DALI Dimming Module Technical Data Overview

Technical Data
Effective August 22, 2014
DALI Dimming Module
Catalog#
Prepared by
Project
Date
Comments
Type
Overview
Fifth Light’s DALI Dimming Module provides continuous dimming
control for incandescent and magnetic low voltage loads.
Features
Integrated DALI communication interface (can be run in the same
conduit as power lines)
Forward phase dimming control for incandescent and magnetic
low voltage loads
Ideal for use in applications requiring finely tuned continuous
dimming control
Automatic loss of DALI power detection circuit defaults to a
programmable state
Form factor allows for simple connection to 4” square
junction box
Technical Data 
DALI Dimming Module


August 2014
Specifications
Catalog #
LCP
Input Voltage
Maximum Load
Minimum Load
120 VAC +/- 10%
20 Amps
Input Frequency
50/60 Hz
Operating
Environment
Dimensions
32°F to 104°F (0°C to 40°C)
For indoor use only
Wiring &
Mounting
Power Wiring: Line in, Neutral, Dimmed Line Out,
Ground 12 AWG stranded TFN
Dimensions
(Inches/mm)
Top VIEW
TOP VIEW
0.125 Amps
SIDE VIEW
4.19/
106.43
8.25"H x 4.19"W x 2.19"D
(209.55mm x 106.43mm x 55.36mm)
5.13/
130.17
DALI: 18 AWG stranded PTFE plenum rated nonpolarized pair
8.2
209
3.13/
79.38
Grounding: Ground wire must be connected to earth
ground TOP VIEW
Control
Specification
Standards
Mounting: Mounts to 4" square junction box. Position
the heat sink fins vertically. Ensure that there is
sufficient area around the heat sink to allow for
convection cooling.
Communication Interface: Digital Addressable Lighting
Interface (DALI)
DALI Current Draw: 2mA
Analog Dimming: Forward phase line voltage dimming
SIDE VIEW
4.19/
106.43
2.19/
55.56
8.25/
209.55
CSA C22.2 No. 184-M1988 (R2009) - Solid State
5.13/
3.13/
Lighting Controls
130.17
79.38
ANSI/UL Std No. 244A - Solid State Controls for
Appliances
Side view
The DALI Dimming Module is equipped with a bracket for mounting
to a 4” junction box. Wires are passed from the underside of the
module and through the bracket.
Wiring Diagram
DALI
DALIDimming
DALIDimming
Module
Module
(Dual
Channel)
DALI
Line In
Neutral
Ground
Line Out
(Dimmed)
Lighting Load
NNote: Install in accordance with all applicable national and local electrical &
building codes.
NNote: Specifications subject to change without notice.
2
www.coopercontrol.com
Line I
Neutr
Grou
Li
Li
Technical Data 
DALI Dimming Module


August 2014
Sample System Topology
DALI COMMUNICATION BUS
Maximum of up to 64 devices on each DALI Bus.
All devices must be within 900 feet of the
Lighting Control Panel (LCP).
16/2 AWG recommended wire.
Scene 1
Scene 2
Scene 3
Scene 4
DALI FIELD
RELAY
DALI DIMMABLE
BALLAST
11:46 06/26/09
DALI MULTI
SENSOR
DALI DAC
0-10 VDC
10%
10%
20%
3
30%
4
40%
DALI
Wallstation
1000
FIFTH LIGHT TECHNOLOGY
1
2
DALI DIMMING
MODULE
DALI RELAY PANEL
Units Are: 1027.1028
LIGHTS
LIGHTING
CONTROL PANEL
GROUPS
SCENES
SUPPORT
VOIP PHONE
TOUCH
SCREEN
MOBILE
APP
ETHERNET
NETWORK SWITCH
CENTRAL SERVER UNIT
Ordering
Catalog #
Description
FLT-HPDM-DALI
Single circuit, forward phase, 20 amp
dimming module
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, GA 30269
CooperControl.com
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. ACC140032
August 22, 2014
Eaton is a registered trademark.
All other trademarks are property
of their respective owners.