Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 DESIGN AND TESTING OF UHV BUSHINGS 1 1 P. Cardano ,2 A.Pigini, 1G.Testin Areva T&D SpA Italy(Unit RPV), 2Consultant *Email: <paolo.cardano@areva-td.com> Abstract: UHV systems are developing in the world, UHV bushings being one of the fundamental components. Aspects related the design of UHV bushings for AC and DC application are examined in the paper, paying special attention to the external insulation requirements. The required external insulation length as a function of the system voltage is analysed, both under service stress and under overvoltages. The alternative application of porcelain and composite housing is discussed. Examples of the UHV bushings developed and successfully tested are reported. At the light of the experience critical testing aspects are pointed out and the need of implementations/modifications of the Standards are discussed looking specifically to the UHV applications. 1. However the reduction of the strength under rain can be contained adopting suitable profiles and composite housings [5], [6]. For the considerations in the following reference is made to the conditions recommended by the Standard (H=0, that means no turret). INTRODUCTION UHV applications imply extreme challenges for bushings from the design testing and manufacturing point of view [1], [2], some of them being examined in the following, indicating, among others, the need of implementation/modification of the recent Standard [3]. 10 9 2. DESIGN ASPECTS 8 7 Evaluation of the required arching distances L (m) 2.1. Switching impulse (SI) requirements. The size of the actual bushings may vary depending on the choices made about field control, housing characteristics, standardisation of the housings. A certain benefit on the strength can derive from the capacitive field control. However the testing experience indicate that the influence of the active parts on the SI performance in dry conditions is limited. Thus a preliminary conservative evaluation of the strength in dry condition can be made considering the configuration as a rod structure one. The required arching distance versus the required rated switching impulse withstand level VSI,, evaluated according to [4] with reference to a rod structure configuration, is given in Fig. 1, for different heights H of the lower structure having a base width of 1.5 m. The longest arching distance L is required when the base is at ground plane, situation which is practically required to be simulated in the standard test [3], which prescribes that the bushing shall be mounted on an earthed plane, radially extended from the axis of the bushing at least 0,4 L in every direction. The arching distance dimensioned according to this criterion is thus conservative with respect to actual configurations (e.g., with the bushing mounted on turrets) and may in particular penalise some UHV applications. The required withstand can be reached in dry conditions even with shorter values of L by adopting suitable shielding electrodes, whose efficiency is however lost under rain conditions and other environmental perturbed conditions (e.g. ice and snow). As a matter of fact higher clearances than those in Fig. 1 can be required under rain. 6 5 4 H=0 H=1,5 H=3 3 2 1 0 500 1000 1500 2000 USI (kV) Fig. 1 - SI, dry condition. Simplified simulation of the bushing by a rod structure configuration. Required arching distance as a function of the rated switching impulse withstand value, for different heights of the lower structure. Lightning impulse (LI) requirements Also with LI the strength depends on the configuration, even if at a less extent than for SI [4]. For the evaluation in the following reference is made to a withstand value (10% flashover probability) of 500 kV/m Pollution (P) requirements are reported in Table 1. The specific creepage distances necessary for AC are taken from [7]. Pending the new Standard provisional values for DC are derived from [8], [9] on the basis of test experience. The values appear much larger than those required in AC and may be subjected to optimization taking into account field experience. To this purpose a questionnaire has been circulated to collect field experience in terms of adopted creepage distances, contamination level on the insulators in the field and actual field performance. Pg. 1 Paper E-51 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 standardised for higher system voltages in the UHV range [11]. By chance, it is pointed out that one of the more stringent standardisation need is the extension of the standardisation of the voltage levels to UHV, possibly to UHVDC also, to avoid the proliferation of too many levels. Table 1 Required specific creepage distances (phase to ground) AC DC mm/kV mm/kV 22 22 Light (L) 27,8 35 Medium (M) 34,7 55 Heavy (H) 43,3 75 Very heavy (VH) 53,7 95 Very light (VL) AC: data from [7] DC: data derived from [8], [9] Fig. 2- Creepage distance. Correction factor as a function of average insulator diameter for porcelain insulators AC [7]. Dotted line: expected test performance. Continuous line: expected service performance taking into account the influence of diameter on contamination. As far as composite insulators are concerned the Standard [10], basically says that for AC the same reference values can be assumed as for ceramic insulators, even if other values can be taken under the responsibility of the users. As a matter of fact in many parts of the world there is the tendency to adopt lower creepage distances for composites than for ceramics, taking into account their better performance. This is one of the matters deserving further investigation especially in view of UHV applications. For the evaluation in the following, taking also into account the results in [6], it is assumed that the specific creepage necessary for composites is 0.8 that for porcelain insulators. The above creepage distances refer to insulators of small diameter. For insulators of large diameter the correction in Fig. 2 is prescribed by the Standards for ceramic insulators under AC voltage [7], while for composite insulators under AC voltage the trend is not clearly specified [10], saying that the influence can be negligible for hydrophobic conditions and the same as for ceramic for hydrophilic conditions (Fig. 3). As a matter of fact recent tests have shown that the influence of the diameter remains low even for insulators which have lost part of their hydrorepellency [6]. Also additional investigations on this aspect would be very important for UHV applications. In the following, based on the results in [6] a negligible influence of the diameter on the required creepage distance is assumed for composites both in AC and DC systems. Fig. 3 - Creepage distance. Correction factor as a function of average insulator diameter for composite insulators AC [10]. It is evident that SI predominates with respect to LI in the upper range of EHV and in the UHV range. The insulation levels are not specified for DC bushings [12], however taking into account the values assumed in the design practice, the same conclusion can be extended to DC bushings also. A comparison of the requirement dictated by SI and pollution is made in Fig 5, 6 and 7. The pollution requirements are evaluated considering typical bushing diameters and a creepage factor of 4. Furthermore it is assumed that for DC the required creepage distance for composite is, as for AC, 80% of that required for ceramic insulators. 2.2. As shown in Fig. 4 SI generally predominates in design for AC, even considering the heavy pollution requirements for insulators of large diameter. Predominant design stresses A comparison of the requirements dictated by LI and SI for AC systems is reported in Fig. 4, where the required arching distances are evaluated according to the criteria in the previous paragraph and on the basis of the insulation levels specified in [3] for rated voltages up to 800 kV and those going to be The predominance of SI would be even greater in case composite housings should be adopted, with a better pollution performance than porcelain (with a creepage distance of about 80% of that of Table 1 and considering a negligible influence of the diameter). Pg. 2 Paper E-51 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 12 An other important aspect to be pointed out is that the determination of the site severity is much more important in DC than in AC. LI min 10 Limax SI min L (m) 8 25 SI P VL PL PM PH P VH SI max 20 6 L (m) 4 2 15 10 0 5 0 500 1000 1500 Um(kV) 0 0 Fig. 4 - AC bushings. Estimate of the required arching distances as a function of the system voltage to withstand LI and SI (minimum and maximum insulation levels in [3], [11]) 200 400 600 800 1000 U (kV) Fig. 6 – DC bushings. Estimate of the required arching distance as a function of system voltage to withstand SI and service voltage under pollution. Porcelain insulators with Creepage Factor=4. 14 SI min 12 SI max 10 P VL 16 8 14 PM 6 PH 12 P VH 10 L (m) L (m) PL 4 2 SI P VL PL PM PH P VH 8 6 0 4 0 500 1000 1500 2 Um (kV) 0 Fig. 5 – AC bushings. Estimate of the required arching distance as a function of system voltage to withstand SI and service voltage under pollution. Porcelain insulators with Creepage Factor=4. 0 200 400 600 800 1000 U (kV) Fig.7 DC bushings. Estimate of the required arching distance as a function of system voltage to withstand SI and service voltage under pollution. Porcelain insulators with Creepage Factor=4. The same evaluations are made in Fig. 6 for DC, assuming SI overvoltages of 2.1 p.u, being SI levels not standardised [12]. It appears that for DC pollution is always the dominating design stress. It is evident that taking into account existing constraints in length (of about 10 m based on manufacturing and transportation limits), only light to medium contamination bushing may be to day produced for UHVDC. By adopting composite housing, requiring less specific creepage distance and with a limited influence of the housing diameter on the creepage distance, more reasonable arching distances are required, making possible to realize UHV bushings even for medium to heavy pollution conditions, as shown in Fig.7. The above considerations point out as the development of the composite solution is essential toward UHVDC development and confirm the need to further investigate, agree and standardise the performance of composite solutions. Simplified pollution design approaches which make reference to basic categories on the basis of the site location as in AC, are not recommended in DC, at least for the final design. Test campaigns with energised insulators are strongly recommended before making detailed design of insulators. The investigation could prove that most of the sites are characterized by pollution level lower than the so called medium one and that in very few extreme cases the pollution severity ranges to heavy and very heavy conditions. 2.3. Influence of altitude on the insulation requirements An other aspect which has to be considered for UHV is the influence of the atmospheric conditions and Pg. 3 Paper E-51 ISBN 978-0-620-44584-9 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° simulation of a bushing mounted on a transformer mock up or a GIS mock up). particularly the influence of altitude on the sea level. To take into account the influence of altitude (air density) the Standard [3] assumes conservative values for the coefficient m, and namely 1 for LI and 0,75 for SI, for all the voltages levels (arching distance values) and prescribes that for installations at an altitude higher than 1000 m, the arcing distance under the standard reference atmospheric conditions shall be designed to withstand the voltages obtained by multiplying the withstand voltages required at the service location by a factor k in accordance in accordance with [3]. A comparison of the coefficient K from [3] and that which should be more correctly applied on the basis of [7] for a SI voltage of 1050 and 1800 kV respectively, is reported in Fig. 8. It appears that the Standards penalize to much the design especially for UHV bushings. Let now we make an example with reference to a bushing for 1100 kV to be designed according to the following insulation levels: LI: 2400 kV, SI: 1800 kV. A bushing with about 9 m arching distance is adequate for application at sea level (see Fig. 1). If we have to design a bushing for 3000 m, according to [3], we should design the bushing for the following voltage values: LI=2400*1,27=3048 kV, SI=1800*1,2=2160 kV. In spite of the large increase LI does not dominate the design (just about a 6m arching distance is sufficient to comply with the new LI requirements). Things are different eith SI: the corresponding bushing length should be about 12,5 m as dictated by SI. On the contrary a correct design made according to [13] and taking into account the predominance of SI on design would imply the following voltage values: SI=1800*1,03=1850 kV. The corresponding required arching distance would be, according to Fig. 1, about 9,5 m. This aspect of the Standard is extremely penalizing and should be possibly modified soon, not only from the point of view of UHV. Particularly critical are also wet test that may need to be made closer to the wet apparatus ( risk of discharge) and for which the uniformity of the rain distribution along the typical UHV arching distances is difficult to be reached. A solution to limit the influence of the laboratory walls is to make the tests outside, however the criticality of the rain test remains. 1,5 K[3] K[13] 1050 kV k[13] 1800 kV K (p.u.) 1,4 1,3 1,2 1,1 1 1000 2000 3000 altitude (m a.s.l.) 4000 Fig. 8 - Coefficient K for SI levels of 1050 and 1800 kV as a function of the altitude above sea level (as derived from [13]. Comparison with values from [3]. As far as DC is concerned, since Dc pollution is the design stress , the altitude correction for DC needs to be carefully assessed. 3. 3.1. TESTING Testing of the external insulation As far as the external insulation is concerned, one of the most critical tests to perform according to the Standards for UHV bushing is the SI one. The data in Fig. 9 [14] indicate that to make the influence of laboratory size negligible at least a free space of 1.5 times the arching distance is necessary. This means that laboratories with a size of at least 30*30*30 m are necessary to perform correct tests in dry condition. Tests in smaller laboratories can lead to too conservative results and design: this is a critical aspect considering the already very large arching distances necessary. The matter is even more complicate if the simulation of actual service conditions is required (e.g. Fig. 9 - Influence of the laboratory size on the flashover voltage [14] One of the other challenges is the correct testing of the lower part of the bushing. One particular aspect which is to be considered in design and testing is the interaction of the apparatus to which the bushing is to be applied with the bushing design. The vessel should be large enough such that the lower part of the bushing is tested correctly, avoiding non representative Pg. 4 Paper E-51 5000 Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° ISBN 978-0-620-44584-9 discharges to the vessel walls and partial discharges which could make difficult the measurement of the PD on the bushing, as required by Standards. For AC the design of the testing vessel has to take into account that the specific strength of transformer oil greatly decreases by increasing the spacing, as shown by typical data in Fig. 10, taken from [15]. Furthermore the performance of the lower part of the bushing under test depends very much on the quality of the transformer oil since the specific oil strength and the ratio between the strength of the oil under LI and AC depends very much on the quality of the oil: highly degasified and filtered oil is essential for a successful testing. The matters are even more complicated in DC. In this case DC stresses, overvoltage stresses and transients during voltage polarity reversal dominate the design such that the design of the bushing side immersed in oil can not be made without considering the actual application. The design of shielding electrodes and barriers in the converter transformer to assure the correct field distribution in DC and during transient is a challenge especially for UHV. Fig. 11 and 12 report the 1100 kV bushing under test at Areva T&D Italy Spa premises and in China. The bushing, have the following main characteristics: Um PFWV LI CW SI In 1100 kV 1200 kV 2400 kV 2760 kV 1950 kV 2500 A Fig.11 - 1100 kV bushing under test at Areva T&d Italy Spa premises The bushing has satisfactorily passed the tests prescribed and now several bushing of this type are in service in China. 7 UF (KV/mm) 6 5 AC rms LI 4 3 2 1 0 0 100 200 300 spacing (mm) Fig. 10 - Typical strength trends of transformer oil as a function of the spacing [15] Fig. 12 - 1100 kV bushing under test In China Pg. 5 Paper E-51 ISBN 978-0-620-44584-9 4. Proceedings of the 16th International Symposium on High Voltage Engineering c 2009 SAIEE, Innes House, Johannesburg Copyright ° for DC and the need to reproduce the actual installation condition in DC. CONCLUSION o Present standards prescribe the testing voltages only for AC up to Um 800 kV. There is urgent need to standardise the voltage ratings for UHV AC and DC also. o SI testing with the simulation of an earth plane at the base of the bushing may be too severe especially for UHV, leading to unnecessary overdesign. o The size of the testing laboratory should be large enough to avoid too much influence of the laboratory walls and ceiling on the strength. Minimum laboratory sizes for UHV testing should be 30*30*30, but larger laboratories can be useful to make tests on more complex and representative configurations. o SI rain tests remain any way critical due to the difficulty of having suitable rain apparatus to create uniform rain conditions at large distances and on long insulator sets. Alternative procedures may need to be found. o The correction for altitude in the present bushing Standards is too conservative and is to be corrected, at least for UHV, since leads to unnecessary and costly overdesign. o SI dominates the design for UHV AC, while pollution dominates the design for UHVDC. The feasibility of UHVDC bushing for severe contamination conditions may be facilitated by the adoption of composite housings. Additional investigations may be needed to give more ground to the knowledge of the performance of composite housings. o Due to the criticality of the pollution in DC a proper assessment of the site pollution is recommended. Specific investigations could prove that probably most of the sites are characterized by a pollution level not higher than medium. o Even the design and testing of the lower part of the bushing may deserve particular attention for UHV. Design should be made in tight cooperation between the bushing manufacturer and the apparatus manufacturer. The need of cooperation is essential for UHVDC for which the design of the bushing is very much related to that of the converter transformer, with the consequent pressboard barrier system. o As far as testing is concerned the test vessel need to be designed taking into account the rather poor performance of oil on large gaps 5. REFERENCES [1] P. Cardano , A. Pigini , R. Berti , M. de Nigris , E. Moal , G Rocchetti.”Application of composite housing to high voltage bushings” CIGRE 2008 paper A3 307 [2] A. Pigini “ External insulation for UHV: design requirements and research needs” IEC CIGRE UHV Symposium Bejing 2007 [3] IEC 60137 Ed. 6.0 “Insulated bushings for alternating voltages above 1 000 V” 2008 [4] WG 33.07 “ Guidelines for the evaluation of the dielectric strength of external insulation” Cigre brochure 72 -1992 [5] CIGRE TF 33.03.03 “Switching Impulse performance of post insulators” Electra n 109 1986 [6] P. Cardano, M. de Nigris, A. Pigini, G. Rocchetti “Dielectric performance of composite housings” ISH 2009 [7] IEC 60815-2008: Selection and dimensioning of high-voltage insulators intended for use in polluted conditions - Part 2: Ceramic and glass insulators for a.c. systems [8] A. Pigini, A.C. Britten, C. Engelbrecht “Development of guidelines for the selection of insulators with respect to pollution for EHV- UHV DC: state of the art and research needs” CIGRE 2008 [9] A.Pigini, N. V. Ramkumar “Aspects related to design and testing of uhv insulator strings with cap and pin insulators” CIGRE IEC UHV Symposium New Delhi 2009 [10] IEC 60815-2008: Selection and dimensioning of high-voltage insulators intended for use in polluted conditions - Part 3: Polymer insulators for a.c. systems. [11]E. Zaima, C Neumann “Insulation Coordination for UHV AC Systems based on Surge Arrester Application (CIGREC4.306)” Cigre IEC workshop on UHV New Delhi 2009 [12]IEC 62199 “Bushings for DC application “ 2005 [13] IEC 60 IEC 60060-1 Ed. 3.0: High-voltage test techniques Part 1: General definitions and test requirements [14]Cigre TF 33.03.03 “Evaluation of the SI strength of external insulation” Electra N94 May 1984 [15]F. Clark “Insulating Materials for Design and Engineering Practice” Book Wiley, New York, 1962 Pg. 6 Paper E-51