501
OAC-U-2000
OAC-U-1000
OAC-U-0501
OAC-P-1500
OAC-P-0500
VNLW-P-1001-MV-N-*
ONW-P-1001-RR7-*
ONW-P-1001-SP-*
ONW-P-1001-D347-*
ONW-P-1001-347-*
ONW-P-1001-DMV-*
ONW-P-1001-MV-*
ONW-D-1001-RR7-*
ONW-D-1001-SP-*
ONW-D-1001-DMV-N*
ONW-D-1001-MV-N-*
ONW-D-1001-MV-*
ONW-D-1001-DMV-*
Specification Grade
OSW-U-0721-MV-*
OSW-P-0451-DMV-*
OSW-P-0451-MV-*
OSW-P-1001-MV-*
Commercial Grade
Commercial Low Voltage Ceiling Sensors
Specifications
Specifications
Passive Infrared
Technology
Ultrasonic
Dual Technology
Mounting
Coverage (sq. ft.)
1000
450
1000
1500
Manual
Self-Adjust
360°
500
1000
2000
500
1000
2000
120 or 277V
120 or 277V
120 or 277V
Not Required
15 sec to 2 hr
10-30 VDC
24 VAC
Required
RR7 Relay
Required
Not Included
120 or 277V
347V
360°
1500
2MHO
360°
up to 25’
Dual Technology Technology
Wall/Corner Mount
Mounting
1200
90 Linear
1200
120°
180°
8 to 12’
120°
120 to 277V
10 to 30 VDC
Required
RR7 Relay
Required
Not Required
Required
Not Required
Included
Not Included
Included
Not Included
Included
Not Included
SP, True
3-Way,
No Neutral
Required
W, V, A
SP, 3-Way*,
No Neutral Required
Dual Relay,
3-Way*, No
Neutral
Required
OAC-P0500-R
OAC-P-1500-R
OAC-U0501-R
OAC-U1000-R
OAC-U2000-R
OAC-DT0501-R
OAC-DT2000-R
SP, 3-Way*,
Light Icon No
Neutral
Dual Relay,
3-Way*, Light
Icon, Fan
Mode, No
Neutral
Required
SP, 3-Way*,
Light Icon,
EcoMeter
Dual Relay,
3-Way*, Light
Icon, Fan
Mode, EcoMeter
SP, Light Icon, EcoMeter
SP, 3-Way*,
No Neutral
Required,
Light Icon,
EcoMeter
Dual Relay,
3-Way*, No
SP, 3-Way*, No
Neutral Neutral, Light
Required, Light
Icon, EcoMeter
Icon, EcoMeter
Dual Relay,
3-Way*, No
Neutral Required,
Light Icon, EcoMeter
SP, Light Icon, EcoMeter
SP, 3-Way*,
Light Icon,
EcoMeter
Night Light
GOOD
BETTER
BEST
BEST
BEST
BEST
BETTER
BETTER
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
Copy/File/Storage
Room
BEST
BEST
BEST
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
Commercial Line Voltage Ceiling Sensors
BEST
GOOD
BEST
BEST
BETTER
BETTER
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
GOOD
GOOD
Hallway
GOOD
GOOD
BETTER
BEST
BEST
BEST
BEST
Office Home
Office Private
Open Office
w/Cubicles
Parking Garage
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
GOOD
GOOD
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER
BETTER
GOOD
GOOD
GOOD
BEST
BEST
BEST
Restroom Partitioned
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BETTER
BETTER
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BETTER
BEST
BETTER
BEST
BETTER
BEST
GOOD
BEST
BEST
BEST
BEST
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
Cafeteria
Classroom
BETTER
BEST
Computer Room
GOOD
BETTER
BEST
Conference Room
BEST
BEST
GOOD
BETTER
Copy/File/Storage
Room
BETTER
Hallway
BEST
Loading Dock
BETTER
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
BEST
GOOD
GOOD
BETTER
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BEST
Office Executive
BEST
BEST
Office Home
Office Private
Open Office
w/Cubicles
Parking Garage
BEST
BEST
Refrigerated Storage
BEST
GOOD
Applications
Cafeteria High Ceiling
GOOD
GOOD
Feature
Closet/Utility
BEST
Residential Room
GOOD
BETTER
BEST
BEST
BEST
BEST
GOOD
BEST
GOOD
Restroom Non-Partitioned
BEST
Restroom Partitioned
BEST
Restroom Residential
GOOD
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
GOOD
BEST
BEST
Warehouse Aisles
BETTER
BETTER
Warehouse Open
BETTER
BETTER
3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out.
SP: Single Pole
Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black
Other specialty sensors available at www.coopercontrols.com
Commercial Low Voltage Wall/Corner Mount
GOOD
BEST
BEST
Fixture Mount
GOOD
BETTER
Stairwell
Environmental Operating
Temperature/Humidity
Up to 5 sensors can be used per Switchpack
GOOD
BEST
Refrigerated Storage
BETTER
OAWC-DT-120W- Photocell
R
BAS/HVAC Relay
BEST
BEST
GOOD
GOOD
BEST
Loading Dock
Office Executive
OAWC-P-009LH-R
BEST
BEST
Computer Room
Conference Room
No Switchpack Required
BEST
BETTER
BEST
OAWC-P-120W-R
Available Colors
Commercial Low Voltage Ceiling Sensors
BEST
Switchpack/Power
Pack
32°F to 104°F (0°C to 40°C) / 20% to 90%, non-condensing
Up to 5 sensors can be used per Switchpack
Classroom
BEST
Not Included
Voltage
Required
W
BEST
BEST
Included
Included
W, V, LA
Commercial Wall Switch Sensors
BEST
Not Included
NEMA WD 7
Standard Tested
Pattern
Mounting Height (ft.)
Time Delay
10 to 30 VDC
Not Required
OAC-DT1000-R
Coverage (sq. ft.)
Adjustment
120 to 277V
-40°F to 125°F (-40°C to 52°C) /
less than 95%, non-condensing
W, V, LA, G, & B
SP 3-Way*,
No Neutral Required
up to 40’
Self-Adjust or Manual
120 to 347V
32°F - 104°F (0°C - 40°C) / 20 to 90%, non-condensing
W, V, LA, G, B
8 to 12’
Self-Adjust
15 sec to 30 min
24 VAC
Cafeteria High Ceiling
Vending Room
500
180°
10-30 VDC
GOOD
Restroom Residential
2MHO
0 sec to 30 min
Cafeteria
Restroom Non-Partitioned
1500
Self-Adjust
15 sec to 30 min
Included
180°
Self-Adjust or Manual
Applications
Residential Room
Passive Infrared
Fixture
8 to 12’
Manual
Environmental Operating
Temperature/Humidity
Closet/Utility
Passive Infrared
Yes
BAS/HVAC Relay
Feature
500
180°
4’
Voltage
Available Colors
Dual Technology
Ceiling
720
Time Delay
Switchpack/Power
Pack
Photocell
Ultrasonic
Wall Switch
NEMA WD 7
Standard Tested
Pattern
Mounting Height (ft.)
Adjustment
Passive Infrared
GOOD
Stairwell
BEST
Vending Room
GOOD
Warehouse Aisle
Warehouse Open
Occupancy Sensor Application Guide
Commercial Wall Switch Sensors
Commercial Line
Voltage
Fixture Mount
Commercial Line Voltage Ceiling Sensor
Commercial Low Voltage
Wall/Corner Mount
OAWC-DT-120W
OAWC-P-009L-H
OAWC-P-120W
OEF-P-2MH0-MV-S
OAC-P-1500-DMV
OAC-P-1500-MV
OAC-P-0500-DMV
OAC-P-0500-MV
OXC-P-2MH0-R
OXC-P-1500-R
OAC-DT-2000
OAC-DT-1000
OAC-DT-0501
OAC-U-2000
OAC-U-1000
OAC-U-0501
OAC-P-1500
OAC-P-0500
VNLW-P-1001-MV-N-*
ONW-P-1001-RR7-*
ONW-P-1001-SP-*
ONW-P-1001-D347-*
ONW-P-1001-347-*
ONW-P-1001-DMV-*
ONW-P-1001-MV-*
ONW-D-1001-RR7-*
ONW-D-1001-SP-*
ONW-D-1001-DMV-N*
ONW-D-1001-MV-N-*
ONW-D-1001-MV-*
ONW-D-1001-DMV-*
Specification Grade
OSW-U-0721-MV-*
OSW-P-0451-DMV-*
OSW-P-0451-MV-*
OSW-P-1001-MV-*
Commercial Grade
Commercial Low Voltage Ceiling Sensors
Specifications
Specifications
Passive Infrared
Technology
Ultrasonic
Dual Technology
Mounting
Coverage (sq. ft.)
1000
450
1000
1500
Manual
Self-Adjust
360°
500
1000
2000
500
1000
2000
120 or 277V
120 or 277V
120 or 277V
Not Required
15 sec to 2 hr
10-30 VDC
24 VAC
Required
RR7 Relay
Required
Not Included
120 or 277V
347V
360°
1500
2MHO
360°
up to 25’
Dual Technology Technology
Wall/Corner Mount
Mounting
1200
90 Linear
1200
120°
180°
8 to 12’
120°
120 to 277V
10 to 30 VDC
Required
RR7 Relay
Required
Not Required
Required
Not Required
Included
Not Included
Included
Not Included
Included
Not Included
SP, True
3-Way,
No Neutral
Required
W, V, A
SP, 3-Way*,
No Neutral Required
Dual Relay,
3-Way*, No
Neutral
Required
OAC-P0500-R
OAC-P-1500-R
OAC-U0501-R
OAC-U1000-R
OAC-U2000-R
OAC-DT0501-R
OAC-DT2000-R
SP, 3-Way*,
Light Icon No
Neutral
Dual Relay,
3-Way*, Light
Icon, Fan
Mode, No
Neutral
Required
SP, 3-Way*,
Light Icon,
EcoMeter
Dual Relay,
3-Way*, Light
Icon, Fan
Mode, EcoMeter
SP, Light Icon, EcoMeter
SP, 3-Way*,
No Neutral
Required,
Light Icon,
EcoMeter
Dual Relay,
3-Way*, No
SP, 3-Way*, No
Neutral Neutral, Light
Required, Light
Icon, EcoMeter
Icon, EcoMeter
Dual Relay,
3-Way*, No
Neutral Required,
Light Icon, EcoMeter
SP, Light Icon, EcoMeter
SP, 3-Way*,
Light Icon,
EcoMeter
Night Light
GOOD
BETTER
BEST
BEST
BEST
BEST
BETTER
BETTER
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
Copy/File/Storage
Room
BEST
BEST
BEST
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
Commercial Line Voltage Ceiling Sensors
BEST
GOOD
BEST
BEST
BETTER
BETTER
BETTER
BETTER
BETTER
BETTER
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
GOOD
GOOD
Hallway
GOOD
GOOD
BETTER
BEST
BEST
BEST
BEST
Office Home
Office Private
Open Office
w/Cubicles
Parking Garage
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
BEST
GOOD
GOOD
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
BETTER
BETTER
GOOD
GOOD
GOOD
BEST
BEST
BEST
Restroom Partitioned
BETTER
BEST
BEST
BEST
BEST
BEST
BEST
BETTER
BETTER
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BETTER
BEST
BETTER
BEST
BETTER
BEST
GOOD
BEST
BEST
BEST
BEST
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
GOOD
Cafeteria
Classroom
BETTER
BEST
Computer Room
GOOD
BETTER
BEST
Conference Room
BEST
BEST
GOOD
BETTER
Copy/File/Storage
Room
BETTER
Hallway
BEST
Loading Dock
BETTER
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
BEST
GOOD
GOOD
BETTER
BETTER
BETTER
BEST
BEST
BEST
GOOD
GOOD
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
BEST
BEST
BEST
Office Executive
BEST
BEST
Office Home
Office Private
Open Office
w/Cubicles
Parking Garage
BEST
BEST
Refrigerated Storage
BEST
GOOD
Applications
Cafeteria High Ceiling
GOOD
GOOD
Feature
Closet/Utility
BEST
Residential Room
GOOD
BETTER
BEST
BEST
BEST
BEST
GOOD
BEST
GOOD
Restroom Non-Partitioned
BEST
Restroom Partitioned
BEST
Restroom Residential
GOOD
GOOD
GOOD
GOOD
BEST
BEST
BEST
BEST
GOOD
BEST
BEST
Warehouse Aisles
BETTER
BETTER
Warehouse Open
BETTER
BETTER
3-Way*: Lights will turn OFF automatically when sensor that detected motion last times out.
SP: Single Pole
Colors: W-White; V-Ivory; LA-Light Almond; A-Almond; G-Gray; B-Black
Other specialty sensors available at www.coopercontrols.com
Commercial Low Voltage Wall/Corner Mount
GOOD
BEST
BEST
Fixture Mount
GOOD
BETTER
Stairwell
Environmental Operating
Temperature/Humidity
Up to 5 sensors can be used per Switchpack
GOOD
BEST
Refrigerated Storage
BETTER
OAWC-DT-120W- Photocell
R
BAS/HVAC Relay
BEST
BEST
GOOD
GOOD
BEST
Loading Dock
Office Executive
OAWC-P-009LH-R
BEST
BEST
Computer Room
Conference Room
No Switchpack Required
BEST
BETTER
BEST
OAWC-P-120W-R
Available Colors
Commercial Low Voltage Ceiling Sensors
BEST
Switchpack/Power
Pack
32°F to 104°F (0°C to 40°C) / 20% to 90%, non-condensing
Up to 5 sensors can be used per Switchpack
Classroom
BEST
Not Included
Voltage
Required
W
BEST
BEST
Included
Included
W, V, LA
Commercial Wall Switch Sensors
BEST
Not Included
NEMA WD 7
Standard Tested
Pattern
Mounting Height (ft.)
Time Delay
10 to 30 VDC
Not Required
OAC-DT1000-R
Coverage (sq. ft.)
Adjustment
120 to 277V
-40°F to 125°F (-40°C to 52°C) /
less than 95%, non-condensing
W, V, LA, G, & B
SP 3-Way*,
No Neutral Required
up to 40’
Self-Adjust or Manual
120 to 347V
32°F - 104°F (0°C - 40°C) / 20 to 90%, non-condensing
W, V, LA, G, B
8 to 12’
Self-Adjust
15 sec to 30 min
24 VAC
Cafeteria High Ceiling
Vending Room
500
180°
10-30 VDC
GOOD
Restroom Residential
2MHO
0 sec to 30 min
Cafeteria
Restroom Non-Partitioned
1500
Self-Adjust
15 sec to 30 min
Included
180°
Self-Adjust or Manual
Applications
Residential Room
Passive Infrared
Fixture
8 to 12’
Manual
Environmental Operating
Temperature/Humidity
Closet/Utility
Passive Infrared
Yes
BAS/HVAC Relay
Feature
500
180°
4’
Voltage
Available Colors
Dual Technology
Ceiling
720
Time Delay
Switchpack/Power
Pack
Photocell
Ultrasonic
Wall Switch
NEMA WD 7
Standard Tested
Pattern
Mounting Height (ft.)
Adjustment
Passive Infrared
GOOD
Stairwell
BEST
Vending Room
GOOD
Warehouse Aisle
Warehouse Open
Sensor Technologies
Passive Infrared (PIR) Technology
•
•
Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF.
PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.
Using this paper versus standard paper
produced the following environmental benefits.
Based on Environmental Defense Fund Paper Calculator
Ultrasonic (US) Technology
•
•
•
Ultrasonic sensors use the Doppler principle. These sensors produce low intensity, inaudible sound and detect changes in sound waves caused by motion.
They are volumetric in nature and therefore not line-of-sight dependant.
They are much more sensitive to smaller motions.
Dual Technology
•
•
•
Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today.
This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use.
Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.
Number of Trees Saved
12
Total Energy Saved—Million BTU’s
7.9
Greenhouse Gas Reduction—lbs of CO2
4391
Gallons of Water Saved
4129
Solid Waste Reduction— lbs of Waste
683
Kilo-watt (kwh) Hours Saved
1702
MicroSet Self-Adjusting Technology
•
•
Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time.
By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.
North America Headquarters
203 Cooper Circle
Peachtree City, GA 30269
P: 800-553-3879
F: 800-954-7016
About Energy Codes
www.coopercontrol.com
ControlsSales@cooperindustries.com
Cooper Controls Ltd
Usk House, Lakeside,
Llantarnam Park,
Cwmbran, NP44 3HD. UK
P: +44 (0)1923 495495
F: +44 (0)1923 867880
Canada
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-507-4000
F: 905-568-7049
www.coopercontrol.com
enquiries@coopercontrols.co.uk
Energy costs and consumption continue to rise. Today, many energy codes and energy policies either require or incentivize the use of
energy efficient lighting controls on commercial projects.
ASHRAE 99.1-1999, 2001, 2004, 2007, 2010
In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off.
• Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the
ASHRAE standard.
• In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee
cafeterias and break rooms.
As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum.
LEED Green Building Rating System
Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a
prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009.
• Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.
Version
3.0
California Title 24
Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied:
•
•
•
•
Offices 250 sq. ft. or smaller
Multipurpose rooms of less than 1000 sq. ft.
Classrooms of any size
Conference rooms of any size
Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices.
Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.
IECC
• ASHRAE and Title 24 requirements must be met.
• IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.
Cooper US, Inc.
600 Travis, Suite 5600
Houston, TX 77002
P: 713-209-8400
F: 713-209-8995
www.cooperindustries.com
ACC120033
Cooper Controls, Greengate, Novitas, PCI Lighting Control Systems, VisionTouch,
VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, IntelliRelay, NeoSwitch,
TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the
U.S. and other countries. You are not permitted to use Cooper Trademarks without
the prior written consent of Cooper Industries.
Printed in USA
Greengate Occupancy
Sensor Guide
Sensor Technologies
Passive Infrared (PIR) Technology
•
•
Designed to detect motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switch lights ON and OFF.
PIR sensors are considered line-of-sight sensors, meaning that the sensor must be able to have a direct line-of-light to the person making the motion.
Using this paper versus standard paper
produced the following environmental benefits.
Based on Environmental Defense Fund Paper Calculator
Ultrasonic (US) Technology
•
•
•
Ultrasonic sensors use the Doppler principle. These sensors produce low intensity, inaudible sound and detect changes in sound waves caused by motion.
They are volumetric in nature and therefore not line-of-sight dependant.
They are much more sensitive to smaller motions.
Dual Technology
•
•
•
Dual Technology is the combination of PIR and Ultrasonic into one sensor and is the ultimate sensing solution available today.
This pairing helps to eliminate false activations (both ON and OFF) thus saving additional energy use.
Dual Technology sensors ensure the greatest sensitivity and coverage for tough applications without the threat of false triggers.
Number of Trees Saved
12
Total Energy Saved—Million BTU’s
7.9
Greenhouse Gas Reduction—lbs of CO2
4391
Gallons of Water Saved
4129
Solid Waste Reduction— lbs of Waste
683
Kilo-watt (kwh) Hours Saved
1702
MicroSet Self-Adjusting Technology
•
•
Continuously adjusts to conditions by adjusting sensitivity and Time Delay in real-time.
By adjusting sensitivity and Time Delay automatically, the sensor is maximizing the potential energy savings that are available.
North America Headquarters
203 Cooper Circle
Peachtree City, GA 30269
P: 800-553-3879
F: 800-954-7016
About Energy Codes
www.coopercontrol.com
ControlsSales@cooperindustries.com
Cooper Controls Ltd
Usk House, Lakeside,
Llantarnam Park,
Cwmbran, NP44 3HD. UK
P: +44 (0)1923 495495
F: +44 (0)1923 867880
Canada
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-507-4000
F: 905-568-7049
www.coopercontrol.com
enquiries@coopercontrols.co.uk
Energy costs and consumption continue to rise. Today, many energy codes and energy policies either require or incentivize the use of
energy efficient lighting controls on commercial projects.
ASHRAE 99.1-1999, 2001, 2004, 2007, 2010
In buildings over 5,000 square feet, all general lighting must be able to be automatically turned off.
• Occupancy sensors can be used through out the building, in lieu of programmable timing, to meet the Automatic-Off requirement outlined in the
ASHRAE standard.
• In every building, regardless of size, ASHRAE requires that occupancy sensors be placed in classrooms, conference/meeting rooms, employee
cafeterias and break rooms.
As of December 30, 2010 The Department of Energy (DOE) recognizes the ASHRAE 2004 standard as the new national minimum.
LEED Green Building Rating System
Both of the above ASHRAE requirements must be met by any project hoping to earn LEED certification. Lighting controls can contribute toward meeting a
prerequisite and earning up to 24 percent or 24 of the 100 points available in LEED 2009.
• Use occupancy sensors to earn LEED points by significantly improving the energy performance of the building.
Version
3.0
California Title 24
Automatic shut-off occupancy sensors must be installed in the following areas to turn off the lighting when a space is unoccupied:
•
•
•
•
Offices 250 sq. ft. or smaller
Multipurpose rooms of less than 1000 sq. ft.
Classrooms of any size
Conference rooms of any size
Space Control - Requires individual control devices in spaces enclosed with floor to ceiling height partitions and include individual rooms for partitioned open offices.
Light level reduction control - Requires simple switching strategies to reduce light levels by up to 50%. Bi-level occupancy sensors can also meet the requirements by offering 2 levels of control.
IECC
• ASHRAE and Title 24 requirements must be met.
• IECC 2003 & 2006, Occupants must be able to reduce lighting load in the space in a reasonably uniform pattern by at least 50%. Bi-Level occupancy sensors offering personal control can be used to comply with this mandatory requirement.
Cooper US, Inc.
600 Travis, Suite 5600
Houston, TX 77002
P: 713-209-8400
F: 713-209-8995
www.cooperindustries.com
ACC120033
Cooper Controls, Greengate, Novitas, PCI Lighting Control Systems, VisionTouch,
VisionSwitch, MicroSet, Digita, ControlKeeper, LiteKeeper, IntelliRelay, NeoSwitch,
TracKeeper, Revio, and Ineo are valuable trademarks of Cooper Industries in the
U.S. and other countries. You are not permitted to use Cooper Trademarks without
the prior written consent of Cooper Industries.
Printed in USA
Greengate Occupancy
Sensor Guide
Download