4. SCHEDULES OF TECHNICAL INFORMATION Section VI – Requirements Environmental Guidelines for Contractors Page 1 of 677 CONTENTS A 400 kV OPEN TERMINAL SWITCHGEAR B 220 kV OPEN TERMINAL SWITCHGEAR C EARTHING AND LIGHTNING PROTECTION D PROTECTION AND INDICATION SYSTEM E TARIFF METERING SYSTEM F FAULT MONITORING SYSTEM G 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) H SUBSTATION CONTROL SYSTEM I DIESEL GENERATOR J LV SERVICES EQUIPMENT K 400/220kV POWER TRANSFORMERS (AIS-AIS) L 400kV SHUNT REACTOR M 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) N NEUTRAL EARTHING RESISTOR O 400kV OVERHEAD LINE P 220 kV OVERHEAD LINE Section VI – Requirements Environmental Guidelines for Contractors Page 2 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required Offered 1. GENERAL 1.1. Standards IEC IEC 62271-100, 62271102, 62271-1, 62155, 60044-1, 60044-5, 60383, 60815 1.2. Rated voltage kV 420 1.3. System Voltage kV 400 1.4. Rated frequency Hz 50 1.5. Rated lightning impulse withstand voltage (at altitude <1000m) KVp 1425 KVp 1425 kVp 1425 (+240) KVp 1050 KVp 1575 kVp 900 (+345) kV 520 - - 1.6. Across the isolating distance Rated switching impulse withstand voltage (at altitude <1000m) - - 1.7. Phase to earth Phase to phase Phase to earth Phase to phase Across the isolating distance Rated power frequency withstand voltage (at altitude <1000m) - Phase to earth Section VI – Requirements Environmental Guidelines for Contractors Page 3 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - Phase to phase kV 520 - Across the isolating distance kV 610 1.8. Rated short-time withstand current (1 s) kA 40 1.9. Rated peak withstand current kA 100 1.10. Rated Current 4000 - at 40 oC A - at 50 oC (Contractor to confirm by calculation) A 1.11. Material of HV conductor 1.12. Material of contacts 1.13. Minimum factors of safety for switchgear - Busbars or other connections based on elastic limit 2.5 - Complete insulators based on electromechanical test 2.5 - Insulator metal fittings based on elastic limit 2.5 - Steel structures based on elastic limit of tension members and on cripping loads of compression members 2.5 - Foundations for structures against overturning or uprooting under maximum simultaneous working loadings Section VI – Requirements Environmental Guidelines for Contractors Offered 2.5 Page 4 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 1.14. Creepage distance (based on Um) 1.15. Seismic factor 2. mm/kV Offered 31 CIRCUIT BREAKER 2.1. Manufacturer & Place of manufacturing 2.2. Type designation 2.3. Type 2.4. Standards 2.5. Rated operating sequence O -0.3 sec- CO -3 min CO 2.6. Auto reclosing O -0.3 sec- CO -3 min CO 2.7. Rated making current KAp 100 2.8 Rated breaking current kA 40 Rated breaking current (asymmetrical) KA To IEC 62271-100 2.9. SF6 single pole %dc Rated breaking current under out-of-phase conditions Section VI – Requirements Environmental Guidelines for Contractors 62271-1, IEC 62271100, 62271-101, 62271-110, 60376, 60480 %dc kA 10 Page 5 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 2.10. First phase to clear factor 2.11 Transient Recovery Voltages 2.12. Rated capacitive breaking current 2.13. 1.3 TRVs To IEC 62271-100 To IEC 62271-100 Rated line charging breaking current A Rated cable charging breaking current A Rated Single/Back to Back Capacitor bank breaking current A Rated small inductive/reactor breaking currents of: To IEC 62271-110 - small inductive A - reactor A 2.14. Maximum overvoltage factor on any switching duty pu 2.3 2.15. Maximum overvoltage factor when interrupting rated line/cable/capacitor bank charging currents pu 2.3 2.16. Maximum overvoltage factor when switching small inductive/reactor currents pu 2.3 2.17. Maximum total break time (trip initiation to final arc extinction) ms 60 2.18. Opening time (trip initiation to contact separation) - Without current Section VI – Requirements Environmental Guidelines for Contractors Offered ms Page 6 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - With 100% rated breaking current 2.19. Maximum time interval between opening of first and last phase of three phase circuit breakers 2.20. Maximum time interval between opening of interrupters of one phase 2.21. Closing time from energisation of close coil to latching of circuit breaker in fully closed position 2.22. Making time (energisation of close coil to contact touch) ms ms ms - 100% making current ms 2.24. Maximum time interval between closure of interrupters of one phase 2.25. Minimum time from extinction of main arc to contact make during auto-reclosing duty 2.26. Mechanical life of circuit breaker and mechanism in No. of operations 2.27. Electrical contact life in number of operations at: Section VI – Requirements Environmental Guidelines for Contractors - ms Without current Maximum time interval between closure of first and last phase of three phase circuit breaker 3 - - 2.23. Offered ms 3.3 - - ms 10,000 Page 7 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - Rated current - 4000 A - Fault current - 40kA - Cumulative ampere rating 2.28. Number of current interrupting break units in series per phase 2.29. Type of operating mechanism 2.30. Type of power device (motor charged) 15 to 20 Two Motor charged spring operated - For closing Spring or hydraulic - For opening Spring or hydraulic 2.31. Hand operating facility Yes 2.32. Manual spring release (suitably positioned to avoid accidental operation) Yes 2.33. Mechanical on/off indicator Yes 2.34. Mechanical spring charge / discharge indication Yes 2.35. Charging time 2.36. Number of trip coils per phase 2 2.37. Number of close coils per phase 1 Section VI – Requirements Environmental Guidelines for Contractors Offered S Page 8 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 2.38. Nominal control and operating voltage V 110 DC 2.39. Nominal heater voltage V 240 AC 2.40. Rated power of trip coil W 2.41. Rated power of close coil W 2.42. Rated motor power W 2.43. Total load of heaters for circuit breaker W 2.44. Mass of circuit breaker complete (three pole) kg 2.45. Mass of single phase circuit breaker Kg 2.46 Emergency Trip Facility 3. Offered - Yes ISOLATORS 3.1. Manufacturer & Place of Manufacturing 3.2. Type designation Section VI – Requirements Environmental Guidelines for Contractors Page 9 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 3.3. Type of operating mechanism 3.4. Standards Offered Motor IEC 62271-102, IEC 62271-1 3.5. Maximum capacitive current that can be interrupted by the isolator A 3.6. Total time from initiation of opening operation to isolator in fully open position S 3.7 Time from contact separation to extinct of capacitive arc S 3.8 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage S 3.9 Hand operating facility Yes 3.10 Locking arrangement in on/off position Yes 3.11 Nominal control and operating voltage 3.12 Automatic isolation of control supplies when lock off Yes 3.13. Accessibility to operating mechanism from ground level Yes 3.14. Nominal heater voltage V 3.15. Rated power of operation coil W Section VI – Requirements Environmental Guidelines for Contractors V 110 DC 240 AC Page 10 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 3.16. Rated motor power W 3.17. Total load of heaters for isolator W 3.18. Total mass of three phase isolator complete kg 3.19 Mass of single phase isolator kg 3.20. Contact type 3.21. Type of interlocking 4. Offered EARTHING SWITCH 4.1. Manufacturer & place of manufacturing 4.2. Type designation 4.3. Type of operating mechanism 4.4. Standards 4.5. Hand operating facility Yes 4.6. Locking arrangement in on/off position Yes Section VI – Requirements Environmental Guidelines for Contractors Motor IEC 62271-102, 62271-1 Page 11 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 4.7. Nominal control and operating voltage 4.8. Automatic isolation of control supplies when lock off Yes 4.9. Accessibility to operating mechanism from ground level Yes 4.10. Nominal heater voltage V 4.11. Total load of heaters for earthing switch W 4.22. Total mass of earthing switch complete kg 5. V Offered 110 DC 240 AC CURRENT TRANSFORMER 5.1. Manufacturer & Place of manufacturing 5.2. Type 5.3. Standards 5.4. Rated continuous thermal current at 40oC Rated extended primary current 5.5. Current transformers Refer to Tender Drawings Section VI – Requirements Environmental Guidelines for Contractors Post IEC 62271-1, 60044-1 Page 12 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - Number of cores - Rated extended primary current - Ratio (TR – turns ratio) - - - - Offered 120% I core A II core A III core A IV core A Class I core II core III core IV core Knee point voltage (Ek) I core V II core V III core V IV core V Exciting current (IE) at Ek I core mA II core mA III core mA IV core mA Rated output (burden to be 25-100% rated burden) I core VA II core VA III core VA Section VI – Requirements Environmental Guidelines for Contractors Page 13 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required IV core Total mass of single phase current transformer complete 6. Offered VA kg CAPACITIVE VOLTAGE TRANSFORMERS 6.1. Manufacturer & Place of manufacturing 6.2. Type 6.3. Standards 6.4. Maximum permissible partial discharge level Capacitive IEC 60044-5 pC 10 pC 5 Um 6.5. Maximum permissible partial discharge level 1.2Um /3 6.6. Method of suppressing ferroresonance phenomena 6.7. Voltage transformer - Number of secondaries - Rated transformation ratio Section VI – Requirements Environmental Guidelines for Contractors Refer to Tender Drawings kV Page 14 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - - - 7 Offered Rated accuracy class I secondary II secondary Rated output (burden to be 25-100% rated burden) I secondary VA II secondary VA Mass of single phase voltage transformer kg METERING INSTRUMENT TRANSFORMERS 7.1 Manufacturer 7.2 Type designation 7.3 Standards 7.4 Rated continuous thermal current at 400C 7.5 Current transformers - Post IEC 60044-3, 61869 Rated extended primary current Number of cores 120% Section VI – Requirements Environmental Guidelines for Contractors Page 15 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - Rated extended primary current - Ratio (TR – turns ratio) • I core • II core - Class • I core • II core - Knee point voltage (Ek) • I core • II core Offered Refer to Tender Drawings V V - Exciting current (IE) at Ek • I core mA • II core mA mA mA Rated output (burden to be 25100% rated burden) • I core VA • II core VA Total mass of single phase current transformer complete VA VA Section VI – Requirements Environmental Guidelines for Contractors Page 16 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required Offered kg 7.6 Voltage transformers - Number of secondaries Refer to Tender Drawings Maximum permissible partial discharge level Um 10 pC Maximum permissible partial discharge level 1.2Um/√3 5 pC - Method of suppressing Ferro resonance - Ratio (TR – turns ratio) - Voltage factor, PU – BS EN 61869 - Rated accuracy class • I secondary • II secondary 1.5PU, 30secs Rated output (burden to be 25-100% rated burden) • I secondary • II secondary - Mass of single phase voltage transformer Section VI – Requirements Environmental Guidelines for Contractors Page 17 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required Offered VA VA kg 8. BUSBARS AND CONNECTIONS 8.1 Manufacturer 8.2 Type (flexible or tubular) 8.3 Material 8.4 Short-circuit current rating / duration 8.5 Normal current rating - at 40oC at 50oC KA/s A A 8.6 Maximum continuous current rating 8.7 Flexible conductors - stranding nominal cross-sectional area outer diameter no. of conductors per bundle spacing between conductors A mm2 mm mm Section VI – Requirements Environmental Guidelines for Contractors Page 18 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 8.8 Offered Tubular conductors - nominal cross-sectional area outer diameter inner diameter mm2 mm mm 8.9 Maximum stress at surface of flexible conductor 8.10 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz 9 kV/mm µV POST TYPE INSULATORS 9.1 Manufacturer 9.2 Type designation 9.3 Insulator material 9.4 Number of units in complete post insulator 9.5 Length of each unit 9.6 Mass of complete post insulator kg 9.7 Maximum cantilever working load (complete post insulator) N Section VI – Requirements Environmental Guidelines for Contractors mm Page 19 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 9.8 Minimum cantilever breaking load, upright (complete post insulator) N 9.9 Power frequency withstand voltage dry: wet kV 9.10 Basic insulation level kVp 9.11 Minimum dry/wet switching surge withstand level kVp 9.12 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz 10 TENSION AND SUSPENSION INSULATORS µv 10.1 Manufacturer 10.2 Type designation 10.3 Insulator material 10.4 Number of units in string mm 10.5 Greatest diameter of units mm 10.6 Distance between centres of units mm Section VI – Requirements Environmental Guidelines for Contractors Offered Page 20 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 10.7 Length of string, overall 10.8 Mass of string complete with all fittings kg 10.9 Maximum working load N 10.10 Power frequency withstand voltage of complete string kV 10.11 Basic insulation level of complete string kVp 10.12 Minimum wet switching surge withstand level of complete string kVp 10.13 Radio influence voltage measured at 1.1 times Us/3 at 1 MHz µv mm 11. 400KV SURGE ARRESTERS 11.1 Type 11.2 Standard 11.3 Rated/system voltage kV 420/400 Maximum overvoltage factor on the system due to any switching duty pu 2.3 11.4 Rated system frequency Hz 50 11.5 Condition of system neutral 11.6 Nominal Discharge current kAcrest 11.7 Energy capability as per IEC 60099-4 kJ/kV 11.8 Rated Voltage – MOA Section VI – Requirements Environmental Guidelines for Contractors Offered MOA IEC 60099-4 Solid kV 20 360 Page 21 of 677 A. 400 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 11.9 Long duration discharge class as per IEC 99-1 Class 4 11.10 Maximum Continuous Operating Voltage (COV) kV 260 min 11.11 TOV capability for 1sec 10sec kV kV Maximum residual voltage with current wave Switching Surges – 1kA/2kA 8/20 μs – 5kA 8/20 μs – 20Ka kV kV kV To IEC 60099-4 To IEC 60099-4 To IEC 60099-4 Discharge current withstand strength High current 4/10 μs Low current 2000 μs KAp KAp To IEC 60099-4 To IEC 60099-4 11.12 11.13 12.. 12.1 12.2 13. Manufacturer quality system in accordance with ISO 9000 Date of issue Validity Type test certificate to be issued by independent laboratory or independently witnessed type test certificate to be submitted Offered Yes Latest Valid Certificates - Yes Yes Note:- Technical parameters stated above to be confirmed following nominated Contractor’s insulation co-ordination study. Section VI – Requirements Environmental Guidelines for Contractors Page 22 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 1. GENERAL 1.1. Standards IEC IEC 62271-100, 62271-102, 62271-1, 62155, 60044-1, 60044-5, 60383, 60815 1.2. Rated voltage kV 245 1.3. System Voltage kV 220 1.4. Rated frequency Hz 50 1.5. Rated lightning impulse withstand voltage (at altitude <1000m) 1.6. - Phase to earth KVp 1050 - Across the isolating distance kVp 1200 Offered Rated power frequency withstand voltage (at altitude <1000m) - Phase to earth kV 460 - Across the isolating distance kV 530 1.7. Rated short-time withstand current (1 s) kA 31.5 1.8. Rated peak withstand current kA 80 1.9. Rated Current A 2000 - at 40 oC Section VI – Requirements Environmental Guidelines for Contractors Page 23 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - at 50 oC (Contractor to confirm by calculation) 1.10. Material of HV conductor 1.11. Material of contacts 1.12. Minimum factors of safety for switchgear A - Busbars or other connections based on elastic limit 2.5 - Complete insulators based on electromechanical test 2.5 - Insulator metal fittings based on elastic limit 2.5 1.13. Steel structures based on elastic limit of tension members and on cripping loads of compression members Foundations for structures against overturning or uprooting under maximum simultaneous working loadings Creepage distance (based on Um) mm/kV 1.14. Seismic factor - 2. Offered 2.5 2.5 31 CIRCUIT BREAKER 2.1. Manufacturer & Place of manufacturing 2.2. Type designation 2.3. Type 2.4. Standards Section VI – Requirements Environmental Guidelines for Contractors SF6 single pole 62271-1, IEC 62271100, 62271-101, 62271-110, 60376, 60480 Page 24 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 2.5. Rated operating sequence O -0.3 sec- CO -3 min - CO 2.6. Auto reclosing O -0.3 sec- CO -3 min - CO 2.7. Rated making current KAp 80 2.8 Rated breaking current kA 31.5 Rated breaking current (asymmetrical) KA To IEC 62271-100 - %dc 2.9. Rated breaking current under out-of-phase conditions 2.10. First phase to clear factor 2.11 Transient Recovery Voltages 2.12. Rated capacitive breaking current 2.13. %dc kA 10 1.5 TRVs To IEC 62271-100 To IEC 62271-100 Rated line charging breaking current A Rated cable charging breaking current A Rated Single/Back to Back Capacitor bank breaking current A Rated small inductive/reactor breaking currents of: To IEC 62271-110 - small inductive A - reactor A Section VI – Requirements Environmental Guidelines for Contractors Offered Page 25 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 2.14. Maximum overvoltage factor on any switching duty pu 2.3 2.15. Maximum overvoltage factor when interrupting rated line/cable/capacitor bank charging currents pu 2.3 2.16. Maximum overvoltage factor when switching small inductive/reactor currents pu 2.3 2.17. Maximum total break time (trip initiation to final arc extinction) ms 60 2.18. Opening time (trip initiation to contact separation) - Without current ms - With 100% rated breaking current ms 2.19. Maximum time interval between opening of first and last phase of three phase circuit breakers 2.20. Maximum time interval between opening of interrupters of one phase 2.21. Closing time from energisation of close coil to latching of circuit breaker in fully closed position 2.22. Making time (energisation of close coil to contact touch) ms 3 - - - ms - Without current ms - 100% making current ms Section VI – Requirements Environmental Guidelines for Contractors Offered Page 26 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 2.23. Maximum time interval between closure of first and last phase of three phase circuit breaker 2.24. Maximum time interval between closure of interrupters of one phase 2.25. Minimum time from extinction of main arc to contact make during auto-reclosing duty 2.26. Mechanical life of circuit breaker and mechanism in No. of operations 2.27. Electrical contact life in number of operations at: - Rated current -2000 A - Fault current - 31.5 kA - Cumulative ampere rating 2.28. Number of current interrupting break units in series per phase 2.29. Type of operating mechanism 2.30. Type of power device (motor charged) ms 3.3 - - - ms 10,000 15 to 20 One Motor charged spring operated - For closing Spring or hydraulic - For opening Spring or hydraulic 2.31. Hand operating facility Yes 2.32. Manual spring release Yes Section VI – Requirements Environmental Guidelines for Contractors Offered Page 27 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 2.33. Mechanical on/off indicator Yes 2.34. Mechanical spring charge / discharge indication Yes 2.35. Charging time 2.36. Number of trip coils per phase 2 2.37. Number of close coils per phase 1 2.38. Nominal control and operating voltage V 110 DC 2.39. Nominal heater voltage V 240 AC 2.40. Rated power of trip coil W 2.41. Rated power of close coil W 2.42. Rated motor power W 2.43. Total load of heaters for circuit breaker W 2.44. Mass of circuit breaker complete (three pole) kg Section VI – Requirements Environmental Guidelines for Contractors Offered s Page 28 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR 2.45. Mass of single phase circuit breaker 2.46 Emergency Trip Facility 3. UNIT - DATA Required Offered - - Yes ISOLATORS 3.1. Manufacturer & Place of Manufacturing 3.2. Type designation 3.3. Type of operating mechanism 3.4. Standards Motor IEC 62271-102, IEC 62271-1 3.5. Maximum capacitive current that can be interrupted by the isolator A 3.6. Total time from initiation of opening operation to isolator in fully open position s 3.7 Time from contact separation to extinct of capacitive arc s 3.8 Total time from initiation of opening operation to time when isolator gap can withstand phase voltage s Section VI – Requirements Environmental Guidelines for Contractors Page 29 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 3.9 Hand operating facility Yes 3.10 Locking arrangement in on/off position Yes 3.11 Nominal control and operating voltage 3.12 Automatic isolation of control supplies when lock off Yes 3.13. Accessibility to operating mechanism from ground level Yes 3.14. Nominal heater voltage V 3.15. Rated power of operation coil W 3.16. Rated motor power W 3.17. Total load of heaters for isolator W 3.18. Total mass of three phase isolator complete kg 3.19 Mass of single phase isolator kg 3.20. Contact type 3.21. Type of interlocking Section VI – Requirements Environmental Guidelines for Contractors V Offered 110 DC 240 AC Page 30 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 4. Offered EARTHING SWITCH 4.1. Manufacturer & place of manufacturing 4.2. Type designation 4.3. Type of operating mechanism 4.4. Standards 4.5. Hand operating facility Yes 4.6. Locking arrangement in on/off position Yes 4.7. Nominal control and operating voltage 4.8. Automatic isolation of control supplies when lock off Yes 4.9. Accessibility to operating mechanism from ground level Yes 4.10. Nominal heater voltage V 4.11. Total load of heaters for earthing switch W Section VI – Requirements Environmental Guidelines for Contractors Motor IEC 62271-102, 62271-1 V 110 DC 240 AC Page 31 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 4.22. 5. Total mass of earthing switch complete Offered kg CURRENT TRANSFORMER 5.1. Manufacturer & Place of manufacturing 5.2. Type 5.3. Standards 5.4. Rated continuous thermal current at 40°C Post IEC 62271-1, 60044-1 Rated extended primary current Note: All Cl PX CTs shall be ISN 1.2 A 5.5. Current transformers - Number of cores - Rated extended primary current - Ratio (TR – turns ratio) - Refer to Tender Drawings 120% I core A II core A III core A IV core A Class I core Section VI – Requirements Environmental Guidelines for Contractors Page 32 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - - - II core III core IV core Knee point voltage (Ek) I core V II core V III core V IV core V Exciting current (IE) at Ek I core mA II core mA III core mA IV core mA Rated output (burden to be 25-100% rated burden) I core VA II core VA III core VA IV core VA Total mass of single phase current transformer complete 6. Offered kg CAPACITIVE VOLTAGE TRANSFORMERS 6.1. Manufacturer & Place of manufacturing 6.2. Type Section VI – Requirements Environmental Guidelines for Contractors Capacitive Page 33 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 6.3. Standards 6.4. Maximum permissible partial discharge level Offered IEC 60044-5 pC 10 pC 5 Um 6.5. Maximum permissible partial discharge level 1.2Um /3 6.6. Method of suppressing ferroresonance phenomena 6.7. Voltage transformer - Number of secondaries - Rated transformation ratio - Rated accuracy class - - 7 I secondary II secondary Refer to Tender Drawings kV Rated output (burden to be 25-100% rated burden) I secondary VA II secondary VA Mass of single phase voltage transformer kg METERING INSTRUMENT TRANSFORMERS Section VI – Requirements Environmental Guidelines for Contractors Page 34 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 7.1 Manufacturer 7.2 Type designation 7.3 Standards 7.4 Rated continuous thermal current at 400C 7.5 Current transformers Offered Post IEC 60044-3, 61869 - Number of cores - Rated extended primary current - Ratio (TR – turns ratio) Rated extended primary current 120% Refer to Tender • I core • II core - Class • I core • II core - Knee point voltage (Ek) • I core • II core Drawings V Section VI – Requirements Environmental Guidelines for Contractors Page 35 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - Exciting current (IE) at Ek • I core mA • II core mA Offered V mA Rated output (burden to be 25100% rated burden) • I core VA • II core VA mA Total mass of single phase current transformer complete VA VA kg 7.6 Voltage transformers - Number of secondaries Refer to Tender Drawings Maximum permissible partial discharge level Um 10 pC Maximum permissible partial discharge level 1.2Um/√3 5 pC - Method of suppressing Ferro resonance - Ratio (TR – turns ratio) Section VI – Requirements Environmental Guidelines for Contractors Page 36 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required - Voltage factor, PU – BS EN 61869 - Rated accuracy class • I secondary • II secondary Offered 1.5PU, 30secs Rated output (burden to be 25-100% rated burden) • I secondary • II secondary - Mass of single phase voltage transformer VA VA kg 7.10 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz 8. BUSBARS AND CONNECTIONS 8.1 Manufacturer 8.2 Type (flexible or tubular) Section VI – Requirements Environmental Guidelines for Contractors µV Page 37 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 8.3 Material 8.4 Short-circuit current rating / duration 8.5 Normal current rating - at 40oC at 50oC Offered KA/s A A 8.6 Maximum continuous current rating 8.7 Flexible conductors - stranding nominal cross-sectional area outer diameter no. of conductors per bundle spacing between conductors A mm2 mm mm 8.8 Tubular conductors - nominal cross-sectional area outer diameter inner diameter mm2 mm mm 8.9 Maximum stress at surface of flexible conductor 8.10 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz Section VI – Requirements Environmental Guidelines for Contractors kV/mm µV Page 38 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 9 Offered POST TYPE INSULATORS 9.1 Manufacturer 9.2 Type designation 9.3 Insulator material 9.4 Number of units in complete post insulator 9.5 Length of each unit 9.6 Mass of complete post insulator kg 9.7 Maximum cantilever working load (complete post insulator) N 9.8 Minimum cantilever breaking load, upright (complete post insulator) N 9.9 Power frequency withstand voltage dry: wet kV 9.10 Basic insulation level kVp 9.11 Minimum dry/wet switching surge withstand level kVp 9.12 Radio influence voltage level measured at 1.1 times Us/3 at 1 MHz Section VI – Requirements Environmental Guidelines for Contractors mm µv Page 39 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 10 Offered TENSION AND SUSPENSION INSULATORS 10.1 Manufacturer 10.2 Type designation 10.3 Insulator material 10.4 Number of units in string mm 10.5 Greatest diameter of units mm 10.6 Distance between centres of units mm 10.7 Length of string, overall mm 10.8 Mass of string complete with all fittings kg 10.9 Maximum working load N 10.10 Power frequency withstand voltage of complete string kV 10.11 Basic insulation level of complete string kVp Section VI – Requirements Environmental Guidelines for Contractors Page 40 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 10.12 Minimum wet switching surge withstand level of complete string kVp 10.13 Radio influence voltage measured at 1.1 times Us/3 at 1 MHz µv 11. 220KV SURGE ARRESTERS 11.1 Type 11.2 Standard 11.3 Rated/system voltage - Maximum overvoltage factor on the system due to any switching duty MOA IEC 6099-4 kV 245/220 pu 2.3 Hz 50 11.4 Rated system frequency 11.5 Condition of system neutral 11.6 Nominal Discharge current kAcrest 11.7 Energy capability as per IEC 60099-4 kJ/kV Section VI – Requirements Environmental Guidelines for Contractors Offered Solid 10 Page 41 of 677 B. 220 kV OPEN TERMINAL SWITCHGEAR UNIT DATA Required 11.8 Rated Voltage – MOA 11.9 Long duration discharge class as per IEC 6099-4 Class 3 11.10 Maximum Continuous Operating Voltage (COV) kV To IEC 60099-4 11.11 TOV capability for - 1sec 10sec Offered kV kV kV 11.12 Maximum residual voltage with current wave - 11.13 Switching Surges – 1kA/2kA 8/20 μs – 5kA 8/20 μs – 20Ka To IEC 60099-4 kV To IEC 60099-4 kV To IEC 60099-4 KAp To IEC 60099-4 KAp To IEC 60099-4 Discharge current withstand strength High current 4/10 μs Low current 2000 μs 12. kV Type test certificate to be issued by independent Yes laboratory or independently witnessed type test certificate to be submitted Section VI – Requirements Environmental Guidelines for Contractors Page 42 of 677 C. EARTHING AND LIGHTNING PROTECTION UNIT DATA Required 1. Offered EARTHING SYSTEM 1.1. Manufacturers 1.2. Standard Applied The following standards shall apply to the earthing installations and to the accessories: Guide for safety in A.C. substation grounding Earthing system in A.C. installation for rated voltages above 1000 V IEEE80 & 81 VDE 0141 1.3. Physical Properties of Copper The most important physical properties of copper used for the earthing conductors: 1.4. Density Electrical resistivity at 20C Melting point Current density at which the conductor temperature rises from 50C to 300C in a time of 1 s if all heat is retained in conductor kg/dm3 8.89 mm2/m 0.0176 C 1083 A/mm2 190 Physical Properties of Lead-Sheathed Copper The most important physical properties of lead-sheathed copper used for the earth electrodes: Section VI – Requirements Environmental Guidelines for Contractors Page 43 of 677 C. EARTHING AND LIGHTNING PROTECTION UNIT DATA Required 1.5. 1.5.1. Thickness of lead sheath Electrical resistivity of copper at 20C mm 2.0 mm2/m 0.0176 Copper melting point C 1083 Lead melting point C 327 Current density at which the conductor temperature rises from 40C to 150C in a time of 1 s if all heat is retained in conductor A/mm2 140 Offered Earthing Conductors Stranded copper conductors The following stranded copper conductor will be used as earthing conductors: Cross-section area mm2 Number of wires No. Diameter of each wire mm Conductor diameter mm Density kg/m Cross-section area mm2 Number of wires No. Diameter of each wire mm Conductor diameter mm Density kg/m Section VI – Requirements Environmental Guidelines for Contractors Page 44 of 677 C. EARTHING AND LIGHTNING PROTECTION UNIT DATA Required 1.5.2. Cross-section area mm Number of wires pcs Diameter of each wire mm Conductor diameter mm Density kg/m Offered Copper Flat Bars The following copper flat bars will be used as earthing conductors: 1.5.3. Cross section area Dimensions Density kg/m Cross section area mm2 Dimensions Density kg/m Cross section area mm2 Dimensions Density mm2 mm x mm mm x mm mm x mm kg/m Copper Cables The following PVC single-core copper cables will be used as earthing conductors: Cross-section area Section VI – Requirements Environmental Guidelines for Contractors mm2 Page 45 of 677 C. EARTHING AND LIGHTNING PROTECTION UNIT DATA Required 1.6. 1.6.1. Cross-section area mm2 Cross-section area mm2 Offered Earth Electrodes Lead-sheathed stranded copper conductors The following lead-sheathed stranded copper conductor will be used as earth electrodes: Thickness of lead sheath mm Copper cross-section area mm2 Number of wires pcs Diameter of each wire mm Conductor diameter mm Density kg/m Thickness of lead sheath mm Copper cross-section area mm2 Number of wires pcs Diameter of each wire mm Conductor diameter mm Density kg/m Thickness of lead sheath mm Copper cross-section area mm2 Diameter of each wire mm Section VI – Requirements Environmental Guidelines for Contractors Page 46 of 677 C. EARTHING AND LIGHTNING PROTECTION UNIT DATA Required 1.6.2. 1.6.3. Conductor diameter mm Density kg/m Offered Earth rod Manufacturer Length Diameter Material (copper, stainless steel) m mm Stainless steel electrodes The following steel flat bars will be used as earth electrodes: Cross-section area dimensions Density mm2 mm x mm kg/m 1.7. Connections Mode of Connection in the Earthing Systems: Between earthing conductors and earth electrodes Crossing of earth electrodes Brazed Compressio n 2. LIGHTNING PROTECTION 2.1. Manufacturers 2.2. Standard Applied: Protection of structures against lightning Section VI – Requirements Environmental Guidelines for Contractors Page 47 of 677 C. EARTHING AND LIGHTNING PROTECTION UNIT DATA Required Offered IEC 62305 2.3. Manufacturer Cross-section area mm2 Thickness of lead-sheath mm Supports Conductor supports of the lightning protection system 2.4. 3. Type Earth rod Manufacturer Length Diameter Material (copper, stainless steel) m mm Type test certificate (to be issued by independent laboratory or independently witnessed type test certificate available) yes Section VI – Requirements Environmental Guidelines for Contractors Page 48 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 1. Offered LINE DIFFERENTIAL PROTECTION AND BACK-UP DISTANCE (87/21L) Manufacturer Type reference Relay design (microprocessor based, numerical) Numerical Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 Differential protection requirements Phase segregated protection Yes Ratio and Vector correction for CTs Yes Adjustable biased differential protection characteristic Yes Sensitivity: - For phase faults - For earth faults Operating time ms <30 Distance protection requirements 3 zone ph-ph & ph-E Yes Phase fault & Earth fault characteristic shapes (Mho, Quad) Quad Operating time <30ms SOTF Yes Power swing blocking (depending on relaying point in the power Yes system) Voltage transformer supervision Yes Time delays for all zones Yes Zone enable/disable for all zones Yes Other requirements DEF comparison function Yes Directional protection 67/67N Overcurrent/Earth fault 50/51/50N/51N Stub protection 50STB Section VI – Requirements Environmental Guidelines for Contractors Yes Page 49 of 677 D. UNIT PROTECTION AND INDICATION SYSTEM DATA Required Offered No Circuit breaker failure. 50BF- (application dependent)) Thermal overload, 49 TBA Auto Reclose 79 (application dependent) Yes Under/Over Voltage Integral intertrip send and receive, with external input interface Yes Event recording function Yes Disturbance recording function Yes Fault locator function Yes Integral LCD operator interface for local interrogation Yes Programmable scheme logic Yes PC based configuration software for HMI, settings, logic and data Yes recorder. 1.1 Programme name 1.2 Included / Separate Tripping contacts rating Carry continuous Make 5A 30A maximum for Yes 0.2s Break dc 50W resistive 25W inductive(L/R40ms) Self checking facility Yes Integral intertrip send and receive, with external input interface Yes Communications Protection Direct optical fibre TBA 1550nm single mode distance (km) 1300nm single mode distance (km) Section VI – Requirements Environmental Guidelines for Contractors Page 50 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered 820nm multi-mode distance (km) Others supported TBA G703.1 X21 Control Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 60870-5-103 Others (please state) Yes Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2- Yes 2 Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Section VI – Requirements Environmental Guidelines for Contractors Page 51 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Yes Type test certificate provided Yes 1.3 2. DISTANCE (21) Manufacturer Type reference Relay design (microprocessor based, numerical) Numerical Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 Distance protection requirements Minimum 3 zone ph-ph & ph-E Yes Phase fault & Earth fault characteristic shapes (Mho, Quad) Nominal Z1 Operating time <30ms SOTF Yes Power swing blocking Yes Voltage transformer supervision Yes Time delays for all zones Yes Zone enable/disable for all zones Yes Other supported Functions DEF comparison function Yes Directional protection 67/67N Overcurrent/Earth fault 50/51/50N/51N Section VI – Requirements Environmental Guidelines for Contractors Page 52 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Yes Stub protection 50STB Circuit breaker failure. 50BF- (application dependent)) TBA Thermal overload, 49 Auto Reclose 79 (application dependent) Under/Over Voltage Integral intertrip send and receive, with external input interface Yes Event recording function Yes Disturbance recording function Yes Fault locator function Yes Integral LCD operator interface for local interrogation Yes Programmable logic Yes PC based configuration software for HMI, settings, logic and data Yes recorder. 2.1 Programme name 2.2 Included / Separate Tripping contacts rating details Carry continuous Make Break A A / time dc W rest. W & L/R Self checking facility Yes Communications Protection Direct optical fibre 2.3 TBA 1550nm single mode distance (km) Section VI – Requirements Environmental Guidelines for Contractors Page 53 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 2.4 1300nm single mode distance (km) 2.5 820nm multi-mode distance (km) Others supported 2.6 2.7 G703.1 2.8 X21 Offered TBA Control Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Others (please state) Yes Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Section VI – Requirements Environmental Guidelines for Contractors Page 54 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Yes Type test certificate provided Yes 2.9 3. MAIN TRANSFORMER / REACTOR BIASED DIFFERENTIAL PROTECTION 87 including HV and LV REF Manufacturer Type reference Relay design (microprocessor based, numerical) 3.1 numerical Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 ms <25 Biased Differential function Operation time at 5 times setting Adjustable bias characteristics Yes Differential current stage Id >> Yes Magnetisation inrush restraint Yes 5th” Harmonic restraint Yes CT ratio and vector group compensation Yes Section VI – Requirements Environmental Guidelines for Contractors Page 55 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 3.2 Offered Restricted earth fault function HV REF Yes LV REF Yes Principle of REF operation High impedance/Low impedance Operation time at 5 times settings Low ms <30 Other requirements Phase overcurrent function 50/51 (requirement depending on No application) Earth fault protection 51N (requirement depending on application) No Integral LCD operator interface for local interrogation Yes Programmable logic Yes PC based configuration software for HMI, settings, logic and data recorder. 3.3 Programme name 3.4 Included / Separate Tripping contacts rating details Carry continuous Make Break A A / time dc W rest. W & L/R Event recording function Yes Disturbance recording function Yes Section VI – Requirements Environmental Guidelines for Contractors Page 56 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Yes Fault recording function Self monitoring and alarm facility Communications Control Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Others (please state) Yes Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration Section VI – Requirements Environmental Guidelines for Contractors IEC 60255-21-3 Page 57 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Type test certificate provided 4. Yes Yes HV CONNECTIONS DIFFERENTIAL PROTECTION 87HC Manufacturer Type reference Section VI – Requirements Environmental Guidelines for Contractors Page 58 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Relay design (microprocessor based, numerical) Offered numerical Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 Principle of operation High impedance/Low impedance 4.1 High or Low Biased Differential function (Low Impedance) No of separate CT inputs Operation time at 5 times setting 4.2 3 ms <25 Adjustable bias characteristics Yes Differential current stage Id >> Yes Magnetisation inrush restraint Yes 5th” Harmonic restraint Yes CT ratio and vector group compensation Yes Differential function (High Impedance) minimum fault setting (% of CT rating) % Yes Operating time at 5 x setting ms <30 Non Linear Resistors (Metrosils) integral Y/N 4.3 Integral LCD operator interface for local interrogation Yes Programmable logic Yes Section VI – Requirements Environmental Guidelines for Contractors Page 59 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered PC based configuration software for HMI, settings, logic and data recorder. 4.4 Programme name 4.5 Included / Separate Tripping contacts rating details Carry continuous A Make Break A / time dc W rest. W & L/R Event recording function Yes Disturbance recording function Yes Fault recording function Yes Self monitoring and alarm facility Communications Control Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Others (please state) Yes Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Section VI – Requirements Environmental Guidelines for Contractors Yes Page 60 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Transport/storage -25C and 70C for 96hrs, IEC 60068-2- Offered Yes 2 Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Section VI – Requirements Environmental Guidelines for Contractors Page 61 of 677 D. UNIT PROTECTION AND INDICATION SYSTEM DATA Required Test method A, 27MHz through 500MHz Offered Yes Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Yes Type test certificate provided 5. LOW IMPEDANCE BUSBAR PROTECTION BREAKER FAILURE PROTECTION Yes INCLUDING Manufacturer Type reference Relay design (static, microprocessor-based, numerical) Numerical Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 State principle of operation, i.e. low impedance Integral check zone feature Distributed Central and Bay Modules or Integrated (Dist / Int) Low Z Yes Either Maximum number of Bays CT saturation detector and stabilisation Integral CT supervision CT matching functions Phase segregated protection Sensitivity Section VI – Requirements Environmental Guidelines for Contractors Page 62 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 1. Phase faults A sec’y 2. Earth faults A sec’y Operating time at 5 x fault setting ms Two stage Circuit Breaker Failure Offered 30 Yes Adjustable current setting Adjustable time delays per stage Other requirements PC based configuration software for HMI, settings, logic and data recorder. 5.1 Programme name 5.2 Included / Separate Yes Tripping contacts rating details Carry continuous Make Break A A / time dc W rest. W & L/R Event recording function Yes Disturbance recording function Yes Self monitoring and alarm facility Communications Bay to central Module communication f.o. Integral LCD operator interface for local interrogation Yes Control Communication ports (Front/rear etc) Section VI – Requirements Environmental Guidelines for Contractors Page 63 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Others (please state) Yes Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Section VI – Requirements Environmental Guidelines for Contractors Page 64 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Yes Type test certificate provided Yes 6. 7. MULTI-FUNCTIONAL DIRECTIONAL OVERCURRENT & EARTH FAULT PROTECTION {67/67N/50/51/50N/51N) Manufacturer Type reference Relay design (static, microprocessor-based, numerical) Numerical Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 Number of phase CT inputs Section VI – Requirements Environmental Guidelines for Contractors Page 65 of 677 D. UNIT PROTECTION AND INDICATION SYSTEM DATA Required Offered Number of earth fault CT inputs Number of VT inputs Characteristics curves conforming to IEC 60255, ANSI Yes Number of overcurrent functions (e.g. No. lowset, highset, IDMTL) Number of earth fault functions Number of group settings Earth fault element suitable of high impedance REF (with external Yes resistor) Other functions provided Thermal overload 49 Y/N U/O Voltage 27/59 Y/N NVD 59N Y/N Integral metering functions No. of opto-isolator inputs No of outputs Programmable logic Yes Event and Fault recording functions Self-monitoring facility PC based configuration software for HMI, settings, logic and data recorder. 7.1 Programme name 7.2 Included / Separate Yes Tripping contacts rating details Carry continuous Make Break A A / time dc W rest. W & L/R Communications Integral operator interface for local interrogation Yes Control Section VI – Requirements Environmental Guidelines for Contractors Page 66 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Yes Others (please state) Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Section VI – Requirements Environmental Guidelines for Contractors Yes Page 67 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 1000V open contact withstand Offered Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Yes Type test certificate provided Yes 8. 9. MULTI-FUNCTIONAL FEEDER MANAGEMENT RELAY {67/67N,50/51,50N/51N, 27, 59, 25, 79, CONTROL, METERING) Manufacturer Type reference Relay design (static, microprocessor-based, numerical) Auxiliary voltage range (Vn = 110Vdc) Section VI – Requirements Environmental Guidelines for Contractors Numerical Vdc 88150 Page 68 of 677 D. UNIT PROTECTION AND INDICATION SYSTEM DATA Required Input frequency range (50Hz nominal) Hz Offered 47.552.5 Number of phase CT inputs Number of earth fault CT inputs Number of VT inputs Characteristics curves conforming to IEC 60255, ANSI IEC Number of overcurrent functions (e.g. No. lowset, highset, IDMTL) Number of earth fault functions Number of group settings Earth fault element suitable of high impedance REF (with external Yes resistor) Other functions provided 9.1 Thermal overload 49 Y/N U/O Voltage 27/59 Y/N NVD 59N Y/N Check Synch 25 Y/N Auto-reclose 79 Y/N Feeder Control (where applicable) Integral LCD operator interface for local control and interrogation Yes Full control of circuit bay Yes Close/Open of circuit breakers Close/Open of Disconnectors/Earth Switches Switching status Interlocking facilities Plant status Active circuit line diagram Integral metering functions No. of opto-isolator inputs No. of outputs Programmable logic Yes Event and Fault recording functions Self-monitoring facility PC based configuration software for HMI, settings, logic and data recorder. Section VI – Requirements Environmental Guidelines for Contractors Page 69 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 9.2 Programme 9.3 Included / Separate Offered Yes Tripping contacts rating details Carry continuous A Make Break A / time dc W rest. W & L/R Communications Control & Monitoring Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Yes Others (please state) Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2- Yes 2 Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure Section VI – Requirements Environmental Guidelines for Contractors Page 70 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Offered Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Type test certificate provided Yes Yes 10. Section VI – Requirements Environmental Guidelines for Contractors Page 71 of 677 D. UNIT PROTECTION AND INDICATION SYSTEM DATA Required 11. Offered OVERCURRENT & EARTH FAULT PROTECTION (50/51/50N/51N) Manufacturer Type reference Relay design (static, microprocessor-based, numerical) Numerical Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 Number of phase CT inputs Number of earth fault CT inputs Characteristics curves conforming to IEC 60255, ANSI Yes Number of overcurrent functions (e.g. No. lowset, highset, IDMTL) Number of earth fault functions Number of group settings Earth fault element suitable of high impedance REF (with external Yes resistor) Other functions provided Thermal overload 49 Y/N 50BF Y/N Integral metering functions No. of opto-isolator inputs Programmable logic Yes Event and Fault recording functions Self-monitoring facility PC based configuration software for HMI, settings, logic and data recorder. 11.1 Programme name Section VI – Requirements Environmental Guidelines for Contractors Page 72 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 11.2 Included / Separate Offered Yes Tripping contacts rating details Carry continuous A Make Break A / time dc W rest. W & L/R Communications Integral LCD operator interface for local interrogation Yes Control Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Yes Others (please state) Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2- Yes 2 Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure Section VI – Requirements Environmental Guidelines for Contractors Page 73 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Offered Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Type test certificate provided Yes Yes 12. Section VI – Requirements Environmental Guidelines for Contractors Page 74 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required 13. Offered HIGH IMPEDANCE DIFFERENTIAL PROTECTION (87) Manufacturer Type reference Relay design (static, microprocessor-based, numerical, E-Mech) Numerical minimum fault setting (% of CT rating) % Operating time at 5 x setting ms Non Linear Resistors (Metrosils) integral Y/N Self monitoring (excluding E-Mech) Yes PC based configuration software for HMI, settings, logic and data recorder. 13.1 Programme name 13.2 Included / Separate Tripping contacts rating details Carry continuous Make Break A A / time dc Section VI – Requirements Environmental Guidelines for Contractors W rest. Page 75 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered W & L/R Communications (numerical relays) Integral LCD operator interface for local interrogation Yes Control Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported IEC 61850 Yes others Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration Section VI – Requirements Environmental Guidelines for Contractors IEC 60255-21-3 Page 76 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Type test certificate provided 14. Yes Yes AUTO-RECLOSE RELAY (79) Manufacturer Type reference Relay design (microprocessor based, numerical) Section VI – Requirements Environmental Guidelines for Contractors Numerical Page 77 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Input frequency range (50Hz nominal) Hz 47.552.5 Offered Auto-Reclose Function requirements No of CB that can be controlled 2 1ph and 3ph AR sequences 1ph+3ph Integrated/External Check Synch Other requirements No of Opto-isolator inputs No of output contacts Integral operator interface for local interrogation Yes Programmable scheme logic Yes PC based configuration software for HMI, settings, logic and data Yes recorder. 14.1 Programme name 14.2 Included / Separate Tripping contacts rating details Carry continuous Make Break A A / time dc W rest. W & L/R Self checking facility Yes Communications Control Communication ports (Front/rear etc) Physical links (RS485/Fibre optic) Protocols supported Section VI – Requirements Environmental Guidelines for Contractors Page 78 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required IEC 61850 others Offered Yes Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Section VI – Requirements Environmental Guidelines for Contractors Yes Page 79 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Type test certificate provided Offered Yes 14.3 15. TRIP CIRCUIT SUPERVISION Manufacturer Type reference Relay design (Electro-Mech, static, numerical) Auxiliary voltage range (Vn = 110Vdc) Vdc Operating time ms 88150 Supervision of the whole trip circuit - CB open and closed. Yes Relay operated indicator Yes Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation Section VI – Requirements Environmental Guidelines for Contractors Page 80 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Yes Type test certificate provided Yes 15.1 16. MULTI-CONTACT TRIPPING RELAYS Manufacturer Type reference Operating time ms <12 Auxiliary voltage range (Vn = 110Vdc) Vdc 88150 Is relay mechanically latched or self resetting Method used to reset latched relay (hand or electrical) Burden at rated voltage Minimum voltage at which reliable operation occurs Section VI – Requirements Environmental Guidelines for Contractors Page 81 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Tripping contacts rating details Carry continuous A Make Break A / time dc W rest. W & L/R Relay operated indicator type Type Tests Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Section VI – Requirements Environmental Guidelines for Contractors Page 82 of 677 D. PROTECTION AND INDICATION SYSTEM UNIT DATA Required Offered Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Yes Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV Type test certificate provided Section VI – Requirements Environmental Guidelines for Contractors Yes Yes Page 83 of 677 E. TARIFF METERING SYSTEM UNIT DATA Required 17. 1 1.1 Offered TARIFF METER Manufacturer Model 1.2 Construction Measuring Principle 3ph, 4wire Type Numerical ≥7 Display/Reading digits Backlit LCD 1.3 1.5 Auxiliary voltage range DC (Vn = 110Vdc) Vdc 88125 AC Vac 230 A 1 pu 1.2 V 110 pu 0.8 – 1.15 Analogue Inputs Current (In) Current measuring range Voltage (Vn) Voltage measuring range Power consumption (burden) 1.6 1.7 Yes VA Accuracy Class Watt hour (IEC 602053-22) 0.2s VAr hour (IEC 602053-23) 2.0 Measurements Section VI – Requirements Environmental Guidelines for Contractors Page 84 of 677 E. TARIFF METERING SYSTEM UNIT DATA Required Offered kWh, kVArh kW, kVAr V, I Four quadrant reactive energy Max Demand THD 1.8 Outputs Pulsed Outputs (IEC 62053-31) 1.9 3 (min) Data Logging Integral Logging/Storage function Duration 180 Channels 4 Programmable Periods y Inputs from external meters 1.10 days y/n Other functions Battery Back-up y/n y Back-up duration days ≥14 GPS clock y/n y Self checking/monitoring facility y/n y Dual supply changeover (VT) y/n y Section VI – Requirements Environmental Guidelines for Contractors Page 85 of 677 E. TARIFF METERING SYSTEM UNIT DATA Required 1.11 Offered Communications Communication ports (Front/rear etc) RS232 RS485 y Optical (IEC 62056-21) y Ethernet y Protocols supported IEC 62056-21, DLMS others y Type Tests 1.12 Atmospheric Environment (62052-11) Operating Range: -10C to 45C y Operation -25C to 55C Transport/storage -25C to 70C 1.13 1.14 Relative Humidity (62052-11) Annual mean <75% y 30 days over one year: 95% y Enclosure IEC 60529 1.15 1.16 y IP51 Mechanical Environment (62052-11) Shock test IEC 60068-2-27 Vibration IEC 60068-2-6 Insulation Strength (IEC 62052-11) y y Dielectric Tests- Section VI – Requirements Environmental Guidelines for Contractors Page 86 of 677 E. UNIT TARIFF METERING SYSTEM DATA Required Offered Impulse voltage (surge) as per IEC 61000-4-5 1.17 Electromagnetic compatibility IEC 62052-11 y Electrostatic Discharge to IEC 61000-4-2 Immunity to Electromagnetic Fields to IEC 61000-4-3 Fast Transient Burst Test to IEC 61000-4-4 Immunity to conducted disturbance by RF fields to IEC 61000-4-6 Damped Oscillatory Waves to IEC 6100-4-12 Radio Interference Suppression to 1.18 Type test certificate provided Section VI – Requirements Environmental Guidelines for Contractors CISPR 22 class B y Page 87 of 677 F. FAULT MONITORING SYSTEM UNIT DATA Required 1 Offered FAULT MONITORING SYSTEM 1.1 Manufacturer 1.2 Type reference DAU unit type Master Station type HMI type Printer type 1.3 Auxiliary voltage range (Vn = 110Vdc) 1.4 Analogue Inputs 8 1.5 Event inputs 16 1.6 A/D converter bit 16bit 1.7 Current input max amplitude In 30 1.8 Current/voltage accuracy % fsd ≤0.5 1.9 Scan Rate Analogue Channel Hz ≥4000 Event Channel Hz ≥2000 ms 1 Pre Fault ms ≥500 Post Fault ms ≥2000 1.10 Time stamp resolution 1.11 Recording range 1.12 Vdc 88150 Trigger response time Section VI – Requirements Environmental Guidelines for Contractors Page 88 of 677 F. FAULT MONITORING SYSTEM UNIT DATA Required Offered Analogue Event 1.13 Memory RAM (Non Volatile) Mb ≥256 HDD Mb ≥500 days ≥14 1.14 Battery Back-up duration 1.15 GPS clock input 1.16 System Software 1.17 Self checking facility 1.18 Communications Yes Yes Communication ports (Front/rear etc) RS232 RS485 RJ45 Other Protocols supported IEC 61850 others Type Tests 1.19 Atmospheric Environment Operation -25C and 55C for 96hrs, IEC 60068-2-1 Yes Transport/storage -25C and 70C for 96hrs, IEC 60068-2-2 Yes Section VI – Requirements Environmental Guidelines for Contractors Page 89 of 677 F. FAULT MONITORING SYSTEM UNIT DATA Required 1.20 1.21 Relative Humidity Operation at 93% Yes Tested to IEC 60068-2-3 with severity class 56 days Yes Enclosure IEC 60529 1.22 IP50 Yes IEC 60255-21-1 Yes Shock and bump IEC 60255-21-2 Yes Seismic Yes Mechanical Environment Vibration 1.23 Offered IEC 60255-21-3 Insulation Rated insulation 1000V high impedance protection CT inputs 250V for other circuits Yes 1000V open contact withstand Yes Dielectric Tests IEC 60255-5 – Series C of table 1 Yes Impulse voltage IEC 60255-5 test voltage 5kV 1.24 Yes Electromagnetic compatibility 1MHz Burst disturbance test, IEC 60255-22-1 severity class III Section VI – Requirements Environmental Guidelines for Contractors Yes Page 90 of 677 F. FAULT MONITORING SYSTEM UNIT DATA Required Offered Electrostatic Discharge IEC 60255-22-2 severity class III Yes Radiated Electromagnetic Field Disturbance IEC 60255-22-3 severity class III Yes Test method A, 27MHz through 500MHz Electromagnetic Emissions IEC 60255-25 Yes Fast Transient Disturbance IEC 60255-22-4 severity level IV 1.25 Type test certificate provided Section VI – Requirements Environmental Guidelines for Contractors Yes Yes Page 91 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required Offered 18. 1 GENERAL 1.1 Name of manufacturer 1.2 Location of manufacturing site 1.3 Manufacturers Quality Certification Certified by (Company Name) Certification valid till (year) 1.4 Circuit rating required 1.5 General description of cable 1.6 ISO 9001 kVA 500 number of cores system voltage kV conductor size mm2 Insulation Type XLPE metal sheath type Lead oversheath type 1or 3 11 MDPE Year of first commercial operation of cable type 2 INSULATION CO-ORDINATION 2.1 Highest system voltage (Um) (insulation class) kV 12 2.2 Nominal voltage between conductors (U) kV 11 2.3 Rated frequency Hz 50 2.4 Nominal voltage between conductor and sheath (Uo) kV 6.35 2.5 Rated impulse withstand voltage (Up) kV 95 2.6 Rated short duration power frequency withstand voltage kV 17 Section VI – Requirements Environmental Guidelines for Contractors Page 92 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required 3 3.1 Offered RATINGS Maximum continuous direct-buried current rating, assuming, Soil thermal resistivity of 2.0K.m/W Flat spaced configuration, phase spacing of 250mm Special bonding of metal sheaths For, 3.2 Guaranteed Current Rating (Single Circuit in Trench) A Guaranteed Current Rating (Double Circuit in one Trench, distance between middle phases, s = 1500 mm) A Ground temperature at burial depth Calculation Method oC IEC 60287 Maximum continuous in-air current rating, assuming, Air temperature (in shade) of 35 °C Special bonding of metal sheaths Flat spaced configuration, group/phase spacing of 150mm Thermally independent of other cable circuits For, 3.3 Guaranteed Current Rating (single circuit) Calculation Method Maximum permissible core temperature for continuous A °C 90 operation 3.4 Short circuit capacity for 1 sec Short circuit current kA As per IEC60502 3.5 3.5.1 Permissible maximum sheath temperature oC 200 Permissible maximum conductor temperature oC 250 Permissible emergency overload Applied on 100% continuous load Emergency current rating Maximum emergency temperature Allowable duration/operation hours Allowable total duration/annum hours Maximum average duration/annum on total life of cable hours Section VI – Requirements Environmental Guidelines for Contractors A oC Page 93 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required 3.5.2 3.5.3 Offered Applied on 50% continuous load Emergency current rating A Maximum emergency temperature °C Allowable duration/operation hours Allowable total duration/annum hours Maximum average duration/annum on total life of cable hours Applied on 20% continuous load Emergence current rating A Maximum emergency temperature °C Allowable duration/operation hours Allowable total duration/annum hours Maximum average duration/annum on total life of cable hours CONSTRUCTION FEATURES 4.0 4.1 Conductor Material Nominal cross-section Shape of conductor Cu or Al mm2 circular 4.2 Overall diameter Waterblocking method Semiconducting binder tape mm Tape/yarn yes Conductor screen Type of material Fully bonded semicon. XLPE 4.3 Nominal thickness mm Minimum thickness mm Nominal overall diameter mm Compound Identification Reference yes Insulation Material Nominal thickness mm Minimum thickness mm Nominal overall diameter mm Section VI – Requirements Environmental Guidelines for Contractors XLPE Page 94 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required 4.4 Maximum continuous operating temperature Compound Identification Reference Maximum stress at nominal voltage At conductor screen kV/mm At insulation screen kV/mm Maximum stress at impulse voltage At conductor screen kV/mm At insulation screen kV/mm oC Offered 90 yes Insulation screen Type of material Nominal thickness mm Nominal overall diameter mm Compound Identification Reference Indelible ink marking on screen Fully bonded semicon. XLPE 4.5 4.6 4.7 yes XLPE Manufacturing Methods Extrusion line type e.g. CCV, MDCV, VCV Single pass, triple extrusion yes Curing method Dry Cooling method Dry Degassing Period days Bedding for moisture absorption Type and material Nominal thickness mm Minimum thickness mm Nominal overall diameter over bedding mm Metallic screen Type and material Nominal thickness mm Minimum thickness mm Wire diameter No. Section VI – Requirements Environmental Guidelines for Contractors Copper wire Page 95 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required 4.8 4.9 4.10 4.11 Nominal diameter over the screen mm Cross sectional area of screen mm2 Short time current density (1 sec) Offered kA/mm2 Bedding/Binder tape Type and material Nominal thickness mm Minimum thickness mm Nominal overall diameter over bedding mm Metallic sheath Type and material Nominal thickness mm Minimum thickness mm Nominal diameter over the sheath mm Cross sectional area of sheath mm2 Short time current density (1 sec.) Lead-alloy 1/2C kA/mm2 Protective anti-corrosion external sheath covering Bitumen undercoat layer Type and material MDPE Color Black Nominal thickness mm Minimum thickness mm Termite resistant Type of anti-termite protection Thermal resistivity yes/no Yes K.m/W Max 6.0 Graphite/or Type of conductive outer layer semicon. polymer 4.12 Nominal overall cable diameter 4.13 Weight of completed cable mm Copper kg/m Insulation kg/m Lead-Alloy kg/m Gross Weight kg/m Section VI – Requirements Environmental Guidelines for Contractors Page 96 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required 5 5.1 Offered LOSSES Maximum dielectric loss per metre / phase when operating at W/m nominal voltage and frequency and at maximum conductor temperature 5.2 Maximum sheath loss per metre / phase when operating at W/m nominal voltage and frequency and at current rating stipulated in Item 1.11. with sheath bonded and earthed as recommended (sectionalizing cross bonding) 5.3 Maximum conductor loss per metre / phase when operating at W/m nominal voltage and frequency and at current rating stipulated in Item 1.11. 5.4 6 Total loss of cable per metre / phase of three phase circuit W/m ELECTRICAL VALUES 6.1 Maximum d.c. resistance of conductor at 20oC 6.2 Maximum a.c. resistance of conductor /m at operating /m temperature 6.3 Equivalent reactance of three phase circuit at 50 Hz /m 6.4 Electrostatic capacitance per conductor of cable at nominal pF/m voltage and operating temperature 6.5 Maximum charging current per conductor at nominal voltage mA/m 6.6 Charging capacity of three phase system (at Uo) VAr/m 6.7 Maximum dielectric loss factor of cable at normal voltage and frequency at a conductor temperature of: 20oC 90oC 6.8 Positive & Negative sequence impedance Section VI – Requirements Environmental Guidelines for Contractors /m Page 97 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required 6.9 6.10 7 Zero sequence impedance (as installed conditions) Resistance /m Reactance /m Capacitance pF/m Surge impedance Number of connections to earth 7.2 Interconnected sheaths at joint positions 8.1 BONDING & EARTHING 7.1 8 Offered Yes/no TESTING As per IEC Routine Tests 60502 8.2 As per IEC Sample Tests 60502 8.3 Type Tests - As per IEC Test Regime 60502 8.4 - Date of Test - Name of independent witness Commissioning Tests - AC voltage withstand test - Oversheath DC voltage test 2Uo for 1 hour kV 10kV max for 15minutes 9 9.1 OTHER INSTALLATION DATA Minimum cable bending radius when laid: Section VI – Requirements Environmental Guidelines for Contractors Page 98 of 677 G. 11kV XLPE INSULATED CABLE SYSTEM (with solid bonding) UNIT DATA Required Direct burial mm In air mm In ducts mm At terminations (with former) mm 9.2 Maximal permissible pulling force of total cable kN 9.3 Maximal side wall bearing pressure to the cable at bending Offered kN/m points 9.4 9.5 Delivery length per drum Normal m Maximum m Maximal weight of full drum with maximum delivery length of kg cable 9.6 Drum dimensions: Flange diameter m Core diameter m Width m Section VI – Requirements Environmental Guidelines for Contractors Page 99 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required Offered 19. 1 2.1 SUBSTATION CONTROL SYSTEM Yes Substation Computer 2.1.1 Manufacturer Yes 2.1.2 Model Yes 2.1.3 Processor 2.1.4 2.1.5 2.1.6 2.1.7 2.1.8 2.1.9 2.1.10 2.1.11 2.1.12 2.1.13 2.1.14 2.1.15 2.1.16 2.1.17 2.1.18 2.1.19 2.1.20 Type Word length Bits Clock speed (minimum) MHz Memory size Supplied (minimum) Mb Supportable/expandable Gb Hard disk size Supplied (minimum) Gb Supportable/expandable Gb Optical Storage Yes Operating system Software supplied Operating temperature range °C Maximum relative humidity % Nominal voltage V ac Operating frequency Hz Starting current A Section VI – Requirements Environmental Guidelines for Contractors Page 100 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 2.1.21 2.1.22 2.1.23 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 2.2.8 2.2.9 2.2.10 2.2.11 2.2.12 2.2.13 2.2.14 2.2.15 2.2.16 2.2.17 2.2.18 2.2.19 2.2.20 Power requirement W Mean time between failure h Mean time to repair h Offered Gateway Manufacturer Yes Model Yes Processor Type Word length Bits Clock speed (minimum) MHz Memory size Supplied (minimum) Mb Supportable/expandable Gb Hard disk size Supplied (minimum) Gb Supportable/expandable Gb Communication Protocols To Control Centre(s) NCC Main IEC 60870-5-101 Yes NCC Alt IEC 60870-5-101 Yes NCC TCP/IP Intranet Yes RCC Main IEC 60870-5-101 Yes RCC Alt IEC 60870-5-101 Yes NCC IEC 60870-5-104 Yes RCC IEC 60870-5-104 Yes Section VI – Requirements Environmental Guidelines for Contractors Page 101 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 2.2.21 2.2.22 2.2.23 2.2.24 2.2.25 2.2.26 2.2.27 2.2.28 2.2.29 2.2.30 2.2.31 2.2.32 2.2.33 2.2.34 2.2.35 2.3.0 2.3.1 2.3.2 2.3.3 2.3.4 2.3.5 2.3.6 2.3.7 Offered Communication Protocols in Substation Yes IEC 61850 List other operating Protocols Data Communications Interface V.35 interface at 64Kb/s Yes X.21 / V.11 interface at 64Kb/s Yes Operating system Operating temperature range °C Maximum relative humidity % Nominal voltage V dc Operating frequency Hz Starting current A Power requirement W Mean time between failure h Mean time to repair h Operator Workstations / HMI Manufacturer Yes Model Yes Literature reference for principle of operation Yes Processor Type Word length Bits Clock speed (minimun) MHz Section VI – Requirements Environmental Guidelines for Contractors Page 102 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 2.3.8 2.3.9 2.3.10 2.3.11 2.3.12 2.3.13 2.3.14 2.3.15 2.3.16 2.3.17 2.3.18 2.3.19 2.3.20 2.3.21 2.3.22 2.3.23 2.3.24 2.3.25 2.3.26 2.3.27 2.3.28 2.3.29 2.3.30 2.3.31 Offered Memory size Supplied (minimum) Mb Supportable/expandable Gb Hard disk size Supplied (minimum) Gb Supportable/expandable Gb Yes Optical Storage Pointer Device Operating system Operator interface screens Operating temperature range °C Maximum relative humidity % Nominal voltage V ac Operating frequency Hz Starting current A Power requirement W Mean time between failure h Mean time to repair h Operator Desk Manufacturer Yes Yes Type of construction Finish and material of working surfaces Method of mounting VDUs Number Section VI – Requirements Environmental Guidelines for Contractors Page 103 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 2.3.32 2.3.33 2.3.34 2.3.35 2.3.36 2.4. 2.4.1 2.4.2 2.4.3 2.4.4 2.4.5 2.4.6 2.4.7 2.4.8 2.4.9 2.4.10 2.4.11 2.4.12 2.4.13 2.4.14 2.4.15 2.4.16 2.5 2.5.1 Offered Operator Chairs Manufacturer Type of construction Type of upholstery Number COLOUR VISUAL DISPLAY UNITS (VDUS) Manufacturer Yes Model Yes Literature reference for principle of operation Yes Screen size across diagonal mm Usable display area mm Resolution (minimum) pixels Dot pitch mm Operating temperature range °C Operating relative humidity range % Nominal voltage V ac Operating frequency Hz Starting current A Power requirement W Approximate lifetime of monitor under continuous use h Mean time between failure h Mean time to repair h Substation Local Area Network (LAN) Architecture and Technology Section VI – Requirements Environmental Guidelines for Contractors Yes Page 104 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 2.5.2 Offered Yes Literature reference for principle of operation Transmission medium (e.g. optical fibre) and physical 2.5.3 2.5.4 2.5.5 2.5.6 2.5.7 2.5.8 2.5.9 specification Protocols IEC 60870-5-101 IEC 60870-5-104 IEC 61850 List all other protocols Data transmission rate(s) Mbps Physical arrangement - Identify all main elements in the 2.5.10 Yes supply including hubs, concentrators, bridges, routers, gateways switches etc. and the number of each 2.5.11 2.5.12 2.5.13 For each element of the LAN indicate the No and type of ports % of spare for each type of port Management software package, functions and facilities, and 2.5.14 2.5.15 2.5.16 2.5.17 2.5.18 2.5.19 2.5.20 2.6 hardware platform % Loading under various system activity scenarios including normal loading for performance testing % high loading for performance testing % system power up % main server fail-over and database resynchronisation Overall availability % INDIVIDUAL ELEMENTS For each element of the LAN equipment provide the following 2.6.1 2.6.2 information Manufacturer Section VI – Requirements Environmental Guidelines for Contractors Page 105 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 2.6.3 2.6.4 2.6.5 Type Nominal voltage Power requirements Range of ambient temp. and max relative humidity for 2.6.6 2.6.7 2.6.8 2.7 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6 2.7.7 2.7.8 2.7.9 2.7.10 2.7.11 2.7.12 2.7.13 2.7.14 2.7.15 2.7.16 Offered continuous reliable operation Mean time between failures Mean time to repair V ac W oC %RH PRINTERS Yes Logging Printer Manufacturer Model Literature reference for principle of operation Number Mounting arrangement Method of printing (e.g. ink jet) Print speed ppm Paper feed mechanism Number of columns (minimum) Operating temperature range °C Maximum relative humidity % Nominal voltage V ac Operating frequency Hz Power requirement W Max noise level at 1 m Section VI – Requirements Environmental Guidelines for Contractors dB(A) Page 106 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 2.7.17 2.7.18 2.7.19 2.7.20 2.7.21 2.7.22 2.7.23 2.7.24 2.7.25 2.7.26 2.7.27 2.7.28 2.7.29 2.7.30 2.7.31 2.7.32 2.7.33 2.7.34 2.7.35 2.7.36 2.7.37 2.7.38 3.0 3.1.0 Mean time between failure h Mean time to repair h Offered COLOUR PRINTERS Manufacturer Yes Model Yes Literature reference for principle of operation Yes Number Mounting arrangement Print speed (minimum) ppm Technology Resolution dpi Paper size Sheet feed paper tray capacity Sheets Internal memory (minimum) Mb Operating temperature range °C Maximum relative humidity % Nominal voltage V ac Operating frequency Hz Power requirement W Max noise level at 1 m dB(A) Mean time between failure h Mean time to repair h BAY CONTROL UNIT HARDWARE 19.1 General Section VI – Requirements Environmental Guidelines for Contractors Yes Page 107 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.1.1 3.1.2 3.1.3 3.1.4 Manufacturer Yes Module designation Yes Literature reference for principle of operation Yes Power supply Power requirements 3.1.5 3.1.6 3.1.7 3.1.8 3.1.9 3.1.10 3.1.11 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6.0 3.2.6.1 3.2.6.2 3.3 3.3.1 3.3.2 3.3.3 V dc Offered 110 W Maximum Number of expansion modules Mean-time to repair for each type of RTU H Mean-time between failure for each type of RTU H Local LCD Display Operating temperature range °C 0 – 50 Operating relative humidity range % 100 BCU ENCLOSURE Manufacturer Module designation Literature reference for enclosure Weight Dimensions Degree of protection Flush Mounted housing Surface mounted housing IEC STANDARDS ( OR EQUIVALENT ) EMC Type tests (Provide Class/Level or Severity rating) EMC Compliance IEC 60255-22-3 Dielectric withstand test IEC 60255-4/-5 Section VI – Requirements Environmental Guidelines for Contractors Page 108 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.3.9 3.3.10 3.3.11 3.3.12 3.3.13 3.3.14 3.4 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 3.4.6.0 3.4.6.1 3.4.6.2 3.4.6.3 3.4.6.4 3.4.6.5 3.4.7.0 Offered High Voltage impulse test IEC 60255-4/-5 Fast transient disturbance test IEC 61000-4-4 Oscillatory transient IEC 61000-4-12 Radiated immunity test IEC 61000-4-6 Electrostatic discharge test IEC 61000-4-2 Emitted interference test IEC 61000-4-3 Mechanical test Compliance Vibration test IEC 60255-21-1 Shock test IEC 60255-21-2 Seismic test IEC 60255-21-3 Temperature rise test IEC 60068-2-2 BCU FUNCTIONS The monitoring functions include: Switching status monitoring (breakers) Indication & alarm status monitoring Analogue measurements (currents, voltages, etc.) Resolution of time tagging ms 1 The control functions include: Close / open of circuit breakers Close / Open of isolators / disconnectors Transformer Automatic tap change control Breaker Voltage Synchronisation Check Control Bay interlocking facilities The reporting functions include: Section VI – Requirements Environmental Guidelines for Contractors Page 109 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.4.7.1 3.4.7.2 Offered Sequence of Events recording Post – Mortem Review / Fault waveform capture Tenderers to state memory capacity and functionality of Sequence of events and fault 3.4.7.3 waveform capture 3.5 3.5.1 3.5.2 3.5.3 3.5.4 3.5.5 3.5.6.0 3.5.6.1 3.5.6.2 3.5.6.3 3.5.6.4 3.5.6.5 3.5.6.6 3.6 3.6.1 3.6.2 3.6.3 3.6.4 3.6.5 3.6.6 19.2 BCU Configuration Number of processors Main processor Secondary processors Communication processor (module) Type of communication between processors Yes LCD Display and selector Buttons on front of BCU Functionality to include Full control of circuit bay Status of bay plant Circuit active line diagram Power system Measurements Display alarms and events PROCESSING UNITS Main CPU Manufacturer Module designation Literature reference for principle of operation Mean - time between failure h Power requirements W Section VI – Requirements Environmental Guidelines for Contractors Page 110 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.6.7 3.6.8 3.6.9 3.6.10.0 3.6.10.1 3.6.10.2 3.6.10.3 3.7.0 3.7.1 3.7.2 3.7.3 3.7.4 3.7.5 3.7.6 3.7.7 3.7.8 3.7.9.0 3.7.9.1 3.7.9.2 3.7.9.3 3.8 3.8.1 3.8.2 3.8.3 Offered Type of processor Word length bit Clock speed MHz Kinds of memory used: Type, size and extension capabilities KByte Type, size and extension capabilities Kbytes Type, size and extension capabilities Kbytes SECONDARY CPU Manufacturer Module designation Literature reference for principle of operation Mean - time between failure h Power requirements W Type of processor Word length bit Clock speed MHz Kinds of memory used: Type, size and extension capabilities Kbytes Type, size and extension capabilities Kbytes Type, size and extension capabilities Kbytes COMMUNICATIONS Manufacturer Yes Module designation Literature reference for principle of operation Section VI – Requirements Environmental Guidelines for Contractors Page 111 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.8.4 3.8.5 3.8.6 3.8.7 3.8.8 3.8.9 3.8.10 3.8.11 3.8.12 3.8.13 3.8.14.0 3.8.14.1 3.8.14.2 3.8.14.3 Offered Number of communications channels Type of processor Word length Clock speed Type and size of memory bit MHz Line interface to communication channel Speed of transmission B/s Number and type of communication ports Meantime between failure h Power requirement W Communication Interfaces IEC60870-5-101 direct to Control Centre(s) IEC60870-5-103 interface to protection IED IEC61850 interface to substation LAN IEC60870-5-101 for remote downloading of BCU 3.8.14.4 3.8.14.5 3.8.15 3.8.16.0 3.8.16.1 3.8.16.2 3.8.16.3 3.9 3.9.1 data List all Protocols available at BCU Local interface for Laptop Computer IED Interface List of manufactures the BCU has interfaced Yes Standard communication protocols available Yes Optional communication protocols available Yes POWER SUPPLY MODULE Module designation Section VI – Requirements Environmental Guidelines for Contractors Page 112 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.9.2 3.9.3 3.9.4 3.9.5 3.9.6 3.9.7 3.9.8 3.9.9 3.10 3.10.1 3.10.2 3.10.3 3.10.4 3.10.5.0 3.10.5.1 3.10.5.2 3.10.5.3 3.10.5.4 3.10.5.5 3.10.6.0 3.10.6.1 3.10.6.2 3.10.7 3.10.8 Offered Literature reference for principle of operation Maximum number of modules per processor Nominal Input voltage VDC Operating voltage range Power requirement W Isolation Meantime between failure h Power requirement W DIGITAL INPUT MODULE Module designation Literature reference for principle of operation Maximum number of modules per processor Input voltage V dc Is contact input type configurable as Status and alarms Sequence of events BCD or parallel inputs Pulse accumulator Or any combination of these Standard number of inputs per module: double position single position Type of input circuit isolation Input galvanic separation Section VI – Requirements Environmental Guidelines for Contractors Page 113 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.10.9 3.10.10 3.10.11 3.10.12 3.10.13 3.10.14 3.10.15 3.11 3.11.1 3.11.2 3.11.3 3.11.4 3.11.5 3.11.6 3.11.7 3.11.8 3.11.9 3.11.10 3.11.11 3.11.12 3.11.13 3.12 3.12.1 3.12.2 Impulse voltage withstand kV Scan time ms Minimal pulse duration ms Input impedance Filter time constant Offered ohm ms Meantime between failure h Power requirement W PULSE COUNTING MODULE Is this facility incorporated into the digital input module? Module designation Literature reference for principle of operation Maximum number of modules per processor Type of counter Maximum count Storage and resetting under control of external clock? Number of inputs per module Input current mA Impulse voltage withstand kV Signal range : pulse widths ms Meantime between failure h Power requirement W COMMAND OUTPUT MODULE Module designation Literature reference for principle of operation Section VI – Requirements Environmental Guidelines for Contractors Page 114 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.12.3 3.12.4.0 3.12.4.1 3.12.4.2 3.12.4.3 3.12.4.4 3.12.5 3.12.6 3.12.7 3.12.8 3.12.9 3.12.10 3.12.11 3.13 3.13.1 3.13.2 3.13.3 3.13.4 3.13.5 3.13.6 3.13.7 3.13.8 3.13.9 3.13.10 Offered Maximum number of modules per processor Contact ratings Switched voltage V Switched power VA max Switched current A Range of duration of command output S Number of two position output channels per module Are outputs activated by select-check-actuate procedure? Are welded contacts checked prior to command output? Are the outputs fused and fuse status monitored? Impulse voltage withstand kV Meantime between failure h Power requirement W DIGITAL OUTPUT MODULE Module designation Literature reference for principle of operation Number of outputs per module Maximum number of modules per processor Maximum output current mA Maximum switched output voltage V Impulse voltage withstand kV Type of protection against back EMF kV Command duration adjustable in the range s Meantime between failure h Section VI – Requirements Environmental Guidelines for Contractors Page 115 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.13.11 3.14 3.14.1 3.14.2 3.14.3 3.14.4 3.14.5 3.14.6 3.14.7 3.14.8 3.14.9 3.14.10 3.14.11 3.14.12 3.15 3.15.1 3.15.2 3.15.3 3.15.4 3.15.5 3.15.6 3.15.7 3.15.8 3.15.9 Power requirement Offered W ANALOGUE TO DIGITAL CONVERSION MODULE Module designation Literature reference for principle of operation Number of inputs per module Maximum number of modules per processor Resolution bits Accuracy % Common mode noise rejection dB Normal mode noise rejection dB Conversion time ms Scanning time (per channel) ms Meantime between failures h Power requirement W ANALOGUE INPUT MODULE Module designation Literature reference for principle of operation Maximum number of modules per processor Scanning resolution Accuracy bits % How are overflow and conversion failures dealt with? Conversion time Input filter attenuation at 50 Hz dB Input signal types (e.g. 4-20 mA) Section VI – Requirements Environmental Guidelines for Contractors Page 116 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.15.10 3.15.11 3.15.12 3.15.13 3.15.14 3.15.15 3.15.16 3.16 3.16.1 3.16.2 3.16.3 3.16.4 3.16.5 3.16.6 3.16.7 3.16.8 3.16.9 3.16.10 3.17.0 3.17.1 3.17.2 3.17.3 3.17.4 3.17.5 Offered Method of isolation Impulse voltage withstand Input impedance kV ohm Type of ADC switching Standard number of inputs per module Mean time between failure h Power requirement W ANALOGUE OUTPUT MODULE Module designation Literature reference for principle of operation Number of outputs per module Maximum number of modules per processor Output voltage range V Output current range mA Type of isolation Load resistance range ohms Maximum error over-current ranges % Impulse voltage withstand kV DIRECT AC CONNECTION VOLTAGE Module designation Literature reference for principle of operation Maximum number of modules processor Number of inputs per module Input voltage ranges Section VI – Requirements Environmental Guidelines for Contractors V ac Page 117 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 3.17.6 3.17.7 3.17.8 3.17.9 3.17.10 3.17.11 3.17.12 3.17.13 3.17.14 3.18.0 3.18.1 3.18.2 3.18.3 3.18.4 3.18.5 3.18.6 3.18.7 3.18.8 3.18.9 3.18.10 3.18.11 3.18.12 3.18.13 3.18.14 Input filter attenuation at 50 Hz dB Burden on instrument transformer circuit VA Conversion time ms Scanning resolution bits Accuracy Offered % What calculations are supported How are overflow and conversion failures dealt with? Method of isolation Impulse voltage withstand kV kV DIRECT AC CONNECTION CURRENT Module designation Literature reference for principle of operation Maximum number of modules processor Number of inputs per module Input current ranges A Input filter attenuation at 50 Hz dB Burden on instrument transformer circuit VA Conversion time ms Scanning resolution bits Accuracy % What calculations are supported How are overflow and conversion failures dealt with? Method of isolation Impulse voltage withstand kV Section VI – Requirements Environmental Guidelines for Contractors kV Page 118 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 4.0 19.34.1.0 4.1.1 4.1.2 4.1.3 4.1.4 4.2 4.2.1 4.2.2 4.2.3 4.2.4 4.2.5 BCU SOFTWARE GENERAL REQUIREMENTS Program structure System software Standard functions programs User functions programs CAPABILITY OF: BCU program downloading from Control Centre Application configuration from Control Centre Remote selection of processing parameters Selection of communication protocols Selection of operation modes (cyclic, polled, etc.) 4.2.6 Appropriate protection of software against power failure 4.2.7 Automatic BCU re-start without software down-loading 4.3 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5 4.4.0 4.4.1 4.4.2 Offered SYSTEM SOFTWARE Operating System (Monitor) Functions and capabilities Calendar program Type, functions and capabilities Time Synchronization Program Functions and capabilities Data Base Updating program Functions and capabilities Testing and Diagnostics Programs Functions and capabilities Yes STANDARD FUNCTIONS PROGRAMS Data Communication Programs: Functions and capabilities Capability of communication protocol selection Section VI – Requirements Environmental Guidelines for Contractors Page 119 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 4.4.3 4.5.0 4.5.1 4.5.2 4.5.3 4.5.4 4.5.5 4.5.6 4.5.7 4.5.8 4.5.9 4.5.10 4.5.11 4.6.0 4.6.1 4.6.2 4.6.3 4.6.4 4.6.5 4.6.6 4.6.7 4.6.8 4.6.9 4.7 Offered Capability of operating modes selection ANALOGUE MEASUREMENTS, SCANNING AND TRANSMISSION PROGRAMS Capabilities of adjustments Transducers constants Periodic transmission/transmission by exception Automatic checking of A/D-conversion accuracy Smoothing Threshold values Limits Scan duration (range) Cycle duration (range) s Priority of transmission s Digital Input Data Scanning and transmission Program FUNCTIONS AND CAPABILITIES Capability of adjustments; Scan duration (range) ms Transient time of status information (range) Cycle duration (range) Debouncing filter ms s Suppression of intermediate status information Time tagging Transmission mode Priority of transmission ALARM AND EVENT HANDLING Section VI – Requirements Environmental Guidelines for Contractors Page 120 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 4.7.1 4.7.2 4.8 4.8.1 4.8.2 4.8.3 4.8.4 4.8.5 4.8.6 4.8.7 4.8.8 4.8.9 4.8.10 4.8.11 4.8.12 4.8.13 4.8.14 4.8.15 4.9 4.9.1 4.9.2 4.9.3 4.9.4 4.9.5 Offered Grouping of alarms and events Maximum number of groups SUPERVISORY CONTROL PROGRAMS: FUNCTIONS AND CAPABILITIES Select before execute Target check Cancelling control after adjustable time delay Capability of adjustments: Duration of output (range) s Allowed duration of execution (range) s Sequence of Events programs Minimal sequence of events time resolution ms Sequence of events memory capacity Events time resolution (adjustable range) Priority of transmission Post - Mortem Review / Program Selection of analogues for post-mortem review Short interval time resolution (adjustable range) s Long interval time resolution (adjustable range) s DATA PROCESSING PROGRAMS: FUNCTIONS AND CAPABILITIES Required minimum data processing: Logic functions Arithmetical functions (MW , Mvar etc ) Limiting functions s Comparative functions Section VI – Requirements Environmental Guidelines for Contractors Page 121 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 4.9.6 5.0 5.1.0 5.1.1 5.1.2 5.1.3 5.1.4 5.2.0 5.2.1 5.2.2 5.2.3 5.2.4 5.2.5 5.2.6 5.2.7 5.0 5.3.1 5.3.2 5.3.3 5.3.4 5.3.5 6.0 19.46.1.0 Offered Time functions GATEWAY SOFTWARE GENERAL REQUIREMENTS DATABASE MANAGEMENT APPLICATION ALARM AND EVENT GROUPING Alarm and Event Separation for NCC and DCC Alarm and Event storage and remote / local access CAPABILITY OF: Gateway program downloading from Control Centre Application configuration from Control Centre Remote selection of processing parameters Selection of communication protocols Selection of operation modes (cyclic, polled, etc.) Appropriate protection of software against power failure Automatic re-start without software down-loading SYSTEM SOFTWARE Operating System (Monitor) Functions and capabilities Calendar program Type, functions and capabilities Time Synchronization Program Functions and capabilities Data Base Updating program Functions and capabilities Testing and Diagnostics Programs Functions and capabilities TRANSDUCERS Current transducer. Section VI – Requirements Environmental Guidelines for Contractors Page 122 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 6.1.1 6.1.2 6.1.3 6.1.4 6.1.5 6.1.6 6.1.7 6.1.8 6.1.9 6.1.10 6.1.11 6.1.12 6.1.13 6.1.14 6.1.15 6.1.16 6.1.17 6.1.18 6.1.19 6.1.20 6.2.0 6.2.1 6.2.2 6.2.3 Offered Manufacturer Type reference Number Principle (e.g. 3 phase, 3 wire, unbalanced) Output range Input ranges available mA A Burden on instrument transformer circuit VA Insulation level kV Impulse withstand level kV peak Minimum accuracy over working range % Response time (0 to 90%) ms Mounting details Operating temperature range °C Operating humidity range % Auxiliary supply if required Voltage range V Power requirements VA Frequency Hz Type of overload protection Permissible continuous input overload %A VOLTAGE TRANSDUCER Manufacturer Type Number Section VI – Requirements Environmental Guidelines for Contractors Page 123 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 6.2.4 6.2.5 6.2.6 6.2.7 6.2.8 6.2.9 6.2.10 6.2.11 6.2.12 6.2.13 6.2.14 6.2.15 6.2.16 6.2.17 6.2.18 6.2.19 6.3.0 6.3.1 6.3.2 6.3.3 6.3.4 6.3.5 6.3.6 6.3.7 Output range Input ranges available mA V Burden on instrument transformer circuit VA Insulation level kV Impulse withstand level Offered kV peak Minimum accuracy over working range % Response time (0 to 90%) ms Mounting details Operating temperature range °C Operating humidity range % Auxiliary supply V range V Power requirements VA Frequency Hz Type of overload protection Permissible continuous input overload %A ACTIVE POWER MW Manufacturer Type reference Number Principle (e.g. 3 phase, 3 wire, unbalanced) Output range mA Input ranges available Voltage Section VI – Requirements Environmental Guidelines for Contractors V Page 124 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 6.3.8 6.3.9 6.3.10 6.3.11 6.3.12 6.3.13 6.3.14 6.3.15 6.3.16 6.3.17 6.3.18 6.3.19 6.3.20 6.3.21 6.3.22 6.3.23 6.3.24 6.3.25 6.3.26 6.4 6.4.1 6.4.2 6.4.3 6.4.4 Current Offered A Burden on instrument transformer circuit Current Transformer (CT) VA Voltage Transformer (VT) VA Insulation level kV Impulse withstand level kV peak Minimum accuracy over working range % Response time (0 to 90%) ms Mounting details Operating temperature range °C Operating humidity range % Auxiliary supply if required Voltage range V Power requirements VA Frequency Hz Type of overload protection Permissible continuous input overload Voltage %V Current %A REACTIVE POWER MVARS Manufacturer Type reference Number Principle (e.g. 3 phase, 3 wire, unbalanced) Section VI – Requirements Environmental Guidelines for Contractors Page 125 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 6.4.5 6.4.6 6.4.7 6.4.8 6.4.9 6.4.10 6.4.11 6.4.12 6.4.13 6.4.14 6.4.15 6.4.16 6.4.17 6.4.18 6.4.19 6.4.20 6.4.21 6.4.22 6.4.23 6.4.24 6.4.25 6.4.26 6.5 6.5.1 Output range Offered mA Input ranges available Voltage V Current A Burden on instrument transformer circuit Current Transformer (CT) VA Voltage Transformer (VT) VA Insulation level kV Impulse withstand level kV peak Minimum accuracy over working range % Response time (0 to 90%) ms Mounting details Operating temperature range °C Operating humidity range % Auxiliary supply Voltage range V Power requirements VA Frequency Hz Type of overload protection Permissible continuous input overload Voltage %V Current %A FREQUENCY Manufacturer Section VI – Requirements Environmental Guidelines for Contractors Page 126 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 6.5.2 6.5.3 6.5.4 6.5.5 6.5.6 6.5.7 6.5.8 6.5.9 6.5.10 6.5.11 6.5.12 6.5.13 6.5.14 6.5.15 6.5.16 6.5.17 6.5.18 6.5.19 6.6 6.6.1 6.6.2 6.6.3 6.6.4 6.6.5 Offered Type Number Measurement range Hz Output range mA Input ranges available V ac Burden on instrument VT circuit VA Insulation level kV Impulse withstand level kV peak Minimum accuracy over working range % Response time (0 to 90%) ms Mounting details Operating temperature range °C Auxiliary supply Voltage range V Power requirements VA Frequency Hz Type of overload protection Permissible continuous input overload %V % POWER FACTOR Manufacturer Type Number Measurement range Output range Section VI – Requirements Environmental Guidelines for Contractors mA Page 127 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 6.6.6 6.6.7 6.6.8 6.6.9 6.6.10 6.6.11 6.6.12 6.6.13 6.6.14 6.6.15 6.6.16 6.6.17 6.6.18 6.6.19 6.7 6.7.1 6.7.2 6.7.3 6.7.4 6.7.5 6.7.6 6.7.7 6.7.8 6.7.9 Input ranges available V ac Burden on instrument VT circuit VA Insulation level kV Impulse withstand level Offered kV peak Minimum accuracy over working range % Response time (0 to 90%) ms Mounting details Operating temperature range °C Auxiliary supply Voltage range V Power requirements VA Frequency Hz Type of overload protection Permissible continuous input overload % COMBINED ACTIVE AND REACTIVE POWER Manufacturer Type Number Measurement range Input ranges available Voltage V ac Current A Burden on instrument transformer circuit Current Transformer (CT) Section VI – Requirements Environmental Guidelines for Contractors VA Page 128 of 677 H. SUBSTATION CONTROL SYSTEM UNIT DATA Required 6.7.10 6.7.11 6.7.12 6.7.13 6.7.14 6.7.15 6.7.16 6.7.17 6.7.18 6.7.19 6.7.20 6.7.21 6.7.22 6.7.23 6.7.24 6.7.25 6.7.26 6.7.27 6.7.28 Voltage Transformer (VT) VA Insulation level kV Impulse withstand level Offered kV peak Minimum accuracy over working range % Response time (0 to 90%) ms Number of analogue outputs Analogue output range mA Calculations available Serial output protocol Mounting details Operating temperature range °C Auxiliary supply Voltage range V Power requirements VA Frequency Hz Type of overload protection Permissible continuous input overload Voltage %V Current %A Section VI – Requirements Environmental Guidelines for Contractors Page 129 of 677 I. DIESEL GENERATOR UNIT DATA Required 1. 1. GENERATOR Details of automatic voltage regulating equipment 1.1 Manufacturer 1.2 Rated power 1.3 Output voltage 1.4 Rated power factor 1.5 Frequency 1.6 Dimensions kVA 500 V 400 Cos Φ 0.8 Hz 50 Diesel Generator mxmxm 1.7 Limits of voltage regulation % 1.8 Manufacturer system in accordance with ISO 9000, 9001, 9002, 9003 and 9004 2 Offered yes ENGINE 2.1 Rating for site conditions 2.2 No and arrangement of cylinders 2.3 Any limitation in part load performance 2.4 Fuel consumption: At rated output At ¾ rated output At ½ rated output l/h 2.5 Lubricating oil consumption at rated output l/h Section VI – Requirements Environmental Guidelines for Contractors kW Page 130 of 677 I. DIESEL GENERATOR UNIT DATA Required 2.6 2.7 2.8 2.9 2.10 2.11 3 Time taken for engine to run up to speed and be ready to receive load Maximum load increment which may be applied with the voltage and frequency maintained within the limits specified Offered sec kVA Estimated running hours between overhauls Top Overhaul Hr Major Overhaul Hr Bulk fuel tank Capacity Dimension l m Daily service fuel tank Capacity Dimension l m Radiator Air flow from radiator Temperature rise of discharge air C Dimension of radiator m m3/s ELECTRICAL EQUIPMENT 3.1 Number of batteries for generating set and type 3.2 Voltage of each battery 3.3 Battery capacity for generating set Section VI – Requirements Environmental Guidelines for Contractors Electrical Starter V A-h Page 131 of 677 I. DIESEL GENERATOR UNIT DATA Required 3.4 Voltage of engine starting system Section VI – Requirements Environmental Guidelines for Contractors Offered V Page 132 of 677 Section VI – Requirements Environmental Guidelines for Contractors Page 133 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required A. LVAC SWITCHGEAR (415/240 V, 50 Hz) 1. GENERAL 1.1. Rated voltage V 415 1.2. Rated frequency Hz 50 2. Offered LVAC SWITCHBOARD 2.1. Manufacturer 2.2. Type designation 2.3. Type of switchboard Metal-clad withdrawable type, multi-tier 2.4. Standards 2.5. Number of years equipment of identical design has been in service 2.6. Rated current of busbars at 50C ambient temperature 2.7. Busbar cross section Section VI – Requirements Environmental Guidelines for Contractors IEC 60439 A mm2 Page 134 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 2.8. Busbar insulation material 2.9. Busbar insulation maximum working temperature 210. Temperature rise on continuous operation at rated current Offered C at 50C 2.11 Rated short-time withstand current (1 s) kA 50 2.12 Rated peak withstand current kA 125 2.13 Test voltage (1 min) V 2500 2.14. Impulse Withstand Voltage 2.15. Type of internal barriers, shutters, etc. 2.16. Degree of protection 2.17. Overall dimensions per cubicle kVp Metallic IP51 Width mm Depth mm Height mm Weight kg Section VI – Requirements Environmental Guidelines for Contractors max 2250 Page 135 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 2.18. 3. Method of circuit breaker withdrawal Offered manual CIRCUIT BREAKER 3.1. Manufacturer 3.2. Type designation 3.3. Type 3.4. Number of poles 3.5. Standard 3.6. Rated current at 50C A 3.7. Rated short-time withstand current (1 s) kA 3.8. Rated peak withstand current kA 3.9. Rated symmetrical breaking current kA 3.10. Rated making current kA Section VI – Requirements Environmental Guidelines for Contractors Air, withdrawable 3 IEC 60947-2 50 Page 136 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 3.11. Breaking time 3.12. Material of: 3.13. 3.14. moving contacts fixed contacts moving contacts fixed contacts Operating mechanism Motor rated power W Motor operating voltage V Weight of draw-out unit 3.16 Protection Module 3.17.1. s Design of: 3.15. 3.17. Offered Type Phase protection functions Neutral protection functions Ground/Earth protection functions kg L,S,I G Type tests Temperature Rise Test Section VI – Requirements Environmental Guidelines for Contractors Page 137 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required Offered Have heating tests at continuous rated normal current been carried out ? 3.17.2. report number date Basic Impulse Voltage Type Test: Has B.I.V test been completed? 3.17.3 circuit breaker report number date Life Test: Has 2000 operating life test at no load (deenergised) been carried out? 4. report number date MOULDED CASE CIRCUIT BREAKERS (MCCBs) 4.1. Manufacturer 4.2. Type designation 4.3. Withdrawable MCCBs type Section VI – Requirements Environmental Guidelines for Contractors yes Page 138 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 4.4. Number of poles 4.5. Standards 4.6. Rated current at 50C A 4.7. Rated short-time withstand current (1 s) kA 4.8. Rated peak withstand current kA 4.9. Rated breaking current kA 4.10. Remote signaling 4.11. Operating mechanism 4.12. Mass 4.13 Protection Module 5. 5.1. Type Phase protection functions Ground (Earth) protection function Offered 3 IEC 60947-2 yes L, I CURRENT TRANSFORMERS Manufacturer Section VI – Requirements Environmental Guidelines for Contractors Page 139 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 5.2. Type 5.3. Type of primary winding (e.g. bar, wound, etc.) 5.4. Standards 5.5. Rated voltage kV 5.6. Rated lightning impulse withstand voltage phase to earth kV 5.7. Rated power frequency withstand voltage phase to earth kV 5.8. Partial discharge test voltage kV 5.9. Rated frequency Hz 5.10. Rated continuous thermal current at 50 oC 5.11. Rated short-time withstand current (1 s) kA 5.12. Rated dynamic current kA 5.13. Line current transformer 5.13.1. Offered IEC 60044-1 50 Type designation Section VI – Requirements Environmental Guidelines for Contractors Page 140 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 5.13.2. Number of cores 5.13.3. Rated extended primary current 5.13.4. Ratio (TR = turns ratio) 5.13.5. I core II core Offered 2 % 120 A 1/750 (TR) A 750/1 Class PX I core II core 1.0 / FS:5 5.13.6. Knee point voltage (EK) I core II core V V 5.13.7. Exciting current (IE) at EK 5.13.8. N/A I core II core A A N/A VA N/A Rated output (burden to be 25-100% rated burden) I core II core VA 5.14. Neutral current transformer 5.14.1. Type designation 5.14.2. Number of cores Section VI – Requirements Environmental Guidelines for Contractors 1 Page 141 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 5.14.3. Rated extended primary current 5.14.4. Ratio (TR = turns ratio) 5.14.5. PX I core I core V I core A Rated output (burden to be 25-100% rated burden) 5.14.9. 1/750 (TR) Exciting current (IE) at EK 5.14.8. A Knee point voltage (EK) 5.14.7. 120 Class 5.14.6. I core % Offered I core Total mass of one current transformer complete VA N/A kg All Class PX CTs shall have a rated secondary current, ISN 6. INSTRUMENTS 6.1. Manufacturer 6.2. Standards 6.3. Type designation 6.4. IEC 60051 Ammeter Voltmeter Total scale range Section VI – Requirements Environmental Guidelines for Contractors Page 142 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required Ammeter Voltmeter 6.5. Dimensions 6.6. Accuracy 6.7. Selector Switches 7.1. Offered mm 96 x 96 1.5 Ammeter Voltmeter Restricted Earth Fault Protection 7.1.1. Manufacturer 7.1.2. Type reference 7.1.3. Relay design (electromechanical, numerical) 7.1.4. Minimum fault setting (% of CT rating) % 7.1.5. Operating time at 5 x setting ms 7.1.7. State principle of operation, i.e. H - high impedance Numerical H L - low impedance 7.1.8. Current transformer requirements: Required knee point voltage, Vk Section VI – Requirements Environmental Guidelines for Contractors Page 143 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required CT maximum winding resistance Magnetising current at Vk Offered V A 7.1.11. 7.2. Tripping contacts rating Undervoltage / Overvoltage Relay 7.2.1. Manufacturer 7.2.2. Type reference 7.2.3. Relay design (electromechanical, static) 7.2.4. Total scale range 7.2.5. Operate time at instantaneous voltage change for undervoltage / overvoltage relay V ms 7.2.6. Reset ratio overvoltage / undervoltage % 8. Manufacturer quality system in accordance with ISO 9000, 9001, 9002, 9003 and 9004 yes 9. Type test certificate to be issued by independent laboratory or independently witnessed type test certificate available yes Section VI – Requirements Environmental Guidelines for Contractors Page 144 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required Section VI – Requirements Environmental Guidelines for Contractors Offered Page 145 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required B D.C. SYSTEMS 1. 110 V D.C SYSTEM - SUBSTATION Offered SERVICES SUPPLY 1.1. 110 V Battery Units 1.1.1 Manufacturer 1.1.2 Type designation 1.1.3 Number of battery units 1.1.4 Type of cell 1.1.5 Operating voltage per cell 1.1.6 Number of cells Section VI – Requirements Environmental Guidelines for Contractors 2 x 50% Nickel-Cadmium V Page 146 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 1.1.7 Standard Offered * IEEE 1115 for calculation * IEC 60623, 60478, 60439 for equipment 1.1.8 Discharge capacity: 10 hour rate Ah min. 250 (to be confirmed by calculation) 1.1.9 1.1.10 1.1.11 1.1.12 5 hour rate Ah 3 hour rate Ah 1 hour rate Ah 30 minute rate Ah Final cell voltage after discharge: 10 hour rate V 5 hour rate V 3 hour rate V 1 hour rate V 30 minute rate V 1.14 Ampere hour efficiency: 10 hour rate % 5 hour rate % 3 hour rate % 1 hour rate % Watt hour efficiency: 10 hour rate % 5 hour rate % 3 hour rate % 1 hour rate % 30 minute rate % Maximum charging voltage per cell V . Section VI – Requirements Environmental Guidelines for Contractors Page 147 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 1.1.13 Normal charging rate range Offered A . 1.1.14 Maximum charging rate range A . 1.1.15 Float charging rate A . 1.1.16 Boost charging rate A . 1.1.17 Normal voltage across battery on float charge V . 1.1.18 Voltage per cell on float charge V . 1.1.19 Normal voltage across battery on boost charge V . 1.1.20 Voltage per cell on boost charge V . 1.1.21 Overall dimensions of one cell mm . 1.1.22 Quantity of electrolyte per cell Litres . 1.1.23. Overall dimensions of each stand 1.1.24. 1 Number of stands 1.1.25. 1 Number of tiers 1.1.26. 1 Material and cross section of connections: between cells between tiers between stands to battery fuse box mm mm2 mm2 mm2 mm2 1.1.27. 1 Method of treating copper connection against corrosion 1.1.28. Method of protecting copper connections against accidental short circuiting 1.1.29. Estimated short circuit current from fully charged A battery Section VI – Requirements Environmental Guidelines for Contractors Page 148 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 1.1.30. Anticipated life of electrolyte under actual operating conditions 1.1.31. Years Anticipated life of electrolyte under actual operating conditions 1.1.32. Offered Years 1 Operating temperatures: Normal operation maximum C minimum C Emergency discharge maximum C minimum C 1.2 110 V D.C Battery Chargers 1.2.1. Manufacturer 1.2.2. Type designation 1.2.3. Degree of protection IP 51 1.2.4. Number of chargers 2 x 100% 1.2.5. Type 1.2.6. Charging characteristic 1.2.7. Input voltage V 3 Phase, 415 1.2.8. Input frequency and range Hz 50 1.2.9. Input power 1.2.10. Minimum working power factor 1.2.11. Rated output power 1.2.12. Output voltage range: Section VI – Requirements Environmental Guidelines for Contractors Thyristor Controlled kVA kW Page 149 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 1.2.13. float charge V boost charge V Offered Continuous output current range: float charge A boost charge A 1.2.14. Accuracy of output voltage % 1.2.15. Overload range % 1.2.16. Voltage ripple % 1.2.17. Ripple frequency Hz 1.2.18. Means of adjusting output 1.2.19. Details of any forced cooling equipment for chargers 1.2.20. Ambient temperature range C 1.2.21. Ambient relative humidity range % 1.2.22. Mean time between failure (MTBF) 1.2.23. Overall dimensions (shall be a separate free- Years mm standing panel/cubicle) 1.2.24. Weight 1.2.25. Boost charge maximum permitted constant potential per cell 1.2.26. % Time to be re-charge to 90% capacity at maximum permitted voltage and current 1.3. V Boost charge maximum permitted current as percentage of 5 hour capacity 1.2.27. kg hrs Battery Fuse Boxes Section VI – Requirements Environmental Guidelines for Contractors Page 150 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 1.3.1. Manufacturer 1.3.2. Type designation 1.3.3. Degree of protection 1.3.4. Fuse rated current at 50oC 1.3.5. Remote signalling 1.4. 110 V D.C. Switchboards 1.4.1. Manufacturer 1.4.2. Type designation 1.4.3. Degree of protection 1.4.4. Standards 1.4.5. Rating voltage V 1.4.6. Rated current of busbars at 50oC ambient A Offered IP 51 yes IP 51 IEC 60439 110 temperature 1.4.7. Busbar cross section 1.4.8. Busbar insulation material 1.4.9. Number of circuits Section VI – Requirements Environmental Guidelines for Contractors mm2 Page 151 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 1.4.10. Main isolator rating A 1.4.11. Main fuse rating A 1.4.12. Single line diagram number 1.4.13. Arrangement drawing number 1.4.14. Details of Contactors: 1.4.15. 1.4.16. Manufacturer Type designation Type Site current rating (at 50°C) A Rated breaking capacity kA Short time current (1 s) kA Maximum operating time opening msec closing msec Voltage / power coil rating Typical circuit diagram number Offered V/W Details of Earth Fault Protection: Manufacturer Type Designation Brochure number Details of Undervoltage / Overvoltage Protection: 1.4.17. Manufacturer Type Designation Brochure number Instruments Manufacturer Voltmeter (type) Ammeter (type) Instruments Section VI – Requirements Environmental Guidelines for Contractors Page 152 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 1.4.18 Offered Details of Moulded Case Circuit Breakers (MCCBs) Manufacturer Type designation Number of poles Standards Rated current at 50C current (1 s) Rated short-time withstand Rated breaking capacity Remote signaling A kA kA Yes 1.4.19 Details of Miniature Circuit Breakers (MCBs) Manufacturer Type designation Number of poles Standards Rated current at 50C current (1s) Rated short-time withstand Breaking capacity at A Remote signalling kA kA Yes Manufacturer quality system in accordance with ISO 9000, 9001, 9002, 9003 and Yes 9004 Section VI – Requirements Environmental Guidelines for Contractors Page 153 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required Type test certificate to be issued by independent Offered Yes laboratory or independently witnessed type test certificate available C. 240 V AC SUPPLY 1. CGENERAL UNINTERRUPTIBLE POWER The uninterruptible power supply (UPS) shall consist but not be limited to the following items: two thyristor controlled 110 V DC / 240 V AC inverters yes two static interrupters and transfer switches yes one 240/240 V single phase isolating by-pass transformer yes two manual by-pass switches one UPS distribution board Section VI – Requirements Environmental Guidelines for Contractors yes yes Page 154 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 2. INVERTER 2.1. Manufacturer 2.2. Type designation 2.3. Degree of protection 2.4. Rated output power Offered IP51 VA min 1200 (to be confirmed by calculation) 2.5. Rated input voltage and range 2.6. Rated input current 2.7. Rated output voltage 2.8. Steady state voltage variation 2.9. Rated output current 2.10. Rated output frequency 2.11. Steady state frequency variation 2.12. Total harmonic distortion 2.13. Rated output power factor 2.14. Maximum harmonic distortion: at any single frequency at all frequencies 2.15. Radio frequency interference (RFI) classification 2.16. Output voltage rise time on turn-on 2.17. Output voltage decay time on turn-off 2.18. Maximum transient voltage variation after full V% A V % A Hz % % % % ms ms load acceptance or rejection for: 1 cycle % 0.1 s % 1s % Section VI – Requirements Environmental Guidelines for Contractors Page 155 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 2.19. Method of cooling 2.20. Ambient temperature range C 2.21. Maximum temperature rise (inside) C 2.22. Ambient relative humidity % 2.23. Method of protecting inverters against high Offered intensity D.C voltage surges 2.24. Mean time between failure (MTBF) 2.25. Dimensions 2.26. Weight 3. STATIC SWITCH Years mm kg Bidder shall fulfil the detailed description of offered static switch possibility with data and diagram 4. ISOLATION BY-PASS TRANSFORMER Section VI – Requirements Environmental Guidelines for Contractors Page 156 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 4.1. Manufacturer 4.2. Standard applied 4.3. Type designation 4.4. Maximum continuous capacity 4.5. Number of phase 1 4.6. Rated voltage under full load V 4.7. Protection class IP 4.8. Dimensions overall 4.9. Total weight 5. MANUAL BY-PASS SWITCH 5.1. Manufacturer Section VI – Requirements Environmental Guidelines for Contractors Offered VA mm kg Page 157 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required 5.2. Type of designation 5.3. Rated current at 50°C 6. DISTRIBUTION BOARD 6.1. Manufacturer 6.2. Type designation 6.3. Degree of protection 6.4. Busbar insulation material 6.5. Number of circuits 6.6. Details of Miniature Circuit Breakers (MCBs) Manufacturer Type designation Number of poles Section VI – Requirements Environmental Guidelines for Contractors Offered A IP 51 Page 158 of 677 J. LV SERVICES EQUIPMENT UNIT DATA Required Standards Rated current at 50oC A Rated breaking capacity kA Remote signalling Offered Manufacturer quality system in accordance with ISO 9000, 9001, 9002, 9003 and 9004 yes Type test certificate to be issued by independent laboratory or independently witnessed type test certificate available Section VI – Requirements Environmental Guidelines for Contractors yes Page 159 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required 19.5 1. Offered Power Transformer Manufacturer & Place of manufacturing Type designation Type Yes Three phase Autotransformer, oil-immersed, core type with stabilising tertiary winding Standards Altitude (If > 1000 m) IEC 60076, 60137, 60214 m Ambient temperature (Zone 1 – within IEC reference values, e.g. inland at altitude) - Maximum Average of hottest month Annual average oC 40 oC 30 oC 20 oC 45 oC 35 oC 30 Ambient temperature (Zone 2 – within IEC reference values, e.g. Coastal with high annual average) - Maximum Average of hottest month Annual average Section VI – Requirements Environmental Guidelines for Contractors Page 160 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Mounting Offered Outdoor Rated voltage ratio (HV/LV) kV 400/220 Rated frequency Hz 50 Vector group YNa0(d) Cooling – 2-stage ONAN/ONAF1/ONA F2 or ONAN/ONAF/OFAF Function of tertiary winding (TV) Aux. supply Method of earthing - HV (Series) winding Solid - LV (Common) winding Solid - TV winding Grounded at one point Type of windings (graded/non-graded) - HV winding (Series) Graded - LV winding (Common) Graded - TV winding Non-graded Rated voltage of windings (Ur) - HV winding Section VI – Requirements Environmental Guidelines for Contractors kV 400 Page 161 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required LV winding TV winding Note*: approximate; to manufacturer’s preference kV 220 kV 11* Offered Highest voltage for equipment (Um) - HV winding kV 420 - LV winding kV 245 - TV winding kV 12* Rated lightning impulse withstand voltage at: - HV terminal kV 1425 - LV terminal kV 1050 - Neutral terminal kV 170 - TV winding ≥75 Rated switching impulse voltage - HV terminals LV terminals kV 1050 kV 850 kV 630 kV 416 kV 365 Rated power frequency withstand voltage at - HV terminal (design value only) HV test value (IVPD enhancement level) HV test value (IVPD PD measurement)) - LV terminal (Design value) kV 460 - Neutral terminal kV 70 - TV terminal kV ≥28 Section VI – Requirements Environmental Guidelines for Contractors Page 162 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Rated power at site conditions (ONAF2 or OFAF) MVA 200 Rated power at site conditions (ONAN) MVA 120 Rated power of tertiary at site conditions (Full cooling) MVA 5 Windings K 65 Hot spot of windings K 78 - Top oil K 60 - Oil at inlet of cooler K - Oil at outlet of cooler K - Core K Offered Maximum temperature rise at rated power at (IEC shown, Zone 1)): - Maximum temperature rise at rated power at (,Zone 2): - Windings Hot spot of windings Top oil - Oil at inlet of cooler Oil at outlet of cooler Core K 55 K 68 K 50 K K K Temperature of winding due to short circuit duration of 2 s at rated load - HV side short circuit rating of 50kA Section VI – Requirements Environmental Guidelines for Contractors oC 250 Page 163 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required - LV side short circuit rating of 40 kA No-load losses at rated voltage and rated frequency oC Offered 250 kW Load losses at 75C, and rated frequency: - ONAF2 or OFAF rated power and principal tapping - ONAF2 or OFAF rated power and maximum voltage ratio - ONAF2 or OFAF rated power and minimum voltage ratio - At ONAN rated power and principal tapping Total auxiliary losses at full load kW Maximum current density at rated power: - HV (Series) winding A/mm2 - LV (Common) winding A/mm2 - TV winding A/mm2 - Tapping A/mm2 Symmetrical short circuit through current (duration 2 s) at system fault rating - HV terminals (50 kA) kA - LV terminals (40 kA) kA Magnetising current (HV winding) - At 90% rated voltage A - At 100% rated voltage A - At 110% rated voltage A Section VI – Requirements Environmental Guidelines for Contractors Page 164 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Offered Maximum flux density in iron at rated voltage, power frequency and principal tapping at: - Wound limbs T - Unwound limbs T - Yokes T - Shields T Maximum flux density in iron at power frequency, principal tapping and 105% rated voltage at: - Wound limbs T - Unwound limbs T - Yokes T - Shields T Type of tap changing On-load Manufacturer of on-load tap changer Type designation of on-load tap changer OLTC location (Provisional) LV line end Type of flux voltage variation C.F.V.V Tapping range (Provisional) +5%/-15% Section VI – Requirements Environmental Guidelines for Contractors Page 165 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Tapping step 1.25% Number of steps (positions) 16 (17) Arrangement Reversing) of tappings (Linear, Offered Coarse/Fine, Automatic voltage control Yes Impedance voltage range at 75C, rated frequency and full rating (Provisional): - At principal tapping > 14% - At maximum voltage ratio >14% - At minimum voltage ratio >14% Resistance of winding at 75C and principal tapping: - HV side /phase - LV side /phase Terminal connection - HV terminal Outdoor bushing - LV terminal Outdoor bushing - Neutral terminal Outdoor bushing - TV terminal Outdoor bushing Section VI – Requirements Environmental Guidelines for Contractors Page 166 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Offered Bushing Creepage Distance (IEC class IV = 31mm/kV - HV terminal (420 kV) LV terminal (kV) Neutral terminal (36 kV) TV terminal (12 kV) mm 13020 mm 7595 mm ≥900 mm 300 Cable box insulation N/A - HV terminal “ - LV terminal “ - HV neutral terminal “ - LV neutral terminal “ Isolating links for test purposes N/A - HV terminal “ - LV terminal “ - Tertiary earthing terminal “ Current transformers Refer to Tender Drawings HV-Bushing turrets - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) I core A II core A III core A Section VI – Requirements Environmental Guidelines for Contractors Page 167 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required - - - - Offered Class I core II core III core Knee point voltage (Ek) I core V II core V III core V Exciting current (IE ) at Ek I core mA II core mA III core mA Rated output (Burden to be 25-100% rated burden) I core VA II core VA III core VA LV Line (Only AIS connections) - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - Class - Knee point voltage (Ek) - Exciting current (IE ) at Ek - Rated output (Burden to be 25-100% rated burden) Section VI – Requirements Environmental Guidelines for Contractors Page 168 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Offered Neutral (HV REF) - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - I core V Exciting current (IE ) at Ek - I core Knee point voltage (Ek) - A Class - I core I core mA Rated output (Burden to be 25-100% rated burden) I core VA Neutral – ends - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - I core V Exciting current (IE ) at Ek - I core Knee point voltage (Ek) - A Class - I core I core mA Rated output (Burden to be 25-100% rated burden) Section VI – Requirements Environmental Guidelines for Contractors Page 169 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required I core All class PX CTs shall have a rated secondary current, Offered VA A ISN Number of coolers per transformer Number of stand-by coolers Number of stand-by fans Rating of each cooler kW Oil - Manufacturer - Type designation - Standards - Minimum flash point - Viscosity IEC 60296 C at 20C mm2/s at 50C mm2/s at 80C mm2/s - Maximum dielectric strength for 1 min. - Dielectric factor - Acidity (neutralization value) Section VI – Requirements Environmental Guidelines for Contractors kV mgKOH/ g Page 170 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Oil preservation system Offered Air-bag Types and arrangement of winding: - HV (Series) winding - LV (Common) winding - TV winding - Regulating - Windings arrangement (i.e. core/TV/LV/HV/Taps) Conductor Material (e.g., copper, work hardened copper, etc.) - HV (Series) windings - LV (Common)windings - TV windings - Regulating windings Conductor insulation: - HV (Series) windings - LV (Common) windings TV windings - Regulating windings - Connecting leads from winding to tap changer Calculated thermal time constant - ONAN cooling min - Full cooling min Section VI – Requirements Environmental Guidelines for Contractors Page 171 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Offered Oil circulation (i.e., natural/partially directed/directed) To the windings: - HV windings (Series) - LV windings (Common) - Regulating windings - TV windings Through the windings: - HV windings (Series) - LV windings (Common) - Regulating windings - TV windings Core construction: - Taped/banded/bolted limbs - Taped/banded/bolted yokes - Taping/banding material - Number of limbs - Number of limbs wound - Type of joint in magnetic core (90% butt, overlap, mitre, etc.) - Type of core steel - Specific loss of core steel at 1.5 tesla W/kg Thickness of transformer tank - Sides Section VI – Requirements Environmental Guidelines for Contractors mm Page 172 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required - Bottom mm - Top mm Offered Material of transformer tank Thickness of radiator plates mm Total volume of conservator Litre Minimum volume of conservator between highest and lowest levels as percentage of total cold oil at 15C volume of transformer Volumetric expansion of oil from 0 to 90C 7.5% m3 Pressure increase inside tank due to expansion of oil Masses of transformer - Core and coils kg - Total mass excluded oil kg - Oil mass - in tank kg in radiators kg total kg Total mass Mass of transformer as arranged for transport (heaviest part) Section VI – Requirements Environmental Guidelines for Contractors kg kg Page 173 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required Offered Dimensions of transformer arranged for transport - Height m - Width m - Length m Filling medium of transformer tank for shipment Maximum sound pressure level (NEMA TR1 – 5dB(A)) dB(A) Conservator vessel, radiators, fan grilles, control boxes or cubicles and pipework anticorrosion protection 74 Hot dip galvanized and painted Tank anticorrosion protection Supply voltage for transformer auxiliaries V 415/240 AC Control/Protection voltage V 110 DC Manufacturer quality assurance - According to ISO 9000, 9001, 9002, 9003 and 9004 Yes Validity Type test certificate to be issued by: - 1.78 Independent laboratory or independently witnessed type test certificate Yes Special Tests to be performed: As Type test = T As Routine test = R Section VI – Requirements Environmental Guidelines for Contractors Page 174 of 677 K. 400/220kV POWER TRANSFORMERS (AIS-AIS) UNIT DATA Required - Measurement of zero-sequence impedance Determination of sound levels Measurement of harmonics of no-load current Frequency response analysis (FRA) Check of external coating Short circuit withstand test/calculations Offered Yes (T) Yes (T) Yes (T) Yes (R) Yes R) Yes (Calculation) 19.6 Section VI – Requirements Environmental Guidelines for Contractors Page 175 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required 19.7 1. Offered Shunt Reactor 1.1 Manufacturer & Place of manufacturing 1.2 Type designation 1.3 Type 1.4 Construction (Gapped core/Air-cored shielded) 1.5 Principal standards 1.6 Max ambient (Design) temperature oC 40 Annual average temperature oC 30 1.7 Altitude m <1000 1.8 Rated voltage kV 400 1.9 Highest voltage for equipment, Um; Reactor must be able to operate continuously at this voltage. kV 420 1.10 Rated frequency Hz 50 Section VI – Requirements Environmental Guidelines for Contractors Outdoor, Oil Immersed IEC 60076-1,-2,-3, 6 Page 176 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required 1.11 Vector group 1.12 Cooling 1.13 Method of earthing 1.14 Type (graded/non-graded) of windings 1.15 Rated lightning impulse withstand voltage at: ONAN Solid Graded HV terminals kV 1425 - HV neutral-end terminals kV 125 kV 1050 Rated switching impulse voltage 1.17 Rated power frequency withstand voltage at 1.18 YN - 1.16 Offered - HV terminals (IVPD enhancement) kV 416 - HV neutral-end terminals kV 50 A 144 A 152 MVAr 100 /phase 1600 Rated power: - Rated current IN Max continuous current at Um - Rated (reactive) power at Ur - Rated reactance XN - Zero sequence reactance X0 - Mutual reactance XM Section VI – Requirements Environmental Guidelines for Contractors /phase Page 177 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required 1.19 Magnetic characteristic: Linear to percent of rated voltage 1.20 Maximum temperature rise at rated power at: % 105 - Windings K 55 - Hot spot of windings K 68 - Top oil K 50 - Oil at inlet of cooler K - Oil at outlet of cooler K - Core Tank Wall K Offered K 1.21 Losses at rated voltage and rated frequency 1.22 Maximum current density at rated power: - 1.23 HV winding kW A/mm2 Maximum flux density at rated voltage, power frequency: - Wound limbs/core packets T - Yokes Shield T T 1.24 Resistance of winding at 75C and principal tapping: Section VI – Requirements Environmental Guidelines for Contractors /phase Page 178 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required 1.25 Offered Terminal connection - Bushing standards Pollution Class Is KD Correction factor required? IEC 60137 (mm/kV) IV (31) Yes - HV terminals Minimum Voltage Class Minimum Current rating Manufacturer Manufacturers designation Type (OIP/RIP) - HV neutral-end terminals Minimum Voltage Class Minimum Current rating Manufacturer Manufacturers designation Type (OIP/RIP/Porcelain) Outdoor Bushing kV 420 A 400 Bushing kV 24 A 400 Porcelain 1.26 Current transformers 1.26a HV-Bushing turrets (provisional – refer to protection drawings) - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - 2 I core A 800/400/1 II core A 800/400/1 Class I core 5P20 II core 5P20 Section VI – Requirements Environmental Guidelines for Contractors Page 179 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required - - - 1.26b Knee point voltage (Ek) I core V II core V Exciting current (IE ) at Ek I core mA II core mA Rated output (Burden to be 25-100% rated burden) I core VA II core VA HV Neutral-End provisional – refer to protection drawings) - Number of cores/phase - Rated extended primary current - Ratio (TR = turns ratio) - - 5P20 I core I core V Exciting current (IE ) at Ek - 800/400/1 I core Knee point voltage (Ek) - 1 Class I core mA Rated output (Burden to be 25-100% rated burden) 1.26b Offered I core VA HV Neutral Section VI – Requirements Environmental Guidelines for Contractors Page 180 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - I core I core I core All class PX CTs shall have a rated secondary current, ISN mA VA A Radiators - 1.28 V Rated output (Burden to be 25-100% rated burden) 1.27 5P20 I core Exciting current (IE ) at Ek - 800/400/1 I core Knee point voltage (Ek) - 1 Class - Offered Tank or Separate Mounting Number banks Number of radiators elements per bank Oil - Manufacturer - Type designation - Standards - Minimum flash point Section VI – Requirements Environmental Guidelines for Contractors IEC 60296 C Page 181 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required - 1.29 Offered Viscosity at 20C mm2/s at 50C mm2/s at 80C mm2/s - Maximum dielectric strength for 1 min. - Dielectric factor - Acidity (neutralization value) kV mgKOH/ g Oil preservation system - Type (Bag/Membrane) Breather Oil Level Gauge Maintenance-free Magnetic 1.30 Types and arrangement of winding: 1.31 Conductor Material (e.g., copper, work hardened copper, etc.) 1.32 Conductor type (CTC, other) 1.33 Conductor insulation: 1.34 Calculated thermal time constant 1.35 Oil circulation (i.e., natural/partially directed/directed) Hours To the windings: Section VI – Requirements Environmental Guidelines for Contractors Page 182 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required Offered Through the windings: 1.36 1.37 Core construction: - Core segment - Core gaps - Taped/banded/bolted limbs - Taped/banded/bolted yokes Taped/banded/bolted shield - Taping/banding material - Number of limbs - Type of joint in core (90% butt, overlap, mitre, etc.) - Core steel - Specific loss of core steel at 1.5 Tesla W/kg Thickness of reactor tank - Sides mm - Bottom mm - Top mm 1.38 Material of reactor tank 1.39 Thickness of radiator plates mm 1.40 Total volume of conservator litres Section VI – Requirements Environmental Guidelines for Contractors Page 183 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required 1.41 Minimum volume of conservator between highest and lowest levels as percentage of total cold oil at 15C volume of transformer 1.42 Volumetric expansion of oil from 0 to 90C 1.43 Pressure increase inside tank due to expansion of oil 1.44 Masses of reactor 7.5% m3 - Core and coils kg - Total mass excluded oil kg - Oil mass - in tank kg in radiators kg total kg Total mass 1.45 Mass of reactor as arranged for transport (heaviest part) 1.46 Dimensions of reactor arranged for transport kg kg - Height m - Width m - Length m 1.47 Filling medium of reactor tank for shipment 1.48 Maximum noise level Section VI – Requirements Environmental Guidelines for Contractors Offered dB(A) 86 Page 184 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required Offered 1.49 Conservator vessel, radiators, control boxes or cubicles and pipework anticorrosion protection 1.50 Tank anticorrosion protection 1.51 Supply voltage for reactor auxiliaries V 415/240 AC 1.52 Control/Protection voltage V 110 DC 1.53 Manufacturer quality assurance - 1.54 Yes According to ISO 9000, 9001, 9002, 9003 and 9004; List current accreditation Type test certificate to be issued by: - 1.55 Hot dip galvanized and painted Yes Independent laboratory or independently witnessed type test certificate Routine tests The IVPD test IEC 60076-3:2013 based on Ur - 1 x 3-phase test Enhanced level 1 hour duration Max PD level during 1 hour stage To IEC 60076-6 kV Yes kV Yes kV 416 kV 365 pC 250 Note 2: The method of carrying out loss measurements and any limitations of manufacturer’s test field which restricts the test programme are to be advised with bid documents. 1.56 Special Tests to be performed: (R=Routine/All units: T=Type/1 unit)) Section VI – Requirements Environmental Guidelines for Contractors Page 185 of 677 L. 400 kV 100 MVAr SHUNT REACTOR UNIT DATA Required - Offered Yes(T) Measurement of zero-sequence reactance Measurement of mutual reactance Determination of sound levels Measurement of harmonics Verification of magnetic characteristic Yes(T) Yes(R) Yes(R) Yes (T) M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required Offered 19.8 1. EARTHING/AUXILIARY TRANSFORMER 11/0.415KV; WITH 500 KVA AUXILIARY WINDING Section VI – Requirements Environmental Guidelines for Contractors Page 186 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required Offered Manufacturer & Place1.of manufacturing 1.1 Type designation Type Three phase, oil immersed, core type Standards IEC 60076-1, -2, -3, -5, -6,-10, NEMA TR1 (Noise) Mounting Outdoor, wheel Rated voltage ratio kV 11/0.415 Rated frequency Hz 50 Vector group ZNyn1 Cooling ONAN Method of earthing - HV winding Solid - LV winding Solid Type (graded/non-graded) of windings - HV winding Section VI – Requirements Environmental Guidelines for Contractors Non-graded Page 187 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required - Offered Non-graded LV auxiliary winding Rated voltage of windings - HV winding kV 11 - LV auxiliary winding kV 0.415 Highest voltage for equipment - HV winding kV 12 - LV auxiliary winding kV 0.433 kV 75 Rated lightning impulse withstand voltage at HV Terminal Rated power frequency withstand voltage at - HV terminal kV 28 - LV terminal kV 3 - HV neutral terminal kV 28 kVA 500 A 1050 Rated power at site conditions Limitation and withstanding of fault current in neutral for 30s Maximum temperature rise at rated power at: Section VI – Requirements Environmental Guidelines for Contractors Page 188 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required - Windings K 55 - Hot spot of windings K 68 - Top oil K 50 - Oil at inlet of cooler K - Oil at outlet of cooler K - Core K Offered Temperature rise of winding due to short circuit duration of 2 s and HV side short circuit current of 25 kA - Copper windings Aluminium windings No load losses at rated voltage and rated frequency oC 250 oC 200 kW Load losses at 75C, and rated frequency, rated power and principal tapping: Maximum current density at rated power: - HV winding A/mm2 - LV auxiliary winding A/mm2 Symmetrical short circuit withstand current (duration 2 s) at: - HV terminal kA - LV auxiliary terminal kA 25 Magnetising current (HV winding) - At 90% rated voltage Section VI – Requirements Environmental Guidelines for Contractors A Page 189 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required - At 100% rated voltage A - At 110% rated voltage A Maximum flux density in core at rated voltage, power frequency and principal tapping Type of tap changing Offered T Off-load Type designation of off-load tap changer Tapped winding Tapping range HV +5% -5% Tapping step 2.5% Number of steps (positions) 4 (5) Impedance voltage range at 75C and principal tapping: - At principal tapping > 4% - At maximum voltage ratio >4% - At minimum voltage ratio >4% Section VI – Requirements Environmental Guidelines for Contractors Page 190 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required Offered Resistance of winding at 75C and principal tapping: - HV side /phase - LV auxiliary side /phase Zero phase sequence impedance of inter-star windings at 75C (LV windings open-circuit) /phase Zero phase sequence impedance of LV windings at 75C (inter-star windings open-circuit) /phase Terminal connection HV + HVN terminal Note*: Separable connector, e.g. Euromold or similar - Air-filled cable box* LV + LVN terminal Air-filled cable box Isolating link for test purposes (not required if separable connector allows testing) - HV terminal No - LV terminal No LV fused switch incorporated in LV terminal box Section VI – Requirements Environmental Guidelines for Contractors A Yes Page 191 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required Offered Mounting of current transformer at - HV terminal - Neutral terminals In tank In tank or box Current transformers Refer to Tender Drawings HV Line - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - - - - I core II core A Class I core II core Knee point voltage (Ek) I core V II core V Exciting current (IE ) at Ek I core mA II core mA Rated output (Burden to be 25-100% rated burden) I core VA II core VA HV Neutral Section VI – Requirements Environmental Guidelines for Contractors Page 192 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - - - - I core II core III core Offered A Class I core II core III core Knee point voltage (Ek) I core II core III core Exciting current (IE ) at Ek I core II core III core Rated output (Burden to be 25-100% rated burden) I core II core III core LV Line (Only AIS connections) - Number of cores - Rated extended primary current Section VI – Requirements Environmental Guidelines for Contractors Page 193 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required - Ratio (TR = turns ratio) - I core Exciting current (IE ) at Ek - I core Knee point voltage (Ek) - I core Class - Offered I core Rated output (Burden to be 25-100% rated burden) I core LV Neutral - Number of cores - Rated extended primary current - Ratio (TR = turns ratio) - Class - I core Exciting current (IE ) at Ek - I core Knee point voltage (Ek) - I core I core Rated output (Burden to be 25-100% rated burden) I core All class PX CTs shall have a rated secondary current, I SN Section VI – Requirements Environmental Guidelines for Contractors Page 194 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required Offered Oil: Manufacturer Type designation Standards Minimum flash point Viscosity IEC 60296 oC At 20oC mm2/s At 50oC mm2/s At 80oC mm2/s Maximum dielectric strength for 1 min Dielectric factor Acidity (neutralization value) kV mgKOH/g Type of dehydrating breather (Non-sealed transformers) Silicagel Conductor material (e.g. copper, work hardened copper, etc.): HV windings LV windings Conductor insulation: HV winding LV winding Calculated thermal time constant Section VI – Requirements Environmental Guidelines for Contractors min Page 195 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required Offered Thickness of transformer tank - Sides mm - Bottom mm - Top mm Material of transformer tank Thickness of radiator plates mm Total volume of conservator litres Masses of transformer - Core and coils kg - Total mass excluded oil kg - Oil mass in tank in radiators - kg kg total kg Total mass kg Mass of transformer as arranged for transport (heaviest part) kg Dimensions of transformer arranged for transport - Height m - Width m - Length m Section VI – Requirements Environmental Guidelines for Contractors Page 196 of 677 M. 11/0.415kV; 500kVA EARTHING/AUXILIARY TRANSFORMERS (CAF-CAF) UNIT DATA Required Maximum noise level (to NEMA TR1) dB Conservator vessel, radiators, fan grilles, control boxes or cubicles and pipework anticorrosion protection Offered 56 Hot dip galvanized and painted Tank anticorrosion protection Control/Protection voltage Manufacturer quality assurance - V 110 DC Yes According to ISO 9000, 9001, 9002, 9003 and 9004 Type test certificates to be issued by: - 1.59 Independent Laboratory or independently witnessed type test certificate Yes Special Tests to be performed: - Measurement of zero-sequence impedance Determination of sound levels Measurement of harmonics of no-load current Vibration test Yes No No No Section VI – Requirements Environmental Guidelines for Contractors Page 197 of 677 N. NEUTRAL EARTHING RESISTOR/ REACTOR UNIT DATA Required 1.1. Manufacturer 1.2. Type 1.3. Standards 1.4. Rated voltage kV 11 1.5. Rated fault current A Refer to drawings 1.6. Continuous current A 1.7 Maximum operating time 1.8 Resistor material resistance cold 1.9 Temperature rise at rated voltage after 10 sec 1.10 Protection class 1.11 Installation: indoor/ outdoor Section VI – Requirements Environmental Guidelines for Contractors Offered IEEE 32, IEC61000-6-3 sec 10 Ohm Deg C 1000 Page 198 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATA Required 1 1.1 LINE CONDUCTOR FITTINGS ACSR Complete line conductor: mm2 990 Number of conductors per phase No 4 Distance between conductor centres of one phase mm 400 1.1.1 Nominal area per phase 1.1.2 1.1.3 1.2 Each single conductor: 1.2.1 Code name 1.2.2 International Standard 1.2.3 National standard 1.2.4 Material of conductor 1.2.5 Number and diameter of wires 1.2.6 Total area of conductor mm2 Aluminium/ Galvanised Steel Al 30/2.92 St 7/2.92 247.8 1.2.7 Overall diameter of stranded conductor mm 20.44 1.2.8 Resistance of conductor (dc) at 20˚C ohm/km 0.1441 1.2.9 Mass of conductor (without grease) kg/km 925 1.2.10 Total mass of greased conductor (greased to Case 2 of IEC 61089) kg/km 1.2.11 Ultimate rated strength of conductor Newton 90,250 1.2.12 Maximum tension of conductor in still air at “everyday” temperature Newton 18,050 1.2.13 Assumed equivalent modulus of elasticity of conductor N/mm2 80,420 1.2.14 Assumed equivalent coefficient of linear expansion of conductor per ˚C 1.78 x 10-5 1.2.15 Maximum length of conductor on drum km 5 120 1.3 Offered Lark IEC 61089 ASTM B 232 No/mm CONDUCTOR GREASE: 1.3.1 Type 1.3.2 Minimum drop-point temperature ˚C Mass of grease per kilometre of conductor (all inner layers greased – Case 2 to IEC 61089) kg Section VI – Requirements Environmental Guidelines for Contractors Page 199 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATA Required 1.4 1.4.1 Type of system (vibration damper + spacer or spacer damper) 1.4.2 Vibration damper (if proposed) type 1.4.2.1 Type of vibration damper 1.4.2.2 National / International standard 1.4.2.3 Number of wires in messenger cable No 19 1.4.2.4 Conductor diameter range mm 20.44 1.4.2.5 Mass of damper 1.4.2.6 Maximum span for: 1.4.2.7 1.4.3 Offered VIBRATION DAMPING SYSTEM: type Stockbridge IEC 61897 kg a. One vibration damper at each end of span m b. Two vibration dampers at each end of span m c. Three vibration dampers at each end of span m Dimensions from clamp mouth to vibration damper attachment: a. First damper mm b. Second damper when required mm c. Third damper when required mm Spacer or spacer damper 1.4.3.1 Type of spacer or spacer damper 1.4.3.2 National / International standard 1.4.3.3 Conductor diameter range 1.4.3.4 Mass 1.4.3.5 Symmetrical / asymmetrical in-span spacing 1.4.3.6 Maximum sub-span length IEC 61854 mm 20.44 kg m NO’S 2 TO 3 NOT USED Section VI – Requirements Environmental Guidelines for Contractors Page 200 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark 4. 4.1 4.1.1 4.2 UNIT DATA Required Aluminium Clad Steel GW EARTH CONDUCTOR AND FITTINGS Complete earth conductor system Number of ACS earth conductors No 1 Each single earth conductor 4.2.1 International Standard No 4.2.2 Material of conductor 4.2.3 Number and diameter of wires 4.2.4 ASTM B416 Aluminium-clad steel No/mm 7/3.26 Total area of conductor mm2 58.6 4.2.5 Overall diameter of conductor mm 9.78 4.2.6 Mass of conductor kg/km 390 4.2.7 Ultimate strength of conductor Newton 71,000 4.2.8 Maximum tension of conductor in still air at “everyday” temperature Newton 4.2.9 Assumed equivalent modulus of elasticity of conductor N/mm2 162,000 4.2.10 Assumed equivalent coefficient of linear expansion of conductor per C 12.96 x 10-6 4.2.11 Minimum bending radius mm 4.2.12 Minimum length of conductor on drum km 4.3 4.3.1 4.4.1 4 Individual wires before stranding Aluminium-clad steel a. 4.4 Offered ASTM B415 Grade of steel 20SA Vibration damping system Maximum span for: a. One vibration damper at each end of span m b. Two vibration dampers at each end of span m c. Three vibration dampers at each end of span m OPGW EARTH CONDUCTOR AND FITTINGS 5 5.1 EARTH CONDUCTOR AND FITTINGS OPGW Complete optical earth conductor system Section VI – Requirements Environmental Guidelines for Contractors Page 201 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark 5.1.1 5.2 Number of OPGW earth conductors UNIT No DATA Required 1 Each single optical earth conductor (OPGW) 5.2.1 International Standard No 5.2.2 Material of conductor 5.2.3 Number and diameter of wires 5.2.4 Total area of conductor mm2 5.2.5 Overall diameter of conductor mm 5.2.6 Mass of conductor IEE 1138 IEC 60794-4-1 Aluminium Alloy/ Aluminium-clad steel 5.2.7 5.2.8 No/mm kg/km <850 Ultimate strength of conductor Newton ≥ 93,000 Maximum tension of conductor in still air at “everyday” temperature Assumed equivalent modulus of elasticity of conductor Newton > 18,500 N/mm2 ≥ 70,000 per C ≤1.98 x 10-5 5.2.11 Assumed equivalent coefficient of linear expansion of conductor Minimum bending radius 5.2.12 Short circuit current rating 5.2.13 Minimum length of conductor on drum 5.2.9 5.2.10 5.3 5.3.1 5.3.2 5.4 5.4.1 6 Offered mm kA2s 496 km 4 %IACS IEC 60104 52.5 Individual wires before stranding Aluminium alloy Standard Minimum conductivity at 20ºC Aluminium-clad steel Standard Grade of Steel Vibration damping system IEC 60232 20SA Maximum span for: a. One vibration damper at each end of span m b. Two vibration dampers at each end of span m c. Three vibration dampers at each end of span m OPGW EARTH CONDUCTOR FIBRE OPTIC TRANSMISSION SYSTEM 6.1 Fibre optic data 6.1.1 Type Section VI – Requirements Environmental Guidelines for Contractors Non-Zero DispersionShifted SingleMode acc. to ITU G.655. Page 202 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT 6.1.2 Wavelength 6.1.3 Number of fibres 6.1.4 Transmission attenuation: a. at 1550 nm b. at 1625 nm 6.1.5 Transmission bandwidth 6.1.6 Fibre identification 6.1.7 Chromatic dispersion nm DATA Required 1550/1625 48 dB/k m dB/k m MHz/ km colour code < 0.22 < 0.24 > 10 000 a. at 1550 nm b. at 1625 nm 6.1.8 Splicing loss ps/nm .km ps/nm .km dB 6.1.9 Polarisation Mode Dispersion (PMD) 6.1.10 Minimum bending radius ps/√k m mm <2 < 12.4 < 0.1 < 20 SDH Optical Multiplex Equipment and Regenerative Repeaters 6.2.1 Transmission mode 6.2.2 Operating wavelength 6.2.3 Optical transmitter DFB laser diode 6.2.4 Optical detector avalanche photodiode 6.2.5 a. Optical transmission rate: 6.2 b. Digital nm 1550 STM-1 Mb/s 155.52 STM-4 Mb/s 622.08 6.2.6 Optical interface Compliant with ITU Rec G957 and Rec G958 6.2.7 Electrical digital interface Compliant with ITU Rec G709 6.2.8 Maximum input attenuation 6.2.9 Maximum admissible jitter 6.2.10 Transmission delay Section VI – Requirements Environmental Guidelines for Contractors Offered dB <6 Compliant with ITU Rec G812 s <1 Page 203 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT 6.2.11 Operating voltage 6.3 Solar arrays power supply system 6.3.1 Type of solar cell Silicon based 6.3.2 Type of batteries Nickel cadmium 6.3.3 Minimum battery autonomy (continuous operation) hours 96 6.3.4 Output voltage V dc 48 (+5%) 6.3.5 Charger and control unit 6.3.6 Manufacturer 6.3.7 Type reference 6.3.8 Place of manufacture 6.3.9 Is local technical support provided in Kenya? 6.3.10 Minimum lighting level required for proper operation of the solar arrays power supply system 6.3.11 Output supply voltage range of the system 6.3.12 Total power output of the solar arrays system 6.3.13 Details of control equipment provided 6.3.14 Charging current 6.3.15 Details of alarm monitoring facilities provided 6.3.16 Details of remote alarm indications provided 6.3.17 Operating temperature range 6.3.18 Operating relative humidity range (non-condensing) 6.3.19 Protection rating IP Standard 6.3.20 Vibration IEC Standard 6.3.21 Shock IEC Standard 6.3.22 Dimension of equipment (H W D) mm mm mm 6.3.23 Mass 6.3.24 Mean time between failures (MTBF) Section VI – Requirements Environmental Guidelines for Contractors DATA Required 48 (+20% 15%) Vdc Y/N lux Offered - V dc W A ºC %rh kg hours Page 204 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATA Required 6.3.24 6.4 Mean time to repair (MTTR) Optical regenerative repeaters (to be completed for each type of repeater used) 6.4.1 Manufacturer 6.4.2 Model reference 6.4.3 Place of Manufacture 6.4.4 Number Provided No 6.4.5 Is local technical support provided in Kenya? Y/N 6.4.6 Regenerator section length (without the use of optical booster/amplifiers) km 6.4.7 km 6.4.8 Regenerator section length (with the use of optical boosters/amplifiers) Nominal operating wavelength nm 6.4.9 Transmission rate 6.4.10 Type of optical transmitter 6.4.11 Minimum transmit level dBm 6.4.12 Maximum transmit level dBm 6.4.13 Type of optical receiver 6.4.14 Receiver sensitivity for BER 10-9 6.4.15 Is interworking with PDH systems possible? 6.4.16 Details of interfacing with the Telecommunications Management System 6.4.17 Service channels: a. Number of channels b. Bit rate c. Type of interface Engineers order wire a. 2 wire/4 wire interface b. Impedance c. Bit rate (for digital) d. Selective calling facility 6.4.18 Offered hours Section VI – Requirements Environmental Guidelines for Contractors Mb/s dBm Page 205 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATA Required 6.4.19 Details of alarm monitoring facilities 6.4.20 Voltage limits for satisfactory operation a. Nominal voltage V dc b. Maximum voltage V dc c. Minimum voltage V dc 6.4.21 Anticipated loading in volt-amperes at 48 V dc. 6.4.22 Electromagnetic interference IEC Standard C 6.4.23 Operating temperature range VA 6.4.24 Operating relative humidity range (non-condensing) 6.4.25 Protection rating IP Standard 6.4.26 Vibration IEC Standard 6.4.27 Shock IEC Standard 6.4.28 Details of ventilation required 6.4.29 Mass of complete equipment 6.4.30 Mean time between failures (MTBF) hours 6.4.31 Mean time to repair (MTTR) hours 6.4.32 Dimensions of cubicle rack 6.5 Solar cells (to be completed for each type of solar cell used) %rh Manufacturer 6.5.2 Type reference 6.5.3 Place of manufacture 6.5.4 6.5.5 Type of solar cells 6.5.6 Lighting level range required for proper operation of the solar cell 6.5.7 Voltage output range of each solar cell 6.5.8 Power output of each solar cell 6.5.9 Method of mounting solar panels Section VI – Requirements Environmental Guidelines for Contractors kg mm mm mm 6.5.1 Number of solar cells provided Offered No lux V dc W Page 206 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATA Required 6.5.10 Operating temperature range 6.5.11 Operating relative humidity range (non-condensing) 6.5.12 Protection rating IP Standard 6.5.13 Vibration IEC Standard 6.5.14 Shock IEC Standard 6.5.15 Dimension of each solar array (H W D) 6.5.16 Dimension of complete solar arrays system (H W D) mm mm mm 6.5.17 Mass of each solar array kg 6.5.18 Mass of complete solar arrays system kg %rh mm mm mm Batteries (to be completed for each type of battery used) 6.6.1 Manufacturer 6.6.2 Type reference 6.6.3 Place of manufacture 6.6.4 Number of batteries provided 6.6.5 Type of batteries 6.6.6 Number of cells per battery 6.6.7 Voltage output of each battery cell V dc 6.6.8 Battery voltage output range V dc 6.6.9 Total capacity of the battery system 6.6.10 Time required to recharge totally discharged batteries to full capacity hours 6.6.11 hours 6.6.12 Ampere hour capacity at 96 hour discharge rate with average temperature at 50ºC Ah 6.6.13 Operating temperature range ºC 6.6.14 Operating relative humidity range (non-condensing) 6.6.15 Dimension of each battery (H W D) 6.6 Autonomy of the battery backup support Section VI – Requirements Environmental Guidelines for Contractors Offered ºC No No Ah %rh mm mm mm Page 207 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATA Required 6.6.16 Dimension of complete battery backup system (H W D) 6.6.17 Mass of each battery/ complete battery backup system 7.0 Insulator and fittings 7.1 Insulator units: Long Rod 7.1.1 kg Suspension units 7.1.1.1 Shed profile 7.1.1.2 Appropriate IEC Number 7.1.1.3 Material 7.1.1.4 Coupling a. Standard b. Type (recommended only) c. Size (recommended only) aerodynamic IEC 61109 Silicone rubber IEC 61120 Ball/Socket 20 7.1.1.5 Minimum failing load kN 7.1.1.6 Outside diameter: mm 7.1.1.7 Mass of unit kg 7.1.1.8 Minimum dry lightning impulse withstand kV 7.1.1.9 Minimum wet power frequency withstand kV 7.1.1.10 Creepage distance 7.1.2 Offered mm mm mm mm 160 16000 Tension units 7.1.2.1 Shed profile 7.1.2.2 Appropriate IEC Number 7.1.2.3 Material 7.1.2.4 Coupling a. Standard b. Type (recommended only) c. Size (recommended only) aerodynamic IEC 61109 Silicone rubber IEC 61120 Ball/Socket 20 7.1.2.5 Minimum failing load 7.1.2.6 Outside diameter: 7.1.2.7 Mass of unit kg 7.1.2.8 Minimum dry lightning impulse withstand kV 7.1.2.9 Minimum wet power frequency withstand kV Section VI – Requirements Environmental Guidelines for Contractors kN 160 Page 208 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark 7.1.2.10 Creepage distance UNIT mm DATA Required 16000 7.2.1 7.2.1.1 7.2.1.2 Minimum failing load, complete set kN 120 /2*120 7.2.1.3 Overall length of set including clamps and all fittings mm ≤ 5150 7.2.1.4 7.2.1.5 Arcing Gap Mass of set, complete with all fittings mm kg 2900 7.2.1.6 Overall length of creepage path per string: Mm 16000 7.2.1.7 50 Hz voltage tests: 7.2 7.2.1.8 Insulator sets complete Suspension sets Number of insulator strings in parallel 1/2 a. Dry withstand voltage of complete set: kV 845 b. One minute wet withstand voltage of complete set : kV 680 50% Impulse withstand: a. 1.2/50 s negative wave: kV 1550 b. 1.2/50 s positive wave: kV 1550 kV 290 7.2.1.10 Set RI test voltage kV 275 7.2.1.11 Set radio noise level dB 45 7.2.2.12 Short circuit current withstand for 1 second (any part of set) kA 31.5 7.2.1.9 7.2.2 Offered Corona test voltage Tension sets 7.2.2.1 Number of insulator strings in parallel 7.2.2.2 Elastic limit load of set fittings: 2 a. Common to each string kN b. Common to conductor kN c. Separate for each sub-conductor kN 7.2.2.3 Minimum failing load, complete set kN 7.2.2.4 Overall length of set including clamps and all fittings mm 7.2.2.5 Arcing Gap mm 320 2900 All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383 Section VI – Requirements Environmental Guidelines for Contractors Page 209 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark UNIT DATA Required 7.2.2.6 Mass of set, complete with all fittings 7.2.2.7 Overall length of creepage path per string: 7.2.2.8 50 Hz voltage tests: 7.2.2.9 mm 16000 a. Dry withstand voltage of complete set: kV 845 b. One minute wet withstand voltage of complete set: kV 690 50% Impulse withstand: a. 1.2/50 s negative wave: kV 1550 b. 1.2/50 s positive wave: kV 1550 7.2.2.10 Corona test voltage kV 290 7.2.2.11 Set RI test voltage kV 275 7.2.2.12 Set radio noise level dB 45 7.2.2.13 Short circuit current withstand for 1 second (any part of set) kA 31.5 7.3 Earth conductor sets 7.3.1 7.3.2 8 8.1 Offered kg Minimum failing load a. Suspension set kN b. Tension set kN Short circuit current withstand for 1 second (any part of set) Clearances kA 31.5 Minimum clearance between live metal and tower steelwork:a. with suspension insulator set swing, at 65º mm 1100 b. with suspension insulator set swing, 0 - 10º mm 3100 c. with suspension insulator set swing 10 - 35º mm 1800 m 5.0 mm 4900 8.4 Minimum clearance to steelwork on which a man may stand for live line maintenance (crossarm floor) 8.5 Downleads – minimum clearances: a. phase to phase clearance in still air All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383 Section VI – Requirements Environmental Guidelines for Contractors Page 210 of 677 O. 400kV OVERHEAD LINE - Line conductor: 4 x Lark b. UNIT phase to phase clearance under conditions of maximum (opposing) swing and sag DATA mm Required 3700 8.6 Earth conductor suspension clamps, unobstructed transverse swing angle from vertical degrees 0 – 50 8.7 Earth conductor maximum shielding angle from vertical at tower attachment point over outer line conductors degrees 17 9.0 Offered QUALITY OF TOWER MATERIALS 9 Steel members .1 9.1.1 Grade/standard: EN10025-2 a. Mild steel S235 b. High tensile steel S355 9.1.2 Tensile breaking stress: a. Mild steel N/mm2 235 b. High tensile steel N/mm2 355 9.1.3 Elongation on breaking: a. Mild steel % b. High tensile steel % 9.1.4 Yield point as percentage of breaking stress: a. Mild steel % b. High tensile steel % 9 Steel nuts and bolts .2 9.2.1 Grade/standard: a. Mild steel 5.6 b. High tensile steel 8.8 9.2.2 Tensile breaking stress: a. Mild steel N/mm2 b. High tensile steel N/mm2 9.2.3 Elongation on breaking: a. Mild steel % b. High tensile steel % Section VI – Requirements Environmental Guidelines for Contractors Page 211 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required Offered 1.0 – 3.0 Not used 4.0 Line conductor and fittings 4.1 Complete line conductor: 4.1.1 Nominal area per phase 4.1.2 Number of conductors per phase 4.2 ACSR mm2 515 No 1 Each single conductor: 4.2.1 Code name 4.2.2 International Standard 4.2.3 National standard 4.2.4 Material of conductor 4.2.5 Number and diameter of wires Canary IEC 61089 ASTM B 232 Aluminium/ Galvanised Steel No/mm Al 54/3.28 St 7/3.28 4.2.6 Total area of conductor Section VI – Requirements Environmental Guidelines for Contractors mm2 515.50 Page 212 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 4.2.7 20. OVERALL DIAMETER OF STRANDED CONDUCTOR 4.2.8 Resistance of conductor (dc) at 20˚C 4.2.9 mm 29.52 ohm/km 0.06328 Mass of conductor (without grease) kg/km 1726 4.2.10 Total mass of greased conductor (greased to Case 2 of IEC 61089) kg/km 4.2.11 Ultimate rated strength of conductor Newton 142,040 4.2.12 Maximum tension of conductor in still air at “everyday” temperature Newton 28,408 4.2.13 Assumed equivalent modulus of elasticity of conductor N/mm2 68,650 4.2.14 Assumed equivalent coefficient of linear expansion of conductor per ˚C 1.93 x 10-5 4.2.15 Maximum length of conductor on drum km 3 ˚C 120 4.3 Offered Conductor grease: 4.3.1 Type 4.3.2 Minimum drop-point temperature Section VI – Requirements Environmental Guidelines for Contractors Page 213 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 4.3.3 4.4 Mass of grease per kilometre of conductor (all inner layers greased – Case 2 to IEC 61089) Offered kg Vibration damping system: 4.4.1 Type of system (vibration damper) 4.4.2 VIBRATION DAMPER type 4.4.2.1 Type of vibration damper type 4.4.2.2 National / International standard 4.4.2.3 Number of wires in messenger cable No 19 4.4.2.4 Conductor diameter range mm 29.52 4.4.2.5 Mass of damper 4.4.2.6 Maximum span for: IEC 61897 kg a. One vibration damper at each end of span m b. Two vibration dampers at each end of span m c. Three vibration dampers at each end of span m Section VI – Requirements Environmental Guidelines for Contractors Stockbridge Page 214 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 4.4.2.7 P. Offered Dimensions from clamp mouth to vibration damper attachment: a. First damper mm b. Second damper when required mm c. Third damper when required mm 220 kV OVERHEAD LINE – Earth Conductor UNIT DATA Required 5.0 Earth Conductor and fittings 5.1 Complete earth conductor system 5.1.1 5.2 Number of ACS earth conductors Offered Aluminium Clad Steel GW No 1 Each single earth conductor 5.2.1 International Standard No ASTM B416 5.2.2 Material of conductor Aluminiumclad steel 5.2.3 Number and diameter of wires 5.2.4 No/mm 7/3.26 Total area of conductor mm2 58.6 5.2.5 Overall diameter of conductor mm 9.78 5.2.6 Mass of conductor kg/km 390 5.2.7 Ultimate strength of conductor Newton 71,000 5.2.8 Maximum tension of conductor in still air at “everyday” temperature Newton 5.2.9 Assumed equivalent modulus of elasticity of conductor N/mm2 162,000 5.2.10 Assumed equivalent coefficient of linear expansion of conductor per C 12.96 x 10-6 5.2.11 Minimum bending radius Section VI – Requirements Environmental Guidelines for Contractors mm Page 215 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 5.2.12 5.3 5.3.1 Minimum length of conductor on drum 5.4.1 20SA Vibration damping system Maximum span for: a. One vibration damper at each end of span m b. Two vibration dampers at each end of span m c. Three vibration dampers at each end of span m Earth Conductor and fittings 6.1 Complete optical earth conductor system 6.2 ASTM B415 Grade of steel 6.0 6.1.1 4 Individual wires before stranding Aluminium-clad steel b. 5.4 km Number of OPGW earth conductors OPGW No 1 Each single optical earth conductor (OPGW) 6.2.1 International Standard No 6.2.2 Material of conductor 6.2.3 Number and diameter of wires 6.2.4 Total area of conductor mm2 6.2.5 Overall diameter of conductor mm 6.2.6 Mass of conductor IEE 1138 IEC 60794-4-1 Aluminium Alloy/ Aluminiumclad steel 6.2.7 6.2.8 No/mm kg/km <850 Ultimate strength of conductor Newton ≥ 93,000 Maximum tension of conductor in still air at “everyday” temperature Assumed equivalent modulus of elasticity of conductor Newton > 18,500 N/mm2 ≥ 70,000 per C ≤1.98 x 10-5 6.2.11 Assumed equivalent coefficient of linear expansion of conductor Minimum bending radius 6.2.12 Short circuit current rating 6.2.9 6.2.10 Offered Section VI – Requirements Environmental Guidelines for Contractors mm kA2s 496 Page 216 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 6.2.13 6.3 6.3.1 6.3.2 6.4 6.4.1 Minimum length of conductor on drum km 4 %IACS IEC 60104 52.5 Offered Individual wires before stranding Aluminium alloy Standard Minimum conductivity at 20ºC Aluminium-clad steel Standard Grade of Steel Vibration damping system IEC 60232 20SA Maximum span for: d. One vibration damper at each end of span m e. Two vibration dampers at each end of span m f. Three vibration dampers at each end of span m 7.0 FIBRE OPTIC TRANSMISSION SYSTEM 7.1 Fibre optic data 7.1.1 Type 7.1.2 Wavelength 7.1.3 Number of fibres 7.1.4 Transmission attenuation: c. at 1550 nm d. at 1625 nm 7.1.5 Transmission bandwidth 7.1.6 Fibre identification 7.1.7 Chromatic dispersion nm 48 dB/k m dB/k m MHz/ km colou r code at 1550 nm d. at 1625 nm 7.1.8 Splicing loss ps/n m.km ps/n m.km dB 7.1.9 Polarisation Mode Dispersion (PMD) 7.1.10 Minimum bending radius < 0.22 < 0.24 > 10 000 c. Section VI – Requirements Environmental Guidelines for Contractors Non-Zero DispersionShifted SingleMode acc. to ITU G.655. 1550/1625 ps/√k m mm <2 < 12.4 < 0.1 < 20 Page 217 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 8.0 Insulator and fittings 8.1 Insulator units: Long Rod 8.1.1 Suspension units 8.1.1.1 Shed profile 8.1.1.2 Appropriate IEC Number 8.1.1.3 Material 8.1.1.4 Coupling d. Standard e. Type (recommended only) f. Size (recommended only) aerodynamic IEC 61109 Silicone rubber IEC 61120 Ball/Socket 16 8.1.1.5 Minimum failing load kN 8.1.1.6 Outside diameter: mm 8.1.1.7 Mass of unit kg 8.1.1.8 Minimum dry lightning impulse withstand kV 8.1.1.9 Minimum wet power frequency withstand kV 8.1.1.10 Creepage distance 8.1.2 Offered mm 70 9300 Tension units 8.1.2.1 Shed profile 8.1.2.2 Appropriate IEC Number 8.1.2.3 Material Section VI – Requirements Environmental Guidelines for Contractors aerodynamic IEC 61109 Silicone rubber Page 218 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 8.1.2.4 Coupling d. Standard e. Type (recommended only) f. Size (recommended only) IEC 61120 Ball/Socket 16 8.1.2.5 Minimum failing load kN 8.1.2.6 Outside diameter: 8.1.2.7 Mass of unit kg 8.1.2.8 Minimum dry lightning impulse withstand kV 8.1.2.9 Minimum wet power frequency withstand kV 8.1.2.10 Creepage distance mm 120 9300 8.2.1 8.2.1.1 8.2.1.2 Minimum failing load, complete set kN 70 /2*70 8.2.1.3 Overall length of set including clamps and all fittings mm ≤ 3100 8.2.1.4 8.2.1.5 Arcing Gap Mass of set, complete with all fittings mm kg 2100 8.2.1.6 Overall length of creepage path per string: Mm 9300 8.2.1.7 50 Hz voltage tests: 8.2 8.2.1.8 Insulator sets complete Suspension sets Number of insulator strings in parallel 1/2 c. Dry withstand voltage of complete set: kV 715 d. One minute wet withstand voltage of complete set : kV 540 50% Impulse withstand: c. 1.2/50 s negative wave: kV 1150 d. 1.2/50 s positive wave: kV 1150 kV 245 8.2.1.10 Set RI test voltage kV 220 8.2.1.11 Set radio noise level dB 45 8.2.1.12 Short circuit current withstand for 1 second (any part of set) kA 31.5 8.2.1.9 Offered Corona test voltage All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383 Section VI – Requirements Environmental Guidelines for Contractors Page 219 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 8.2.2 Tension sets 8.2.2.1 8.2.2.2 Minimum failing load, complete set kN 8.2.2.3 Overall length of set including clamps and all fittings mm 8.2.2.4 Arcing Gap mm 8.2.2.5 Mass of set, complete with all fittings 8.2.2.6 Overall length of creepage path per string: 8.2.2.7 50 Hz voltage tests: 8.2.2.8 Number of insulator strings in parallel 1/2 120/2*120 2100 kg mm 9300 c. Dry withstand voltage of complete set: kV 715 d. One minute wet withstand voltage of complete set: kV 540 50% Impulse withstand: c. 1.2/50 s negative wave: kV 1150 d. 1.2/50 s positive wave: kV 1150 kV 245 8.2.2.10 Set RI test voltage kV 220 8.2.2.11 Set radio noise level dB 45 8.2.2.12 Short circuit current withstand for 1 second (any part of set) kA 31.5 8.2.2.9 8.3 8.3.1 8.3.2 Offered Corona test voltage Earth conductor sets Minimum failing load c. Suspension set kN d. Tension set kN Short circuit current withstand for 1 second (any part of set) kA 31.5 All flashover and withstand voltage levels corrected to normal temperature and pressure in accordance with IEC 60383 Section VI – Requirements Environmental Guidelines for Contractors Page 220 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required 9.1 – 9.2 9.3 Not used Minimum clearance between live metal and tower steelwork:a. with suspension insulator set swing, at 65º mm 500 b. with suspension insulator set swing, 0 - 10º mm 2150 c. with suspension insulator set swing 10 - 35º mm 1500 m 3.9 9.4 Minimum Clearance to steelwork on which a man may stand for live line maintenance (crossarm floor) 9.5 Downleads – minimum clearances: c. phase to phase clearance in still air mm 3500 d. phase to phase clearance under conditions of maximum (opposing) swing and sag mm 2650 9.6 Earth conductor suspension clamps, unobstructed transverse swing angle from vertical degrees 0 – 50 9.7 Earth conductor maximum shielding angle from vertical at tower attachment point over outer line conductors degrees 3 10.0-13.0 14.0 Not used QUALITY OF TOWER MATERIALS 14.1 Steel members 14.1.1 Grade/standard: 14.1.2 14.1.3 EN10025-2 a. Mild steel S235 b. High tensile steel S355 Tensile breaking stress: a. Mild steel N/mm2 235 b. High tensile steel N/mm2 355 Elongation on breaking: a. 14.1.4 Offered Mild steel % Yield point as percentage of breaking stress: a. Mild steel % b. High tensile steel % Section VI – Requirements Environmental Guidelines for Contractors Page 221 of 677 P. 220 kV OVERHEAD LINE – Line Conductor 1 x Canary UNIT DATA Required Offered 14.2 Steel nuts and bolts 14.2.1 Grade/standard: 14.2.2 14.2.3 a. Mild steel 5.6 b. High tensile steel 8.8 Tensile breaking stress: a. Mild steel N/mm2 b. High tensile steel N/mm2 Elongation on breaking: a. Mild steel % b. High tensile steel % Section VI – Requirements Environmental Guidelines for Contractors Page 222 of 677