FTA902, 903, 952,953 Separately Mounted Power Transfer Switch Model Number Selection Guide

advertisement
FTA902, 903, 952,953
Separately Mounted Power Transfer Switch
for Electric Fire Pump Controllers
Model Number Selection Guide
Fire Pump Controllers for
Business-Critical Continuity
SEPARATELY MOUNTED FIRE PUMP POWER TRANSFER SWITCH
FTA902, 903, 952, 953 (Ex..FTA902-AL100B-75HP-E)
FTA ___ -A___ ___ ___ - ___HP-___
Options and Modifications
(See Back)
Transfer Switch Type
902 - Separately Mounted for generator
alternate source. Required disconnecting means and overcurrent protective devices for normal (utility) source
supplied by others.
903 - Separately mounted for generator alternate source. Required disconnecting means and overcurrent protective
devices for normal (utility) source are
supplied and integrally installed by
Firetrol.
952 - Separately mounted for second utility
alternate source. Required disconnecting means and overcurrent protective devices for normal (utility) source
supplied by others.
953 - Separately mounted for second utility
alternate source. Required disconnecting means and overcurrent protective devices for normal (utility) source
are supplied and integrally installed
by Firetrol.
SEE BACK
Fire Pump
Horsepower Rating
03 05 07(7.5) 10 15 20
25 30 40 50 60 75 100
125 150 200 250 300 350
400 450 500 600 700
Three Phase Operating Voltage
A = 220-240V, 60Hz (230V)
AZ = 220-240V, 50Hz
B = 440-480V, 60Hz (460V)
BZ = 415V, 50Hz
C = 550-600V, 60Hz (575V)
F = 380V, 60Hz
FZ = 380V, 50Hz
H = 208V, 60Hz
HH = 200V, 60Hz
Transfer Switch Single Motor
Continuous Current Rating*
100 = 100A
150 = 150A
260 = 260A
400 = 400A
600 = 600A
800 = 800A
1000 = 1000A
*Sized based on motor FLA x 1.15
Type
902
903
952
953
Code
L
M
N
P
Q
R
M
N
P
Q
R
M
N
P
Q
R
Short Circuit Rating
Normal
Alternate
See Table 1
L
M
N
P
Q
R
See Table 1
See Table 1
See Table 1
See Table 1
See Table 1
M
N
P
Q
R
L
L
L
L
L
M
N
P
Q
R
M
N
P
Q
R
Generator Service
L - Standard short circuit rating
100-150A Transfer Switch
22,000A RMS Sym., 200-480V
250-400A Transfer Switch
35,000A RMS Sym., 200-480V
600-800A Transfer Switch
50,000A RMS Sym., 200-480V
100-800A Transfer Switch
10,000A RMS Sym., 550-600V
Utility Service
M - Standard short circuit rating
100,000A RMS Sym., 200-600V
N - Intermediate short circuit rating
150,000A RMS Sym., 200-600V
P - High short circuit rating
200,000A RMS Sym., 200-480V
Q - Standard Intermediate short circuit rating
65,000A RMS Sym., 200-480V
R - Standard Low short circuit rating
42,000A RMS Sym., 550-600V
Table 1
Transfer Switch Rating Amps
UL1008 Withstand and Close-On Ratings @ 480VAC
“Any” Breaker
Specific Breaker
Current-Limiting Max. Fuse Size
Rating **
Rating **
Fuse Rating
Amps Types
100, 150
200,000
**
J, L
22,000
10,000
260, 400
200,000
**
J, L
42,000
35,000
600, 800
200,000
**
J, L
65,000
50,000
** Overcurrent protection must be selected by fuses (or set by circuit breakers) to indefinetely carry
the locked-rotor current of the fire pump motor per NFPA20, NPFA70 and UL218. For more information on transfer switch withstand and close-on ratings, see ASCO publication 1128.
Options and Modifications
Special Enclosures
-T
NEMA Type 3R (IEC IP14), Painted Steel
-E
NEMA Type 4 (IEC IP56), Painted Steel
-F
NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Brushed finish
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel,
Painted Finish
-FD NEMA Type 4X (IEC IP56), #316 Stainless Steel,
Brushed Finished
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam
Welded, #316 Stainless Steel, Polished and
Brushed Finish
-FDP NEMA Type 4X (IEC IP56), #316 Stainless
Steel Painted Finish
-G
NEMA Type 12 (IEC IP52), Painted Steel
Anti-Condensation Space Heaters
-H 120 Volt Space Heater
-J 120 Volt Space Heater with Thermostat
-K 120 Volt Space Heater with Humidistat
-L 240 Volt Space Heater
-M 240 Volt Space Heater with Thermostat
-N 240 Volt Space Heater with Humidistat
Miscellaneous
-EC Extra contacts for remote indication, transfer switch
position
-S Tropicalization
SD902-50
Emerson Network Power.
The global leader in enabling Business-Critical Continuity.
EmersonNetworkPower.com
Racks & Integrated Cabinets
AC Power
Embedded Computing
Outside Plant
Connectivity
Embedded Power
Power Switching & Controls
Services
DC Power
Monitoring
Precision Cooling
Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co.
'iretrol Brand Products … Cary North Carolina 21 6SA … Phone 1 0 200 … 'aY 1 0 20 … www.firetrol.com
Download